Siemens SAMMS-MV User Manual

SAMMS-MV
Siemens Advanced Motor Master System for Medium Voltage Motors
User's Manual
14
13
12
11
10
9
8
7
4
3
2
1
6
5
15
16
Manual No. MVC-9108
The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equip­ment purchased. Siemens reserves the right to make changes in the specifica­tions shown herein or to make improvements at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence.
For the purpose of this manual a qualified person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved. In addition, he has the following qualifications: (a) is trained and authorized to de-energize, clear, ground, and tag circuits
and equipment in accordance with established safety practices.
(b) is trained in the proper care and use of protective equipment such as
rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices.
(c) is trained in rendering first aid.
IMPORTANT
QUALIFIED PERSON
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local sales office.
The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Energy & Automation, Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Energy & Automation, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.
SUMMARY
Contents
1 Introduction .............................................2
1.1 About this Manual ............................................3
1.2 About the SAMMS-MV Device ..........................3
1.2.1 The SAMMS-MV Device Models ............4
1.2.2 Advanced Protection for Medium-Voltage
Motors ...................................................4
1.2.3 Overload Protection ...............................5
1.2.4 Programming Control Circuits ................5
1.2.5 Using the Standardized Control Panel....5
2 Installing the SAMMS-MV Device..........7
2.1 Receiving and Storing the SAMMS-MV Device. 7
2.2 Where to Locate the Device .............................7
2.3 Mounting the Device .........................................7
2.4 Connecting the Device .....................................7
2.4.1 Wiring Guidelines ...................................7
2.4.2 Grounding the Device ............................9
2.4.3 Connecting the Device to a Control Power
Source...................................................9
2.4.4 Connecting Input and Output Devices to
the SAMMS-MV Device .........................9
2.4.5 Communications Connection ................. 9
3 Operating the SAMMS-MV Device ......11
3.1 Password Protection.......................................11
3.2 Using the Reset/Test Push Button ..................11
3.2.1 Performing a Lamp Test .......................11
3.2.2 Performing an Overload Relay Test...... 11
3.3 Motor Control .................................................11
3.4 Output Devices ............................................... 12
3.5 Input Devices ..................................................12
3.6 Ladder Diagrams............................................13
3.6.1 Library of Standard Ladder Diagrams...13
3.6.2 Custom Ladder Diagrams ....................13
3.7 Incomplete Sequence ..................................... 17
3.8 Intelligent Reduced-Voltage
Starting (SAMMS-MVX Only)...........................17
3.9 Ridethrough Upon Loss of Power
(SAMMS-MVX Only) ........................................ 17
3.10 Overload Protection........................................ 17
3.11 Motor Ambient Temperature ...........................17
3.12 Protection Curves and Overload
Classes ..........................................................19
3.13 Ultimate Trip Level and Service Factor ............23
3.14 Phase Unbalance ........................................... 23
3.15 Dual Overload Protection................................ 23
3.16 Jam Protection (SAMMS-MVX Only) ...............23
3.17 Loss of Load Protection/Warning
(SAMMS-MVX Only) ........................................ 23
3.18 Process Current Warning (SAMMS-MVX Only) 23
3.19 Stator Protection.............................................23
3.20 Rotor Protection .............................................23
3.21 Repetitive Starts .............................................24
3.22 Start Inhibit .....................................................24
3.23 Cooling T ime Constants .................................24
3.24 Normalized Temperature Rise for Class B and
Class F Insulation ...........................................24
3.25 Ground Fault Detection .................................. 24
3.26 Autoreset After a Trip (SAMMS-MVX Only) ......26
3.27 Emergency Restarting .................................... 26
3.28 Using the Hand Held Communicator (HHC) ...26
3.28.1 The (F)unction Key ...............................26
3.28.2The LIST Key ....................................... 26
3.28.3 UP and DOWN Keys ............................28
3.28.4 Using the ENTER Key ..........................28
3.29 Using the SAMMS-MV Device
Functions ....................................................... 28
3.29.1Program Mode/Passwords...................32
3.29.2 SAMMS-MV Functions ........................32
4 Troubleshooting the SAMMS-MV
Device.....................................................40
Appendix A - Technical Specifications of the
SAMMS-MV Device...............................43
©Copyright 1994 Siemens Energy & Automation, Inc. ACCESS, SAMMS, SAMMS-MV, Series 81000, SEAbus, Power Monitor, Power Monitor PC, WinPM, and SIEServe are trademarks of Siemens Energy & Automation, Inc. Microsoft is a registered trademark and Windows is a trademark of Microsoft Corporation. IBM is a registered trademark of International Business Machines, Inc.
1
1 Introduction
1 Introduction
The SAMMS-MV electronic motor control and protection de-
vice is designed and manufactured in accordance with the
latest applicable provisions of the National Electric Code,
Underwriters Laboratories Standards and Procedures, NEMA
Standards, and the National Electric Safety Code. You must
thoroughly read and understand this users manual before you
begin any work with the SAMMS-MV device. Successful appli-
cation and operation of this equipment depends as much upon
proper installation and maintenance by the user as it does upon
the careful design and fabrication by Siemens.
The purpose of this instruction manual is to assist the user in
developing safe and efficient procedures for the installation,
maintenance, and use of the equipment.
Contact the nearest Siemens representative if any additional
information is desired.
Qualified Person
For the purpose of this manual and product labels, a Qualified
Person is one who is familiar with the installation, construction
and operation of this equipment, and the hazards involved. In
addition, this person has the following qualifications;
Signal Words
The signal words Danger, Warning, and Caution used
in this manual indicate the degree of hazard that may be
encountered by the user. These words are defined as:
DangerIndicates an imminently hazardous situation which,
if not avoided, will result in death or serious injury.
WarningIndicates an potentially hazardous situation which,
if not avoided, could result in death or serious injury.
CautionIndicates an potentially hazardous situation which,
if not avoided, may result in minor or moderate injury.
Dangerous Procedures
In addition to other procedures described in this manual as
dangerous, user personnel must adhere to the following:
1. Always work on de-energized equipment. Always de-ener-
gize a breaker, or contactor, and remove it from the equip-
ment before performing any tests, maintenance, or repair.
2. Always perform maintenance on equipment employing springs
after the spring-charged mechanisims are discharged.
3. Always let an interlock device or safety mechanism perform
its function without forcing or defeating the device.
Field Service Operation
Siemens can provide compentent, well-trained Field Service
Representatives to provide technical guidance and advisory
assistance for the installation, overhaul, repair, and mainte-
nance of Siemens equipment, processes, and systems. Con-
tact regional service centers, sales offices, or the factory for
details.
 Training and authorization to energize, de-energize, clear,
ground, and tag circuits and equipment in accordance with
established safety practices.
 Training in the proper care and use of protective equipment
such as rubber gloves, hard hat, safety glasses, face shields,
flash clothing, etc., in accordance with established safety
procedures.
 Training in rendering first aid.
2
1 Introduction
1.1 About this Manual
This manual introduces you to the Siemens Advanced Motor
Master System (SAMMS-MV) motor protection and control
relay which incorporates protection designed for medium
voltage machines. This manual also contains information for
installing and operating the device, communicating with other
devices over the ACCESS electrical distribution communica-
tions system, and troubleshooting the device. This manual also
provides a helpful technical reference for you to use. Refer to
table 1.1 to determine which section of the manual contains the
information that you need.
These instructions prepare you to handle, install, operate and
maintain the SAMMS-MV device and the Hand-Held Commu-
nicator (HHC). The individual starters and controllers used are
designed for specific applications based upon your equipment
and needs. Instructions covering these starters and compo-
nents are not included in this manual. For this information, refer
to instructions and drawings furnished with your equipment, or
contact your Siemens representative. You must read these
instructions and determine applicability of your equipment.
Refer to the nameplate data on your controller and to the
electrical diagrams supplied with your controller to determine
applicability of your equipment.
1.2 About the SAMMS-MV Device
The SAMMS-MV device, shown in Figure 1.1, is a software-
configured electronic motor control and overload protection
device that incorporates protection tailored to the special
characteristics of medium voltage motors. The SAMMS-MV
system includes a microprocessor-based SAMMS-MV device
which receives signal inputs from a set of current transformers
(either 3-1Ø or 1-3Ø) and power input from a 12 volt tap on the
controllers control power transformer. To perform certain
monitoring and setup activities, a Hand-Held Communicator
(HHC) shown in Figure 1.2, is required. The SAMMS-MV device
is a multi-functional device offering the following:
 advanced motor protection for medium voltage motors
 pre-programmed control circuits
 standardized control panel with input/output devices replac-
ing conventional push-buttons, pilot lights and selector
switches
 diagnostics
 statistical motor data
 real-time metering
 local display of all motor and control circuit data
 open architecture communications using the ACCESS sys-
tem
Note: The SAMMS-MV device does not replace the disconnect
device (drawout contactor mounting or isolating switch) or the
contactor itself.
If you need to... ...refer to this section
learn about the SAMMS-MV device Section 1, Introduction
install the SAMMS-MV device Section 2, Installing the SAMMS-MV Device
operate the SAMMS-MV device Section 3, Operating the SAMMS-MV Device
operate the Hand-Held Communicator Section 3, Operating the SAMMS-MV Device
connect the SAMMS-MV device to the ACCESS
Section 2, Installing the SAMMS-MV Device
System
troubleshoot the SAMMS-MV device Section 4, Troubleshooting the SAMMS-MV Device
learn about the technical specifications of the
Appendix A, Technical Specifications of the SAMMS-MV Device
SAMMS-MV device
Table 1.1 Where to find information
3
1 Introduction
16
15
14
13
12
11
10
9
8
7
6
4
5
3
2
1
Figure 1.1 SAMMS-MV, front view
1.2.1 The SAMMS-MV Device Models
The SAMMS-MV device is available in two models: SAMMS-MVE
and SAMMS-MVX. Each model meets the various demands of
industrial and commercial specifications and installations. Table
1.2 compares the features of each model.
The SAMMS-MV device is designed for critical process control
where prevention of downtime is critical. It offers motor control
and protection along with motor diagnostic and motor/driven
equipment protection. Engineering and operating personnel
have access to important data enabling them to optimize
motor-driven equipment capabilities, maximize the process
system output and facilitate maintenance.
SAMMS-MVX is a full function model, applicable to all control
needs, from a simple across-the-line unit to a more compli-
cated reduced voltage scheme. It includes all of the functions
listed in table 3.7. Any of the standard control circuits listed in
table 3.3, or a custom circuit, may be downloaded. The
SAMMS-MVX device accepts up to four remote inputs, while
SAMMS-MVE accepts two remote inputs.
SAMMS-MVE is a model of SAMMS-MV tailored to across-the-
line (FVNR) applications. It provides all of the protective func-
tions of the SAMMS-MVX device, except that it has no jam
protection (F23), loss of load protection/alarm (F24), or process
current warning (F22) functions. Functions F3 and F5 associ-
ated with two-speed applications are not available. No provi-
sion for automatic reset (F8) is provided. SAMMS-MVE accepts
one remote input, and provides one output to actuate a single
contactor. An alarm contact is not available with SAMMS-MVE.
These remote inputs are compatible with all PLCs and electro-
mechanical remote control devices that have a 120VAC or
125VDC input signal.
1.2.2 Advanced Protection for
Medium-Voltage Motors
For advanced protection of medium voltage motors, the
SAMMS-MV device uses a motor model algorithm that continu-
ally calculates the stator winding and housing temperature as
well as the rotor temperature as a function of the motor rms
current. The motor model compares the calculated tempera-
ture to trip temperature values and provides a signal that trips
the motor off line when the motor reaches a trip temperature
value. The model closely emulates the heating and cooling of
the motor windings as well as the rotor and provides protection
against both transient and steady-state overload conditions.
4
1 Introduction
across-the-line starters to complicated reduced-voltage start-
ers. With optional software, the specified control circuit can be
loaded either from the library or from a modified version into the
microprocessors memory, in the factory or on site, using an
IBM®-PC compatible computer. If you would like to learn more
about this software package, refer to SAMMS Custom Soft-
ware Manual, Bulletin CP 3291.
Highly specialized control circuits can be developed and exist-
ing circuits can be modified using an optional IBM-PC compat-
ible software package. This software uses conventional engi-
neering symbols along with pull-down menus and a mouse to
draw ladder diagrams. When you have finished drawing the
diagram, the software translates the diagram into microproces-
sor machine code and downloads it into the SAMMS-MV
devices memory.
1.2.5 Using the Standardized Control Panel
The SAMMS-MV device can be used for local and/or remote
control. The SAMMS-MVE device provides two light bars, while
the SAMMS-MVX model provides three light bars. Each model
includes six pushbuttons with lights and tactile feedback. You
can program these light bars and pushbuttons for the various
functions of the control circuit used.
Figure 1.2 Hand-Held Communicator (HHC)
1.2.3 Overload Protection
The motor model offers the selection of overload classes 2
through 23.
The SAMMS-MV device offers more accurate motor protection
than traditional thermal overload and most electronic motor
protection devices. This prolongs motor life by eliminating
nuisance tripping for multiple restarts, and allowing for proper
cool down time when the motor winding temperature or rotor
temperature reaches a critically high value.
1.2.4 Programming Control Circuits
The SAMMS-MV device allows you to modify its configuration
by programming the microprocessor. The SAMMS-MV device
replaces conventional timers, overload relays, pushbuttons,
and selector switches.
SAMMS-MVE is preloaded with seven across-the-line control
circuits, and the desired control circuit can be selected using
the Hand-Held Communicator (HHC.) Alternatively, a custom
across-the-line circuit may be downloaded from a PC.
The test/reset button is used to test and reset the overload
function and to test the front panel lights.
Diagnostics
Eight diagnostic LEDs, located on the front panel, provide
information about conditions affecting the motor.
Statistical Data about the Motor
The microprocessors memory stores statistical data about the
motor and displays this data on the Hand-Held Communicator
(HHC).
Real-Time Metering Data
The Hand-Held Communicator displays real-time metering
data.
Local Displaying of Motor and Circuit Data
The HHC and the eight (8) diagnostic LEDs display motor and
control circuit data. The eight (8) diagnostic LEDs are located on
the front panel of the device.
Communicating with Other Devices
The SAMMS-MV device communicates with other devices via
the ACCESS system. When connected to the ACCESS system,
the SAMMS-MV device provides two-way communication with
the Power Monitor display and monitoring unit, an IBM PC-
compatible computer running the Power Monitor PC com-
munications and supervisory software or another supervisory
device. This ability allows you to control and monitor motors
from a centralized location. You can have remote access to all
SAMMS-MV data such as diagnostics, statistical data, real-
time metering, and controller status. If you would like to learn
more about the ACCESS system, refer to Installing the AC-
CESS System (manual no. SG6028).
A library of more than 40 typical control circuits exists for use
with SAMMS-MVX to meet applications ranging from simple
5
1 Introduction
SAMMS-MV Model SAMMS-MVE SAMMS-MVX
Application
Across-the-line (FVNR)
Reversing
Two-speed
Reduced voltage
Functions available (see table 3.7)
Ridethrough upon loss of power
Ground fault protection/alarm
Programmable alarm contact
Control circuits
Change settings requires password
Remote inputs
Outputs
Light bars
Table 1.2 SAMMS-MV models
X X
F0-F21 plus F25-F27 (except no
F3, F5, or F8)
No Yes
Yes Yes
No Yes
Seven (preloaded), selectable with
HHC. May download any custom
across-the-line control circuit
Yes Yes
One Four
One Three
Two Three
X
X
X
F0-F27
Any downloadable control circuit
6
2 Installing the SAMMS-MV Device
2 Installing the SAMMS-MV Device
This section provides instructions for installing the SAMMS-MV device. You should adapt these instructions to suit the needs of your installation and equipment.
2.1 Receiving and Storing the SAMMS-MV Device
Thoroughly inspect the equipment before accepting the ship­ment from the transportation company. Compare each item received against the packing list and report any shortages or damaged equipment to the carrier.
If you are not going to install the SAMMS-MV device immedi­ately, store it in a clean, dry location at ambient temperatures from -40° C to 85° C. The surrounding air should not contain any corrosive fumes or electrically conductive contaminants. The storage location should prevent condensation from forming within the equipment enclosure.
Note: Improper storage can cause equipment damage. Follow all storage instructions carefully. Failure to follow storage in­structions will void the warranty.
2.2 Where to Locate the Device
You can locate the SAMMS-MV device and its associated devices in most industrial equipment environments. Unless the device is designed for specific requirements, you should install the SAMMS-MV device and its controller in an area where the following conditions exist:
• Ambient air must be free of dirt, combustible vapor, steam, electrically conductive or corrosive material.
• Area around the controller must provide access to the equipment for inspection, maintenance and operation.
2.3 Mounting the Device
The SAMMS-MV device mounts in a front door panel of the low voltage compartment of Siemens Series 81000™ medium voltage control (MVC) equipment. Mount the device in the normal low-voltage compartment associated with each me­dium voltage controller.
2.4 Connecting the Device
This section contains general guidelines that you should follow to connect the SAMMS-MV device. These guidelines include instructions for routing the wire, connecting the wire and grounding the device. Use these guidelines to install the SAMMS-MV device and its peripheral devices in a motor controller. Also use these guidelines to connect the motor controller to the motor.
When Siemens supplies a SAMMS-MV device as part of a motor controller, Siemens personnel install the wiring between the SAMMS-MV device and its peripheral devices in the motor
controller at the factory. The schematic diagram used contains three components: a connection diagram, a ladder diagram and a wiring diagram. The connection diagram illustrates the connections between the SAMMS-MV device and its periph­eral devices. The ladder diagram illustrates the control circuit loaded into the SAMMS-MV device. Figure 2-1 shows a typical connection diagram for the SAMMS-MV device.
If Siemens does not supply the motor controller, the retrofitter or original equipment manufacturer should develop an equiva­lent electrical scheme.
2.4.1 Wiring Guidelines
You must observe the following guidelines when installing the SAMMS-MV device and connecting it with its peripheral de­vices.
Note: Failure to follow these guidelines can cause pickup of unwanted signals resulting in erratic operation and damage to the SAMMS-MV device.
Guideline 1: Separate the low-voltage (115 VAC or less) from the higher voltage conductors (460 VAC or higher) as much as possible. If low-voltage and medium-voltage wires must cross paths, make sure that they intersect at a right angle.
Guideline 2: To eliminate noise coupling, install all twisted pairs or wrap wires in such a way that a complete twist or wrap occurs at least every two inches.
Guideline 3: Place the low-voltage leads near the controller chassis.
Guideline 4: Use at least AWG 14 stranded copper wire for any low-voltage control wiring that you route outside the motor controller enclosure. Connections to the SAMMS-MV unit must be made with wire no larger than AWG 14.
Guideline 5: To avoid ground loops, ground each motor controller at a single ground point.
The top portion of the device contains 16 terminal locations for connecting control power leads, power supply, ground, inputs and outputs. (Refer to Figure 2.2 for a description of each terminal block assignment.)
7
2 Installing the SAMMS-MV Device
Figure 2.1 Full voltage non-reversing connection diagram
8
2 Installing the SAMMS-MV Device
2.4.2 Grounding the Device
As stated in Guideline 5, ground each motor controller at a single ground point. The grounding path to earth must be permanent and continuous. It must also be able to safely conduct ground fault currents that may occur in the system to ground through minimum impedance. The earth ground does not carry any current under normal conditions.
Note: Do not ground the SAMMS auxiliary current sensor (ACT) leads. (See figure 2.1.)
ALARM RELAY OUTPUT
115VAC (CPT INPUT)
12VAC (CPT INPUT) 12VAC (CPT INPUT)
Connect a ground bus to the chassis of each controller or to the chassis of the mounting equipment containing the earth ground through a grounding conductor.
Refer to Article 250 of the National Electrical Code for informa­tion about the types and sizes of wire conductors and methods for safely grounding electrical equipment and components.
2.4.3 Connecting the Device to a Control Power Source
The SAMMS-MV device requires a 12 VAC control power source in order to operate. Connect the control power source to terminals 5 and 6 located on the top of the relay.
2.4.4 Connecting Input and Output Devices to the SAMMS-MV Device
Connect your devices to the input and output connections on the SAMMS-MV device as illustrated in Figure 2.2.
2.4.5 Communications Connection
The SAMMS-MV device is equipped with an RS-485 commu­nications port on the back of the device. The communications port allows connection to a communications module which
AC INPUT 4 AC INPUT 3 AC INPUT 2 AC INPUT 1
ACT RETURN
ACT INPUT 1 ACT INPUT 2 ACT INPUT 3
12345678 9 10 11 121314
SAMMS-MVX
LED on LED Flashing
LED
Current
> 40%
Unbalance Impending
> 110%
Trip Overload
Overload
Trip Incomplete
Trip
Sequence
Trip: Loss
External
of Load, or
TripAlarm
Jam, or RTDInput Trip: CPU
CPU
Failure or
Fault
Low Voltage
Ground
Trip
Fault
20 - 40% > 100%
< 110% Start
Inhibit
Alarm: Loss of Load or Prcs Current
Alarm
CPU Fault
Ground Fault
Ready
Current Unbalance
Impending Trip
Overload Trip
Incomplete Sequence
External Trip/Alarm
Reset/Test
15 16
RETURN OUTPUT 3 OUTPUT 2 OUTPUT 1
Figure 2.2 Terminal block assignments
9
2 Installing the SAMMS-MV Device
enables the SAMMS-MV to communicate with a remote super­visory device. Examples of the remote supervisory device include the Power Monitor display and monitoring unit, a standard personal computer running the Power Monitor PC communications and supervisory software, or Siemens Microsoft® Windows™ based SIEServe™ or WinPM™ soft­ware. These supervisory devices and programs can communi­cate with the SAMMS-MV device and allow it to operate in the
1 = ­2 = GND 3 = + 4 = 12VDC+ 5 = 12VDC-
Top View
ACCESS electrical distribution communications system. The SAMMS-MV device connects to the SEAbus™ RS-485 via
the 5 pin plug on the Communications Module CM-1. The communications connections are illustrated in Figure 2.3. Refer to Installing the ACCESS System (manual no. SG-6028), for detailed information on connecting the SAMMS-MV device to the ACCESS network.
Proper make-up of 5 pin plug
Rear View
54321
Side View
5 pin plug
12345
4
3
1 2
Ribbon cable assembly
12Vdc(-) 12Vdc(+)
BLK
Comm Cable Comm Cable
SAMMS Communications Module CM-1
WHT
Shield
Figure 2.3 SAMMS-MV device communications connections
10
Rear view of the SAMMS-MV device
3 Operating the SAMMS-MV Device
3 Operating the SAMMS-MV Device
This section explains how to operate the SAMMS-MV device.
3.1 Password Protection
Changing the settings of the SAMMS-MV device requires the
use of the Hand-Held Communicator (HHC) in the program
mode. To access the program mode, the user needs a
password. The SAMMS-MV device is shipped from the factory
with the password 0000. This password can be changed by
the user as described in section 3.29.1. Display of data using
the HHC does not require use of a password.
3.2 Using the Reset/Test Push Button
The Reset/Test pushbutton is located at the bottom center of
the front panel of the SAMMS-MV device as illustrated in Figure
3.1. You press this pushbutton to manually reset the SAMMS-MV
device after a fault or a trip condition occurs so that the motor
can be restarted. You can also use the Reset/Test pushbutton
to perform a lamp test or an overload relay test.
3.2.1 Performing a Lamp Test
To test the diagnostic LEDs, the control LEDs and the light bars
on the front panel, use the following procedure:
1. Press and hold the Reset/Test pushbutton for one to two
seconds.
3.2.2 Performing an Overload Relay Test
You may perform an overload relay test whenever the motor is
stopped. Use the following procedure to perform an overload
relay test.
1. Press and hold the Reset/Test pushbutton for at least the
duration of the class time. The class time is set by accessing
function F7. If you need to know how to access function F7,
see Section 3.29. If you release the Reset/Test pushbutton
before the duration of the class time, the device performs a
lamp test. If a fault or trip condition exists when you press the
Reset/Test pushbutton, the device performs a reset instead
of a lamp test.
2. Continue to hold down the Reset/Test pushbutton. After
reaching the class time duration, the Impending Trip and the
Phase Unbalance LEDs illuminate.
3. Release the Reset/Test pushbutton. The Impending Trip
and Phase Unbalance LEDs go off, and the Overload Trip
LED illuminates for two seconds. If the SAMMS-MV device
is tripped, it is automatically reset at the end of the overload
relay test.
Use the following procedure to reset the SAMMS-MV device
after a trip event.
1. Press the Reset/Test pushbutton.
2. Release the Reset/Test pushbutton. (All LEDs and light bars
on the front panel illuminate for two seconds.)
If a fault or trip condition exists when you press the Reset/Test
pushbutton, the device performs a reset instead of a lamp test.
Figure 3.1 Front view of SAMMS-MV
2. Release the Reset/Test pushbutton. The device resets the
alarm LEDs. If the motor has cooled sufficiently, you can
restart the motor.
3.3 Motor Control
You can configure the SAMMS-MV device to perform many
motor starting and control functions. These functions include
basic across-the-line, to more complicated reversing, two-
speed, and reduced-voltage starting. The SAMMS-MV device
stores in its memory the executable code representing the
ladder diagram for the users control application. The
SAMMS-MV device and ladder diagram code replace the
conventional control logic defined by wired interconnection of
electromechanical timers, control relays, pushbuttons, selector
switches, and pilot lights. A library of over 40 standard ladder
diagrams available for the SAMMS-MV device covers most
applications. In addition to the standard ladders, you can
construct custom ladder diagrams, using optional software, to
handle special applications.
Figures 3.2 and 3.3 illustrate the ladder symbols representing
input and output devices available for the SAMMS-MV device.
The circular symbols represent output devices such as contactor
coil drivers, pilot LEDs on the front panel of the SAMMS-MV
device, software time-delay relays and software control relays.
All other symbols represent input devices such as software
auxiliary contacts, remote AC inputs, front-panel pushbuttons,
and software timer instantaneous and timed contacts.
11
3 Operating the SAMMS-MV Device
STATE
LED On Flashing
Current
Unbalance
> 40% 20 - 40%
Impending Trip > 110% > 100% - <110%
Overload Trip Trip Start Inhibit
Incomplete
Sequence
Trip
External
Trip/Alarm
Trip: Loss of Load
or Jam or RTD
Alarm: Loss of
Load or Process
Current
CPU Fault Trip: CPU Failure or
Low Voltage
Ground Fault Trip Alarm
Light bar (L1) Stop or Off Off Delay Timer
Timing
Light bar (L2) Start, On, Forward,
Low Speed, Right
On Delay Timer
Timing
Light bar (L3) Reverse, High
Speed, Left
On Delay Timer
Timing
3.4 Output Devices
You can use the following SAMMS-MV output devices:
AC Outputs
The SAMMS-MVX device provides up to three AC coil drivers
capable of driving contactors up to size H6, while SAMMS-MVE
provides one coil driver.
Control Relays
The device provides up to eight software-controlled relays.
These relays are helpful in local two-wire and other applications
requiring maintained contacts.
Timing Relays
The SAMMS-MV device contains four internal software timing
relays. You can configure all four timers as on-delay timers;
however, if needed, you can configure the two adjustable timers
(timing relays TR1 and TR2) as either on-delay or off-delay
timers. Using the Hand Held Communicator, you can program
timing relays TR1 and TR2 from 0 through 200 seconds
(functions F13 and F14). Timing relay TR3 has a fixed 1 second
delay, and timing relay TR4 has a fixed 30 seconds delay. Table
3.1 illustrates the type of timers used on the device and their
ranges.
Timer Type Time (in seconds)
TR1 Programmable on-delay or
off-delay
TR2 Programmable on-delay or
off-delay
TR3 Fixed on-delay 1
0 - 200
0 - 200
Front Panel Pushbuttons
The SAMMS-MV device has six front-panel pushbuttons for
local control of the device. You must use pushbutton 1 (PB1) for
stopping the motor. You must use three of the pushbuttons
(PB4-PB6) for the Hand, Off and Auto functions if these
functions are used in your configuration. If these functions are
not used, you may use PB4-PB6 for other functions. You can
configure the other two pushbuttons (PB2 and PB3) at your
discretion. Refer to Figure 3.4 for assignment of pushbuttons.
Insert labels are used to identify the function associated with
each pushbutton or light bar.
Software Auxiliary Contacts
Any number of internal (software) auxiliary contacts can be
configured. These contacts show either a normally open (NO)
or normally closed (NC) status. You can set up these auxiliary
contacts using the SAMMS-MV software. Through the
SAMMS-MV software, the pilot LEDs also have auxiliary con-
tacts.
TR4 Fixed on-delay 30
Table 3.1 Types of software tming relays
Pilot LEDs
The SAMMS-MVX device contains three light bars on the front
panel, while the SAMMS-MVE contains two light bars. Light bar
L1 is reserved and must be used as the STOP or OFF LED. You
can configure L2 and L3 at your discretion. The Hand, Off and
Auto LEDs correspond to the Hand, Off and Auto pushbuttons
on the front panel as illustrated in Figure 3.4. You can use the
Incomplete Sequence LED in reduced-voltage applications or
to verify contactor operation. Refer to Figure 3.4 for the location
of the LEDs and Table 3.2 for a description of the LED states.
Flashing Pilot LEDs
The front panel contains two or three flashing light bars that
indicate various conditions such as on-delay timing. These
flashing light bars, L1, L2 and L3 as defined above, indicate
different output devices if they are flashing rather than if they are
on constantly. Refer to Figure 3.4 for an illustration of pilot LEDs.
3.5 Input Devices
You can use the following input devices with the SAMMS-MV
device.
Remote AC Inputs
For SAMMS-MVX you can use four 120 VAC or VDC inputs for
remote control, or you can use one input for SAMMS-MVE.
12
Table 3.2 Description of pilot LEDs
Software Timer Inputs
Each timer has an unlimited number of normally open (NO) and
normally closed (NC) contacts. Timers configured as on-delay
timers have an unlimited supply of normally open timed-closed
(NOTC), and normally closed timed-open (NCTO) contacts.
Timers configured as off-delay timers have an unlimited supply
of normally open timed-open (NOTO), and normally closed
timed-closed (NCTC) contacts.
Communications Inputs
A serial, RS-485 communications port is located on the back of
the device for external communications.
3 Operating the SAMMS-MV Device
The communications inputs must be included in the ladder logic
(control circuit).
3.6 Ladder Diagrams
3.6.1 Library of Standard Ladder Diagrams
The SAMMS-MV library of more than 40 ladder diagrams
covers most standard motor control applications. Table 3.3 lists
the standard control circuits and the input and output assign-
ments for the library. You can use the library with the following
starter types:
across-the-line, non-reversing
across-the-line, reversing
two-speed, two winding
two-speed, one-winding, constant or variable torque
two-speed, one-winding, constant horsepower
reduced-voltage, autotransformer
reduced-voltage, reactor
For each starter type, the library includes seven control types:
local two-wire
local three-wire
local three-wire, remote two-wire
local two-wire, remote two-wire
local three-wire, remote three-wire
remote two-wire
remote three-wire
SAMMS-MVE has seven preloaded circuits (ladder diagrams)
for use with across-the-line (FVNR) applications. SAMMS-MVX
may be used with any of the circuits.
For details on the library of standard ladder diagrams, refer to
the SAMMS Standard Circuit Manual.
3.6.2 Custom Ladder Diagrams
For special motor control applications not covered by the library
of standard ladders, you can construct custom ladder dia-
grams using the input and output devices and their associated
symbols for the SAMMS-MV device. Siemens personnel can
build these custom ladder diagrams or you can build your own.
You can purchase an optional IBM PC-compatible software
package to develop custom ladder diagrams for special control
applications. The package also includes a library of standard
symbols. The package enables you to reconfigure existing
SAMMS-MV devices to meet changing plant needs. Refer to
the Custom Software Manual for the SAMMS device, Bulletin
CP 3291.
Figure 3.2 Ladder symbols used with the SAMMS-MV device (sheet 1)
13
3 Operating the SAMMS-MV Device
Figure 3.3 Ladder symbols used with the SAMMS-MV device (sheet 2)
12345678 9 10 11 12
STOP or OFF
SAMMS-MVX
LED on LED Flashing
LED
VARIABLE
Current Unbalance
Impending Trip
Overload Trip
Incomplete Sequence
External TripAlarm
CPU Fault
Ground Fault
> 40%
> 110%
Overload
VARIABLE
Trip Trip: Loss
of Load,or Jamor RTDinput
Trip: CPU Failure or Low Voltage
Trip
20 - 40% > 100%
< 110% Start
Inhibit
Alarm: Loss of Load or Prcs Current
Alarm
L1
L2
L3
CPU Fault
Ground Fault
Ready
Current Unbalance
Impending Trip
Overload Trip
Incomplete Sequence
External Trip/Alarm
Reset/Test
13
15 16
14
PB6
AUTO or VARIABLE
PB5
OFF or VARIABLE
PB4
HAND or VARIABLE
PB3
PB2
PB1
VARIABLE
VARIABLE
STOP or OFF
Figure 3.4 Assignment of pushbuttons and light bars
14
Loading...
+ 36 hidden pages