Siemens Advanced Motor Master System for
Low Voltage Motors
User's Manual
14
13
12
11
10
9
8
7
6
4
3
2
1
5
15
16
Manual No. MCC-3298
The use of unauthorized parts in the repair of the equipment or tampering by
unqualified personnel will result in dangerous conditions which will cause severe
personal injury or equipment damage. Follow all safety instructions contained
herein.
The information contained herein is general in nature and not intended for specific
application purposes. It does not relieve the user of responsibility to use sound
practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or
obligations. Should a conflict arise between the general information contained in
this publication and the contents of drawings or supplementary material or both,
the latter shall take precedence.
For the purpose of this manual a qualified person is one who is familiar with the
installation, construction or operation of the equipment and the hazards involved.
In addition, he has the following qualifications:
(a)is trained and authorized to de-energize, clear, ground, and tag circuits
and equipment in accordance with established safety practices.
(b)is trained in the proper care and use of protective equipment such as
rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc.,
in accordance with established safety practices.
(c)is trained in rendering first aid.
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency
to be met in connection with installation, operation, or maintenance. Should further information be desired or should
particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to
the local sales office.
IMPORTANT
QUALIFIED PERSON
SUMMARY
The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment
or relationship. The sales contract contains the entire obligation of Siemens Energy & Automation, Inc. The warranty
contained in the contract between the parties is the sole warranty of Siemens Energy & Automation, Inc. Any statements
contained herein do not create new warranties or modify the existing warranty.
SAMMS-LVE is preloaded with seven across-the-line control
circuits, and the desired control circuit can be selected using
the Hand-Held Communicator (HHC.) Alternatively, a custom
across-the-line circuit may be downloaded from a PC.
The test/reset button is used to test and reset the overload
function and to test the front panel lights.
Diagnostics
Eight diagnostic LEDs, located on the front panel, provide
information about conditions affecting the motor.
Statistical Data about the Motor
The microprocessors memory stores statistical data about the
motor and displays this data on the Hand-Held Communicator
(HHC).
Real-Time Metering Data
The Hand-Held Communicator displays real-time metering
data.
Local Displaying of Motor and Circuit Data
The HHC and the eight (8) diagnostic LEDs display motor and
control circuit data. The eight (8) diagnostic LEDs are located on
the front panel of the device.
Communicating with Other Devices
The SAMMS-LV device communicates with other devices via
the ACCESS system. When connected to the ACCESS system,
the SAMMS-LV device provides two-way communication with
the Power Monitor display and monitoring unit, an IBM PC-
compatible computer running the Power Monitor PC com-
munications and supervisory software or another supervisory
device. This ability allows you to control and monitor motors
from a centralized location. You can have remote access to all
SAMMS-LV data such as diagnostics, statistical data, real-time
metering, and controller status. If you would like to learn more
about the ACCESS system, refer to Installing the ACCESS
System (manual no. SG-6028).
A library of more than 70 typical control circuits exists for use
with SAMMS-LVX to meet applications ranging from simple
5
1 Introduction
SAMMS-LV ModelSAMMS-LVESAMMS-LVX
Application
Across-the-line, non reversing
Across-the-line, reversing
Two-speed, one winding, constant or
variable torque
Two-speed, one winding, constant
horsepower
Two-speed, two winding
Reduced voltage, autotransformer
Reduced voltage, Y-D, open transition
Reduced voltage, Y-D, closed transition
Part winding
Wye-delta
Full voltage, part winding
Functions available (see table 3.7)
Ridethrough upon loss of power
Ground fault protection/alarm
XX
F0-F21 plus F25-F27 (except no
F3, F5, or F8)
NoYes
YesYes
X
X
X
X
X
X
X
X
X
X
F0-F27
Programmable alarm contact
Control circuits
Change settings requires password
Remote inputs
Outputs
Light bars
Table 1.2 SAMMS-LV models
NoYes
Seven (preloaded), selectable with
HHC. May download any custom
across-the-line control circuit
YesYes
TwoFour
OneThree
TwoThree
Any downloadable control circuit
6
2 Installing the SAMMS-LV Device
2 Installing the SAMMS-LV Device
This section provides instructions for installing the SAMMS-LV
device. You should adapt these instructions to suit the needs of
your installation and equipment.
2.1 Receiving and Storing the
SAMMS-LV Device
Thoroughly inspect the equipment before accepting the shipment from the transportation company. Compare each item
received against the packing list and report any shortages or
damaged equipment to the carrier.
If you are not going to install the SAMMS-LV device immediately, store it in a clean, dry location at ambient temperatures
from -40° C to 85° C. The surrounding air should not contain any
corrosive fumes or electrically conductive contaminants. The
storage location should prevent condensation from forming
within the equipment enclosure.
Note: Improper storage can cause equipment damage. Follow
all storage instructions carefully. Failure to follow storage instructions will void the warranty.
2.2 Where to Locate the Device
You can locate the SAMMS-LV device and its associated
devices in most industrial equipment environments. Unless the
device is designed for specific requirements, you should install
the SAMMS-LV device and its controller in an area where the
following conditions exist:
• Ambient air must be free of dirt, combustible vapor, steam,
electrically conductive or corrosive material.
and a wiring diagram. The connection diagram illustrates the
connections between the SAMMS-LV device and its peripheral
devices. The ladder diagram illustrates the control circuit
loaded into the SAMMS-LV device. Figure 2-1 shows a typical
connection diagram for the SAMMS-LV device.
If Siemens does not supply the motor controller, the retrofitter
or original equipment manufacturer should develop an equivalent electrical scheme.
2.4.1 Wiring Guidelines
You must observe the following guidelines when installing the
SAMMS-LV device and connecting it with its peripheral devices.
Note: Failure to follow these guidelines can cause pickup of
unwanted signals resulting in erratic operation and damage to
the SAMMS-LV device.
Guideline 1: Separate the low-voltage (115 VAC or less) from
the higher voltage conductors (460 VAC or higher) as much as
possible. If low-voltage and medium-voltage wires must cross
paths, make sure that they intersect at a right angle.
• Area around the controller must provide access to the
equipment for inspection, maintenance and operation.
2.3 Mounting the Device
The SAMMS-LV device mounts in a front door of Siemens
motor control center (MCC), or on the front door of any motor
controller.
2.4 Connecting the Device
This section contains general guidelines that you should follow
to connect the SAMMS-LV device. These guidelines include
instructions for routing the wiring, connecting the wires and
grounding the device. Use these guidelines to install the
SAMMS-LV device and its peripheral devices in a motor
controller. Also use these guidelines to connect the motor
controller to the motor.
When Siemens supplies a SAMMS-LV device as part of a motor
controller, Siemens personnel install the wiring between the
SAMMS-LV device and its peripheral devices in the motor
controller at the factory. The schematic diagram used contains
three components: a connection diagram, a ladder diagram
Guideline 2: To eliminate noise coupling, install all twisted pairs
or wrap wires in such a way that a complete twist or wrap occurs
at least every two inches.
Guideline 3: Place the low-voltage leads near the controller
chassis.
Guideline 4: Use at least AWG 14 stranded copper wire for any
low-voltage control wiring that you route outside the motor
controller enclosure. Connections to the SAMMS-LV unit must
be made with wire no larger than AWG 14.
Guideline 5: To avoid ground loops, ground each motor
controller at a single ground point.
The top portion of the device contains 16 terminal locations for
connecting control power leads, power supply, ground, inputs
and outputs. (Refer to Figure 2.2 for a description of each
terminal block assignment.)
7
2 Installing the SAMMS-LV Device
Figure 2.1 Full voltage non-reversing connection diagram
8
2 Installing the SAMMS-LV Device
2.4.2 Grounding the Device
As stated in Guideline 5, ground each motor controller at a
single ground point. The grounding path to earth must be
permanent and continuous. It must also be able to safely
conduct ground fault currents that may occur in the system to
ground through minimum impedance. The earth ground does
not carry any current under normal conditions.
Note: Do not ground the SAMMS auxiliary current sensor (ACT)
leads. (See figure 2.1.)
ALARM RELAY OUTPUT
115VAC (CPT INPUT)
12VAC (CPT INPUT)
12VAC (CPT INPUT)
Connect a ground bus to the chassis of each controller or to the
chassis of the mounting equipment containing the earth ground
through a grounding conductor.
Refer to Article 250 of the National Electrical Code for information about the types and sizes of wire conductors and methods
for safely grounding electrical equipment and components.
2.4.3 Connecting the Device to a Control
Power Source
The SAMMS-LV device requires a 12 VAC control power
source in order to operate. Connect the control power source
to terminals 5 and 6 located on the top of the relay.
2.4.4 Connecting Input and Output Devices
to the SAMMS-LV Device
Connect your devices to the input and output connections on
the SAMMS-LV device as illustrated in Figure 2.2.
2.4.5 Communications Connection
The SAMMS-LV device is equipped with an RS-485 communications port on the back of the device. The communications
port allows connection to a communications module which
AC INPUT 4
AC INPUT 3
AC INPUT 2
AC INPUT 1
ACT RETURN
ACT INPUT 1
ACT INPUT 2
ACT INPUT 3
12345678 9 10 11 121314
SAMMS-LVX
LED on LED Flashing
LED
Current
> 40%
Unbalance
Impending
> 110%
Trip
Overload
Overload
Trip
Incomplete
Trip
Sequence
Trip: Loss
External
of Load, or
TripAlarm
Jam
Trip: CPU
CPU
Failure or
Fault
Low Voltage
Ground
Trip
Fault
20 - 40%
> 100%
< 110%
Start
Inhibit
Alarm: Loss
of Load or
Prcs Current
Alarm
CPU
Fault
Ground
Fault
Ready
Current
Unbalance
Impending
Trip
Overload
Trip
Incomplete
Sequence
External
Trip/Alarm
Reset/Test
15 16
RETURN
OUTPUT 3
OUTPUT 2
OUTPUT 1
Figure 2.2 Terminal block assignments
9
2 Installing the SAMMS-LV Device
enables the SAMMS-LV to communicate with a remote supervisory device. Examples of the remote supervisory device
include the Power Monitor display unit, a standard personal
computer running the Power Monitor PC communications and
supervisory software, or Siemens Microsoft
®
Windows™ based
SIEServe™ or WinPM™ software. These supervisory devices
and programs can communicate with the SAMMS-LV device
and allow it to operate in the ACCESS electrical distribution
1 = 2 = GND
3 = +
4 = 12VDC+
Top View
5 = 12VDC-
communications system.
The SAMMS-LV device connects to the SEAbus™ RS-485 via
the 5 pin plug on the Communications Module CM-1. The
communications connections are illustrated in Figure 2.3. Refer
to Installing the ACCESS System (manual no. SG-6028), for
detailed information on connecting the SAMMS-LV device to
the ACCESS network.
F16Display the most recent trip current.1A: 0.0 - 16.8A
F17Display the percentage current
1A: 0.0 - 16.8A
1B: 0.0 - 67.1A
1C: 0.0 - 99.9A
100 - 268A
2A: 0.0 - 402A
2B: 0.0 - 503A
3: 0.0 - 1006A
4: 0.0 - 1509A
5: 0.0 - 3018A
6: 0.0 - 6036A
0.1A
0.1A
0.1A
1A
1A
1A
1A
1A
1A
2A
0.1A
1B: 0.0 - 67.1A
1C: 0.0 - 99.9A
100 - 268A
2A: 0.0 - 402A
2B: 0.0 - 503A
3: 0.0 - 1006A
4: 0.0 - 1509A
5: 0.0 - 3018A
6: 0.0 - 6036A
0.1A
0.1A
1A
1A
1A
1A
1A
1A
2A
0 - 100%1%N/A
unbalance. OFF is displayed if
unbalanced protection is off.
Table 3.8 Motor control and protection functions (page 2 of 3)
1.5A
5A
5A
10A
10A
10A
10A
10A
20A
N/A
N/A
28
3 Operating the SAMMS-LV Device
Function
Function Description RangeStep SizeDefault Value
Number
F18Display the elapsed motor running time
in tens of hours.
0.0 - 6553 (x 10 hr.)0.1x10hr.
up to 999.9,
1x10hr.
up to 6553
F19Display the number of motor starts in
tens of hours.
0.0 - 6553 (x 10)0.1x10
up to 999.9,
1x10
up to 6553
F20Display the number of overload trips.0 - 99991N/A
F21Reset motor data. Zeroes the elapsed
N/AN/AN/A
running time, the number of starts, and
the number of overload trips.
F22Set process current warning0-100% I1% IOFF
FLC
FLC
F23Jam protectionON/OFFN/AON
F23ASelect jam pickup current120-400% I5%200%
FLC
F24Loss of LoadON/OFFN/AON
F24ASelect loss of load pickup current20-95% of running
5%50%
current
F25Display percentage of motor winding
0 to 250%1%N/A
temperature
F26Select baud rate2400/4800/9600N/A4800
F27Select address1-2241200
N/A
N/A
Table 3.8 Motor control and protection functions (page 3 of 3)
3.28 Using the SAMMS-LV Device Func-
tions
This section lists the 28 major motor control and protection
functions and several related functions (F0-F27, F4A, F5A,
F12A, F23A, and F24A) and how to use them. The functions
available for each version of the SAMMS-LV device are shown
in table 3.7. Table 3.8 provides a description of each function
and its associated range, step size, and default value.
To access a function perform the following steps:
1. Connect the HHCs cable to the communications port on
the front of the SAMMS-LV device.
2. Locate the desired function using the (F)unction and UP and
DOWN keys.
3. Then locate and follow the steps provided with the function
you wish to perform.
3.28.1 Program Mode/Passwords
To access the functions in program mode, the user is required
to enter a password. The default password is 0000, and may
be changed at any time. To enter the password and have
access to program mode:
1. Press and hold the (F)unction key for several seconds until
dISP is displayed.
2. Press the UP or DOWN key to change to the program mode.
The display reads Prog.
3. Press the ENTER key, and the display shows HHH0, the
prompt for entering the password.
4. Press the UP or DOWN key to select the first digit, then press
ENTER. The display reads HH0-.
5. Continue to select password digits and press ENTER to
enter each digit.
6. After correctly entering the four digit password, the display
reads - - - -, and pressing ENTER gives access to the
functions in program mode.
7. If the password was entered incorrectly, the display will read
Err. Press the ENTER key to return to program mode and
try again.
29
3 Operating the SAMMS-LV Device
Press and hold F key
F
UPDOWN
Display
mode
ENTERENTER
Program
mode
Prompt for
password
To change
password
UPDOWN
Enter new
password
twice
UPDOWN
ENTER
ENTER
To select function
for viewing
Prompt for
new password
To select
digit
To enter
digit
First digit
selected
Enter following
digits in the
same manner
0000-9999
ENTER
No
UPDOWN
UPDOWN
ENTER
ENTER
UPDOWN
To select
digit
To enter
digit
Password
Correct?
Yes
To select function
to change settings
First digit
selected
Enter following
digits in the
same manner
0000-9999
Authorized to
change settings
Password
No
entered
twice?
Yes
Figure 3.13 Entering and changing passwords
30
ENTER
3 Operating the SAMMS-LV Device
To change the password:
1. Enter the password as described above.
2. With the password entered and the display showing - - - -,
press the UP or DOWN key to enter change mode. The
display reads CHg.
3. Press the ENTER key, and the display shows HHH0, the
prompt for entering the new password.
4. Enter the new password in the same way described above.
After entering all four digits of the new password, the display
will again display HHH0.
5. Enter the new password a second time. If it was entered
correctly the display reads donE, and pressing ENTER
gives access to the functions in program mode.
6. If the password was entered incorrectly, the display will read
Err. Press the ENTER key to return to program mode and
try again.
3.28.2 SAMMS-LV Functions
F0 - Ambient Temperature
1. Press the LIST key to view the ambient temperature se-
lected. The default value is 40° C and the range of possible
values is from 0° C to 70° C in increments of 5° C.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings, until the selected setting appears on the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
down the ENTER key and the SAMMS-LV device stores the
new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
F1 - Control Circuit Number and Incomplete Se-
quence Status
1. Press the LIST key to view the control circuit number
programmed at the factory. The circuit numbers range from
0 through 9999. (The UP, DOWN and ENTER keys become
disabled.)
2. For SAMMS-LVE, to change the settings, you must be in the
program mode. The available selections are program blocks
10-16 (refer to table 3.3). If you have loaded a custom circuit,
the designation for that circuit will be shown.
3. Press the UP or DOWN key to scroll through the range of
circuit numbers, until the desired circuit number appears on
the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
down the ENTER key and the SAMMS-LV device stores the
new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
7. To enable or disable incomplete sequence, press the EN-
TER key for a period of one second or more. A . will be
displayed after the F1 on the HHC if incomplete sequence
is enabled. (The SAMMS-LV is shipped from the factory with
the incomplete sequence enabled.)
F2 - Size for Overload Relay #1
Overload relay #1 protects single-speed motors and two-
speed motors running on high speed. The possible values are
1A, 1B, 1C, 2A, 2B, 3, 4, 5, and 6. Use the following procedure
to display the size for overload relay #1.
1. Press the LIST key to view the size selected for overload
relay #1.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings, until the selected setting appears on the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
down the ENTER key and the SAMMS-LV device stores the
new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
F3 - Size for Overload Relay #2 (SAMMS-LVX Only)
Overload relay #2 protects two-speed motors running on low
speed. The possible values are 1A, 1B, 1C, 2A, 2B, 3, 4, 5, 6,
and OFF. OFF appears for single-speed motors. Use the
following procedure to display the size for overload relay #2.
1. Press the LIST key to view the size selected for overload
relay #2.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings, until the selected setting appears on the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
down the ENTER key and the SAMMS-LV device stores the
new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
31
3 Operating the SAMMS-LV Device
F4 - Full-Load Current for Overload Relay #1
1. Press the LIST key to view the active full-load current setting
for overload relay #1. The setting should normally be the full
load current as shown on the motor nameplate (high speed
for two-speed machine). The range of possible settings and
the factory default value depend on the size displayed in F2
as follows:
Overload
Relay Size
Setting
Range
StepDefault
1A0.3 - 1.5A0.1A0.3A
1B1.2 - 6.0A0.1A1.2A
1C4.8 - 24.0A0.1A4.8A
2A10 - 36A1A10A
2B10 - 45A1A10A
320 - 90A1A20A
440 - 135A1A40A
580 - 270A1A80A
6160 - 540A2A160A
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings until the selected setting appears.
down the ENTER key and the SAMMS-LV device stores the
new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
F5 - Full-Load Current for Overload Relay #2
(SAMMS-LVX Only)
1. Press the LIST key to view the active full-load current setting
for overload relay #2. This setting should normally be the full
load current for the low speed shown on the motor name-
plate. The range of possible settings and the factory default
value depend on the size displayed in F3. The values are
similar to those found in the table in the procedure for F4. If
the control is not a two-speed control, OFF appears on the
display, and UP, DOWN and ENTER keys become disabled.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings until the selected setting appears.
4. Press the ENTER key to change the active setting to the
selected value. The display becomes blank while you hold
down the ENTER key, and the SAMMS-LVX device stores
the new setting. (If you make an incorrect selection, repeat
steps 3 and 4).
4. Press the ENTER key to change the active setting to the
selected value. The display becomes blank while you hold
down the ENTER key, and the SAMMS-LV device stores the
new setting. (If you make an incorrect selection, repeat
steps 3 and 4).
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
F4A - 5A CT Primary Current Selection for Overload
Relay #1
SAMMS-LV is normally used with SAMMS sensors to provide
the current input signals to the device. Optionally, SAMMS-LV
may be used with conventional 5A secondary current trans-
formers.
1. Press the LIST key to view the sensor in use for overload
relay #1. If standard SAMMS sensors are used, the display
will read OFF. If 5A secondary CTs are in use, the CT
primary current will be displayed.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings, until the selected setting appears on the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
F5A - 5A CT Primary Current Selection for Overload
Relay #2 (SAMMS-LVX Only)
SAMMS-LV is normally used with SAMMS sensors to provide
the current input signals to the device. Optionally, SAMMS-LV
may be used with conventional 5A secondary current trans-
formers.
1. Press the LIST key to view the sensor in use for overload
relay #2. If standard SAMMS sensors are used, the display
will read OFF. If 5A secondary CTs are in use, the CT
primary current will be displayed.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings, until the selected setting appears on the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
down the ENTER key and the SAMMS-LVX device stores
the new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
32
3 Operating the SAMMS-LV Device
6. Press the (F)unction key to step through to another function.
F6 - Service Factor
1. Press the LIST key to view the active service factor, 1.0 or
1.15. The factory default is 1.15. A service factor of 1.15
adjusts the overload trip thresholds up by 15% over their
values for a service factor of 1.0. This results in more margin
before tripping.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key to
alternate between the two choices until the selected value
is displayed.
4. Press the ENTER key to change the active setting to the
selected value. The display becomes blank while you hold
down the ENTER key, and the SAMMS-LV device stores the
new setting. (If you make an incorrect selection, repeat
steps 3 and 4.)
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
F7 - Overload Trip Class
The trip class is the time in seconds that it takes the overload
relay to trip for a starting current of 600% of the full-load current
setting. The range of possible values is 2-23.
1. Press the LIST key to view the active trip class.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key to scroll
through the range of settings until the selected setting
appears.
4. Press the ENTER key to change the active setting to the
selected value. The display becomes blank while you hold
down the ENTER key, and the SAMMS-LV device stores the
new setting. (If you make an incorrect selection, repeat
steps 3 and 4.)
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog.Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
F8 - Autoreset (SAMMS-LVX Only)
1. Press the LIST key to view the active autoreset setting, either
ON or OFF. If autoreset is ON, the SAMMS-LV device
automatically resets 30 seconds after an overload or exter-
nal trip. At this time the motor can start. If autoreset is OFF,
you must manually reset the overload relay with the Reset/
Test button before restarting the motor. The factory default
is OFF.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key to select
the new setting.
4. Press and hold the ENTER key. If the displayed setting is
ON, go to step 6. If the displayed setting is OFF go to step
5.
5. Release the ENTER key while the display appears blank.
When you release the key, the setting changes to OFF. Go
to step 6.
6. Release the ENTER key. SUrE appears on the display.
7. Press the ENTER key to make the change to ON.
Note: The reason for displaying SUrE and requiring you to
press the ENTER key a second time is because the motor can
restart immediately after an overload trip if autoreset is ON.
8. If you made an incorrect selection, repeat steps 3 through
7.
9. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
10.Press the (F)unction key to step through other functions.
F9 - Phase Unbalance Protection
1. Press the LIST key to view the active phase unbalance
protection setting (ON or OFF). The factory default setting is
ON.
a. When phase unbalance protection is enabled (ON), cur-
rent unbalances of greater than 40% accelerate overload
tripping. The Phase Unbalance LED flashes for unbal-
ances between 20% and 40%. It remains steadily illumi-
nated for unbalances greater than 40%.
33
3 Operating the SAMMS-LV Device
b. When phase unbalance protection is disabled (OFF), the
Phase Unbalance LED remains off, unbalanced condi-
tions have no effect on protection, and F17 (Display
Unbalanced Current) displays OFF.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key to display
the setting options, then press ENTER to select the setting
that is shown. The display blanks while the ENTER key is
pressed.
4. Repeat Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to go to other functions.
F10 - Display Time to Restart
1. Press the LIST key to view the time remaining before the
motor can be restarted. The time is displayed in seconds.
While the motor is cooling, the time to restart counts down
from the maximum winding temperature allowed to the
steady-state, full-load temperature. The display is always
zero if the motor is not in a start inhibit mode. If a time to
restart displays, the motor can only be restarted by an
emergency restart (see F11).
2. The UP, DOWN, and ENTER keys are disabled.
3. Press the (F)unction key to go to other functions.
F11 - Emergency Restarting
1. Press the LIST key to view the emergency restart setting (ON
or OFF). The factory default is OFF. With emergency restart
enabled (ON), you can restart the motor after the overload
relay is reset (manually or automatically), even when the time
to reset is not zero. When you initiate an emergency restart,
the motor conditions are reset to zero to simulate a com-
pletely cold start. The emergency restart function is auto-
matically disabled after any restart (emergency or normal),
and you must manually re-enable the emergency restart
function by setting F11 to ON.
2. Emergency restart can be enabled in either the program
mode or the display mode.
4. If the selected setting is OFF, the display blanks while the
ENTER key is pressed. When the ENTER key is released, the
setting is changed to OFF. Skip to Step 6.
5. If the selected setting is ON, SUrE is displayed when you
release the ENTER key. Press ENTER again to make the
change to ON.
Note: The motor can be damaged if restarted before it is
allowed to cool. The SUrE display allows you to reconsider
your actions before pressing the ENTER key a second time
to select the ON setting.
6. Repeat Step 3 if you select an incorrect setting.
7. If you are in the program mode, press and hold the (F)unction
key for several seconds to exit. The display will show Prog.
Press the UP or DOWN key to change to the display mode.
8. Press the (F)unction key to go to other functions.
F12 - Ground Fault Protection or Warning
1. Press the LIST key to view the active ground fault detection
setting (ON or OFF). The factory default setting is warning
(OFF), and the other setting is protection (ON).
a. When warning (OFF) is selected, the Ground Fault LED
flashes if the ground current increases beyond the pickup
level. The LED stops flashing as soon as the current drops
below the pickup level.
b. When protection (ON) is selected, a ground current above
the pickup level will cause a trip. The motor stops, and the
Ground Fault LED is steadily lit. You must reset the unit
before the motor can be restarted.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key to display
the setting options, then press ENTER to select the setting
that is shown. The display blanks while the ENTER key is
pressed.
4. Repeat Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
3. To change the setting, press the UP or DOWN key to display
the setting options, then press ENTER to select the setting
that is shown. If the selected setting is ON, skip to Step 5.
34
6. Press the (F)unction key to go to other functions.
3 Operating the SAMMS-LV Device
F12A - Ground Fault Pickup Current
1. Press the LIST key to view the active ground fault pickup
current in use. The range of values and default values are
shown in the table below:
SizePickup Current
Range
Default Pickup
Current
1A1.5A1.5A
1B2A to 5A5A
1C2A to I5A
2A2A to I10A
2B2A to I10A
32A to I10A
42A to I10A
55A to I10A
610A to I20A
* I
is the value of I
FLC
OFF, I
is the value of I
FLC
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key to display
the setting options, then press ENTER to select the setting
that is shown. The display blanks while the ENTER key is
pressed.
4. Repeat Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to go to other functions.
for OLR#2 if F3 is not set to OFF. If F3 is
FLC
FLC
FLC*
FLC*
FLC*
FLC*
FLC*
FLC*
FLC*
for OLR#1.
F13 - Set Programmable Timer #1
1. Press the LIST key to view the active setting for timer #1. The
default setting is OFF. If the timer is not used in the control
circuit, OFF is displayed and the UP, DOWN, and ENTER
keys are disabled. OFF is also displayed for a setting of 0
seconds. The timer may be adjusted from 0 - 200 seconds
in one second increments.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key until the
desired value is displayed then press the ENTER key to
select the setting. The display blanks while the ENTER key
is pressed.
4. Repeat Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to go to other functions.
F14 - Set Programmable Timer #2
1. Press the LIST key to view the active setting for timer #2. The
default setting is OFF. If the timer is not used in the control
circuit, OFF is displayed and the UP, DOWN, and ENTER
keys are disabled. OFF is also displayed for a setting of 0
seconds. The timer may be adjusted from 0 - 200 seconds
in one second increments.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key until the
desired value is displayed then press the ENTER key to
select the setting. The display blanks while the ENTER key
is pressed.
4. Repeat Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to go to other functions.
F15 - Display Current
1. Press the LIST key to view the instantaneous line currents or
the average instantaneous line current. (The LIST key is
disabled for full voltage, part-winding starters.) For instanta-
neous line currents, the display shows the phase designator
(A, b , or C) in the left-most character followed by three
significant digits of the value of the current. For the average
instantaneous line current, four digits are displayed without
a phase designator.
a. Because only four characters can display at a time,
individual line currents of 1000 amps and above are
displayed as three dashes following the phase designa-
tor, e.g., A - - -.
b. For sizes 1A, 1B, and 1C, the current is displayed to the
nearest 0.1 amp for currents less than 100 amps; for 100
amps and above, currents are displayed to the nearest 1
amp. For sizes 2A, 2B,3, 4, and 5, the current is displayed
to the nearest 1 amp. For size 6, current is displayed to the
nearest 2 amps.
2. To view another line current, press the UP or DOWN key to
scroll through the four selections.
3. The ENTER key is disabled for this function.
4. Press the (F)unction key to go to other functions.
F16 - Trip Current
1. Press the LIST key to view the value of the current that
caused the most recent trip.
2. The UP, DOWN, and ENTER keys are disabled for this
function.
3. Press the (F)unction key to go to other functions.
35
3 Operating the SAMMS-LV Device
F17 - Current Unbalance
1. Press the LIST key to view the percentage current unbal-
ance. When unbalance protection is disabled (F9 = OFF),
OFF is displayed. The percentage unbalance is the ratio of
the greatest deviation of the three phase currents from their
average to the average of the three phase currents ex-
pressed as a percentage.
2. The UP, DOWN, and ENTER keys are disabled for this
function.
3. Press the (F)unction key to go to other functions.
F18 - Display Total Elapsed Run Time of the Motor
1. Press the LIST key to view the total elapsed running time of
the motor. The run time is displayed in tens of hours as
follows:
Actual Number of HoursDisplayed Time
00.0
9999999.9
100001000
655356553
655360.0 (roll over)
The displayed value does not increment until a full hour, or for
elapsed times greater than 10000 hours a full ten hours, have
elapsed. Internally, however, the elapsed time is maintained
to the nearest 0.1 second.
Note: The value can be reset to zero with F21.
2. The UP, DOWN, and ENTER keys are disabled for this
function.
3. Press the (F)unction key to go to other functions.
F19 - Number of Motor Starts
1. Press the LIST key to view the number of motor starts. The
number of starts is displayed in tens of starts as follows:
Actual Number of StartsDisplayed Number
00.0
9999999.9
100001000
655356553
655360.0 (roll over)
Note: The value can be reset to zero with F21.
F20 - Number of Overload Trips
1. Press the LIST key to view the number of overload trips, up
to 9999.
Note: The value can be reset to zero with F21.
2. The UP, DOWN, and ENTER keys are disabled for this
function.
3. Press the (F)unction key to go to other functions.
F21 - Reset Motor Data
1. To reset to zero the elapsed running time, the number of
starts, and the number of overload trips, press the LIST key.
CLr is displayed.
2. Press the ENTER key. SUrE is displayed.
3. Press the ENTER key again to zero the motor data.
4. To return to Step 1, press the LIST key at any time.
5. The UP and DOWN keys are disabled for this function.
6. Press the (F)unction key to go to other functions.
F22 - Process Current Warning Level (SAMMS-LVX
Only)
1. Press the LIST key to view the active process current level.
The value represents the percentage of the full load current
setting above which a motor current causes the External
Trip LED to flash. The function is disabled for five times the
class time after starting, or after a speed or direction
change. The range of settings is in 1% increments from zero
(OFF) through 100. The factory default is OFF.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key until the
desired setting is displayed then press the ENTER key to
select the setting. The display blanks while the ENTER key
is pressed.
3. Return to Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to go to other functions.
F23 Jam Protection (SAMMS-LVX Only)
1. Press the LIST key to view the active jam protection setting
(ON or OFF). The factory default setting is ON. If jam
protection is enabled (ON) and the motor running current
increases to the pickup current value within 360 msec, the
motor will trip off-line and the External Trip LED is steadily lit.
The function is disabled for five times the class time after
starting, or after a speed or direction change.
2. The UP, DOWN, and ENTER keys are disabled for this
function.
3. Press the (F)unction key to go to other functions.
36
2. To change the setting, you must be in program mode.
3 Operating the SAMMS-LV Device
3. To change the protection setting, press the UP or DOWN
key to display ON or OFF, then press ENTER to select the
setting that is shown. The display blanks while the ENTER
key is pressed.
4. Return to Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
F23A Jam Pickup Current (SAMMS-LVX Only)
1. Press the LIST key to view the jam current pickup value in
use. The range of possible values is between 120% and
400% to the FLC, in increments of 5%. The factory default
is 200%.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key until the
desired setting is displayed then press the ENTER key to
select the setting. The display blanks while the ENTER key
is pressed.
4. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
5. Press the (F)unction key to step through to another function.
F24 - Loss of Load Protection or Warning
(SAMMS-LVX Only)
1. Press the LIST key to view the active loss of load setting (ON
or OFF). The factory default setting is warning (OFF), and the
other setting is protection (ON). This function is disabled for
five times the class time after starting or speed or direction
changes.
a. When protection (ON) is selected and the motor current
drops below the pickup current value, within 360 msec,
the External Trip LED will light and the SAMMS-LV trips.
b. When warning (OFF) is selected and the motor current
drops below the pickup current value within 360 msec,
the External Trip LED flashes but the SAMMS-LV does not
trip.
2. To change the setting, you must be in program mode.
3. To change the protection setting, press the UP or DOWN
key to display ON or OFF options, then press ENTER to
select the setting that is shown. The display blanks while the
ENTER key is pressed.
4. Return to Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
F24A - Loss of Load Pickup Current (SAMMS-LVX
Only)
1. Press the LIST key to view the active setting. The range of
possible values is between 20% and 95% to the FLC, in
increments of 5%. The factory default is 50%.
2. To change the setting, you must be in program mode.
3. To change the setting, press the UP or DOWN key until the
desired setting is displayed then press the ENTER key to
select the setting. The display blanks while the ENTER key
is pressed.
4. Return to Step 3 if you select an incorrect setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to go to other functions.
F25 - Percentage of Motor Winding Temperature
1. Press the LIST key to view the temperature of the motor
windings as a percentage of the steady-state, full-load
winding temperature. The maximum allowable winding tem-
perature percentage is 175%.
2. The UP, DOWN, and ENTER keys are disabled for this
function.
3. Press the (F)unction key to go to other functions.
F26 - Baud Rate
1. Press the LIST key to view the active setting. Allowable
settings are 2400, 4800, or 9600 baud. The factory default
is 4800.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings, until the selected setting appears on the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
down the ENTER key and the SAMMS-LV device stores the
new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
37
3 Operating the SAMMS-LV Device
F27 - Address
1. Press the LIST key to view the active setting. Allowable
addresses are 1-224. The factory default is 200.
2. To change the setting, you must be in program mode.
3. Press the UP or DOWN key to scroll through the range of
settings, until the selected setting appears on the display.
4. Press the ENTER key to change the active setting to the
selected setting. The display becomes blank while you hold
down the ENTER key and the SAMMS-LV device stores the
new setting.
5. To exit the program mode, press and hold the (F)unction key
for several seconds. The display will show Prog. Press the
UP or DOWN key to change to the display mode.
6. Press the (F)unction key to step through to another function.
38
4 Troubleshooting the SAMMS-LV
Device
This section discusses how to troubleshoot the SAMMS-LV
device. The troubleshooting guide below lists basic errors that
can occur while operating the SAMMS-LV device. Use the
guide as necessary to solve error conditions as they arise. Do
not attempt to solve any error condition that is not listed in the
troubleshooting guide. Instead, contact your Siemens representative.
Note: When contacting your Siemens representative, refer to
the SAMMS-LV production control label to identify production
date, hardware version, and software version. This label is
mounted on the right side of the unit when viewed from the front.
For example, 93-250-456-01/03 represents a device that was
produced in 93, the 250th day of the year, unit number 456,
hardware version 01, and software version 03.
Troubleshooting Guide
4 Troubleshooting
Error ConditionMain CauseRemedy
Current UnbalanceCurrent unbalance LED is illuminated if
current unbalance exceeds 40%, or it
flashes if current unbalance is between
20 and 40%. Current unbalance may
be due to voltage or load unbalance.
Overload TripIndicates motor exceeded winding,
housing, or rotor temperature
threshold.
1.2.Correct the cause of voltage or load unbalance.
Verify current transformer secondary voltage is
unbalanced at SAMMS-LV terminals 1, 2, and 3 with
reference to 4.
1.
Verify that the full load current F4 and service factor
F6 on the HHC matches the full load current and the
service factor on the motor nameplate.
2.
If the motor tripped during start, increment the
overload class one step and start again. If still
unsuccessful, the motor’s rotor may be locked or
stalled. Correct motor malfunction before restarting.
3.
If the motor tripped after running for a period more
than the overload class selected, the trip may be due
to a running overload such as excessive loading on a
conveyor belt or bad bearings. Remove the cause of
the overload before restarting the motor.
4.
F16 on HHC displays the most recent overload trip
current value.
39
4 Tr oubleshooting
Troubleshooting Guide
Error ConditionMain CauseRemedy
Incomplete
Sequence
Indicates the SAMMS-LV unit does not
detect current one second after a start
command, or it detects current one
second after a stop command.
1.
If the unit trips one second after start, verify that
current transformer secondary input is present in the
range of 100 mVAC to 3.54 VAC at terminals 1, 2,
and 3 with reference to 4. Verify that the coil voltage
is 115 VAC at terminals 14, 15, or 16 with reference
to 13 when the motor is started. Verify 115 VAC at
terminal 7 with reference to 13. Correct conditions if
necessary. Call Siemens if unit continues to trip.
2.
If the unit trips one second after a stop command,
verify the contactor is open. Repair or replace the
contactor if it is not functioning properly.
3.
Verify operation of mechanical interlock, and replace
or adjust.
4.
Verify absence of voltage at terminals 1, 2, and 3 with
reference to 4, and at terminals 14, 15, or 16 with
reference to 13. If voltage is present, define the
source and reconnect so that the motor current only
passes through the current transformer.
5.
To disable incomplete sequence, select F1 on the
HHC, press the ENTER key for one or more seconds
and start the motor. The incomplete sequence will
remain disabled until the above procedure is
repeated.
External TripIf the external trip LED is solidly
illuminated and the motor is stopped, it
indicates a jam or loss of load
condition.
CPU FaultIndicates a problem in the
microprocessor or a low voltage
condition.
1.
Jam conditions such as a blocked conveyor belt or
gear train cause a sudden increase in motor current,
which can damage the motor’s insulation in a short
period of time.
2.
Loss of load conditions, such as a broken blade of an
impeller or loss of back pressure of a pump, result in
a sudden decrease in motor current.
3.
F16 on the HHC displays the external trip current at
the time of the trip.
In any case, determine the reason for the external trip
and correct the problem before restarting the motor.
If the external trip LED flashes and the motor
continues to run, it indicates loss of load warning or
process current warning.
Verify voltage between terminals 5 and 6 is more than
10 VAC. If fault persists, call Siemens.
40
Troubleshooting Guide
Error ConditionMain CauseRemedy
4 Troubleshooting
Ground FaultIndicates the ground fault current
exceeded the threshold. If ground fault
protection was selected, the ground
fault LED illuminates solidly and the
motor stops. If ground fault warning
was selected, the ground fault LED
flashes and the motor continues to run.
Ready Light not
Illuminated
Improper Remote
Operation
Usually indicates lack of control power.1.
Indicates connection or operator error.1.
The cause of the ground fault should be determined
and removed before using the motor again. F16 on
the HHC displays the ground fault trip current.
Verify the presence of 12 VAC between terminals 5
and 6 of the SAMMS-LV unit.
2.
If control power is not present, check the control
power fuses or the control power transformer and
replace if defective.
3.
If control power is present, push the RESET button to
test lights and unit. If the Ready light does not
illuminate, call Siemens.
Verify the SAMMS-LV unit is in the Auto mode.
2.
Verify 115 VAC input at SAMMS-LV terminals 9, 10,
11, and 12 with reference to 13, and at terminal 7
with reference to 13.
3.
If remote operation is intermittent, verify connections
are made in a manner to avoid noise interference.
Refer to Section 2 of this manual for instructions.
Improper Alarm
Contact Operation
Improper Light
Operation
Improper Local
Operation
Improper Contactor
Operation
Cannot Change
HHC Settings
Improper
SAMMS-LV
Operation
Indicates connection error.Verify 115 VAC at terminals 7 and 8 with reference to
13.
Usually indicates programming error.1.2.Perform lamp test by pressing RESET button.
Verify ladder diagram.
Operator error.Verify SAMMS-LV is in Local mode.
Connection error.Verify 115 VAC at terminal 7 with reference to 13,
and at output terminals 14, 15, or 16 with reference
to 13 when the motor is started.
Usually indicates motor is running, or
incorrect password.
Usually indicates improper grounding
or noise interference.
1.2.Verify that the motor is stopped before changing
parameters.
Verify that the correct password is in use. If the
password cannot be determined, call Siemens.
Refer to Section 2 of this manual for instructions.
41
Appendix A Technical Specifications
Appendix A - Technical Specifications of the SAMMS-LV Device
Motor Control Specifications
InputsSAMMS-LVX:
Six pushbuttons
Four remote inputs
OutputsSAMMS-LVX:
Three coil drivers
Three light bars
One programmable alarm contact
Diagnostic LEDs* Current unbalance
* Impending trip
* Overload trip
* External trip
* Incomplete sequence
* Ground fault
* CPU fault
* Ready
* Light bar flashes (timer timing)
* Impending trip LED flashes (motor temperature warning)
* Overload trip LED flashes (start inhibit)
* CPU LED ON (momentary loss of voltage)
Overload classesOverload classes 2 through 23 with one second increments.
Trip CharacteristicsTripping time at 6 x I = 95% of the overload class (±5%).
Tripping time at 1.5 x I within two minutes for warm conditions for all classes.
Tripping threshold(1.1 ± 0.05) x I for motors with 1.00 service factor, and
(1.2 ± 0.05) x I for motors with 1.15 service factor.
Tripping time20 minutes @1.15 x I for motors with service factor 1.
Mechanical jam protection
SAMMS-LVX only
Sudden increase of the motor running current. Pick-up current adjustable from 120 to
400% in increments of 5% of I . Pick-up time 360 msec.
Default value: 200% I .
Loss of load protection
SAMMS-LVX only
Sudden decrease of motor running current. Pick-up current adjustable from 20 to 95% in
increments of 5% of I . Pick-up time 360 msec.
Default value: 50% I .
Process current warning
Settings from 0 to 100% of I .
FLC
FLC
FLC
FLC
FLC
FLC
FLC
FLC
FLC
FLC
SAMMS-LVX only
Accuracy± 5% of overload trip curve values.
± 2% repeat accuracy.
Phase unbalance protectionResponse time after 1 second
Shifted trip threshold value to 0.9 x I at 40% phase unbalance.
FLC
Equipment ground fault protection Response time after overload class in seconds.
Pick-up time: 360 msec.
Pick-up current:
Overload Relay Size Pick-up Current Default
1A 1.5A 1.5A
1B 2A- 5A 5A
1C 2A- I 5A
2A 2A- I 10A
2B 2A- I 10A
3 2A- I 10A
4 2A- I 10A
5 5A- I 10A
6 10A- I 20A
FLC
FLC
FLC
FLC
FLC
FLC
FLC
I is the value of I for OLR#2 if F# is not set to OFF. If F3 is OFF, I is the value of
FLC
I for OLR#1.
FLC
FLC
Ambient temperatureMotor ambient temperature adjustable 0 - 70°C in increments of 5°C.
Default value: 40°C.
FLC
43
Appendix A Technical Specifications
Statistical Data
Elapsed motor running time- x10
- Range: 0.0 to 6553 (65,536 hours)
- Unit increments: 10 hours
Number of motor starts- x10
- Range:0.0 to 6553 (65,536 hours)
- Unit increments: 10 operations
Number of overload trips- Range: 0 to 9999
- Increments: 1 trip
Current displayOverload Relay Size Current Increments
Timer 4: 30 seconds fixed value
Timer auxiliary contactsSoftware instantaneous and timed contacts
Control relays8
Auxiliary contactsSoftware instantaneous contacts
44
Appendix A Technical Specifications
Dimensions
SAMMS-LV6.25 inches W; 6.00 inches H; 2.125 inches D
Handheld Communicator3.15 inches W; 5.7 inches H; 1.37 inches D
Environments
Operating temperature range-25º C to +70º C.
Storage temperature-40º C to +85º C.
Relative humidity5 to 95% non-condensing.
Altitude6600 ft.
Vibration5 g's at a frequency range of 10 to 60 Hz.
Electrostatic dischargeNo hardware failures at 15 kV at any point in the front of the unit.
Electromagnetic interference5 kV repeated pulses, per UL-991 and ANSI C37.90A.
Radio frequency interferenceUp to 95 MHz and 61.3 V/M field strength
Control Power Specifications
Unit powered by12 VAC (+10%, -15%) supply
Power requirements4VA
Control circuit inputs120 VAC or 125 VDC (+10%, -15%)
Control circuit outputs120 VAC (+10%, -15%)
Maximum output loading allowed