Siemens GBB132.1U, GBB132.1P, GBB131.1P, GBB136.1P, GIB131.1U Technical Instructions

...
Technical Instructions
June 22, 2015
Non-spring Return 24 Vac, Floating Control, Rotary
and face and bypass dampers requiring up to
Document Number 155-177P25
OpenAir™ GBB/GIB Series
Description
The OpenAir direct coupled 24 Vac, non-spring return (NSR) rotary electric actuator is designed for floating control of building HVAC dampers.
EA GBB/GIB-2
Features
Application
Product Numbers
221 lb-in (25 Nm)
310 lb-in (35 Nm)
Unique self-centering shaft coupling
All metal housing
Manual override
Independently adjustable dual auxiliary switches available
Built in potentiometer option
Two torque ranges available
UL, CE and cUL listed
These actuators are used in constant or variable air volume installations for the control of return air, mixed air, exhaust, 221 lb-in (25 Nm) or 310 lb-in (35 Nm) torque.
Table 1.
24 Vac Operating Voltage
Torque Cabling Standard
Standard GBB131.1U GBB132.1U GBB136.1U Plenum GBB131.1P GBB132.1P GBB136.1P Standard GIB131.1U GIB132.1U GIB136.1U Plenum GIB131.1P GIB136.1P
Potentiometer
Only
Auxiliary
Switches
Only
Siemens Industry, Inc.
Technical Instructions OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control
Operating voltage 24 Vac, ±20% Operating voltage Class 2, in accordance with UL/CSA
Feedback potentiometer (GBB132x)
Document No. 155-177P25 June 22, 2015
Warning/Caution Notations
WARNING:
CAUTION:
Specifications
Frequency 50/60 Hz
Power supply Equipment rating
Auxiliary features
Power consumption: 7 VA/7W
Plenum type actuators as whole device Class 2, in accordance with UL/CSA
Sliding contact (P2) 0 to 1000 ohm Load <1W
Voltage <24 Vac/dc Control signal adjustment
Offset (start point) Between 0 to 5 Vdc Factory setting 0 Vdc Span Between 2 to 30 Vdc
Dual auxiliary switches
AC rating (standard cable) 24 to 250 Vac AC 6A resistive AC 2A general purpose
AC rating (Plenum cable) 24 Vac AC 4A resistive AC 2A general purpose
DC rating (Standard/Plenum cable) 12 to 30 Vdc DC 2A Switch Range Switch A 0 to 90° with 5° intervals Recommended range usage 0 to 45° Factory setting Switch B 0 to 90° with 5° intervals Recommended range usage 45 to 90° Factory setting 85° Switching hysteresis
Personal injury/loss of life may occur if you do not perform a procedure as specified.
Equipment damage or loss of data may occur if you do not perform a procedure as specified.
Page 2 Siemens Industry, Inc.
WARNING:
Apply only line voltage or only Class 2 voltage to the switching outputs of both auxiliary switches A and B. Mixed operation is not permissible. See Wiring for details.
OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control Technical Instructions
Running torque
Shaft size 3/8 to 1-inch (8 to 25.6 mm) diameter
Enclosure NEMA 2 in vertical position to 90°
Ambient temperature
UL listed to UL873
Pre-cabled connection 18 AWG
Document No. 155-177P25 June 22, 2015
Specifications, Continued
Function
Mounting
Housing
Ambient condi tions
GBB… 221 lb-in (25 Nm) GIB… 310 lb-in (35 Nm) Runtime for 90° opening or closing 150 seconds at 50 Hz
125 seconds at 60 Hz Nominal angle of rotation 90° Maximum angular rotation 95°
1/4 to 5/8-inch (6 to 18 mm) square Minimum shaft length 3/4-inch (20 mm)
to the left and right of vertical See Figure 14. NEMA 3R rated when installed with
ASK75.1U Weather Shield in the vertical position. See Accessories.
IP54 according to EN 60 529 Material Die-cast aluminum alloy Gear lubrication Silicone-free
operation -25°F to 130°F (-32°C to 55°C) storage and transport -40°F to 158°F (-40°C to 70°C)
Ambient humidity (non-condensing) 95% rh
Agency certification
cUL certified to Canadian Standard C22.2 No. 24-93
CE conformity:
Low-voltage directive 2006/95/EC
Miscellaneous
Cable length 3 feet (0.9 m) length Life cycle Designed for over 60,000 full strokes
and a minimum of 1.5 million repositions at rated torque and temperature
Noise level <45 dBA (running) Dimensions See Figure 26. Weight 4.4 lbs (2 kg)
Electromagnetic compatibility 2004/108/EC
Siemens Industry, Inc. Page 3
Technical Instructions OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control
ASK71.1U:
OpenAir actuators. Kit should be used for in a foot Kit contains:
Support bearing ring to minimize side
Required mounting fasteners
ASK71.2U:
actuators directly to a damper frame. Kit should be used with louvers and vents and in applications where use of the floor mount kit is not possible. Kit contains:
Support bearing ring to minimize side
Required mounting fasteners
ASK71.3
to provide an auxiliary linear drive. Kit can be used to simultaneously drive a set of opposing or adjacent dampers with a single actuator. Kit contains:
Required mounting fasteners
ASK71.4: Allows economical mounting of an OpenAir actuator to a variety of surfaces. Kit should be used in applications where the actuator can be rigidly surface mounted and a linear stroke output is required. Kit contains:
Document No. 155-177P25 June 22, 2015
Accessories
NOTE: Neither the auxiliary switches nor the feedback potentiometer can be added in
the field. Order the product number that includes these options.
Allows foot mounting of the
-the-air stream applications or anywhere
-mounted actuator can be mounted.
Crank arm for changing angular
Figure 1. Floor Mount Kit.
Figure 2. Frame Mount Kit.
rotation into a linear stroke
loading on the actuator’s output bearing
Mounting bracket
Allows mounting of OpenAir
Crank arm to change the angular rotation into a linear stroke
loading on the actuator’s output bearing
Mounting bracket
Page 4 Siemens Industry, Inc.
Figure 4. Crank Arm Kit with Mounting
Figure 3. Crank Arm Kit.
Bracket.
: Allows a direct-coupled actuator
Crank arm to attach to the splined hub of the shaft adapter
Crank arm to attach to the splined
hub of the shaft adapter
Mounting bracket
Required mounting fasteners
OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control Technical Instructions
Accessories, continued
inch (25 mm) jackshafts that are slightly
Document No. 155-177P25 June 22, 2015
ASK73.1: Bracket provides an extended
Figure 5. Tandem Mount Bracket.
anti-rotation pin that allows two GIB13x OpenAir actuators to directly drive a single damper shaft. For use with three­position actuators.
ASK74.1U: Shaft adapter attaches to a
1.05-inch (26.6 mm) diameter shaft; whereas, the standard self-centering adapter accepts up to a 1.00-inch (25.4 mm) diameter shaft.
Figure 6. Special Shaft Adapter.
Figure 7. NEMA 3R Weather Shield.
Figure 8. NEMA Type 4X Weather Shield.
Adapter can be used for coupling to 1­oversized. Adapter is 13/16-inches (20 mm) shorter than the height of the self­centering shaft adapter.
985-052P20: (no picture) Small shaft insert (package of 20) when using the GIB actuator on a damper shaft less than 3/4-inch (20 mm) diameter.
ASK75.1U: GBB/GIB actuators are UL listed to meet NEMA 3R requirements (a degree of protection against rain, sleet, snow, and damage from external ice formation) when installed with the ASK75.1U Weather Shield and outdoor-rated conduit fittings in the vertical position. For dimensions, see Figure 24.
ASK75.7U: GBB and GIB Actuators are UL listed to meet NEMA Type 4X requirements (a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose­directed water, corrosion, and damage from external ice formation) when installed with an ASK75.7U Weather Shield and outdoor-rated conduit fittings. This weather shield may be mounted in any orientation. For dimensions, see Figure 25.
Siemens Industry, Inc. Page 5
985-106: Provides protection for GIB, GBB and GCA OpenAir actuators in an outside low temperature. Assembly includes:
Weather Shield (ASK75.1U)
Heater Kit (985-105)
Figure 9. Heater/Weather
Shield Assembly.
Loading...