Configurable BI/UI inputs overview 3
Model Chart 5
Network ready 5
Terminal, Identification and Function 6
Terminal identification 6
Wiring 6
Main outputs wiring 7
Typical applications 8
Remote sensor accessories 11
Status display 13
User Interface 14
Local keypad interface 16
Dual occupied setpoints adjustment 16
Single occupied setpoints adjustment 17
Unoccupied and stand-by setpoints adjustments 17
Mode button menu sequence 17
Installer Configuration Parameter Menu 18
Configuration interface 19
Specifications 32
Drawing & Dimensions 33
1 | PIR Ready VT7300 Series-Installation Guide
INSTALLATION
Remove the security screw on the bottom of
the Fan Coil Terminal Equipment Controller
cover.
Open unit by pulling on the bottom
side of Fan Coil Terminal
Equipment Controller (Fig. 1).
Remove wiring terminals from
sticker.
Please read the FCC ID and IC
label installed in the cover upon
removal of cover for the wireless
products.
Location
1.Should not be installed on an
outside wall.
2.Must be installed away from any
direct heat source.
3.Should not be installed near an air
discharge grill.
4.Should not be affected by direct sun
radiation.
5.Nothing should restrict vertical air
circulation to the Fan Coil Terminal
Equipment Controller.
Installation
1.Swing open the Fan Coil Terminal
Equipment Controller PCB to the
left by pressing the PCB locking
tabs (Fig. 2).
2.Pull out cables 6” out from the wall.
3.Wall surface must be flat and clean.
4.Insert cable in the central hole of
the base.
5.Align the base and mark the
location of the two mounting holes
on the wall. Install proper side of
base up.
6.Install anchors in the wall.
7.Insert screws in mounting holes on
each side of the base (Fig. 2).
8.Gently swing back the circuit board
on the base and push on it until the
tabs lock it.
9.Strip each wire 1/4 inch from end.
10. Insert each wire according to wiring
diagram.
11. Gently push excess wiring back into
hole (Fig. 3).
2 | PIR Ready VT7300 Series-Installation Guide
12. Re-Install wiring terminals in their correct locations (Fig. 3).
If replacing an old Terminal Equipment Controller, label the wires
before removal of the old Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulation and installing the Terminal Equipment
Controller.
Short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
Anti-short cycling can be set to 0 minutes for equipment that possess
their own anti cycling timer. Do not use that value unless the
equipment is equipped with such internal timer. Failure to do so can
damage the equipment.
All VT7000 series Terminal Equipment Controllers are to be used only
as operating controls. Whenever a control failure could lead to
personal injury and/or loss of property, it becomes the responsibility of
the user to add safety devices and/or alarm system to protect against
such catastrophic failures.
13. Re-install the cover (top side first) and gently push extra wire length back into the
hole in the wall.
14. Install security screw.
CONFIGURABLE BI/UI INPUTS OVERVIEW
Binary input #1 can be configured for the following functions:
1.(None): No function will be associated with the input
2.(Rem NSB): remote NSB timer clock input. The scheduling will now be set as
per the binary input. It provides low cost setback operation via a dry contact
Contact opened = Occupied
Contact closed = Unoccupied
3.(Motion NO) and (Motion NC): Advanced PIR occupancy functions using a
normally open (NO) or normally closed (NC) remote PIR motion sensor.
Occupancy mode is now set as per applied PIR function and configuration.
Application information and examples are available on document: APP-PIR-Guide-Exx. This document will provide the installers and system designers with
detailed examples on applications, parameter configuration information,
sequence of operation, troubleshooting and diagnostic help required for the
proper usage of the PIR accessory covers
4.(Window) EMS: Forces the system to disable any current heating or cooling
Binary input #2 can be configured for the following functions:
3 | PIR Ready VT7300 Series-Installation Guide
action by the Terminal Equipment Controller. The mode stays the same and the
current setpoints are the same occupied setpoints. Only the outputs are
disabled. There is a Door/Window alarm displayed on the Terminal Equipment
Controller to indicate to the local tenant that the door/window needs to be closed
for cooling or heating to resume. Use NC contact.
Contact opened = System disabled with local Window alarm
Contact closed = System enabled
1.(None): No function will be associated with the input
2.(Door Dry) Door contact & Motion detector: This configuration is only
functional if binary input #1 is set to Motion NO or Motion NC or a PIRaccessory cover is used. With this sequence enabled, the occupancy is now
dictated through those 2 inputs. Any motion detected will set the zone to
occupied status. The zone will remain permanently in occupied mode until the
door contact switch opens momentarily. The Terminal Equipment Controller will
then go in stand-by mode. If more movements are detected, the occupied mode
will resume. While the door is opened, any movements detected by the remote
PIR sensor or the PIR accessory cover will be ignored. Use a Normally Closed
contact switching device.
Contact opened = Door opened
Contact closed = Door closed
3.(RemOVR): temporary occupancy remote override contact. This function
disables the central button override function on the Terminal Equipment
Controller. The override function is now controlled by a manual remote
momentarily closed contact. When configured in this mode, the input operates in
a toggle mode. It is now possible to toggle between unoccupied & occupied
setpoints for the amount of time set by parameter (TOccTime) temporary
occupancy time.
4.(Filter): a backlit flashing Filter alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied to a
differential pressure switch that monitor filters
Contact opened = No alarm
Contact closed = Alarm displayed
5.(Service): a backlit flashing Service alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
Universal input #3 can be configured for the following functions:
1.(None): No function will be associated with the input
2.(COC/NH) Change over dry contact. Normally Heat: Used for hot / cold air /
water change over switching in 2 pipe systems.
Contact closed = Cold air / water present
Contact opened = Hot air / water present
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
3.(COC/NC) Change over dry contact. Normally Cool: Used for hot / cold air /
water change over switching in 2 pipe systems.
Contact closed = Hot air / water present
Contact opened = Cold air / water present
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
4.(COS) Change over analog sensor: Used for hot / cold air / water change over
switching in 2 pipe systems.
4 | PIR Ready VT7300 Series-Installation Guide
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
If temperature is > 77 °F = Hot air / water present
If temperature is < 75 °F = Cold air / water present
5.(SS) Supply air sensor monitoring: Used for supply air temperature
monitoring.
Only used for network reporting of the supply air temperature. Has no internal
function in the Terminal Equipment Controller.
MODEL CHART
Network ready
5 | PIR Ready VT7300 Series-Installation Guide
All Viconics VT7300 series Terminal Equipment Controllers are designed for
1- High Fan SpeedFan-H1- High Fan SpeedFan-H
2- Medium Fan SpeedFan-M2- Medium Fan SpeedFan-M
3- Low Fan SpeedFan-L3- Low Fan SpeedFan-L
4- 24 V~ Hot24 V~ Hot4- 24 V~ Hot24 V~ Hot
5- 24 V~ Com24 V~ Com5- 24 V~ Com24 V~ Com
6- Aux BO 5BO 5-Aux6- Aux BO 5BO 5-Aux
7- Aux BO 5BO 5-Aux7- Aux BO 5BO 5-Aux
8- BO 3 Open HeatBO 3
9- BO 4 Close HeatBO 49- AO 2 HeatAO 2
10- BO 1 Open CoolBO 1 10- AO 1 CoolAO 1
11- BO 2 Close CoolBO 2Not used BlankBlank
12- BI #1BI 112- BI #1BI 1
13- RSRS13- RSRS
14- ScomScom14- ScomScom
15- BI #2BI 215- BI #2BI 2
16- UI #3 COS / COC /SSUI 3
16- UI #3 COS / COC /SS
UI 3
Fan-H
Fan-M
Fan-L
24 V~ Hot
24 V~ Com
24 V~ transformer relay pack
3 speed 2 speed Single speed
High
Med
Low
High
Low
High
Power & Fan ( All models )
stand-alone (Network Ready) operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
o VCM7000V5000W,Terminal Equipment Controller wireless
communication adapter
o VCM7300V5000B, Terminal Equipment Controller BACnet™ MS-TP
communication adapter
o VCM7300V5000E, Terminal Equipment Controller Lontalk™