Schneider Electric TSXCUSBMBP User Manual

TSXCUSBMBP USB Modbus Plus
Communications Adapter User Manual
35011984 eng
2

Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 Glossary of Abbreviations and Acronyms . . . . . . . . . . . . . . . . .9
Glossary of Abbreviations and Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Modbus Plus Communication for Applications . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Modbus Plus Network Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
TSXCUSBMBP Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 3 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Upgrading From Previous Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Installing the TSXCUSBMBP Driver Software. . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installing the TSXCUSBMBP Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Chapter 4 Establishing a Connection to the TSXCUSBMBP . . . . . . . . . . 19
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Rescan Adapters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Show Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 5 Configuring the TSXCUSBMBP Driver . . . . . . . . . . . . . . . . . . .21
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
The TSXCUSBMBP Driver Interface Window. . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Configuring the Modbus Plus Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Configuring the Slave Response Timeout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Configuring the Virtual Serial (COM) Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Configuring the Modbus Plus Routing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3
Chapter 6 Connecting to a Modbus Plus Network . . . . . . . . . . . . . . . . . . 33
Modbus Plus Network Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 7 Using the TSXCUSBMBP with an Application . . . . . . . . . . . . 35
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Start the TSXCUSBMBP Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Configure the Application Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Connect!. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Chapter 8 Modbus Plus Network Diagnostic Functions . . . . . . . . . . . . . 39
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.1 Starting the Diagnostic Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Procedure for Starting the Diagnostic Functions . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.2 Scanning the Modbus Plus Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Procedure for Scanning the Modbus Plus Network . . . . . . . . . . . . . . . . . . . . . . . 42
8.3 Displaying Diagnostic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Procedure for Displaying Diagnostic Information. . . . . . . . . . . . . . . . . . . . . . . . . 44
Node Error Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Node Personality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Internal Path Transactions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Token Owner Work Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Active Station Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Token Station Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Global Data Present Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Read Global Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Appendix A TSXCUSBMBP Settings for Unity. . . . . . . . . . . . . . . . . . . . . . . 57
TSXCUSBMBP Settings for Unity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Appendix B TSXCUSBMBP Settings for Concept & ProWORX32 . . . . . . . 61
TSXCUSBMBP Settings for Concept & ProWORX32 . . . . . . . . . . . . . . . . . . . . . 61
4

Safety Information

Important Information
§
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or equipment damage.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
35011984 02/2006 5
Safety Information
PLEASE NOTE
Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons.
© 2006 Schneider Electric. All Rights Reserved.
6
35011984 02/2006

About the Book

At a Glance
Document Scope This document provides an installation, setup and usage guide for the Schneider
Automation TSXCUSBMBP (USB Modbus Plus) communications adapter.
It describes the basic procedures required to
z install the hardware,
It describes the basic procedures required to install the hardware, install and configure the driver software, access the TSXCUSBMBP from a software application, and use the Modbus Plus network diagnostics features of the driver software.
z install and configure the driver software, z access the TSXCUSBMBP from a software application, and z use the Modbus Plus network diagnostics features of the driver software.
Validity Note The information in this manual is applicable only for TSXCUSBMBP
communications adapters.
Product Related Warnings
Schneider Electric assumes no responsibility for any errors that appear in this document. No part of this document may be reproduced in any form or means, including electronic, without prior written permission of Schneider Electric.
User Comments We welcome your comments about this document. You can reach us by e-mail at
techpub@schneider-electric.com
35011984 02/2006 7
About the Book
8
35011984 02/2006

Glossary of Abbreviations and Acronyms

1
Glossary of Abbreviations and Acronyms
Introduction This glossary provides an expansion of abbreviations and acronyms used in this
documentation.
Glossary of Abbreviations and Acronyms
The following table lists all abbreviations and acronyms and their respective expansions.
Abbreviation/Acronym Expansion
MBP Modbus Plus
MB+ Modbus Plus
MODBUS+ Modbus Plus
USB Universal Serial Bus
VSP Virtual Serial Port
WinNT Windows NT
WinXP Windows XP
SP2 Service Pack 2
Win2k Windows 2000
35011984 02/2006 9
Abbreviations & Acronyms
10
35011984 02/2006
At a Glance

Overview

2
Subject of this chapter
What's in this Chapter?
The TSXCUSBMBP communications adapter is designed to provide a bridge between a simple and inexpensive USB connection and a Modbus Plus Network. The device is a combination of hardware (TSXCUSBMBP) and software drivers (TSXCUSBMBP Driver and Virtual Serial Port) that operate together as a single entity.
The TSXCUSBMBP has its own Modbus Plus Node Address on the Modbus Plus network, which is set via the TSXCUSBMBP Driver software.
The TSXCUSBMBP provides two areas of functionality. The first one allows software applications using serial Modbus RTU communications to communicate on a highspeed Modbus Plus network. The second one provides diagnostic tools for a Modbus Plus network.
This chapter contains the following topics:
Topic Page
Modbus Plus Communication for Applications 12
Modbus Plus Network Diagnostics 13
TSXCUSBMBP Hardware 13
35011984 02/2006 11
Overview
Modbus Plus Communication for Applications
Introduction Most Win32 applications that support serial Modbus communications can
communicate on a Modbus Plus network with the TSXCUSBMBP.
Virtual Serial Port (VSP)
Modbus Plus Communication­Process
A Virtual Serial Port (VSP) is used as the mechanism for redirecting communications from programs such as Concept, Unity, and ProWorx32 to the TSXCUSBMBP adapter. The VSP presents the same interface as a standard serial port to the software. As such it is indistinguishable from a physical serial port.
The Modbus Plus Communication process is described in the following table:
Stage Description
1 After the VSP is installed, it will create one serial port with the port reference (COM1-
COM12) defined in the TSXCUSBMBP Driver software.
2 When configuring the Modbus application software, this port reference for the VSP
is selected as the serial port for the application to use.
3 The TSXCUSBMBP Driver will then work like a Bridge Multiplexer to redirect serial
Modbus Plus messages onto a Modbus Plus network, but at a much faster rate since no serial communications are actually taking place.
Illustration:
Windows XP
Operating System
Modbus Plus Network
Application
Software
Virtual
Serial Port
Driver
TSX C
USB MBP
Driver
USB-MBP
Driver
USB
Controller
USB
Cable
USB-MBP
Routing Table A routing table similar to that used by Modicon's BM85 Bridge Multiplexer is used to
associate Modbus Slave IDs with 5-byte Modbus Plus routing paths. This allows the application software to communicate with any Modbus Plus device within range on a Modbus Plus network.
12
35011984 02/2006
Overview
Modbus Plus Network Diagnostics
TSXCUSBMBP The TSXCUSBMBP provides a diagnostic tool for Modbus Plus networks. It has the
same basic functionality as the MBPSTAT program but adds the ability to scan a complete Modbus Plus network.
TSXCUSBMBP Hardware
Description The TSXCUSBMBP consists of a box with a USB cable extending from one end for
connection to a PC, and a standard Modbus Plus DB9 connector on the other end for connection to a Modbus Plus network.
LEDs in the top cover of the device indicate the presence of power from the USB port and the status of the Modbus Plus connection. No external power supply is needed.
Illustration
Modbus Plus Cable
ODBUS PLUS STATUS
35011984 02/2006 13
USB
POWER
MODBUS PLUS
PC
USB
Port
Overview
14
35011984 02/2006
At a Glance

Installation

3
Subject of this chapter
What's in this Chapter?
This section describes the procedures required to install the TSXCUSBMBP Driver software and the TSXCUSBMBP communications adapter.
Note: Do not attach the TSXCUSBMBP device to a USB port until installation of the Driver Software is complete.
This chapter contains the following topics:
Topic Page
Installation Requirements 16
Upgrading From Previous Version 16
Installing the TSXCUSBMBP Driver Software 17
Installing the TSXCUSBMBP Hardware 17
35011984 02/2006 15
Installation
Installation Requirements
Installation Requirements list
Installation requirements are as follows:
z Microsoft Windows XP Operating System with Service Pack 2 or greater installed
(Windows 2000 with Service Pack 4 or greater can also be used on most computers),
z 1 MB free disk space, z at least 256 MB RAM, z at least one free USB port or a USB Hub supporting USB 1.1 or greater.
Upgrading From Previous Version
Introduction Currently, if a previous version of the TSXCUSBMBP Driver has been installed, the
Virtual Serial Port component of the driver must be manually uninstalled using
Device Manager before a new version can be installed.
How to uninstall the Virtual Serial Port?
These steps must be followed to uninstall the Virtual Serial Port from your system.
Step Action
1 Close any software applications using the TSXCUSBMBP Driver.
2 Exit the TSXCUSBMBP Driver by right clicking on the Icon at the bottom then
selecting Exit Driver.
3 Unplug the USB Modbus Plus Device from the USB port on the computer (or USB
Hub if using one).
4 Start up the Windows Device Manager.
On most systems, this is done by the following steps.
z Open Control Panel, System, Hardware, then Device Manager. z In Device Manager, left click on the + next to ABT Virtual Device. Virtual Serial
Port will now appear underneath ABT Virtual Device.
z Right click on Virtual Serial Port and select Uninstall. z When prompted, confirm the device removal. z After ABT Virtual Device disappears from the list, close the Device Manager.
16
35011984 02/2006
Installation
Installing the TSXCUSBMBP Driver Software
Introduction The TSXCUSBMBP Driver must be installed before connecting the TSXCUSBMBP
device to the USB port.
How to install the TSXCUSBMBP Driver?
Use the following procedure to install the Driver software.
Step Action
1 Insert the CD-ROM labeled TSXCUSBMBP Driver into your CD-ROM drive.
2 The installation should begin automatically. If not, follow the procedure below to start
the installation manually.
z From the Start menu (Start button on Windows XP task bar), select Run z Type in D:\Setup.exe (if your CD-ROM drive is not D:, substitute the drive letter of
your CD-ROM drive) and press Ok.
3 Follow the on-screen instructions to complete the software installation.
4 The final step of the software installation will display a message window containing
instructions. Please read the instructions carefully.
Installing the TSXCUSBMBP Hardware
Introduction The TSX C USB MBP can be connected directly to a USB port on the PC or
through a USB Hub. The TSXCUSBMBP acquires power from the USB port or Hub, therefore no power connection is required.
Note: Do not connect the Modbus Plus network cable to the Modbus Plus port on the TSXCUSBMBP until after the Modbus Plus Node Address has been configured in the Driver Software. This will avoid the potential for duplicate Modbus Plus node addresses on your network.
35011984 02/2006 17
Installation
How to install the TSXCUSBMBP Hardware
Use the following procedure to install the TSXCUSBMBP hardware.
Step Action
1 After installing the TSXCUSBMBP Driver software, insert the USB cable from the
TSXCUSBMBP into a USB port on the PC or into a USB Hub connected to the PC. Once the TSXCUSBMBP is connected to the PC or Hub, the Power LED on the TSXCUSBMBP will light. This indicates that the TSXCUSBMBP is getting power from the USB port or Hub.
2
If this is the first time the TSXCUSBMBP has ever been connected to the USB port or Hub, the
Found New Hardware
up. If this occurs, follow these steps to complete the hardware installation:
z Select No, not this time when the message Can Windows connect to Windows
Update pops up, then click on Next.
z Select Install the software automatically (Recommended) when the message
What do you want the wizard to do? pops up, then click on Next.
z If the message The software you are installing has not passed Windows Logo
Testing pops up, select Continue Anyway. When finished, click on Finish.
z The Found New Hardware message will pop up again followed by the New
Hardware Wizard.
z Select No, not this time when the message Can Windows connect to Windows
Update pops up, then click on Next.
z Select Install the software automatically (Recommended) when the message
What do you want the wizard to do? pops up, then click on Next.
z If the message The software you are installing has not passed Windows Logo
Testing pops up, select Continue Anyway.
z When the wizard has finished installing the software, click on Finish. z Wait for the Found New Hardware message to pop up with Your new hardware
is ready to use.
3 Restart the computer.
message will pop up and the
New Hardware Wizard
will start
18
35011984 02/2006
At a Glance

Establishing a Connection to the TSXCUSBMBP

4
Subject of this chapter
Status of the Driver
What's in this Chapter?
The TSXCUSBMBP Driver is added to the Startup group during installation. After restarting the computer at the end of the hardware installation, the driver will automatically start and will continue to do so each time the computer is powered up or restarted.
If the TSXCUSBMBP Driver is ever removed from the Startup menu, you will need to start the driver manually by going to the Programs menu and selecting Schneider Electric then TSXCUSBMBP then TSXCUSBMBP Driver. The TSXCUSBMBP Driver allows for only one instance of it to run at any time, so starting it multiple times is not a concern.
When the TSXCUSBMBP Driver is running, an icon will appear in the system tray of the computer to indicate the status of the driver, as shown in the table below.
Icon Color Status of the driver
normal A TSXCUSBMBP was found.
red No TSXCUSBMBP was found.
yellow A TSXCUSBMBP was found, and is in the process of initializing and
connecting to a Modbus Plus network.
This chapter contains the following topics:
Topic Page
Rescan Adapters 20
Show Interface 20
35011984 02/2006 19
Establishing a Connection
Rescan Adapters
Introduction
If the TSXCUSBMBP device was not connected to the PC when the TSXCUSBMBP Driver started up, it will be necessary to rescan for a connected TSXCUSBMBP adapter before the driver will detect its presence. A red icon in the system tray will indicate this.
How to rescan? To rescan, right click on the icon in the system tray and select Rescan Adapters. The
driver should then find the TSXCUSBMBP, and the icon will turn yellow for several seconds while the TSXCUSBMBP initializes and listens to the Modbus Plus network. It will then go to normal operation.
If the icon remains red...
If the icon in the tray remains red following a rescan, check your USB connection and make sure the appropriate USB drivers are installed and enabled on your computer.
Show Interface
Introduction
How to display the Interface Window?
As long as the TSXCUSBMBP driver is running, the driver Interface Window can be displayed to show driver configuration and connection information. It does not matter if the TSXCUSBMBP driver has established a connection with the TSXCUSBMBP device or not (the color of the icon in the system tray does not matter).
To display the Interface Window, right click on the icon in the tray and select Show Interface.
20
35011984 02/2006
At a Glance

Configuring the TSXCUSBMBP Driver

5
Subject of this Chapter
What's in this Chapter?
This chapter describes how to configure the TSXCUSBMBP driver.
This chapter contains the following topics:
Topic Page
The TSXCUSBMBP Driver Interface Window 22
Configuring the Modbus Plus Node Address 23
Configuring the Slave Response Timeout 24
Configuring the Virtual Serial (COM) Port 26
Configuring the Modbus Plus Routing 27
35011984 02/2006 21
Configuring the TSXCUSBMBP Driver
The TSXCUSBMBP Driver Interface Window
Introduction The Interface Window is used to configure the TSXCUSBMBP driver and device. It
also has a message area where status and error information is displayed.
Interface Window Display
To display the Interface Window:
z right click on the TSXCUSBMBP icon in the system tray and z select Show Interface.
The Interface Window is displayed hereunder:
22
35011984 02/2006
Configuring the Modbus Plus Node Address
Configuring the TSXCUSBMBP Driver
Address Assignment
Address Configuration
Address Changing Process
The TSXCUSBMBP communications adapter must be assigned a Modbus Plus Node Address in order to communicate on the Modbus Plus network.
The Modbus Plus Node Address assignment window is displayed:
To configure the Modbus Plus Node Address of the TSXCUSBMBP device:
Step Action
Select
Settings
1
2 Type the new address into the field labeled Modbus+ Node Address
3 Click on the Save button to save the new address.
from the top level menu of the TSXCUSBMBP Driver Interface Window
After the Save button is pressed, the process of changing the Modbus+ Node address of the TSXCUSBMBP device will begin.
To complete this process, the TSXCUSBMBP device must be reinitialized.
z An information window will pop up, designating that the node address is being
changed, and it will take approximately 10 seconds to complete the process.
z Click on OK to exit the information window.
The Settings Menu will remain disabled until the process of changing the node address is complete.
After the process has completed, the Modbus Plus cable can be connected to the TSXCUSBMBP device without risk of a duplicate Modbus+ node address on the network.
35011984 02/2006 23
Configuring the TSXCUSBMBP Driver
Configuring the Slave Response Timeout
Introduction The Slave Response Timeout is used by the TSXCUSBMBP each time it sends a
request from an application out the Modbus Plus network to a slave device.
Slave Response Timeout
This timeout is variable due to the possibility of a radio link or serial link somewhere in between the TSXCUSBMBP device and the slave device it is communicating with:
z The interface between the application and the TSXCUSBMBP driver has the
same characteristics of an actual serial port.
z One request must be completed before another request can be sent out. z If the slave device does not respond to the TSXCUSBMBP, it must time out from
waiting on the response before it can accept another request from the application.
Timeout Value The value for the Slave Response Timeout needs to be determined by adding
together the following times:
1. The maximum amount of time it can take for a request to be sent to any slave
device that the TSXCUSBMBP will be communicating with. This time must include any delays induced by modems, RF links, network bridges, etc.
2.
The maximum amount of time it can take for any slave device to process a request.
Note:
Start operations on certain PLCs can take as long as 4 seconds or more to
process. If the Slave Response Timeout value is lower than this, timeouts may occur.
3. The maximum amount of time it can take for a response to be sent from any slave
device back to the TSXCUSBMBP. This time must include any delays induced by modems, RF links, network bridges, etc.
4. Some additional time to provide a ‘safety zone’ to allow for the ‘unexpected’. A
value of 500 ms is adequate if all slave devices are connected on the local Modbus Plus network or through a high-speed bridge. If any slower network interfaces are in the communication path between the TSXCUSBMBP and any slave device, an adequate value is usually between 1000 and 2000 ms. Note: When performing a Modbus network scan using ProWorx or Concept, changing the Slave Response Timeout value from its default of 5000 ms to 600 ms before the scan will greatly improve performance. However, the Slave Response Timeout must be set back to the proper value before attaching to a PLC in programming mode and performing Start operations.
24
35011984 02/2006
Configuring the TSXCUSBMBP Driver
Timeout Configuration
Once the appropriate value has been determined, the Slave Response Timeout is configured as follows:
Step Action
1
Select
Settings
from the top level menu of the TSXCUSBMBP Driver Interface Window.
2 Type the appropriate timeout value into the field labeled Slave Response Timeout.
3 Click on the Save button to save the new Slave Response Timeout.
Timeout Saving A new Slave Response Timeout saving window is displayed:
Note: When the Save button is pressed, the new timeout setting will take effect immediately.
35011984 02/2006 25
Configuring the TSXCUSBMBP Driver
Configuring the Virtual Serial (COM) Port
Introduction The Virtual Serial Port used by the application to send Modbus requests to the
TSXCUSBMBP Driver will default to COM3 during installation.
COM3 Assignment
If another device is already installed on COM3, the Virtual Serial Port will need to be changed.:
If... Then...
another device is already installed on COM3
the Virtual Serial Port will need to be changed
Port Changing To change the port reference for the Virtual Serial Port in the application:
1 If an application is open that is using the Virtual Serial Port to communicate with the
TSXCUSBMBP, it should be closed.
2Select Virtual Modbus Port from the top level menu on the TSXCUSBMBP Driver
Interface Window.
3 Select the desired COM port from the list of available COM ports.
4 Click on the Save button to save the new setting.
Note: The new setting will take effect immediately upon pressing the Save button. The application being used with the TSXCUSBMBP must be configured to communicate using the serial port configured here.
26
35011984 02/2006
Configuring the Modbus Plus Routing
Configuring the TSXCUSBMBP Driver
Introduction
Addressing Methods
When interfacing to an application through the Virtual Serial Port, the TSXCUSBMBP operates as a serial Modbus to Modbus Plus converter, similar to the BM85 Bridge Multiplexer. The Virtual Serial Port captures serial Modbus RTU messages sent by a Modbus application and redirects them to the TSXCUSBMBP driver. The driver then converts each message from the Modbus RTU format into the Modbus Plus format before sending it out onto the network and waiting for a response.
When converting a Modbus RTU request to Modbus Plus, the driver must convert a single Modbus ID into a 5-byte Modbus Plus routing path. The TSXCUSBMBP driver supports three different methods of doing this:
1. Explicit Addressing,
2. Direct Addressing,
3. Implicit Addressing.
The first method, known as Explicit Addressing, uses the TSXCUSBMBP driver's Modbus Routing Table. A unique Modbus ID (also known as Modbus Slave Address or Modbus Slave ID) is assigned by the user to each Modbus Plus device that will be accessed from a Modbus application. An entry is then made into the Modbus Routing Table that specifies the Modbus Plus Routing path to use whenever a Modbus application sends a Modbus RTU message to that Modbus ID.
The second and third methods use the value of the Modbus ID to generate the Modbus Plus routing path according to a predefined set of rules. These methods include Direct Addressing and Implicit Addressing, where the actual addressing type used is determined by the range of values that the Modbus ID falls into. Direct Addressing and Implicit Addressing are only used when an entry does not exist in the Modbus Routing Table for a Modbus ID.
The Explicit, Direct, and Implicit addressing methods are the same methods used by the BM85 Bridge Multiplexer.
Before configuring
Before configuring the Modbus Plus routing
1. make a complete list of all Modbus Plus nodes that will be accessed from Modbus applications. Do not include any Modbus Plus nodes that will be accessed only with the Diagnostic functions of the TSXCUSBMBP,
2. determine which nodes can be accessed using Direct Addressing or Implicit Addressing (see below). The Modbus Routing Table has a maximum size of 64 entries and using Direct or Implicit Addressing where possible will limit the number of table entries that must be used,
3. assign Modbus IDs to all remaining Modbus Plus nodes before entering them into the Modbus Routing Table where Explicit Addressing will be used.
35011984 02/2006 27
Configuring the TSXCUSBMBP Driver
1. Explicit Addressing
2. Direct Addressing
3. Implicit Addressing
The Explicit Addressing process is described as follows:
z Explicit Addressing is used whenever the Modbus ID in a message received
through the Virtual Serial Port is present in the Modbus Routing Table, regardless of what range of values the Modbus ID falls into. In Explicit Addressing, the routing path will be the one that was entered into the Modbus Routing Table for the Modbus ID of the received message.
z Any value can be selected for the Modbus ID as long as it does not conflict with
any Modbus IDs currently used by the application for Direct Addressing or Implicit Addressing. However, it is helpful for each Modbus ID to have some correspondence in value to the Modbus Plus node that it will be used to access.
z If no Modbus Plus node addresses are duplicated in the network (same
Modbus Plus node address used on more than one local network if separated by Bridge Plus devices), the Modbus IDs to use for Explicit Addressing can be the actual Modbus Plus node addresses.
The Direct Addressing process is described as follows:
z If the Modbus ID in a message received through the Virtual Serial Port is not
present in the Modbus Routing Table and it is in the range of 1-64, the TSXCUSBMBP Driver will use Direct Addressing.
z In Direct Addressing, the Modbus ID of the received message is used directly as
the 1st byte of the routing path, and the remaining 4 bytes are set to 0.
z For example, a Modbus ID of 2 would be routed to [2.0.0.0.0], and a Modbus ID
of 45 would be routed to [45.0.0.0.0]
The Implicit Adressing process is described as follows:
z If the Modbus ID in a message received through the Virtual Serial Port is not
present in the Modbus Routing Table and it is in the range of 80-255, Implicit Addressing will be used.
z When the TSXCUSBMBP driver uses Implicit Addressing, it divides the Modbus
ID of the received message by 10. The quotient is used as the 1st byte of the routing path, the remainder is used as the 2nd byte of the routing path, and the remaining 3 bytes are set to 0. For example, a Modbus ID of 87 would be routed to [8.7.0.0.0], and a Modbus ID of 230 would be routed to [23.0.0.0.0].
28
35011984 02/2006
Routing Example Routing example:
Configuring the TSXCUSBMBP Driver
5
TSX­CUSB
15
PLC
16
PLC
23
Bridge Plus
43
Bridge Plus
9
10
5
1
PLC
2
PLC
3
PLC
PLC
6
20
20
Bridge Plus
The following table shows the routing table entries that must be made to route messages to the PLCs at Modbus Plus Node Addresses 1, 2, 3, 10, 15, and 16.
Modbus + Node Address
10 10 Modbus ID 10,
Slave ID used by application
1 231 None Required 23.1.0.0.0 as determined through Implicit Addressing If desired, Explicit
2 232 None Required 23.2.0.0.0 as determined through Implicit Addressing If desired, Explicit
3 233 None Required 23.3.0.0.0 as determined through Implicit Addressing If desired, Explicit
6 26 Modbus ID 26,
TSXCUSBMBP Routing Table Entry
Routing Path
23.20.6.0.0
Routing Path
43.10.0.0.0
Modbus Plus Routing Path
Addressing could be used by selecting an unused Modbus ID and placing an entry for that Modbus ID into the Routing Table going to
23.1.0.0.0
Addressing could be used by selecting an unused Modbus ID and placing an entry for that Modbus ID into the Routing Table going to
23.2.0.0.0
Addressing could be used by selecting an unused Modbus ID and placing an entry for that Modbus ID into the Routing Table going to
23.3.0.0.0
23.20.6.0.0 as determined through Explicit Addressing from the Modbus Routing Table
43.10.0.0.0 as determined through Explicit Addressing from the Modbus Routing Table
PLC
35011984 02/2006 29
Configuring the TSXCUSBMBP Driver
Modbus + Node Address
Slave ID used by application
TSXCUSBMBP Routing Table Entry
Modbus Plus Routing Path
15 15 None Required 15.0.0.0.0 as determined through Direct AddressingIf desired, Explicit
Addressing could be used by selecting an unused Modbus ID and placing an entry for that Modbus ID into the Routing Table going to
15.0.0.0.0
16 16 None Required 16.0.0.0.0 as determined through Direct AddressingIf desired, Explicit
Addressing could be used by selecting an unused Modbus ID and placing an entry for that Modbus ID into the Routing Table going to
16.0.0.0.0
30
35011984 02/2006
Configuring the TSXCUSBMBP Driver
Entering Routing Paths into the Routing Table
Use the following procedure to change an entry in the Routing Table:
Step Action
1
Select
Routing
from the top level menu on the TSXCUSBMBP Driver Interface window.
2 Select the entry to be changed in the table by left clicking on it (the entry will become
highlighted)
3 Enter the Modbus ID and the associated Modbus Plus Routing Path in the fields below
the table.
4 Click on the Update button to update that entry in the table. You will see the entry in
the table above change to the new values.
5 Repeat steps 2-4 for each entry to change in the Routing table.
Note: Clicking on the Close button will save all Routing Table entries and return to the top level menu. The new Routing Table will take effect immediately.
35011984 02/2006 31
Configuring the TSXCUSBMBP Driver
32
35011984 02/2006
Connecting to a Modbus Plus Network
6
Modbus Plus Network Status Indicator
Introduction The Modbus Plus Network Status Indicator displays the status of the Modbus Plus
communications on the TSXCUSBMBP device.
During initial monitoring of the network, the Indicator will flash at approximately 1 time/second. If successful Modbus Plus communications are established, it will flash more rapidly, approximately 6 times/second. Otherwise, it will flash an error code, indicating that there is a problem with the connection.
Flash Codes The table below indicates the valid flash codes for the Modbus Plus Network Status
Indicator:
LED Flash Code Description
6 flashes/second The TSXCUSBMBP is successfully receiving and passing the token on
the Modbus Plus network. This is the normal operating mode for a node on a Modbus Plus network.
1 flash/second
2 flashes, then pause
3 flashes, then pause
4 flashes, then pause
The TSXCUSBMBP is offline, and monitoring the Modbus Plus network to determine which nodes are active prior to attempting to join the network.
The TSXCUSBMBP can hear the token being passed, but never receives the token.
The TSXCUSBMBP cannot hear the token being passed. This is the flash code to expect if the Modbus Plus cable is not connected to the TSXCUSBMBP.
The TSXCUSBMBP has detected another node on the Modbus Plus network using the same node address as the TSXCUSBMBP. The TSXCUSBMBP will remain in this state until it has not heard any messages from any other node with the same node address for at least 5 seconds.
35011984 02/2006 33
Connecting to a Modbus Plus Network
34
35011984 02/2006
Overview

Using the TSXCUSBMBP with an Application

7
The TSXCUSBMBP with an Application
What's in this Chapter?
The TSXCUSBMBP is designed to interface with any Win32 application software that communicates using serial Modbus RTU over a user-selectable COM port. The application must be running under Windows XP or in some cases, Windows 2000.
The following general procedure can be used with any applicable application software.
Note: Refer to the appendix for more detailed instructions on using the TSXCUSBMBP with Unity, Concept and Proworx32.
This chapter contains the following topics:
Topic Page
Start the TSXCUSBMBP Driver 36
Configure the Application Software 37
Connect! 37
35011984 02/2006 35
Using the TSXCUSBMBP with an Application
Start the TSXCUSBMBP Driver
Introduction Before an application can communicate through the TSXCUSBMBP, the
TSXCUSBMBP Driver must:
z be running, and z be connected to a TSXCUSBMBP device.
Note: See Sections 4 and 5 of this User's Guide for more information on installing and setting up the TSXCUSBMBP Driver.
36
35011984 02/2006
Using the TSXCUSBMBP with an Application
Configure the Application Software
Introduction Because the software interface to the TSXCUSBMBP uses a Virtual Serial Port, it is
relatively simple to configure an application to use it for communications.
A Typical Configuration
The following steps illustrate a typical configuration:
Step Action
1 Determine which serial (COM) port the TSXCUSBMBP Driver is using.
This information is displayed automatically whenever the mouse hovers over the TSXCUSBMBP Driver icon in the system tray, as shown in the example below:
TSXCUSBMBP (Device Status) Port: COM3
2 In the application's configuration, select the serial port shown (COM3 in the example
above). Note: Don't worry about Baud Rate, Parity, etc. - the Virtual Serial Port ignores those settings.
3 Select standard Modbus RTU for the protocol.
Connect!
Introduction Tell the application software to connect, just as if it were connecting to a hardware
serial port. The TSXCUSBMBP Driver will handle the rest.
35011984 02/2006 37
Using the TSXCUSBMBP with an Application
38
35011984 02/2006
At a Glance
Modbus Plus Network Diagnostic Functions
8
Subject of this Chapter
What's in this Chapter?
This chapter describes the Modbus Plus network diagnostic functions.
This chapter contains the following sections:
Section Topic Page
8.1 Starting the Diagnostic Functions 41
8.2 Scanning the Modbus Plus Network 42
8.3 Displaying Diagnostic Information 43
35011984 02/2006 39
Modbus Plus Network Diagnostic Functions
40
35011984 02/2006
Modbus Plus Network Diagnostic Functions

8.1 Starting the Diagnostic Functions

Procedure for Starting the Diagnostic Functions
Introduction This section describes how to start the diagnostic functions of the TSXCUSBMBP.
Procedure To start the diagnostic functions of the TSXCUSBMBP proceed as follows:
Step Action
1 Right click on the TSXCUSBMBP Icon in the system tray.
2 Select Show Interface.
Result: the Interface Window of the TSXCUSBMBP driver opens.
3 Left click on the MB+ Network Diags heading on the top-level menu.
Result: the Modbus Plus Network Diagnostics screen will then be displayed:
35011984 02/2006 41
Modbus Plus Network Diagnostic Functions
8.2 Scanning the Modbus Plus Network
Procedure for Scanning the Modbus Plus Network
Introduction When the Diagnostics screen is first displayed, the only node that will appear in the
list of Modbus Plus Network nodes is the TSXCUSBMBP device itself. A Scan function is used to locate other nodes on the network.
Scanning Local or Complete Network
A scan can be done on either the local Modbus Plus network or the complete Modbus Plus network.
z When scanning the local network, Bridge Plus devices will be shown in the list but
no scanning will be done on the second network connection on the Bridge Plus.
z When the complete Modbus Plus network is scanned, every Modbus Plus device
accessible from the TSXCUSBMBP device will be shown. Note: The complete network scan is performed as follows:
z The system sequentially queries each address. z The system sends a query to address 1. If a reponse is obtained, the
information is displayed and the system sends a request to the next address. If the device is not connected to the network the system waits for a defined timeout period before moving on to the next address.
z Address polling may be time consuming. For example, depending on the
network arcitecture (number of devices connected or disconnected) identifying 247 devices can take up to 12 minutes.
Modbus ID Field If a node displayed in the scan list has been entered into the routing table used by
application software to route messages for a specific Modbus ID to that Modbus Plus node, the Modbus ID used by the application will be shown in the Modbus ID field for that node.
42
35011984 02/2006
Modbus Plus Network Diagnostic Functions

8.3 Displaying Diagnostic Information

At a Glance
Introduction
What's in this Section?
This section describes the diagnostic information that can be displayed for each node.
This section contains the following topics:
Topic Page
Procedure for Displaying Diagnostic Information 44
Node Error Statistics 46
Node Personality 47
Internal Path Transactions 48
Token Owner Work Table 49
Active Station Table 50
Token Station Table 51
Global Data Present Table 52
Read Global Data 53
35011984 02/2006 43
Modbus Plus Network Diagnostic Functions
Procedure for Displaying Diagnostic Information
Introduction After the Modbus Plus network has been scanned, the nodes are displayed in the
Modbus Plus Network Diagnostics screen.
Modbus Plus Network Diagnostics Screen
Structure of the Modbus Plus Network Diagnostics screen:
1
2
1 Node Selected for Display field. 2 Diagnostic data types buttons.
44
35011984 02/2006
Modbus Plus Network Diagnostic Functions
Procedure To display the diagnostic information from a node proceed as follows:
Step Action
1 Select the node to display diagnostic information from by scrolling to it in the list and
clicking the mouse on it.
Results:
z the node is highlighted, z the routing path for that item is shown in the Node Selected for Display field.
2 Click on the appropriate diagnostic data types button (Node Error Statistics, Node
Personality, Read Global Data, etc.)
Result: the information is read from the selected node and displayed in a new screen. Note: the data on that screen is continually updated as long as the screen is open.
35011984 02/2006 45
Modbus Plus Network Diagnostic Functions
Node Error Statistics
Introduction This section describes the Node Error Statistics screen.
Node Error Statistics Screen
The Node Error Statistics screen displays the error counters that are returned in the Modbus Plus diagnostics data for the selected node:
The counters can be cleared by clicking on the Clear Error Counters button.
46
35011984 02/2006
Modbus Plus Network Diagnostic Functions
Node Personality
Introduction This section describes the Node Personality screen.
Node Personality Screen
The Node Personality screen displays the type, version, and status of the selected node:
35011984 02/2006 47
Modbus Plus Network Diagnostic Functions
Internal Path Transactions
Introduction This section describes the Internal Path Transactions screen.
Internal Path Transactions Screen
The Internal Path Transactions screen displays the transaction counts for each path in the selected node:
48
35011984 02/2006
Modbus Plus Network Diagnostic Functions
Token Owner Work Table
Introduction Clicking on the Token Owner Work Table button displays the Node Token Owner Bit
Map screen. This section describes this screen.
Node Token Owner Bit Map Screen
The Node Token Owner Bit Map screen shows a bit map reflecting the current token status of each path in the selected node. Each position in the bit map will be colored green when active and gray when inactive:
35011984 02/2006 49
Modbus Plus Network Diagnostic Functions
Active Station Table
Introduction This section describes the Active Station Table screen.
Active Station Table Screen
The Active Station Table screen shows a bit map reflecting the status of each node on the local network of the selected node. Each position in the bit map will be colored green when active and gray when inactive:
50
35011984 02/2006
Modbus Plus Network Diagnostic Functions
Token Station Table
Introduction This section describes the Token Station Table screen.
Token Station Table Screen
The Token Station Table shows a bit map reflecting the token passing status of each node on the local network of the selected node. Each position in the bit map will be colored green when active and gray when inactive:
35011984 02/2006 51
Modbus Plus Network Diagnostic Functions
Global Data Present Table
Introduction This section describes the Global Data Present Table screen.
Global Data Present Table Screen
The Global Data Present Table screen shows a bit map reflecting the Global data status of each node on the local network of the selected node. Each position in the bit map will be colored green when active and gray when inactive:
52
35011984 02/2006
Modbus Plus Network Diagnostic Functions
Read Global Data
Introduction Clicking on the Read Global Data button displays the Global Data screen. This
section describes this screen.
Global Data Screen
The Global Data screen is used to display the Global Data sent by the selected node. If no Global Data is present for that node, the Global Data Words Read field will contain a 0 and no data will be displayed in the data area:
35011984 02/2006 53
Modbus Plus Network Diagnostic Functions
54
35011984 02/2006

Appendices

At a Glance
Introduction The following appendices describe the TSXCUSBMBP settings
z for Unity, and z for Concept & ProWORX32.
What's in this Appendix?
The appendix contains the following chapters:
Chapter Chapter Name Page
A TSXCUSBMBP Settings for Unity 57
B TSXCUSBMBP Settings for Concept & ProWORX32 61
35011984 02/2006 55
Appendices
56
35011984 02/2006

TSXCUSBMBP Settings for Unity

A
TSXCUSBMBP Settings for Unity
Introduction This section describes how to configure Unity to work the TSXCUSBMBP.
Important Information
If the serial Modbus driver for Unity comes up before the TSXCUSBMBP driver during system startup, Unity will not work properly. The following steps will prevent this situation from occurring:
Step Action
1 Close the Unity application if it is open.
2 Shut down Unity's serial Modbus driver by right-clicking on the Modbus driver's icon
in the system tray then selecting Close.
3 Start the Unity application. Unity will automatically restart its serial Modbus driver.
35011984 02/2006 57
TSXCUSBMBP Settings for Unity
Configuring Unity
The following steps are required to configure Unity to work the TSXCUSBMBP:
Step Action
1 Configure the USB MBP virtual COM port, as shown in the following window:
2 Set the routing parameters if needed: (With the settings shown I can use 55, 5, or 15
to connect to the same Unity PLC.)
58
35011984 02/2006
TSXCUSBMBP Settings for Unity
Step Action
3 Install and make sure the Modbus Driver is running for Unity's Modbus
Communication. (This is used by Unity, OFS, etc.)
4 Configure the Modbus Driver to use the USB MBP Virtual port (COM3).
5 Setup Unity's PLC Address setting for Modbus01 (Modbus Driver), and the local
Modbus Plus address or the address as defined in the USB MBP routing table.
6 Make sure both drivers are running:
35011984 02/2006 59
TSXCUSBMBP Settings for Unity
Step Action
7 You should now be able to Connect:
60
35011984 02/2006

TSXCUSBMBP Settings for Concept & ProWORX32

B
TSXCUSBMBP Settings for Concept & ProWORX32
Introduction This section describes how to configure Concept & ProWORX32 to work the
TSXCUSBMBP.
Setting the Optimum Baud Rate in Concept
Setting the Optimum Baud Rate in ProWORX32
When using serial Modbus communications with Concept, a delay of approximately 50 milliseconds occurs before each Modbus request is transmitted.
When using Concept with the TSXCUSBMBP, a serial interface must be selected.
Therefore, the overall throughput of the TSXCUSBMBP with Concept is only slightly above that of a serial Modbus interface. Setting the baud rate in Concept to 19200 instead of the 9600 default will slightly improve performance.
When using serial Modbus communications with ProWORX32, there are no delays inserted and the TSXCUSBMBP runs at the expected USB speed.
35011984 02/2006 61
TSXCUSBMBP Settings for Concept & ProWORX32
Configuring Concept & ProWORX32
The following steps are required to configure Concept & ProWORX32 to work the TSXCUSBMBP:
Step Action
1 Configure the USB MBP virtual COM port, as shown in the following window:
2 Set the routing parameters if needed: (With the settings shown I can use 55, 5, or 15
to connect to the same Unity PLC.)
62
3 Set Concept's or ProWORX 32's Protocol to Modbus.
4 Set the Device or Port to the port USB MBP Virtual port (COM3).
35011984 02/2006
TSXCUSBMBP Settings for Concept & ProWORX32
Step Action
5 Set the PLC Node or Modbus Address to the local Modbus Plus address or the
address as defined in the USB MBP routing table.
ProWORX32
Concept
35011984 02/2006 63
Loading...