Schneider Electric TSMN-57011-xxx-0-01, TSMN-58011-000-0-01, TSMN-81011-000-0-01 Installation Instructions

Application
The Electronic Room Temperature Sensor is a resistance-temperature device (RTD) available in various models. See Table-1 below for model variations and options.
Features
Contemporary, low-profile packaging
Easily installed base plate and electronic assembly
TSMN-90xxx Series TSMN-57011-xxx-0-01 TSMN-58011-000-0-01 TSMN-81011-000-0-01
Electronic Room Temperature Sensor
General Instructions
Suitable for direct-wall, 2 x 4 electrical box, 1/4 DIN
electrical box, and surface box mounting
UL 916 Listed
Table-1 Model Chart.
Base Plate Terminals
Model No. Function
TSMN-90110-000-0-01 10K thermistor no shunt, ASD jack X X X X X
TSMN-90220-850-0-01 10K thermistor w/11K shunt, ASD jack X X X X X
TSMN-90221-850-0-01
TSMN-90230-850-0-01 10K thermistor w/11K shunt, ASD jack, ovrd X X X X X
TSMN-90231-850-0-01
TSMN-90250-850-0-01
TSMN-90250-852-0-01
TSMN-90251-850-0-01
TSMN-90256-852-0-01
TSMN-90261-850-0-01
TSMN-57011-0-01 10K thermistor 6” Pigtail leads
TSMN-57011-850-0-01 10K thermistor with 11K shunt 6” Pigtail leads
TSMN-58011-000-0-01 1K Platinum element 6” Pigtail leads
TSMN-81011-000-0-01 1K BALCO element 6” Pigtail leads
10K thermistor w/11K shunt, ASD jack, F temp ind
10K thermistor w/11K shunt, ASD jack, F temp ind, ovrd
10K termistor w/11K shunt, ASD jack, F setpt, ovrd
10K thermistor w/11K shunt, ASD jack, C setpt, ovrd
10K thermistor w/11K shunt, ASD jack, F temp ind, F setpt, ovrd
10K thermistor w/11K shunt, ASD jack, C temp ind, C setpt, ovrd
10K thermistor w/11K shunt, ASD jack, F temp ind, F setpt
ASD+ ASD- SETPT SP+ COM SPACE PSI
12345678
XX X X X
XX X X X
XXXXXX X
XXXXXX X
XXXXXX X
XXXXXX X
XXXXXX X
SPECIFICATIONS
Sensing Element: See Table-1 and Table-2. Mounting: Direct-wall,2x4electrical box, 1/4 DIN, or surface box. Ambient Temperature Limits:
Shipping & Storage, -40 to 160 °F (-40 to 71 °C)
Operating, 40 to 140 °F (4 to 60 °C) Humidity: 5 to 95%, non-condensing. Locations: NEMA.
Table-2 Temperature Versus Resistance.
Nominal Resistance Value
Temperature
°F (°C)
40 (4) 7596 1017 935.9
50 (10) 18790 6938 1039 956.9
68 (20) 12260 5798 1077.9 995.6
77 (25) 10000 5238 1097.3 1015.4
86 (30) 8194 4696 1116.7 1035.4
104 (40) 5592 3707 1155.4 1076.2
122 (50) 3893 2875 1194 1118.0
140 (60) 2760 2206 1232.4 1160.9
Sensor Type
TSMN-90110 Series TSMN-57011 Series
Thermistor, 10Kat77
(25°C)
TSMN-90xxx-85x Series
TSMN-57011-850
Thermistor, 10Kat77
°F
(25°C), *with 11K shunt
resistor
TSMN-58011
°F
Platinum, 1000 at 32
(0°C)
°F
Balco, 1000 at 70°F
TSMN-81011
(21.1°C)
*TSMN-90110 and TSMN-57011 do not have a shunt resistor.
INSTALLATION
The electronic room temperature sensor is packaged, in disassembled form, in one container. It consists of three major parts: a pre-wirable base plate; an electronic assembly containing the sensor and its associated circuitry; and a removable cover.
Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If
undamaged, open the package and inspect the device for obvious damage. Return damaged products.
Requirements Job wiring diagrams
Tools (not provided):
– Digital volt-ohm meter (DVM) – Appropriate drill and drill bit for mounting screws – Appropriate screwdrivers for mounting screws and terminal connections
Training: Installer must be a qualified, experienced technician
Appropriate accessories
– Communication adapter
For use of this product with TAC System 8000, refer to the Environmental Controls
Application Manual, F-21335
Precautions Warning
Electrical shock hazard! Disconnect power before installation to prevent electrical shock or equipment damage.
Mounting Locate the sensor where it will be exposed to an unrestricted circulation of air which
represents the average temperature of the controlled space. Do not locate the sensor near sources of heat or cold such as lamps, motors, sunlight, or concealed ducts or pipes. The sensor is designed for service in any normally encountered human environment.
The electronic room temperature sensor may be installed directly onto a wall, or onto a 2 X 4 electrical box, a 1/4 DIN electrical box, or a surface box. Refer to Figure 1.
2 Copyright 2009 Schneider Electric All Rights Reserved. F-26004-8
Loading...