For proportional temperature control of pneumatic valves and
actuators to maintain discharge temperature of reheat
systems and sampling chamber or return air temperature of
terminal units and as a proportional low limit thermostat.
GENERAL INFORMATION
Proportional control type of pneumatic instrument, using
balanced lever system actuated by a liquid-filled thermal
copper element with a 3’ (914 mm) capillary.
Maximum Safe Air Pressure: 30 psig (207 kPa).
Maximum Sale Case Temperature: 140°F (60°C).
Mounting: Directly by means of top mounting holes or with
a right angle mounting bracket included with thermostat.
Air Connections: Post with barb for 1/4" O.D. plastic tubing.
Air Consumption for Sizing Air Compressor: .016 scfm
(8 ml/s) @ 15 psig (103 kPa), .024 scfm (11 ml/s) @ 20 psig
(138 kPa).
Air Capacity for Sizing Air Mains: 36 scim (10 ml/s) @ 15
psig (103 kPa), 50 scim (14 ml/s) @ 20 psig (138 kPa).
Dimensions: 4-5/8" (117 mm) high x 2-1/8" (54 mm) wide x
1-5/8" (41 mm) deep.
TK-2001, TK-2012, TK-2201,
TK-3001, TK-3201, TK-4001,
TK-4012, TK-4212 TK-4212-201
Pneumatic Bulb Thermostats
General Instructions
Options
None
ACCESSORIES
AT-208 Duct mounting kit
Tool-95 Pneumatic calibration tool kit
Printed in U.S.A. 12/09 © Copyright 2009 Schneider Electric All Rights Reserved. F-12585-8
Table-1 Model Chart.
Bulb Style
Dimensions in
inches (mm)
Straight
7/32 x 14 (6 x 356)
Coiled
1 x 5 (25 x 127)
Averaging
1/8 x 48 (3 x 1.2 m)
Straight
7/32 x 14 (6 x 356)
Coiled
1 x 5 (25 x 127)
Straight
3/16 x 11-1/4 (5 x
286)
Averaging
3/32 x 54 (2 x 1.4 m)
Averaging
3/32 x 54 (2 x 1.4 m)
Averaging
3/32 x 54 (2 x 1.4 m)
Part
Number
Description and
Action
a
Max. Safe
Bulb Temp.
°F (°C)
TK-2001
Heating
b
DA
TK-4001
TK-2201
Heating-Cooling
140 (60)
20 (138) DA
TK-3201
TK-2012
15 (103) RA
Heating
b
DA
TK-4012
TK-4212
Heating-Cooling
20 (138) DA
230 (110)
15 (103) RA
TK-4212-201
Heating-Cooling
Low Limit
20 (138) DA Full
c
Output 15 (103)
a
Direct Acting (DA) - Increase output pressure on temp. rise.
Reverse Acting (RA) - Decrease output pressure on temp. rise.
b
Field changeable to reverse acting.
c
AT 20 psi (138 kPa) unit can bleed down a branch line from a controlling thermostat.
At 15 psi (103 kPa) unit is inoperative, i.e. passes controlling thermostat signal.
Control Dial
Range
°F (°C)
Dial Marked
Cooler-Warmer
60-90
(15-32)
Dial Marked
Cooler-Warmer
30-90 (-1 to 32)
Throttling Range
Adjustable 2-10°F
(1-6
°C)/10 psi (69 kPa)
Factory Set
4°F (2°C)/
10 psi (69 kPa)
Adjustable 5-25°F
(3-14
°C)/
10 psi (69 kPa) Factory
Set
10°F (6°C)/
10 psi (69 kPa)
Supply Air
Pressure psig
(kPa)
15 (103)TK-3001
15 (103) RA
Cooling
20 (138) DA
a
a
Heating
15 (103)
15 (103) RA
Cooling
20 (138) DA
a
a
Heating
15 (103
Full Output
20 (138) DA
a
Heating
DIMENSIONS
Figure-1 Mounting Dimensions.
2 © Copyright 2009 Schneider Electric All Rights Reserved. F-12585-8