Read these instructions carefully and look at the equipment to become
familiar with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this manual or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that
an electrical hazard exists which will result in personal injury if the instructions are
not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury
or death.
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
Please note
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, can
result in minor or moderate injury.
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this signal word.
Electrical equipment should be installed, operated, serviced and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Page 4
Notices
FCC Part 15 Notice
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures.
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment to an outlet on a circuit different from that to which the
receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
FCC Part 68 Notice
This equipment complies with Part 68 of the FCC rules and the requirements
adopted by the Administrative Council for Terminal Attachments (ACTA). On the
side of this equipment is a label that contains, among other information, a product
identifier in the format US: AAAEQ##TXXXX. If requested, this number must be
provided to the telephone company.
This equipment uses the following Universal Service Order Codes (“USOC”) jacks:
RJ11.
A plug and jack used to connect this equipment to the premises wiring and
telephone network must comply with the applicable FCC Part 68 rules and
requirements adopted by the ACTA. A compliant telephone cord and modular plug
or compliant modular jack is provided with this product.
The REN is used to determine the number of devices that may be connected to a
telephone line. Excessive RENs on a telephone line may result in the devices not
ringing in response to an incoming call. In most but not all areas, the sum of RENs
should not exceed five (5.0). To be certain of the number of devices that may be
connected to a line, as determined by the total RENs, contact the local telephone
company. The REN for this product is part of the product identifier that has the
format US: AAAEQ##TXXXX. The digits represented by ## are the REN without a
decimal point (e.g., 03 is a REN of 0.3).
If this equipment, Digital Power Meter with Internal Modem, causes harm to the
telephone network, the telephone company will notify you in advance that service
may be temporarily discontinued. When advance notice is not practical, the
Page 5
telephone company will notify you as soon as possible. You will also be advised of
your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations
or procedures that could affect the operation of this equipment. If this happens, the
telephone company will provide advance notice in order for you to make necessary
modifications to maintain uninterrupted service.
If you experience trouble with this equipment, Digital Power Meter with Internal
Modem, please contact Schneider Electric at 615-287-3400. If this equipment is
causing harm to the telephone network, the telephone company may request that
you disconnect this equipment until the problem is resolved.
There are no user serviceable parts in this equipment.
Connection to party line service is subject to state tariffs. Contact the state public
utility commission, public service commission or corporation commission for
information.
If your premises has specially wired alarm equipment connected to the telephone
line, ensure that the installation of this Digital Power Meter with Internal Modem
does not disable your alarm equipment. If you have questions about what will
disable alarm equipment, consult your telephone company or a qualified installer.
Network Compatibility Notice for the Internal Modem
The internal modem in meters equipped with this option is compatible with the
telephone systems of most countries in the world, with the exception of Australia
and New Zealand. Use in some countries may require modification of the internal
modem’s initialization strings. If problems using the modem on your phone system
occur, please contact Schneider Electric Technical Support.
Page 6
Page 7
930-134-01-A.00 PowerLogic
11/2013Table of Contents
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
Introduction
This document describes the PowerLogic EM4033 and EM4080 meters, including
procedures to install and start up the unit, and complete the initial configuration:
•“System Description” on page 1
•“Pre-Installation” on page 6
•“Installation Procedures” on page 7
•“Connecting Pulse Inputs” on page 26
•“Fuse Replacement” on page 30
This documentation is intended for those responsible for installing and configuring
the PowerLogic EM4033 and EM4080 meters. Installers must be qualified
electricians with knowledge of local and national code requirements. See “Safety
Precautions” on page 5.
System Description
The PowerLogic EM4033 and EM4080 meters support:
•single-phase, 2-wire
•single-phase, 3-wire (network)
•three-phase wye and Delta services
Depending on how the meters are installed and configured, they can meter 8, 12, or
24 individual meter points. The PowerLogic EM4033 and EM4080 meters are
designed for residential, commercial, and industrial use and display the power and
consumption readings for each measurement point.
PowerLogic EM4000 series System Specifications
The PowerLogic EM4000 series system architecture includes:
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
Safety Precautions
Carefully observe these safety instructions.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Apply appropriate personal protective equipment (PPE) and follow
safe electrical work practices. See NFPA 70E.
•Only qualified electrical workers should install this equipment. Such
work should be performed only after reading this entire set of
instructions.
•The equipment must be accessible to authorized personnel only.
Equipment must be installed in areas where access can be
restricted.
•NEVER work alone.
•Before performing visual inspections, tests, or maintenance of this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized,
tested, and tagged. Pay particular attention to the design of the
power system. Consider all sources of power, including the
possibility of backfeeding.
•Turn off all power supplying the meter and the equipment in which
it is installed before working on it.
•Always use a properly rated voltage sensing device to confirm that
all power is off.
•Before closing all covers and doors, carefully inspect the work area
for tools and objects that may have been left inside the equipment.
•Successful equipment operation requires proper handling,
installation, and operation. Neglecting fundamental installation
requirements can lead to personal injury as well as damage to
electrical equipment or other property.
•NEVER bypass external fusing.
•NEVER short the secondary of a Potential Transformer (PT).
•Always short the secondary of a current transformer prior to
disconnecting current input loads.
Failure to follow these instructions will result in death or serious
injury.
Electrical Standards Compliance
•Use the unit only in accordance with the electrical power rating
•The unit is only to be installed by a qualified electrician
•Initial installation of the unit must be inspected by the local electrical Inspection Authority
•Install the unit in compliance with the following local and national electrical codes:
•Canada: Canadian Electrical Code, Part I, CSA C22.1
•United States: National Fire Protection Association (NFPA) 70; US National
Electrical Code
•Elsewhere: International Electrotechnical Commission (IEC) 364, Part 1-7
•Ensure that the unit is properly earthed
•If the equipment is installed or used in a manner other than that specified in this
document, it may void your warranty or impair the protection of the equipment.
PowerLogicTM Series EM4000 930-134-01-A.00
Installation Guide11/2013
Installation
This section contains the following installation topics:
•“Pre-Installation” on page 6
•“Installation Procedures” on page 7
•“Connecting Pulse Inputs” on page 26
Pre-Installation
The pre-installation checklist and site planning must be performed before installing
the equipment at the site.
Receiving
The equipment required for each PowerLogic EM4000 meter installation includes:
•high-density meter (PowerLogic EM4033 or PowerLogic EM4080)
•For the PowerLogic EM4033 and PowerLogic EM4080, one 12-ft (4-m) AMP
cable with one 50-pin connector supplied with each unit
•CD and meter configuration software, this installation manual and an installation
record form
When you receive your order, verify that the items listed above are included with
the shipment, and visually inspect them for damage. If any parts are missing or
damaged, contact your Schneider Electric representative.
Pre-Installation Checklist
The installer must provide the following information, tools, and equipment before
proceeding with the installation:
•certified current transformers for metering (not supplied)
•an appropriate 15-Amp maximum circuit breaker or a fused disconnect switch
for the type of panel
•current/voltage meter to test the phasing of panels
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
3. Determine the number and types of meters or monitors required (single-phase,
network, or three-phase).
4. Determine the model number and correct sense voltage based on the voltage
label on the top right side of the unit.
Access to Power and Lighting
The installation site must be supplied with access to the main electrical panel and
any sub-panels. Portable or permanent lighting must be available to provide the
installers with a clear view of the equipment and of the installation environment.
Each installation may vary depending on physical site restrictions.
Installation Procedures
This section provides information about activities that must be performed to install
the PowerLogic EM4033 and EM4080 meters in a single-phase 2-wire,
single-phase 3-wire (network), or three-phase 4-wire application. The installation
procedures must be performed in the following order:
1. “Mounting the PowerLogic EM4000 meter” on page 7
2. “Installing Potential Transformers for Three-Phase Service Greater Than 277V”
on page 9
3. “Installing the Sense Voltage and Control Voltage Cables in Wye and Delta
Services” on page 11
4. “Installing the Current Transformers” on page 18
5. “Connecting the Communications” on page 25
a.“Connecting the Ethernet Cable” on page 25
b.“Connecting the Modbus RTU Communications” on page 25
6. “Manually Testing Communications” on page 26
7. “Connecting Pulse Inputs” on page 26
8. “Recording the Meter Map” on page 28
Mounting the PowerLogic EM4000 meter
Figure 3 shows the general mounting layout for metering 120V/208V wye services,
and Figure 4 shows the general mounting layout for metering 347V/600V wye
services.
1. Remove the front cover from the meter by removing the four screws with a #2
Phillips screwdriver. Retain the cover and screws for later re-installation.
2. Mount the PowerLogic meter on the wall and secure it by inserting a screw in
each mounting keyhole and tightening the screws.
3. Mount the shorting block enclosure on the wall as shown in Figures 3 and 4.
Secure it by inserting a screw in each mounting keyhole and tightening the
screws.
4. Install the conduit for voltage and current connections.
In Figure 3, the meter is powered and takes its sense voltage directly from a
breaker within the panel.
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
Installing Potential Transformers for Three-Phase Service Greater
Than 277V
Potential transformers are required when metering services greater than the rated
voltage input of the meter. Potential transformers are used to reduce the
line-to-neutral voltage of the service to 120V. The accuracy class should be 0.3%
or better, with a burden rating of 30VA.
For applications in Canada, Measurement Canada approved potential transformers
are required. Measurement Canada requires an accuracy class of 0.3% or better,
with a 150VA rating.
NOTE: Potential transformer burden depends on the control voltage source. If
control voltage is provided separately (not derived from the metered voltage), then
lower transformer burden may be acceptable. Contact your local Schneider Electric
representative for details.
Mount the potential transformer enclosure between the supply voltage and the
PowerLogic meters as shown in Figure 4. Transformer configuration must be Y||Y
(wye-wye).
In Figure 4, the meter is powered from the potential transformers that are fed from a
breaker within the 600Y/347V panel. The CT cable is connected to the shorting
enclosure before connecting to the CTs in the panel.
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
Installing the Sense Voltage and Control Voltage Cables in Wye and
Delta Services
The sense voltage (A, B, C, N) provides phase voltages for metering. The
configuration depends on the type of service being metered:
•see “For a single-phase panel with the 120V variant of the meter:” on page 13
•see “For a 208Y/120V three-phase wye panel with the 120V variant of the
meter:” on page 14
•see “For a 480Y/277V three-phase wye panel with the 277V variant of the
meter:” on page 15
•see “For a 600Y/347V or higher three-phase wye panel with potential
transformers with the 120V variant of the meter:” on page 16
•see “For a three-phase Delta panel with the 120V variant of the meter:” on page
17
The PowerLogic EM4033 and EM4080 meters are shipped from the factory with a
control voltage jumper that can be used to connect the control voltage input and the
sense voltage inputs to provide control voltage to the unit. The following procedures
explain how to connect the sense voltage inputs for each of the service types.
For a single-phase panel, use a 3-wire (red, black, white), 14 AWG (1.63 mm
o
90
C (194oF) cable. For a three-phase panel, use a 4-wire (red, black, blue, white),
14 AWG (1.63 mm
black, blue), 14 AWG (1.63 mm
2
), 90oC (194oF) cable. For a Delta service, use a 3-wire (red,
2
), 90oC (194oF) cable. Metallic, flexible armored
cable (BX cable) is recommended for commercial installations as shown in Figure 5
on page 13.
2
),
The PowerLogic meters must be connected to the sense voltage and control
voltage through a properly rated disconnect that disconnects all line and neutral
wires, so it can be powered down. The disconnect must be located within easy
reach of the meter operator, and must be labeled as such. Opening the disconnect
or breaker is the disconnect device. For multiple PowerLogic meter installations,
the same disconnect can be used to power all meters, and must be labeled for all
meters it supplies power to. The disconnect device must meet IEC 60947-1, IEC
60947-3 and/or comply with the local electrical code.
PowerLogicTM Series EM4000 930-134-01-A.00
Installation Guide11/2013
To install the control voltage cable in a 208Y/120V or 120/240V application:
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Apply appropriate personal protective equipment (PPE) and follow
safe electrical work practices. See NFPA 70E.
•This equipment must only be installed and serviced by qualified
electrical personnel.
•Turn off all power supplying this equipment before working on or
inside equipment.
•Always use a properly rated voltage sensing device to confirm
power is off.
•Replace all devices, doors and covers before turning on power to
this equipment.
•The meters must be connected to the sense voltage and control
voltage through a properly rated voltage disconnect (not shown in
the wiring diagrams).
Failure to follow these instructions will result in death or serious
injury.
NOTE: If the circuit breaker panel does not designate phase A, phase B and phase
C feeds, make your own designation and use it for the rest of the installation.
1. Before connecting the sense voltages, turn off the power to the circuit being
connected.
2. Always use a properly rated voltage sensing device to confirm power is off.
3. Connect the sense voltages phase A, B, C, and N leads from the voltage
disconnect to the meter as described in Figure 5 on page 13 and Figure 6 on
page 14.
NOTE: The phase wiring sequence A, B, C between the PowerLogic EM4000
meter and the panel must match or the measurement readings will be wrong.
4. If more than one meter is being installed, repeat this procedure for each
additional meter.
Legend:
1 BX cable
2 Earth
3 Phase B (black)
4 Shorting jumper
5 Sense voltage terminal block (J3)
6 Neutral (white)
7 Phase A (red)
8 0.75-inch (1.9-cm) strain relief
11/2013Installation Guide
For a single-phase panel with the 120V variant of the meter:
•Connect meter terminal A to the voltage disconnect phase A (red wire)
•Connect meter terminal B to the voltage disconnect phase B (black wire)
•Connect meter neutral terminal to neutral bar in the voltage disconnect panel
(white wire)
•Connect earth wire to earth post using lug provided
•Meter terminal C is not connected
•Install power supply shorting jumpers (see Figure 5)
The PowerLogic EM4033 and EM4080 meters are rated for direct input of 120V to
277V 60Hz phase potential. When metering services greater than 120V, the meter
is powered from a separate 120V instrument transformer. Figure 7 shows the wiring
of the control voltage transformer for a 277V service.
Figure 5: PowerLogic EM4000 meter in a 120/240V single-phase connection
Legend:
1 BX cable
2 Earth
3 Phase C (blue)
4 Phase B (black)
5 Shorting jumper
6 Sense voltage terminal block (J3)
7 J3-B to J3-N shorting wire
8 Phase A (red)
9 0.75-inch (1.9-cm) strain relief
11/2013Installation Guide
Delta service metering
To use the PowerLogic EM4000 meter in a Delta service, the line-to-line voltage
from the Delta service must be reduced to 120V line-to-line using appropriate
potential transformers. Metering a Delta service requires only two potential
transformers, and only two CTs for phase A and C.
For a three-phase Delta panel with the 120V variant of the meter:
•Connect meter terminal A to the voltage disconnect phase A (red wire)
•Connect meter terminal C to the voltage disconnect phase C (blue wire)
•Connect meter neutral terminal to meter terminal B (black wire)
•Connect earth wire to earth post using lug provided (see Figure 9)
Figure 9: PowerLogic EM4000 meter three-phase Delta service connection
PowerLogicTM Series EM4000 930-134-01-A.00
Installation Guide11/2013
Installing the Current Transformers
The two models of PowerLogic EM4000 meter use current transformers (CTs) with
different secondary outputs. The PowerLogic EM4033 meter uses split-core 0.333V
CTs (see Figure 10), and the PowerLogic EM4080 meter uses 80mA CTs only (see
Figure 11) and is typically used where accuracy is important and long secondary
CT wiring is required (up to 300 feet [91.44 meters]). The PowerLogic EM4080
meter can also use a 5A CT if a 5A converter has first been installed.
For instructions, see “Installing the CTs on the PowerLogic EM4033 and
PowerLogic EM4080” on page 20, and “Installing 5A Converters and CTs on the
PowerLogic EM4080” on page 21.
Current transformers connect to the PowerLogic EM4033 and PowerLogic EM4080
meters through the 50-conductor CT cable provided with the meter. Table 2
describes the CT wire pairs and the cable color scheme for each meter point. You
can also find this information on the inside of the meter’s outer cover.
Each CT has an X1 (positive) and X2 (neutral) wire pair and uses butt-splice
connectors to attach the CT to a specific meter wire pair. The direction of the
energy flow is indicated on the CT by: a label (“This side towards source”); an arrow
that points away from the source; or a stamp/label indicating which side is H1 (H1
side faces toward the source).
CT shorting blocks are recommended for all CT installations. CTs measuring live
current must either be connected to the PowerLogic meter via the 25-pair CT cable,
or the secondary output of the CTs must be shorted together. Open-circuit CTs
may generate a hazardous voltage and could damage equipment or cause
personal injury.
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Turn off all power supplying this equipment before working on or
inside the equipment.
•Always use a properly rated voltage sensing device to confirm the
power is off.
•NEVER open circuit a CT; use the shorting block to short circuit the
leads of the CT before removing the connection from the meter.
•Do not crimp the insulation when making the wire connections.
Failure to follow these instructions will result in death or
serious injury.
1. Connect the 50-pin connector to the PowerLogic connector located at the
bottom side of the unit, and secure it in place with the retaining clips.
2. Feed the free end of the cable through the bottom left of the meter enclosure.
This cable is made up of twisted-pair wires for connecting the individual CTs to the
metered points. The color codes for the X1 (positive) and X2 (neutral) connections for
each CT are listed in Table 2 on page 24.
NOTE: The direction of the energy flow is indicated on the CT.
3. Turn off the power feed to the panel where the CTs are being installed. Always
use a properly rated voltage sensing device to confirm power is off.Feed the CT
cable into the panel through an appropriate punch-out with an approved strain
relief.
4. Strip the plastic sheaths on the cable to an appropriate length to expose the wire
pairs. Cut and strip the CT leads and wire pair leads to an appropriate length.
Crimp the CT leads to the wire pairs for each meter point.
5. Connect the X1 lead of the CT to the X1 lead of the cable, then connect the X2
lead of the CT to the X2 lead of the cable (see Table 2).
6. When using solid-core CTs, remove the feed wire from the circuit breaker, place
the CT over the wire, and reconnect to the circuit breaker. Ensure that the arrow
on the CT label is pointing in the direction of the energy flow (toward the load).
7. When using split-core CTs, separate the halves of the CT and place the CT over
the wire to the circuit breaker. Ensure that the CT is facing the source as shown
on the label. Install cable ties to ensure that the CT halves are held together
securely.
8. Repeat steps 4 to 7 for the remaining CTs.
Installing 5A Converters and CTs on the PowerLogic EM4080
When both low-current (200A and 400A) and high-current (600A or higher) circuits
need to be measured with the same PowerLogic meter, converters are available to
allow the use of Measurement Canada approved 5A CTs with the appropriate
current rating. 5A CT converters transform the 5A maximum output from a standard
CT to the 80mA maximum of the PowerLogic meter.
The 5A side of the converter is the black and red wire pair, and the 80mA side of
the converter is the black and white wire pair.
NOTE: It is recommended that 5A converters and shorting devices be installed in a
sealable metal enclosure.
PowerLogicTM Series EM4000 930-134-01-A.00
Installation Guide11/2013
To connect the 5A CT to the converter on the PowerLogic EM4080, follow these
steps:
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Turn off all power supplying this equipment before working on or
inside the equipment.
•Always use a properly rated voltage sensing device to confirm the
power is off.
•NEVER open circuit a CT; use the shorting block to short circuit the
leads of the CT before removing the connection from the meter.
•Do not crimp the insulation when making the wire connections.
Failure to follow these instructions will result in death or
serious injury.
1. Connect the X1 lead of the 5A CT to the shorting device.
2. Connect the X2 lead of the 5A CT to the shorting device.
3. Connect the X1 lead (red) from the 5A side of the converter to the CT X1 lead on
the shorting device.
4. Connect the X2 lead (black) from the 5A side of the converter to the CT X2 lead
on the shorting device.
5. Connect the X1 lead (white) from the 80mA side of the converter to the X1 lead
within the 25 pair cable for the selected meter point ID listed in Table 2.
6. Connect the X2 lead (black) from the 80mA side of the converter to the X2 lead
within the 25 pair cable for the selected meter point ID listed in Table 2
Figure 12 shows a 5A CT connected to the converter.
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
Connecting the Communications
Connections for communications using the Ethernet port or Modbus RTU port are
described in this section.
Connecting the Ethernet Cable
If the Ethernet port is used to report data, an RJ45 patch cable is required to
connect the Ethernet port to the local Ethernet network.
1. Route the cable through the slot in the PowerLogic EM4000 meter enclosure.
2. If the local network automatically assigns IP addresses through a DHCP server,
the PowerLogic EM4000 meter will be able to report using its factory default IP
settings. If the local network is configured for static IP addresses, refer to the
PowerLogic EM4000 meter Configuration Guide for instructions on how to
configure default static IP addresses.
Connecting the Modbus RTU Communications
If the Modbus port is used to report data, an RS422/RS485 serial cable is required
to connect the Modbus RTU port to the local Modbus network.
1. Route the cable through the slot in the PowerLogic EM4000 meter enclosure.
2. Depending on the position of the PowerLogic EM4000 meter in the Modbus
network as shown in Figure 13, set the DIP switches as follows:
PowerLogic meter locationS1S2S3S4
Head endOnOffOffOff
IntermediateOffOffOffOff
Tail endOnOnOnOff
3. Refer to the PowerLogic meter Configuration Guide for instructions on how to
configure the baud rate, parity settings, and Modbus base address for the
RS485 RTU communications.
PowerLogicTM Series EM4000 930-134-01-A.00
Installation Guide11/2013
Connecting Pulse Inputs
Each PowerLogic meter has two pulse inputs that can be used to count and report
pulses generated by another meter (pulsing device).
Connect the output of the pulsing device to one of the two pulse input terminal
blocks in the PowerLogic meter, as shown in Figure 2. Each terminal block has a
negative terminal pin on the right, and a positive terminal pin on the left. The pulse
inputs are compatible with both dry and solid-state form A contacts, 10 Hz
(maximum), 20 ms pulse width (minimum).
When the pulsing device provides dry relay contacts, the PowerLogic meter pulse
inputs are not polarity-sensitive. When the pulsing device provides solid-state
form A outputs, the negative terminal from the source device must be connected to
the negative terminal of the PowerLogic meter pulse in terminal block.
The pulsing device can be located up to 1,000 feet away from the PowerLogic
meter with 22 AWG twisted pair wire.
Start-Up Sequence
Use the following procedure to start up the PowerLogic EM4000 meter.
1. Ensure that all CT and sense voltage wiring is securely installed.
2. Remove all tools from the work area.
3. Re-install all cover plates and equipment covers.
4. Power up the meter. The LCD on the front panel of the meter indicates the
operating status of the unit as follows:
a.Initial power up message “PowerLogic EM4000”
b.After the internal configuration is complete, the display shows default information
for the first meter.
Manually Testing Communications
This procedure clears the meter memory, manually tests the communications from
the PowerLogic EM4000 meter, and updates the meter clock. To force the meter to
send data, follow these steps:
1. Press and hold the Display button for 5 to 7 seconds until the diagnostics mode
is displayed, then release.
2. If communicating via Ethernet, press the Display button until "Local IP Address"
appears on the display.
a.If the IP address is 169.254.0.10, the meter has not found a DHCP server. As a
result, the meter will use its default IP configuration and may not be able to report.
See the PowerLogic EM4000 meter Configuration Guide for instructions on how to
program default IP addresses.
b.If the IP address is not 169.254.0.10, the meter has acquired an IP address from
the local network, and will be able to report data and synchronize time.
3. Press the Display button until the “Send” command appears on the display.
4. Press the left or right arrow button to manually force the PowerLogic EM4000
meter to report metering data using the Ethernet or modem connection. This
clears data from the PowerLogic EM4000 meter memory, and ensures the time
is set correctly.
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
Display Navigation
The PowerLogic EM4000 meter has three buttons to control the information
presented on the LCD. The display has a normal and a diagnostics mode. The
PowerLogic EM4000 meter starts in normal mode, and enters diagnostics mode
when the Display button is pressed and held for 5 seconds. To adjust the contrast,
hold down the Display button, and use the right and left arrow buttons to increase
and decrease the contrast respectively.
Normal Mode
In Normal mode, the Display button scrolls through the information for each meter.
The left and right arrow buttons select the previous or next meter points
respectively. The following information is available:
•Real Energy Delivered kWh D
•Real Energy Received kWh R
•Real Power Watts
•Reactive Energy Delivered kVarhD
•Reactive Energy Received kVarhR
•Reactive Power Var
•Peak Demand Peak W (Watts)
In Normal mode, the right and left arrow buttons scroll the display from meter points
1 to 8, 1 to 12, or 1 to 24, depending on your configuration.
Diagnostics Mode
Diagnostics mode is accessed by pressing and holding the Display button for 5
seconds. In Diagnostics mode, pressing the Display button will scroll through the
following additional information:
•Send data command
•CT Primary value and Real Power Watts per phase
•Current (Amps) per phase
•Power factor (pf) per phase
•Phase angle (degrees) per phase
•Voltage per phase
•Local IP address
•Reset factory default IP address command
•Verify
•Badge #
•Date and time (UTC)
In Diagnostics mode, the right and left arrow buttons scroll the display from meter 1
to 8, 1 to 12, or 1 to 24, depending on your configuration. When the local IP
address is shown on the LCD, use the right and left arrow buttons to scroll through
the following information:
PowerLogicTM Series EM4000 930-134-01-A.00
Installation Guide11/2013
•Default gateway
•PPP user name
•Phone number
•AT command string
•Alternate phone number
•Unit serial number
•Firmware build number
•Ethernet port MAC address
•Firmware revision
•Potential transformer ratio
Recording the Meter Map
The final step in the installation process is to complete the Installation Record, and
record the mapping of the meters to the wired points. A copy of Figure 14, which is
organized to resemble a breaker panel, is provided with each PowerLogic EM4000
meter, and is to be completed and delivered to your system administrator.
Do not perform any operation or maintenance procedures that are not described in this
product documentation. Visually inspect the equipment yearly and ensure it is free of dust or
other particles. If necessary, wipe with a clean cloth. Individual components are not
user-serviceable and must be returned to Schneider Electric for repair.
Fuse Replacement
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Apply appropriate personal protective equipment (PPE) and follow
safe electrical work practices. See NFPA 70E.
•Turn off all power supplying this equipment before working on or
inside equipment.
•Always use a properly rated voltage sensing device to confirm the
power is off.
•Replace all devices, doors and covers before turning on power to
this equipment.
Failure to follow these instructions will result in death or serious
injury.
1. Turn off all sources of power before attempting to replace the fuse. Always use
a properly rated voltage sensing device to confirm the power is off.
2. Remove the outer cover from the unit.
3. Locate fuse F1 at the top left corner inside the unit.
4. Remove the fuse cover, then remove the fuse from the holder as shown in
Figure 15.
5. Replace fuse F1 with a fuse that meets the specifications listed in Table 1 on
page 2.
6. Replace the fuse cover.
7. Re-install the cover and turn on the power source.
930-134-01-A.00 PowerLogicTM Series EM4000
11/2013Installation Guide
Regulatory Compliance
The PowerLogic EM4000 meter must be installed by a qualified electrician with
knowledge of local installation regulations. Initial installation of the unit, and any
subsequent modification to the unit, must be inspected by the local electrical
inspection authority.
The PowerLogic EM4000 meter complies with the standards listed in Table 3.
Table 3: Regulatory Compliance
DisciplineRegulatory and industry standard
StandardsUL certified to IEC/EA/UL/CSA 61010-1 2nd Edition
CSA-C22.2 No. 61010-1-04
Emissions (EMC)FCC Part 15 Class B, ICES-003 EN55022, IEC 6100-4-5
Surge power/telephone linesANSI/TIA968-A: 2002
Equipment servicing and access
The information in this section must be considered as a mandatory requirement,
and must be strictly adhered to when installing and operating PowerLogic EM4033
and EM4080 meters.
Access to equipment
The equipment must be accessible to authorized personnel only. Equipment must
be installed in areas where access can be restricted.
Servicing the equipment
No preventive maintenance is required on any of the equipment. Visually inspect
the equipment yearly and ensure it is free of dust or other particles. If necessary,
wipe with a clean cloth.
Component servicing
Individual components are not user-serviceable, and must be returned to Schneider
Electric for repair. If an equipment fault occurs, do not attempt to repair the faulty
component.
All maintenance activities should be performed by qualified personnel only. Do not
perform any operating or maintenance procedures that are not described in the
product documentation provided by Schneider Electric.
Graphical symbols
Table 4 shows the graphical symbols that appear on the equipment.
PowerLogicTM Series EM4000
High-Density Meter Installation Guide
Schneider Electric
35 rue Joseph Monier
92500 Rueil-Malmaison, France
www.schneider-electric.com
PowerLogic is a trademark or registered trademark of Schneider Electric in France, the USA and
other countries. Other trademarks used are the property of their respective owners.
This product must be installed, connected and used in compliance with prevailing standards
and/or installation regulations. As standards, specifications and designs change from time to time,
always ask for confirmation of the information given in this publication.