Schneider Electric EM400, EM4800 User Manual

Page 1
PowerLogic
Multi-Circuit Meters
930-112-01-D.00 11/2013
TM
Series EM4000/EM4800
Page 2
Page 3
Safety Information
Important Information
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Please note
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
Page 4
Notices
FCC Part 15 Notice
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures.
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
FCC Part 68 Notice
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the Administrative Council for Terminal Attachments (ACTA). On the side of this equipment is a label that contains, among other information, a product identifier in the format US: AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
This equipment uses the following Universal Service Order Codes (“USOC”) jacks: RJ11.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord and modular plug or compliant modular jack is provided with this product.
The REN is used to determine the number of devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. The REN for this product is part of the product identifier that has the format US: AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3).
If this equipment, Digital Power Meter with Internal Modem, causes harm to the telephone network, the telephone company will notify you in advance that service may be temporarily discontinued. When advance notice is not practical, the
Page 5
telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of this equipment. If this happens, the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
If you experience trouble with this equipment, Digital Power Meter with Internal Modem, please contact Schneider Electric at 615-287-3400. If this equipment is causing harm to the telephone network, the telephone company may request that you disconnect this equipment until the problem is resolved.
There are no user serviceable parts in this equipment.
Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission or corporation commission for information.
If your premises has specially wired alarm equipment connected to the telephone line, ensure that the installation of this Digital Power Meter with Internal Modem does not disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your telephone company or a qualified installer.
Network Compatibility Notice for the Internal Modem
The internal modem in meters equipped with this option is compatible with the telephone systems of most countries in the world, with the exception of Australia and New Zealand. Use in some countries may require modification of the internal modem’s initialization strings. If problems using the modem on your phone system occur, please contact Schneider Electric Technical Support.
Page 6
Page 7
930-112-01-D.00 PowerLogic 11/2013 Table of Contents
TM
EM4000/EM4800 Series
Table of Contents
PowerLogic configuration tool ..................................................................... 1
System Set-up and Description ............................................................. 1
Configuration and Programming...................................................... 1
Display Navigation........................................................................... 3
Communications Connections ......................................................... 5
Configuring the Meters .......................................................................... 7
Login................................................................................................ 7
Connecting to a Meter ..................................................................... 8
Unit Field Configuration Tab.......................................................... 10
Manufacturing Tab......................................................................... 19
Meter Points (Circuits) Tab............................................................ 21
Pulse Probes Tab .......................................................................... 24
Completing the Meter Configuration .............................................. 26
User notes ................................................................................................. 29
©2013 Schneider Electric All Rights Reserved
i
Page 8
PowerLogic
TM
EM4000/EM4800 Series 930-112-01-D.00
Table of Contents 11/2013
©2013 Schneider Electric All Rights Reservedii
Page 9
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013

PowerLogic configuration tool

This document describes how to configure the PowerLogic EM4000/EM4800 Series meters, using the PowerLogic configuration tool. It includes the following configuration tool information:
“System Set-up and Description” on page 1
“Configuration and Programming” on page 1
“Display Navigation” on page 3
“Communications Connections” on page 5
“Configuring the Meters” on page 7
“Login” on page 7
“Connecting to a Meter” on page 8
“Unit Field Configuration Tab” on page 10
“Manufacturing Tab” on page 19
“Meter Points (Circuits) Tab” on page 21
“Pulse Probes Tab” on page 24
“Completing the Meter Configuration” on page 26
This documentation is intended for those responsible for configuring the PowerLogic meters.

System Set-up and Description

The configuration tool supports the following PowerLogic meters
PowerLogic EM4000 Series: PowerLogic EM4033 and EM4080 meters
PowerLogic EM4800 Series: PowerLogic EM4805, EM4833, and EM4880 meters
Depending on how the meters are installed and configured, they can meter 8, 12, or 24 individual meter points. The PowerLogic meters are designed for residential, commercial, and industrial use and display the power and consumption readings for each measurement point.

Configuration and Programming

The configuration tool is used to set any of the programmable parameters of the PowerLogic EM4000/EM4800 Series meter. The combination of the configuration tool and the state of the meter programming switches determine which parameters can be set or changed. As shown in Figure 1, the programming switches are two-position DIP switches labeled SW1, and are located inside the meter cover below the Display button. To enable meter configuration, both switches must be physically set to the ON (down) position (default).
©2013 Schneider Electric All Rights Reserved 1
Page 10
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00
"SW1"
11/2013
Figure 1: Programming Switch location
Table 1 lists the programming capabilities associated with each parameter in combination with the programming switches. After the meter has been programmed, the programming switches can be turned OFF to prevent tampering with metering parameters.
Table 1: Programming access to meter parameters
Parameter Read access Write access Activation time
Meter name Configuration tool Configuration tool Immediate
Badge number Configuration tool Configuration tool Immediate
Phone number Configuration tool Configuration tool Immediate
Alternate phone number Configuration tool Configuration tool Immediate
AT string Configuration tool Configuration tool Immediate
Host upload directory Configuration tool Configuration tool Immediate
Host download directory Configuration tool Configuration tool Immediate
Host IP address Configuration tool Configuration tool Immediate
PPP user name Configuration tool Configuration tool Immediate
PPP password Configuration tool Configuration tool Immediate
2 ©2013 Schneider Electric All Rights Reserved
Page 11
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Parameter Read access Write access Activation time
FTP user name Configuration tool Configuration tool Immediate
FTP password Configuration tool Configuration tool Immediate
Daily report interval start time Configuration tool Configuration tool Immediate
Daily report interval end time Configuration tool Configuration tool Immediate
Report period Configuration tool Configuration tool Immediate
Report interval in minutes Configuration tool Configuration tool Immediate
PT ratio Configuration tool Configuration tool + prog. switch ON Immediate
Default IP address Configuration tool Configuration tool Immediate
Default netmask Configuration tool Configuration tool Immediate
Default gateway Configuration tool Configuration tool Immediate
Reset dial readings No Access Configuration tool + prog. switch ON Immediate
Send PC time No Access Configuration tool Immediate
Programming switch state Configuration tool No Access Immediate
MAC address Configuration tool No Access Immediate
Report types Configuration tool Configuration tool Immediate
Manufacturing
Serial number Configuration tool No Access N/A
Part number Configuration tool No Access N/A
Model number Configuration tool Configuration tool + prog. switch ON After reset
Revision Configuration tool No Access
Firmware revision Configuration tool No Access N/A
Build number Configuration tool No Access
Meter and probe points
Name Configuration tool Configuration tool After reset
CT 1 current Configuration tool Configuration tool + prog. switch ON After reset
CT 2 current Configuration tool Configuration tool + prog. switch ON After reset
CT 3 current Configuration tool Configuration tool + prog. switch ON After reset
CT 1 phase Configuration tool Configuration tool + prog. switch ON After reset
CT 2 phase Configuration tool Configuration tool + prog. switch ON After reset
CT 3 phase Configuration tool Configuration tool + prog. switch ON After reset

Display Navigation

The display on the front of the meter provides status information for each circuit, and general information for metering. The PowerLogic meter has three buttons for navigating: a Display button, and left and right arrow buttons. The display has a normal and a diagnostics mode.
©2013 Schneider Electric All Rights Reserved 3
Page 12
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Normal Mode
In Normal mode, the Display button scrolls through the information for each meter. The left and right arrow buttons select the previous or next meter points respectively. The following information is available:
Real Energy Delivered kWh D
Real Energy Received kWh R
Real Power Watts
Reactive Energy Delivered kVarhD
Reactive Energy Received kVarhR
Reactive Power Var
Peak Demand PeakW (Watts)
In Normal mode, the right and left arrow buttons scroll the display from meter points 1 to 8, 1 to 12, or 1 to 24, depending on your configuration.
Diagnostics Mode
Diagnostics mode is accessed by pressing and holding the Display button for 5 seconds. In Diagnostics mode, pressing the Display button will scroll through the following information in addition to the Normal mode data:
Send data command
CT Primary value and Real Power (Watts) per phase
Current (Amps) per phase
Power Factor (pf) per phase
Phase angle (Degrees) per phase
Voltage per phase
Local IP address
Reset factory default IP address command
•Verify
Badge #
Date and time (UTC)
In Diagnostics mode, the right and left arrow buttons scroll the display from meter 1 through N. When the local IP address is shown on the LCD, use the right and left arrow buttons to scroll through the following information:
Remote host server IP address
Time server IP address
Default IP address
Default NetMask
Default gateway
PPP user name
Phone number
AT command string
Alternate phone number
Unit serial number
Firmware build number
4 ©2013 Schneider Electric All Rights Reserved
Page 13
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Ethernet port MAC address
Firmware revision
Potential transformer ratio

Communications Connections

If you are configuring the meter at an installation site, see the PowerLogic EM4000 Series Meter Installation Guide or the PowerLogic EM4800 Series Meter Installation Guide for instructions on connecting the power. Power connections vary
depending on whether the meter is configured for single-phase or three-phase operation.
If you are pre-configuring the meter in the shop, only Phase A, Neutral, and protective earth connections are required to power up the meter for configuring.
The PowerLogic EM4000/EM4800 Series Configuration Tool runs on a Windows PC and communicates with the PowerLogic meters through an Ethernet network connection. A network connection can be accomplished in two ways: either Direct, or by connecting to a LAN (Local Area Network).
Direct Connection Ethernet Requirements
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
This equipment must only be installed and serviced by qualified electrical personnel.
Turn off all power supplying this equipment before working on or inside equipment.
Always use a properly rated voltage sensing device to confirm power is off.
Replace all devices, doors and covers before turning on power to this equipment.
The meters must be connected to the sense voltage and control voltage through a properly rated disconnect.
Failure to follow these instructions will result in death or serious injury.
To connect a PC directly to the PowerLogic meter:
1. Disconnect power from the meter with the installed breaker or disconnecting device. Use a properly rated voltage sensing device to confirm power is off.
2. Remove the outer cover.
3. If you are changing parameters that require the programming switch to be on, remove the inner cover and ensure the programming switches are in the ON position.
4. Re-install the inner cover.
5. Remove the local LAN Ethernet cable if present and connect the CAT 5 Ethernet cable between the PC and the PowerLogic meter. If the PC does not have auto-crossover detection, an Ethernet crossover cable will be required.
6. Restore power to the meter.
©2013 Schneider Electric All Rights Reserved 5
Page 14
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
7. Assign the PC a static IP address such that the first three segments are the same as the default IP address, and the last segment is different from the default IP address. For example, 169.254.0.xxx, where xxx differs from the last segment of the default IP address.
Enter 255.255.255.0 into the subnet mask field.
For Windows 7 users, you must enter the IP address of the meter into the Default Gateway field.
8. Configure the meter. See “Configuring the Meters” on page 7 for configuration instructions.
9. Remove power. Use a properly rated voltage sensing device to confirm power is off.
10.If you wish to lock the configuration parameters, remove the inner cover and move the programming switches (SW1) to the OFF (up) position.
11.Re-install the inner cover.
12.Connect the LAN Ethernet cable if present.
13.Re-install the outer cover.
14.Restore power.
NOTE: All PowerLogic meters have a default IP address of 169.254.0.10 in the absence of a DHCP service.
Network Connection Ethernet Requirements
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
This equipment must only be installed and serviced by qualified electrical personnel.
Turn off all power supplying this equipment before working on or inside equipment.
Always use a properly rated voltage sensing device to confirm power is off.
Replace all devices, doors and covers before turning on power to this equipment.
The meters must be connected to the sense voltage and control voltage through a properly rated disconnect.
Failure to follow these instructions will result in death or serious injury.
To connect the PowerLogic meter to the network:
1. Turn off power to the meter with the installed breaker or disconnecting device. Use a properly rated voltage sensing device to confirm power is off.
2. Remove the outer cover.
3. If you are changing parameters that require the programming switch to be on, remove the inner cover and ensure the programming switches are in the ON position.
6 ©2013 Schneider Electric All Rights Reserved
Page 15
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
4. Re-install the inner cover.
5. Using a CAT 5 Ethernet patch cable, connect the meter and the PC to a local Ethernet switch.
6. Re-install the outer cover.
7. Restore power. When control power is restored, the meter will receive an IP address from a local DHCP server. This IP address can be viewed from the Diagnostics menu.
NOTE: To use a static IP address, have your local network administrator assign the desired IP address to the MAC address of the meter in the DHCP server configuration. To display the MAC address, see “Display Navigation” on page 3.

Configuring the Meters

The PowerLogic EM4000/EM4800 Series configuration tool is available on the CD shipped with each unit, and is used to configure all programmable parameters listed in Table 1.
NOTE: Disable any firewall software on your PC before attempting to connect to a meter using the configuration tool.

Login

Use the following procedure to log in to the meter.
1. Establish an Ethernet network connection with the meter using one of the methods described in “Communications Connections” on page 5.
2. Ensure the programming switches are in the ON position. The programming switches are two-position DIP switches labeled SW1, and are located inside the meter cover below the Display button. To enable meter configuration, both switches must be physically set to the ON position. When both switches are in the OFF position, meter configuration is disabled.
3. Start the configuration tool by entering “PowerLogic” as the User Name, and “E4800” as the Password (see Figure 2). Click Ok.
Figure 2: Login screen
4. The main window displays as shown in Figure 3.
©2013 Schneider Electric All Rights Reserved 7
Page 16
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Figure 3: Configuration tool main window

Connecting to a Meter

The configuration tool automatically detects and lists the PowerLogic meters on the same network segment as the PC. The configuration tool can also be used with meters on a different network.
8 ©2013 Schneider Electric All Rights Reserved
Page 17
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
To connect to a meter on the same network:
1. Click Unit in the menu bar, then select List from the drop-down menu. The Discovered Units window appears, displaying a list of meters available for configuration. See Figure 4.
Figure 4: Discovered Units dialog box
2. Select the Load Unit Configuration check box, then click Ok. The main configuration tool window appears populated with the current programming information for the selected meter. See Figure 5.
3. Proceed to “Unit Field Configuration Tab” on page 10.
To connect to a meter on a different network:
1. Click Unit in the menu bar, then select Connect from the drop-down menu. The Connect to Unit window appears. See Figure 5.
Figure 5: Connect function window
©2013 Schneider Electric All Rights Reserved 9
Page 18
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
2. Enter the IP address of the meter to be configured, then click Connect. The configuration tool main window appears populated with the current programming information for the selected meter. See Figure 6.
3. Proceed to “Unit Field Configuration Tab” on page 10.
Figure 6: Main configuration window with configured parameters

Unit Field Configuration Tab

Use Table 2 to set meter configuration parameters in the Unit Field Configuration tab.
10 ©2013 Schneider Electric All Rights Reserved
Page 19
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Table 2: Unit Field Configuration tab parameters
Field Parameter Description
Unit Field Configuration Current IP Address The current IP address for the unit .This parameter is read only and cannot be
Mac Address The current MAC address for the unit. This parameter is read only and cannot be
Revision The revision number of the unit.
Default IP Configuration IP Address The default IP address. This parameter is configured when DHCP has been disabled,
Netmask The default subnet mask. This parameter is configured when DHCP has been
Gateway The default gateway. This parameter is configured when DHCP has been disabled, or
DNS Primary The primary domain name server. This parameter is configured when DHCP has been
DNS Secondary The secondary domain name server. This parameter is configured when DHCP has
DHCP Enabled If DHCP is not enabled, the meter uses the Default IP Configuration parameters. If
Report See “Report Parameters” on page 12
Main Meter PT Ratio The main meter potential transformer ratio. This is an internal multiplier used by the
Modem Phone # The phone number of your internet service provider’s PPP service.
Alternate Phone # An alternate phone number of your internet service provider’s PPP service.
changed by the user.
changed by the user.
or DHCP services are not available on the network.
disabled, or DHCP services are not available on the network.
DHCP services are not available on the network.
disabled, or DHCP services are not available on the network.
been disabled, or DHCP services are not available on the network.
DHCP is enabled, the meter uses the IP configuration parameters provided by the network DHCP service.
meter for external potential transformers. External PTs can be used with a PT ratio of 1 if the billing system will apply the PT multiplier.
Use a PT Ratio of 1 with no external PTs.
AT String AT command string to customize modem operation. Default string is ATX3, do not wait
Wait for Dial Tone Do not enable this parameter if the line has a broken dial tone due to a message
Host Server IP Address The IP address or domain name of the FTP server for data storage.
Upload Directory The sub-directory used for data reporting within the root directory. The root directory
Download Directory The sub-directory used by the meter to retrieve configuration updates. The FTP
FTP Login User Name The user name for the FTP account.
Password The password for the FTP account.
PPP Login User Name The user name for the PPP account. This is only required if using dial-up reporting.
Password The password for the PPP account. This is only required if using dial-up reporting.
NTP Host (Time Server) IP Address The IP address of the NTP server that provides timing to the meter.
for dial tone.
waiting feature.
is determined by the FTP user name and the FTP server configuration. The FTP account must have write access to this directory.
account must have read access to this directory..
©2013 Schneider Electric All Rights Reserved 11
Page 20
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Report Parameters
The Report section in the main configuration window has six tabs:
Intervals tab allows the user to configure the recording interval at which meter data is
collected, and the demand interval for which demand readings are calculated. Figure 7 shows the Intervals tab, and Table 3 lists the configuration parameters within the tab.
Types tab allows the user to define the metering data parameters that are to be logged
on each recording interval, then reported per the Reporting Schedule. Figure 8 shows the Types tab, and Table 4 lists the configuration parameters within the tab.
Reporting Schedule tab allows the user to configure how often the meter is to send
recording interval data to a server. Figure 9 shows the Reporting Schedule tab, and Table 5 lists the configuration parameters within the tab.
Calculations & Format tab allows the user to configure the type of power factor
calculation and the display format for leading vs. lagging power factor. Figure 10 shows the Calculations & Format tab, and Table 6 lists the configuration parameters within the tab.
BACnet tab allows the user to configure the BACnet Device interface. Figure 11 shows
the BACnet tab, and Table 7 lists the configuration parameters within the tab.
Comms tab allows the user to configure the communications module and change the
Meter Utility Password. Figure 12 shows the Comms tab, and Table 8 lists the configuration parameters within the tab.
Figure 7: Intervals tab in the Report section
Table 3: Intervals tab configuration parameters
Parameter Description
Recording Interval in Minutes The interval at which meter data is collected.
Demand Interval Setup
Block Demand Select Block Demand calculation for demand data.
Sliding Window Demand Select Sliding Window Demand calculation for demand data.
12 ©2013 Schneider Electric All Rights Reserved
Page 21
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Parameter Description
Demand Interval in Minutes The size of the block demand window in minutes (select from the
Number of Sub-intervals The number of recording sub-intervals that make up the sliding
pull-down menu).
demand interval (select from the pull-down menu).
Example: Selecting a Recording Interval of 5 minutes with Sliding Window Demand enabled and 3 Sub-intervals, creates a demand calculation every 5 minutes based on the previous 15 minutes. This is the common demand measurement used by North American utilities when billing for Demand.
NOTE: To activate the Demand Interval Setup settings, Peak Demand must be enabled (
) in the Types tab (see Figure 8).
Figure 8: Types tab in the Report section
©2013 Schneider Electric All Rights Reserved 13
Page 22
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Table 4: Types tab configuration parameters
Parameter Description
Watt Hours Delivered Interval/Register These types of records can be enabled by
Watt Hours Received Interval/Register
VAR Hours Delivered Interval/Register
VAR Hours Received Interval/Register
VA Hours Interval/Register
Present Demand
Peak Demand
Peak Current
Voltage
Pulses
selecting () the check box.
NOTE: If parameters are grayed out, they are not available on the variant or firmware revision of the meter being configured.
14 ©2013 Schneider Electric All Rights Reserved
Page 23
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Figure 9: Reporting Schedule tab in the Report section
Table 5: Reporting Schedule tab configuration parameters
Parameter Description
Daily (default) Enables daily real time reporting.
Start Time When daily reporting is enabled, select the reporting period start time.
End Time When daily reporting is enabled, select the reporting period end time.
Minutes Enables real time reporting every x number of minutes by selecting the
The unit sends the data file at a randomly selected time within the report window specified by the start and end time .
radial button and entering the interval in minutes.
NOTE: When selecting a Daily report schedule, the Start Time must occur before the End Time within the midnight to midnight 24-hour time period.
©2013 Schneider Electric All Rights Reserved 15
Page 24
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Figure 10: Calculations & Format tab in the Report section
Table 6: Calculations & Format tab configuration parameters
Parameter Description
Power Factor
Sign Format IEEE In the display, the sign (+ or -) indicates leading (+) or
IEC (default) In the display, the sign (+ or -) indicates the direction
Method of Calculation Arithmetic Selects the arithmetic method for calculating Power
Vector (default) Selects the vector method for calculating Power
lagging (-) power. The direction of active power is not indicated.
of active power. Lead or lag indicates capacitive or inductive power.
Factor.
Factor
16 ©2013 Schneider Electric All Rights Reserved
Page 25
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Figure 11: BACnet tab in the Report section
Table 7: BACnet tab configuration parameters
Parameter Description
Device ID Set the BACnet device ID by entering a a numeric ID between 0 and
Network Port The BACnet specific port number for this device (default is 47808).
BBMD Timeout Enter the amount of time (seconds) required for connection to a BACnet
BBMD Address Enter the address of the BBMD device that controls all devices in the
Description A user selectable description of the device (default is Power Meter)
Vendor ID BACnet Vendor Identification number (default is 10)
Vendor Name Schneider Electric (default)
Software Version The software version of the PowerLogic product (fixed).
UTC Offset Fixed at 0
Location A user selectable description of the physical location of the unit (default is
Object Name PowerHawk Meter (default)
4194303.
network.
BACnet network.
Unknown).
©2013 Schneider Electric All Rights Reserved 17
Page 26
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Figure 12: Comms tab in the Report section
18 ©2013 Schneider Electric All Rights Reserved
Page 27
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Table 8: Comms tab configuration parameters
Parameter Description
Parameters
Comms Option Modem Selecting Modem configures the communications
None Selecting None disables the communications
RTU Adapter Selecting RTU Adapter configures the
RTU comms config Enter the RTU serial port parameters as a string
Modbus base address Enter the Modbus RTU address for this device (1
Utility Password
Current Password The default meter Utility Password is listed here
Enter new password To change the password, enter the new password.
Enter new password again To confirm, re-enter the new password.
module as a dial-up modem for remote reporting via a phone line.
module interface
communications module as a Modbus RS422/RS485 serial interface.
with the following selections: baud rate (19200 or
9600), number of bits (8), number of start bits (1), number of stop bits (1), parity type (e – even, n – none
Example: 19200,8,1,e (default)
to 255)
whenever the Configuration Tool is started or when a configuration is uploaded from a meter.
If the Utility Password for the meter is not the default password, enter the Current Password here to change metering specific parameters or to change the password again.
NOTE: The Modbus and RTU Adapter Comms Option parameters are valid only when a Modem module or an RTU adapter module is present. The RTU Adapter parameters apply only to Modbus RTU communications. There are no configuration options when Modbus over TCP/IP is used.
NOTE: : The meter Utility Password is used to control access to changing the metering specific parameters in the PowerLogic meter. The following parameters and functions cannot be changed or activated unless the correct Utility Password is entered before sending the new config to the meter:
PT Ratio CT Current and Phase Reset Dial Readings Model Number Change Password All other parameters and functions can be changed or accessed without entering the correct Utility Password for the meter being configured.

Manufacturing Tab

The Manufacturing tab allows the user to define the metering configuration for the PowerLogic meters. The meters support the configurations listed in Table 9.
©2013 Schneider Electric All Rights Reserved 19
Page 28
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Table 9: List of supported PowerLogic metering configurations
EM4033xx EM4080xx EM4805xx EM4833xx EM4880xx
EM4033xx-1P-12 EM4080xx-1P-12 EM4805xx-1P-12 EM4833xx-1P-12 EM4880xx-1P-12
EM4033xx-1P-24 EM4080xx-1P-24 EM4805xx-1P-24 EM4833xx-1P-24 EM4880xx-1P-24
EM4033xx-2P-12 EM4080xx-2P-12 EM4805xx-2P-12 EM4833xx-2P-12 EM4880xx-2P-12
EM4033xx-2P-24 EM4080xx-2P-24 EM4805xx-2P-24 EM4833xx-2P-24 EM4880xx-2P-24
EM4033xx-3P-08 EM4080xx-3P-08 EM4805xx-3P-08 EM4833xx-3P-08 EM4880xx-3P-08
To view the manufacturing information for a specific meter, select a model number from the Model # pull-down list shown in Figure 13. The part number, revision number and serial number for the selected model will be shown.
Figure 13: Manufacturing tab
20 ©2013 Schneider Electric All Rights Reserved
Page 29
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013

Meter Points (Circuits) Tab

The Meter Points (Circuits) tab contains the configuration information for each of the metering points. It shows the number of elements used, the phase, the current ratings, and the user-defined identification string for each meter point. Default information is entered when the metering configuration is selected in the
Manufacturing Tab (see “Manufacturing Tab” on page 19).
Meter Point Configuration
The current rating and phase assignment for each meter point can be configured individually, by meter, or all at once. The configuration in all three cases does not take effect until the new settings have been sent to the meter (see “Completing the Meter Configuration” on page 26).
To change the current rating and phase assignment for an individual meter point:
1. Select one probe at a time from the Meter Points (Circuits) List. The selected probe number will appear in the middle pane beside Probe, and its assigned Current and Phase are shown beneath it. See Figure 14.
2. To change the Current, enter the required number. To change the Phase, select the required phase type from the pull-down list.
Figure 14: Meter Points configuration screen
©2013 Schneider Electric All Rights Reserved 21
Page 30
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
To change the current rating for all probes assigned to a meter point:
1. Select a meter from the Meter Points (Circuits) List. The selected meter will appear in the Name field of the middle pane. See Figure 14.
2. In the Alter Current for Probes pane, enter the desired value referenced to the CT primary rating in the Current field, and click on Change Probes in Selected Meter.
To change the current rating for all probes assigned to all meter points:
1. In the Alter Current for Probes pane, enter the desired value referenced to the CT primary rating in the Current field, and click on Change all Probes in all
Meters. See Figure 14.
Badge Numbering
Each meter point can be configured with a name defined by the user. The meter point name, known as the badge number, can be up to 13 alphanumeric characters in length. The Badge Numbering pane allows the user to set two types of badge numbers:
sequential, which assigns a badge number to each meter point after the prefix (for example CORP-00000001 to CORP-00000012)
grouped by meter, which uses a base prefix to designate the meter, then assigns a sequential badge number suffix to each meter point assigned to that meter (for example CORP-00001-01 to CORP-00001-12)
The configuration tool provides examples before the badge number is assigned to the meter. In the Badge Numbering pane shown in Figure 15, the following fields and buttons are provided for assigning badge numbers:
Prefix field - an alphanumeric field that prefixes the number field.
Badge Number field - a numeric field that becomes part of the prefix for meter points assigned to that meter, or the first number in the sequence to be assigned to individual meter points.
Badge Number Width field - a numeric field that defines the number of digits in the badge number field. Zeroes (0) are automatically entered at the beginning of the badge number field until the total number of digits in the badge number field equals the number of digits defined in the badge number width field.
Incremental badge numbers button - selecting this button assigns a sequential badge number for each meter point
Single badge number button - selecting this button assigns one badge number prefix followed by a numeric suffix for each meter point assigned to that meter.
Assign Badge Numbers button - selecting this button implements the badge numbering defined by the user in the previous fields.
22 ©2013 Schneider Electric All Rights Reserved
Page 31
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Figure 15: Badge Numbering pane
Reset Buttons
Reset Dial Readings button - selecting this button resets all registers for all energy types and pulse counts to zero. This function takes effect immediately and does not require a send action.
Send PC Time button - selecting this button configures the meter with the current PC UTC and local time. This function takes effect immediately and does not require a send action. This function can be used when access to the network time service is not available.
©2013 Schneider Electric All Rights Reserved 23
Page 32
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
Adjust Dial Reading button - selecting this button allows the operator to set all of the following energy type registers to the same fixed initial value:
Delivered Watt Hours
Received Watt Hours
Delivered VAR Hours
Received VAR Hours
VA Hours
This function takes effect immediately and does not require a send action.
Reset Demand Reading button - selecting this button resets the Peak Demand register for all meter points to zero. This function takes effect immediately and does not require a send action.

Pulse Probes Tab

The Pulse Probes tab contains the configuration information for each pulse input. It shows the measurement type in units for each input, and the scale factor applied to the collected pulse counts. Figure 16 shows the Pulse Probes tab of the main configuration tool window.
To configure a pulse probe:
1. Enable () Pulses in the Types tab of the Report section in the Unit Field Configuration tab. See Figure 8 on page 13.
NOTE: The Pulse Probe settings are not active unless Pulses are enabled in the Types tab.
2. Select a pulse probe from the Probe List.
3. Select a measurement type from the Type pull-down list.
4. Enter a value in the Scale Factor field.
NOTE: This scale factor only changes the pulse values in the TR3 report. The pulse count in the device web page is not scaled.
24 ©2013 Schneider Electric All Rights Reserved
Page 33
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
Figure 16: Pulse Probes tab
©2013 Schneider Electric All Rights Reserved 25
Page 34
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013

Completing the Meter Configuration

Once you have defined all of the configurable parameters, the PowerLogic meter is ready to be programmed.
To complete the meter configuration:
1. Click Unit in the menu bar, then select Save from the drop-down menu. See Figure 17.
Figure 17: Saving the configuration settings
26 ©2013 Schneider Electric All Rights Reserved
Page 35
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013
2. Click Unit in the menu bar, then select Send from the drop-down menu to transmit the configuration settings from your PC to the selected PowerLogic meter. The confirmation message File loaded successfully! should appear in the bottom left corner of the window. See Figure 18.
Figure 18: Sending the configured settings to the meter
©2013 Schneider Electric All Rights Reserved 27
Page 36
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
28 ©2013 Schneider Electric All Rights Reserved
Page 37
930-112-01-D.00 PowerLogicTM Series EM4000/EM4800 11/2013

User notes

©2013 Schneider Electric All Rights Reserved 29
Page 38
PowerLogicTM Series EM4000/EM4800 930-112-01-D.00 11/2013
30 ©2013 Schneider Electric All Rights Reserved
Page 39
Page 40
PowerLogicTM Series EM4000/EM4800 Multi-Circuit Meters
Schneider Electric
35 rue Joseph Monier 92500 Rueil-Malmaison, France www.schneider-electric.com
PowerLogic is a trademark or registered trademark of Schneider Electric in France, the USA and other countries. Other trademarks used are the property of their respective owners.
This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations. As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.
930-112-01-D.00 11/2013
©2013 All Rights Reserved
Loading...