Schneider Electric APC Smart-UPS RT Users Manual

Page 1
User Manual
English
APC Smart-UPS® RT
Uninterruptible Power Supply
Rack-Mount 3U/Tower
120/208/240 Vac
SURTD6000RMXLJP
100/200 Vac
990-3271 07/2008
Page 2
Page 3
Introduction
The APC Smart-UPS® RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.
INSTALLATION
Read the Safety Guide before installing the UPS.
Unpacking
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents:
UPS (with battery modules disconnected)Front bezelStabilizing feet and screwsTop cover and screwsSURTRK2 rail kitSerial cableNetwork Management Card
(i
ncluded in the UP
S)
Specifications
TEMPERATURE OPERATING S
TORAGE
MAXIMUM ELEVATION
PERATING
O
TORAGE
S
HUMIDITY WEIGHT
UPS
WITH
UPS PACKAGING
0° to 40° C (32° to 104° F)
-15° to 45° C (5° to 113° F) charge the UPS battery(s) every six months
3,000 m (10,000 ft) 15,240 m (50,000 ft)
0 to 95% relative humidity, non-condensing
58 kg (128 lbs) 72 kg (159 lbs)
Literature kit containing:
Product documentation User Manual CD Warranty Information Software CD
Network Management Card documentation
This unit is intended for indoor use only. Select a location sturdy enough to handle the weight.
Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the specified limits.
Ensure that the air vents are not blocked.
Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.
1
Page 4
I
NSTALL THE MOUNTING RAILS
For detailed rail installation instructions, refer to the rail installation guide included in the rail kit.
I
NSTALL IN A RACK
For detailed rack installation instructions, refer to the Installation Guide – Tower to SURTRK2 Rack Conversion document.
R
EMOVE THE BATTERIES
The unit is heavy. To lighten the unit, remove the batteries.
 
 
2
Page 5
 
R
ACK-TO-TOWER CONVERSION
3
Page 6

I
NSTALL THE BATTERIES
 
4
Page 7
Z
\


5
Page 8
B
ASIC CONNECTORS
Connect the UPS to a computer terminal.
Use only cables approved by APC.
Serial Port
Any other interface cable will be incompatible with the UPS connector.
Manually put equipment into bypass mode.
On-Line or Bypass Switch
Connect the UPS to the central EPO system.
EPO Terminal
Connect the ground lead on surge suppression devices, such as telephone
TVSS Screw
and network line protectors.
When connecting grounding cable, disconnect the unit from the utility power outlet.
Optional external battery packs provide extended run time during power outages. These units support up to ten external battery pa cks.
External Battery Pack Connector
See the APC Web site, www.apc.com battery pack, SURT192RMXLBP.
CONNECT EQUIPMENT AND POWER TO THE UPS
for the information on the external
1. Connect equipment to the UPS (cables not included). Avoid using extension cords.
Using a power cord, plug the UPS into a three-pole, four-wire, grounded receptacle only.
SURTD6000RMXLP3U and SURTD6 00 0R MXLJP3U models: To draw full power from the
UPS have a qualified electrician cut off the input plug and hardwire the UPS to the appropriate power panel.
2. Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all
connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.
3. Press Test on the front panel to turn the UPS on.
The UPS battery charges when it is connected to utility power. The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery ru n capability during this initial charge period.
PTIONS
O
Refer to the APC Web site, www.apc.com
External Battery Pack SURT192RMXLBP, SURT192XLBP Service Bypass Panel
for available accessories.
6
Page 9
P
OWER RATINGS OF THE UPS UNDER DIFFERENT LOADS
MAX OUTPUT with Standard Plug, 50-60 Hz
Model MAX OUTPUT PER PHASE
SURTD5000RMXLP3U
SURTD6000RMXLP3U
SURTD6000RMXLJP3U
Model MAX OUTPUT PER PHASE
SURTD5000RMXLP3U
SURTD6000RMXLP3U
SURTD6000RMXLJP3U
OPERATION
Load
MAX OUTPUT AT 200 V/208 V
AT 100 V/ 120 V, SPLIT-PHASE
2500 VA, 2000 W, 120 V, 21A 4350 VA, 3500 W, 208 V, 21 A
2880 VA, 2100 W, 120 V, 24 A 5000 VA, 3675 W, 208 V, 24 A
2400 VA, 2100 W, 100 V, 24 A 4800 VA, 4200 W, 200 V, 24 A
MAX OUTPUT with Input Hardwired, 50-60 Hz
AT 100 V/ 120 V, SPLIT-PHASE
2500 VA, 2000 W, 120 V, 21A 4350 VA, 3500 W, 208 V, 21 A
3000 VA, 2100 W, 120 V, 25 A 5200 VA, 3675 W, 208 V, 25 A
3000 VA, 2100 W, 100 V, 30 A 6000 VA, 4200 W, 200 V, 30 A
SMART-UPS RT FRONT DISPLAY
(LINE - LINE LOADING)
MAX OUTPUT AT 200 V/208 V
(LINE - LINE LOADING)
Battery Charge
Indicator Description
Online
The Online LED illuminates when the UPS is drawing utility power and performing double conversion to supply power to connected equipment.
On Battery
The UPS is supplying battery power to the connected equipment.
Bypass
The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility power is sent directly to connected equipment during bypass mode.Bypass mode operation is the result of an internal UPS fault, an overload condition or a user initiated command.Battery operation is not available while the UPS is in bypass mode. Refer to Troubleshooting.
7
Page 10
Overload
An overload condition exists. See Troubleshooting.
Fault
Replace Battery
The UPS detects an internal fault. Refer to Troubleshooting in this manual.
The battery is disconnected or must be replaced. See Troubleshooting.
Feature Function
Power On
Press this button to turn on the UPS. (See below for additional capabilities.)
Power Off
Press this button to turn off the UPS.
Cold Start
When there is no utility power and the UPS is off, press and hold the power up the UPS and connected equipment.
The UPS will emit two beeps. During the second beep, release the button.
Self-Test
Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery.
button to
Manual: Press and hold the
Diagnostic Utility Voltage
The UPS has a diagnostic feature that displays the utility voltage.
button for a few seconds to initiate the self-test.
Plug the UPS into the normal utility power.
The UPS starts a self-test as part of this procedure. The self­test does not affect the voltage display.
Press and hold the display. The five-LED, Battery Charge
the front panel shows the utility input voltage. Refer to the figure at left for the volt age reading (values are not
listed on the UPS). The display indicates the voltage is between the displayed value
on the list and the next higher value. The display shows the high value of the input phase voltages.
8
button to view the utility voltage bar graph
display on the right of
Page 11
PDU OPTIONS
Default
Smart-UPS RT 5/6kVA 100/120/200//208 V PDU Kit—SURT016
Smart-UPS RT 5/6kVA 200/208 V PDU Kit (20 A)—SURT015
Smart-UPS RT 5/6kVA 100/120 V PDU Kit—SURT014
9
Page 12
Smart-UPS RT 5/6kVA 200/208 V PDU Kit (30 A)—SURT017
Smart-UPS RT 5/6kVA Input/Output PDU Kit (Hardwire)—SURT018
CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.
ACTORY
FUNCTION
Automatic Self-Test On start-up and
F
EFAULT
D
every 14 days, thereafter
SER SELECTABLE CHOICES DESCRIPTION
U
On start-up and every 7 days thereafter
Set the interval at which the UPS will execute a self-test.
On start-up and every 14 days thereafter
On start-up only No self-test
Date of Last Battery Replacement
Minimum Run time Before Return from Shutdown
Manufacture date Date of
battery replacement
Reset this date when you replace the battery modules.
0 seconds 0 to 3600 seconds Specify the amount of battery
runtime required to turn the UPS back on after the battery has been completed discharged. This prevents the UPS from turning back on until the batteries have been charged to the specified levels. (Note: 0 disables this function.)
Audible Alarm Setting
ON ON, OFF Enable or disable all alarms
permanently.
10
Page 13
NOTE: SETTINGS ARE MADE THROUGH SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION
Simple Shutdown Delay
ACTORY
F D
EFAULT
USER SELECTABLE CHOICES DESCRIPTION
90 seconds 0 to 1800 seconds Set the interval between the
time when the UPS receives a simple shutdown command and the actual shutdown.
Simple Low Run
150 seconds 0 to 1800 seconds Change the warning interval
Time Warning
Bypass Tolerance Wide Wide, Medium, Narrow, or
Custom
High Bypass Point
Output Voltage Setting: 200 /100 Vac
220/110 Vac
212Vac–280 Vac L-L 106Vac–140 Vac L-N
Output Voltage Setting: 208/120 Vac
229/132 Vac
220 Vac– 242 Vac L-L
127 Vac–140 Vac L-N
Output Voltage Setting: 240 /120 Vac
264/132 Vac
254 Vac–280 Vac L-L 127 Vac–140 Vac L-N
default to a higher setting if the operating system requires a longer interval for shutdown.
The low battery warning beeps are continuous when 150 seconds of run time remain.
Select one of these settings, based on the operating environment.
If Wide, Medium, or Narrow is selected, factory defined values are used for the High Bypass Point, Low Bypass Point, and Bypass Acceptable settings. If changes are made to any of these settings, the tolerance value will change to Custom. (See Tolerance Settings at the bottom of this table.)
Maximum voltage that the UPS will pass to connected equipment during internal bypass operation.
11
Page 14
Low Bypass Point
Output Voltage Setting: 200/100 Vac 164/82 Vac
170 Vac–184 Vac L-L 85 Vac–92 Vac L-N
Minimum voltage that the UPS will pass to connected equipment during internal bypass operation.
Output Voltage Setting: 208/120 Vac
171/98 Vac
170 Vac–192 Vac L-L 98 Vac–110 Vac L-N
Output Voltage Setting: 240 /120 Vac
196/98 Vac
170 Vac–220 Vac L-L 85 Vac–110 Vac L-N
Bypass Acceptable1
Not required
Required/Not required Phase and frequency lock
required/not required before the UPS will switch to bypass.
Output Voltage
RMXLP3U models:
2
Auto 208/240/120 Vac
200/100 Vac, 208/120 Vac, 240/120 Vac,
Allows the user to select the on-line output voltage.
Auto2 208/240/120 Vac
RMXLJP3U models:
200/100 Vac
Output Frequency Automatic
50 ± 3 Hz or 60 ± 3 Hz
200/100 Vac, 208/120 Vac, 240/120 Vac
50 ± 3 Hz 50 ± 1 Hz 50 ± 0.1 Hz
60 ± 3 Hz 60 ± 1 Hz 60 ± 0.1 Hz
Auto 50 ± 3 Hz or 60 ± 3 Hz
1
There can be a phase hop in output voltage when ‘not required’ option is selected in Bypass Acceptable mode.
2
The phase voltage in Auto mode is always 120Vac. The Output phase difference between two phases tracks the input phase
difference.
Allows the user to select the on-line output voltage.
Sets the allowable UPS output frequency. Whenever possible, the output frequency tracks the input frequency.
Tolerance Settings
Wide Medium Narrow High Bypass
Point Low Bypass
Point Bypass
Acceptable Number of
External Battery Packs
264 Vac L-L/132Vac L-N 260 Vac L-L/130 Vac L-N 254 Vac L-L/127 Vac L-N
197 Vac L-L/98 Vac L-N 208 Vac L-L/104 Vac L-N 220 Vac L-L/110 Vac L-N
Not Required Not Required Not Required
0 0 to 100 Defines the number of external
connected battery packs for proper run time prediction.
12
Page 15
200/100
Wide Medium Narrow High Bypass
Point Low Bypass
Point Bypass
Acceptable
208/120
Wide Medium Narrow High Bypass
Point Low Bypass
Point Bypass
Acceptable
VAC OUTPUT VOLTAGE SETTING:
220 Vac L-L/110Vac L-N 216 Vac L-L/108 Vac L-N 212 Vac L-L/106 Vac L-N
164 Vac L-L/82 Vac L-N 174 Vac L-L/87 Vac L-N 184 Vac L-L/92 Vac L-N
Not Required Not Required Not Required
VAC OUTPUT VOLTAGE SETTING:
229 Vac L-L/132 Vac L-N 225 Vac L-L/130 Vac L-N 220 Vac L-L/127 Vac L-N
171 Vac L-L/98 Vac L-N 181 Vac L-L/104 Vac L-N 192 Vac L-L/110 Vac L-N
Not Required Not Required Not Required
C
ONNECTING THE EPO (EMERGENCY POWER OFF) OPTION
The output power can be disabled in an emergency by closing a switch connected to the EPO.
Adhere to national and local electrical codes when wiring the EPO.
The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers. The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC
standard). Both Class 2 and SELV circuits must be isolated from all primary circuitry.
Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.
If circuit standard cannot be confirmed, use a contact closure switch. Use one of the following cable types to connect the UPS to the EPO
switch:
CL2: Class 2 cable for general use
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
13
Page 16
Configure UPS Parameters using terminal mode
Terminal Mode is a menu driven interface that enables configuration of the UPS by users not using the installed Network Management Card interfaces.
C
ONFIGURE UPS CONNECTION USING TERMINAL MODE
1. Connect the serial cable to the serial port on the back of the UPS.
2. Open a terminal program, such as HyperTerminal
®
. From the desktop, go to Start, Programs,
Accessories, Communication, HyperTerminal.
3. Follow the prompts to choose a name and select an icon. Disregard the message, “...must install
a modem,” if it is displayed. Click OK.
4. Select File, Properties.
5. Select the COM port that is connected to your UPS.
6. Click Configure.
7. Enter the settings:
bits per second - 9600
data - bits 8
parity - none
stop bit - 1
flow control – none
8.
Click OK.
9.
Press Enter to initiate the connection to the UPS.
C
ONFIGURE NUMBER OF BATTERY PACKS USING TERMINAL MODE
1. Connect to the unit (see Configure UPS Connection using Terminal Mode).
2. Press 1 to modify the UPS settings.
3. Press D - # of External Battery Packs.
4. Enter the number of battery packs
5. Press Enter and Y to accept the changes.
6. Press ESC to exit the program.
ONFIGURE THE UPS CONNECTING USING NMC TERMINAL MODE
C
1. Connect the serial cable to the serial port on the back of the UPS. (If using USB communication
to the UPS, disconnect the USB cable first.)
2. Open a terminal program, such as HyperTerminal
®
. From the desktop, go to Start, Programs,
Accessories, Communication, HyperTerminal.
3. Follow the prompts to choose a name and select an icon. Disregard the message, “...must install
a modem,” if it is displayed. Click OK.
4. Select File, Properties.
5. Select the COM port that is connected to your UPS.
6. Click Configure.
14
Page 17
7. Enter the settings:
bits per second - 9600
data - bits 8
parity - none
stop bit - 1
flow control – none
8.
Click OK.
9.
Press Enter to initiate the connection to the UPS.
CONFIGURE THE NUMBER OF BATTERY PACKS USING NMC TERMINAL MODE
1. Once the blank terminal window is open, press Enter multiple times, until the prompt.
2. Press 1 and Enter to select Device Manager. Select the model by entering the corresponding
number, then press ENTER.
3. Press 3 and Enter to select Configuration.
4. Press 1 and Enter to select Battery.
5. Press 2 and Enter to change the Battery Settings.
6. Type in the number of external battery packs (four battery modules per pack), and press ENTER.
(Number of packs: 1 = 1 SURT192RMXLBP, 2 = 2 SURT 19 2R M X LB P et c.)
7. Press 3 and ENTER to accept the changes.
8. Press ESC multiple times (5) to return to the main menu.
9. Press 4 and ENTER to log out.
15
Page 18
TROUBLESHOOTING
Use the table below to solve minor installation and operation problems. Refer to the APC Web site,
www.apc.com for assistance with complex UPS problems.
PROBLEM AND POSSIBLE
AUSE
C
S
OLUTION
UPS WILL NOT TURN ON
Battery not connected properly. Check that the battery connectors are fully engaged.
button not pushed. Press the button once to power the UPS and the connected equipment.
UPS not connected to utility power supply.
Check that the power cable from the UPS to the utility power supply is securely connected at both ends.
Very low or no utility voltage. Check the utility voltage.
UPS WILL NOT TURN OFF
button not pushed. Press the button once to turn the UPS off.
Internal UPS fault. Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
UPS BEEPS OCCASIONALLY
Normal UPS operation when
None. The UPS is protecting the connected equipment.
running on battery.
UPS DOES NOT PROVIDE EXPECTED BACKUP TIME
The UPS battery(s) are weak due to a recent outage or battery(s) are near the end of their service life.
FRONT PANEL LEDS FLASH SEQUENTIALLY
The UPS has been shut down
Charge the battery(s). Battery modules require recharging after extended outages. They wear faster when put into service often or when operated at elevated temperatures. If the battery(s) are near the end of their service life, consider replacing the battery(s) even if the Replace Battery LED is not illuminated.
None. The UPS will restart automatically when utility power returns. remotely through software or an optional accessory card.
ALL LEDS ARE OFF AND THE UPS IS PLUGGED INTO A WALL OUTLET
The UPS is shut down and the battery is discharged from an
None. The UPS will return to normal operation when the power is restored and
the battery has a sufficient charge. extended outage.
BYPASS AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE
The UPS is overloaded The connected equipment exceeds the specified “maximum load” as defined in
Specifications on the APC Web site, www.apc.com
.
The alarm remains on until the overload is removed. Disconnect nonessential
equipment from the UPS to eliminate the overload condition.
16
Page 19
PROBLEM AND POSSIBLE
C
AUSE
BYPASS LED ILLUMINATES
The bypass switch has been turned on manually or through an accessory.
FAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE
The UPS has ceased sending power to connected equipment.
FAULT LED ILLUMINATES
Internal UPS fault. Do not attempt to use the UPS. Turn the UPS off and have it serviced
REPLACE BATTERY LED ILLUMINATES
Replace Battery LED flashes and short beep is emitted every two seconds to indicate the battery is disconnected.
Weak battery. Allow the battery to recharge for 24 hours. Then, perform a self-test. If the
Failure of a battery self-test. The UPS emits short beeps for one minute and the Replace Battery LED
If bypass is the chosen mode of operation, ignore the illuminated LED. If bypass is not the chosen mode of operation move the bypass switch on the
back of the UPS, to the normal position.
The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC Web site, www.apc.com
Disconnect nonessential equipment from the UPS to eliminate the overload condition.
Press the OFF button, then the ON button to restore power to connected equipment.
immediately.
Check that the battery connectors are fully engaged.
problem persists after recharging, replace the battery.
illuminates. The UPS repeats the alarm every five hours. Perform the self-test procedure after the battery has charged for 24 hours to confirm the Replace Battery condition. The alarm stops and the LED clears if the battery passes the self-test.
OLUTION
S
.
UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS
Very high, low, or distorted line voltage. Inexpensive fuel powered generators can distort the voltage.
Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display.
DIAGNOSTIC UTILITY VOLTAGE
All five LEDs are illuminated The line voltage is extremely high and should be checked by an electrician. There is no LED illumination If the UPS is plugged into a properly functioning utility power outlet, the line
voltage is extremely low.
ONLINE LED
There is no LED illumination The UPS is running on battery, or it is not turned on. The LED is blinking The UPS is running an internal self-test.
17
Page 20
MAINTENANCE, TRANSPORT, AND SERVICE
Replacing the Battery Module
This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. See your dealer or contact APC at the Web site, www.apc.com replacement battery modules.
The battery replacement procedure must include replacing all battery modules in the UPS and connected external battery pack(s).
See Removing the Batteries and Installing the Batteries in this manual for additional information.
for information on
Once the battery(s from power outages.
Be careful during battery replacement, the battery modules are heavy. Be sure
in the replacement battery packing material.
to deliver spent batteries to a recycling facility or ship to the manufacturer
) are disconnected, the connected equipment is not protected
Disconnecting the Battery for Transport
Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations.
The battery(s) may remain in the UPS.
1. Shut down and disconnect any equipment attached to the
2. Shu
3. Unplug t Fo
t down and disconnect the UPS from the power supp
he battery connectors. Refer to the Replacing Battery Modules section in this manua
r shipping instructions contact APC at the Web site, www.apc.com
UPS.
ly.
.
l.
18
Page 21
Alw
ays DISCONNECT THE BATTERY(S) before shipping in compliance with U.S. Department of
Transportation (DOT) and IATA regulations. The battery(s) may remain in the UPS.
4. Mark the RMA# on the outside of the package.
5. Return the UPS by insured, prepaid carrier to the address given to you by Customer Support.
REGULA TOR Y AND WARRANTY INFORMATION
Regulatory Agency Approvals and Radio Frequency Warnings 200,
208, 240 V MODELS
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference. The user is responsible for correcting the interference.
Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits.
19
Page 22
Two Year Factory Warranty 1
The limited warranty provided by American Power Conversion (APC®) in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business.
Terms of Warranty
APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. The APC obligation under this warranty is limited to repairing or replacing, at its sole discretion, any such defective products. This warranty does not apply to equipment that has been damaged by accident, negligence or misapplication or has been altered or modified in any way. Repair or replacement of a defective product or part thereof does not extend the original warranty period. Any parts furnished under this warranty may be new or factory remanufactured.
Non-transferable Warranty
This warranty applies only to the original purchaser who must have properly registered the product. Product may be registered at www.apc.warranty.com
Exclusions
APC shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation or testing. Further APC shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere, repair, installation, start-up by non-APC designated personnel, a change in location or operating use, exposure to the elements, Acts of God, fire, theft, or installation contrary to APC recommendations or specifications or in any event if the APC serial number has been altered, defaced, or removed, or any other cause beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CO NTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISE D IN ADVANCE OF THE POSSIBILIT Y OF SUCH DAMAGES. SPECIFICALLY, APC IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC OFFICER AND LEGAL DEPARTMENT
.
.
Warranty Claims
Customers with warranty claims issues may access the APC worldwide customer support network by referring to the APC Web site, www.apc.com
. Select your country from the country selection pull-down menu. Open the Support tab at the top of
the web page to obtain contact information for customer support in your region.
1
To determine which factory warranty applies to the APC product you purchased, consult the factory warranties located on
the APC Web site, www.apc.com/products
.
20
Page 23
E
ntire contents copyright 2008 American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part
without permission is prohibited. APC, the APC logo, Smart-UPS, and PowerChute are trademarks of American Power Conversion Corporation. All other
trademarks, product names, and corporate names are the property of their respective owner s and are used for informational purposes only.
21
Loading...