Schneider Electric APC Smart-UPS Users Manual

User Manual English
APC Smart-UPS
2400/3000 VA
100/110-120 VAC 3U
Tower / R a c k Moun t
Uninterruptible Power Supply
990-2233A 02/2005
Introduction/Before Installation
W
Introduction/Before Installation
About this Manual
®
The APC Smart-UPS
RT (SURTA2400XLJ/SURTA3000XL/SURTA3000XLTW) is a high-performance Uninterruptible Power Supply (UPS) designed to prevent blackouts, brownouts, sags and surges from reaching your computers, servers, and other sensitive electronic equipment.
This manual describes procedures on how to properly unpack and install the UPS, connect the battery and equipment, configure accessories, and start up the system.
Illustrations are representative. Your configuration, including components and optional APC equipment, may be different from the models shown in this manual. The user manual is accessible from the supplied CD and the APC Web site, www.apc.com.
Contact Information
Refer to www.apc.com to contact APC or for additional information about this product.
Safety Information
Read the Safety Guide before you begin the installation, operate the UPS, or perform equipment maintenance. Failure to comply with safety instructions could result in
arning
bodily injury or equipment damage.
Unpacking and Equipment Placement
The UPS is heavy. Two people are required to lift the UPS. Select a location sturdy enough to handle the weight of the UPS.
1. Unpack the equipment. The packaging is recyclable; save it for reuse or dispose of it properly.
2. Inspect the equipment upon receipt. Notify the carrier and dealer if there is damage.
3. Check the package contents
UPS and front bezel
UPS literature kit containing: – product documentation – safety information
:
110-120 V models:
•PowerChute® CD
• Serial communication
100 V models:
• Serial communication cable
cable
– warranty information
. Place the UPS where it will be used.
4
– Ensure that air vents on the front and rear of the UPS are not blocked. – Do not operate the UPS where there is excessive dust or the temperature or humidity are outside the
specified limits.
40°C 104°F
2.5 cm
2.5 cm
0%
95%
Installation
Installation
Refer to instructions below for information on how to install the UPS in a rack, in a tower configuration, or when installing the UPS with optional battery pack(s). Once the UPS has been placed in the desired tower or rack location, complete the remaining installation steps in sequential order, beginning with “Connect Equipment to the UPS” on page 4.
To Install the UPS in a Rack
See the installation sheet supplied with the optional rail kit (SURTRK2) to install the UPS in the rack. It is recommended that you remove the battery before attempting to install it in the rack. See “To Install a Replacement Battery” on page 12 for the procedure.
To Install the UPS in a Tower Configuration
For stability, the UPS is shipped with stabilizing feet. Using the UPS in a tower configuration without the feet may result in bodily injury or equipment damage.
To Install the UPS with External Battery Pack(s)
In addition to the UPS, if your configuration includes optional Smart-UPS RT battery pack(s) (SURT192XLBP, SURT192XLBPJ), see the battery pack user manual to complete the physical installation for the UPS with external battery pack(s).
The UPS must be installed above external battery pack(s) when in a rack. When installing the UPS in a tower configuration, battery pack(s) must be installed to the right of the UPS when facing the front of the UPS. Failure to follow these instructions could result in cabling shortage.
Connect Equipment to the UPS
Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power circuits. See step 1 on page 5 for procedure.
The UPS is equipped with the following connectors.
Connectors Type Description
Serial Com Use only the supplied cable to connect to the serial port.
NOTE: A standard serial interface cable is incompatible with the UPS.
Normal bypass Manual bypass enables the user to manually put connected equipment into
bypass mode.
EPO terminal The Emergency Power Off (EPO) terminal allows the user to connect the UPS
to the central EPO system.
OTE: Adhere to national and local codes when wiring the EPO switch.
N
TVSS screw The UPS features a Transient Voltage Surge-suppression (TVSS) screw located
4 Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual
on the rear panel, for connecting the ground cable on surge suppression devices such as telephone and network line protectors.
OTE: Prior to connecting the grounding cable, disconnect the UPS from the
N
utility power outlet and turn off the UPS.
External battery pack connector
Optional Smart-UPS RT external battery packs provide extended run-time during power outages. These units support up to ten external battery packs.
OTE: See the APC Web site, www.apc.com for information on
N
the external battery pack, SURT192XLBP, SURT192XLBPJ.
Connectors Type Description
Installation
OUTPUT:
120V 50-60 Hz
20A
LISTED 42C2
100V~ 50-60Hz 20A
E95463
OUTPUT:
120V 50-60 Hz 15A PER RECEPTACLE GRO UP
100V~ 50-60Hz 20A
100V~ 50-60Hz 15A
Uninterru ptible
Power Supply
LR63938
2400
LISTED 42C2
E95463
UNINTERRUPTABLE
POWER SUPPLY
Model: SURTA3000XL
3000VA / 2100W
100V~50-60Hz 24A MAX (NEMA L5-30P)
2.4KVA / 1680W 24A
120V/3000 VA PDU Receptacles
100V/2400 VA PDU Receptacles
110-120 V 3000 VA PDU Receptacles
Connect equipment to the Power Distribution Unit (PDU) receptacles on the rear of the UPS.
Connect equipment to the Power Distribution Unit (PDU) receptacles on the rear of the UPS.
Connect equipment to the Power Distribution Unit (PDU) receptacles on the rear of the UPS.
輸出
:
110-120V
50-60Hz 20A
輸出
:
110-120V 50-60 Hz 15A PER RECEPTACLE GR OUP
輸入
:
110-120V~50-60Hz 24A MAX
(NEMA L5-30P)
LR63938
LISTED 42C2
E95463
Model:
SURTA3000XLTW
3000VA / 2100W
1. Connect ground cable of voltage surge-suppression equipment or the optional Smart-UPS RT battery pack to the TVSS screw.
2. Add optional accessories to the Smart-Slot. a. Remove the cover and screws. Discard or save cover. Do not attempt to reinstall it.
b. Refer to the accessory manual to install equipment.
Installation
If Required, Connect the Emergency Power Off (EPO) Feature
The EPO interface is a safety extra low voltage (SELV) circuit. Connect it only to other SELV circuits. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit, properly isolated from the utility.
The EPO feature provides immediate de-energizing of the UPS and connected equipment from a remote location, without switching to battery operation.
1. Use one of the following cable types to connect the UPS to the EPO switch.
– CL2: Class 2 cable for general use. – CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air. – CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft. – CLEX: Limited use cable for use in dwellings and for use in raceways. – For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable). – For installation in other countries: Use standard low-voltage cable in accordance with national and
local regulations.
2. Locate the EPO connector on the rear of the UPS. Use a normally-open contact to connect cable to each EPO terminal.
Connect the Battery and Install the Front Bezel
The battery is shipped in the disconnect position. Do not connect the battery until you are ready to use the equipment.
1. Snap the battery connectors together .
2. Install the front bezel .

Connect Power and Start Up the UPS
The UPS battery charges when it is connected to utility power and will charge to 85% capacity within three hours. Do not expect full battery run capability from a new battery or after On Battery operation until the battery recharges.
To use the UPS as a master ON/OFF switch, ensure all connected equipment is switched on. The equipment will not be powered until the UPS is turned on.
6 Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual