Read these instructions carefully and look at the equipment to become
familiar with the device before trying to install, operate, service, or maintain
it. The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label
indicates that an electrical hazard exists which will result in personal injury if
the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not
avoided, can result in death or serious injury.
PLEASE NOTE
Class A FCC Statement
CAUTION
CAUTION indicates a potentially hazardous situation which, if not
avoided, can result in minor or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially
hazardous situation which, if not avoided, can result in property damage.
NOTE: Provides additional information to clarify or simplify a procedure.
Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. This document is not intended as an instruction
manual for untrained persons. No responsibility is assumed by Square D for
any consequences arising out of the use of this manual.
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designated to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Table 1–1: Summary of Circuit Monitor Instrumentation
• Current (per phase, N, G, 3-Phase)
• Voltage ( L–L, L–N, N–G, 3-Phase)
• Real Power (per phase, 3-Phase
• Reactive Power (per phase, 3-Phase)
• Apparent Power (per phase, 3-Phase)
• Power Factor (per phase, 3-Phase)
• Frequency
• Temperature (internal ambient)
• THD (current and voltage)
• K-Factor (per phase)
• Demand Current (per phase present, 3-Phase avg.)
• Demand Voltage (per phase present, 3-Phase avg.)
• Average Power Factor (3-Phase total)
• Demand Real Power (per phase present, peak)
• Demand Reactive Power (per phase present, peak)
• Demand Apparent Power (per phase present, peak)
• Coincident Readings
• Predicted Power Demands
The circuit monitor is a multifunction, digital instrumentation, data acquisition
and control device. It can replace a variety of meters, relays, transducers and
other components. The circuit monitor can be located at the service entrance
to monitor the cost and quality of power, and can be used to evaluate the
utility service. When located at equipment mains, the circuit monitor can
detect voltage-based disturbances that cause costly equipment downtime.
The circuit monitor is equipped with
RS-485 and RS-232 communications for
integration into any power monitoring and control system. However, System
Manager™ software (
SMS)fromPOWERLOGIC, which is written specifically
for power monitoring and control, best supports the circuit monitor’s
advanced features.
The circuit monitor is a true rms meter capable of exceptionally accurate
measurement of highly nonlinear loads. A sophisticated sampling technique
enables accurate, true rms measurement through the 255th harmonic. You
can view over 50 metered values plus extensive minimum and maximum data
from the display or remotely using software. Table 1–1 summarizes the
readings available from the circuit monitor.
63230-300-212Chapter 1—Introduction
April 2 001What is the Circuit Monitor?
Accessories and Options for the
Circuit Monitor
The circuit monitor has a modular design to maximize its usability. In addition
to the main meter, the circuit monitor has plug-on modules and accessories,
including:
• Current/voltage module (CVM). A standard part of the circuit monitor is
the current/voltage module where all metering data acquisition occurs.
• Remote display . The optional remote 4-line display is available with a
back-lit liquid crystal display (LCD) or a vacuum fluorescent display (VFD).
The VFD model includes an infrared port that can be used to
communicate directly with the circuit monitor from a laptop and can be
used to download firmware, which keeps the circuit monitor up to date with
the latest system enhancements.
• I/O Extender. The I/O extender, located on the side of the circuit monitor,
enables you to “plug in” up to 8 industry-standard inputs and outputs.
Several preconfigured combinations are available, or you can create a
custom configuration.
• Digital I/O Card. You can further expand the I/O capabilities of the circuit
monitor by adding a digital I/O card (4 inputs and 4 outputs). This card fits
into one of the option slots on the top of the circuit monitor.
• Ethernet Communications Card. The Ethernet communications card
provides an Ethernet port that accepts a 100 Mbps fiber optic cable or a
10/100 Mbps UTP and provides an RS-485 master port to extend the
circuit monitor communications options. This card is easily installed into
option slot A on the top of the circuit monitor.
Table 1–2 lists the circuit monitor parts and accessories and their associated
instruction bulletins.
Table 1–2: Circuit Monitor Parts, Accessories, and Custom Cables
DescriptionPart NumberDocument Number
Circuit MonitorCM400063230-300-200
Current/Voltage ModuleCVM63230-301-200
VFD Display with infrared (IR) port and proximity sensorCMDVF
LCD DisplayCMDLC
Optical Communications Interface (for use with the VFD display only)OCIVF63230-306-200
I/O Extender Module
with no preinstalled I/ Os, accepts up to 8 individual I/O modules with a
maximum of 4 analog I / Os
with 4 digital inputs (32 Vdc), 2 digital outputs ( 60 Vdc),
1 analog output (4–20 mA), and 1 analog input (0–5Vdc)
with 4 analog inputs (4–20 mA) and 4 digital inputs (120 Vac)IOX0404
with 8 digital inputs (120 Vac)IOX08
Digital I/O Card
Field installable with 4 digital inputs (120 Vac), 3 (10 A) relay outputs (120Vac),
1 pulse output (KYZ)
Ethernet Communications Card with
100 Mbps fiber or 10/100 Mbps UTP Ethernet port and 1 RS-485 master port
Chapter 1—Introduction63230-300-212
Topics Not Covered in This BulletinApril 2001
Table 1–2: Circuit Monitor Parts, Accessories, and Custom Cables
63230-204-316
CM4 Mounting AdaptersCM4MA
4-ft display cable (1.2 m)CAB-4
12-ft display cable (3.6 m)CAB-12
30-ft display cable (9.1 m)CAB-30
10-ftRS-232cable(3m)CAB-106
For parts list of individual inputs and outputs, see Table 5–1onpage70.
63230-300-206
63230-305-201
N/A
Features
Some of the circuit monitor’s many features include:
• True rms metering to the 255th harmonic
• Accepts standard CT and PT inputs
• 600 volt direct connection on metering inputs
• Certified ANSI C12.20 revenue accuracy and IEC 687.2 class revenue
accuracy
• High accuracy—0.04% current and voltage
• Min/max readings of metered data
• Power quality readings—THD, K-factor, crest factor
• Real-time harmonic magnitudes and angles to the 63rd harmonic
• Current and voltage sag/ swell detection and recording
• Downloadable firmware
• Easy setup through the optional remote display (password protected)
where you can view metered values
• Setpoint-controlled alarm and relay functions
• Onboard alarm and data logging
• Wide operating temperature range –25° to 70°C
• Modular, field-installable digital and analog I/O modules
• Flexible communications—RS-485 and RS-232 communications are
standard, optional Ethernet communications card available with fiber optic
connection
• Two option card slots for field-installable I/O and Ethernet capabilities
• Standard 8MB onboard logging memory (field upgradable to 16 MB, 32
MB, and higher
• CT and PT wiring diagnostics
• Revenue security with utility sealing capability
TOPICS NOT COVERED IN
THIS BULLETIN
4
Some of the circuit monitor’s advanced features, such as onboard data logs
and alarm log files, can only be set up over the communications link using
SMS. SMS versions 3.12 and higher support the CM4000 device type.This
circuit monitor instruction bulletin describes these advanced features, but
does not tell how to set them up. For instructions on using
SMS online help and the
SMS-3000 Setup Guide,
which is available in
SMS,refertothe
English (63220-060-200), French (63220-060-201), and Spanish (63220060-202). For information about related instruction bulletins, see Table 1–2
on page 3.
63230-300-212Chapter 1—Introduction
April 2 001FirmwAre
FIRMWARE
This instruction bulletin is written to be used with firmware version 11.000 or
higher. See “Identifying the Firmware Version” on page 124 for instructions
on how to determine the firmware version.
63230-300-212Chapter 2—Safety Precautions
April 2 001
CHAPTER 2—SAFETY PRECAUTIONS
This chapter contains important safety precautions that must be followed
before attempting to install, service, or maintain electrical equipment.
Carefully read and follow the safety precautions outlined below.
DANGER
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION
• Only qualified workers should install this equipment. Such work
should be performed only after reading this entire set of instructions.
• NEVER work alone.
• Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
and tagged. Pay particular attention to the design of the power
system. Consider all sources of power, including the possibility of
backfeeding.
• Turn off all power supplying this equipment before working on or
inside.
• Always use a properly rated voltage sensing device to confirm that all
power is off.
• Beware of potential hazards, wear personal protective equipment,
carefully inspect the work area for tools and objects that may have
been left inside the equipment.
• Use caution while removing or installing panels so that they do not
extend into the energized bus; avoid handling the panels, which could
cause personal injury.
• The successful operation of this equipment depends upon proper
handling, installation, and operation. Neglecting fundamental
installation requirements may lead to personal injury as well as
damage to electrical equipment or other property.
• Before performing Dielectric (Hi-Pot) or Megger testing on any
equipment in which the circuit monitor is installed, disconnect all input
and output wires to the circuit monitor. High voltage testing may
damage electronic components contained in the circuit monitor.
63230-300-212Chapter 3—Operation
April 2 001Chapter Contents
CHAPTER 3—OPERATION
This chapter tells how to set up the circuit monitor from the display only.
Some advanced features, such as configuring the onboard logs of the circuit
monitor, must be set up over the communications link using
SMS instruction bulletin and online help file for instructions on setting up
advanced features not accessible from the display.
Running the Diagnostics Wiring Error Test . ...................46
9
Chapter 3—Operation63230-300-212
Operating the DisplayApril 2001
OPERATING THE DISPLAY
MAIN MENU
Meters
Min/Max
View Alarms
How the But tons Work
The display shows four lines of information at a time. Notice the arrow on the
left of the display screen. This arrow indicates that you can scroll up or down
to view more information. For example, on the Main Menu you can view the
Resets, Setup, and Diagnostics menu options only if you scroll down to
display them. When at the top of a list, the arrow moves to the top line. When
the last line of information is displayed, the arrow moves to the bottom as
illustrated in Figure 3–1.
MAIN MENU
Resets
Setup
Diagnostics
Figure 3–1: Arrowon the display screen
The buttons on the display let you scroll through and select information, move
from menu to menu, and adjust the contrast. Figure 3–2 shows the buttons.
Menu button
Arrow buttons
Contrast button
Enter button
Figure 3–2: Display buttons
The buttons are used in the following way:
• Arrow buttons. Use the arrow buttons to scroll up and down the options
on a menu. Also, when a value can be changed, use the arrow buttons to
scroll through the values that are available. If the value is a number,
holding the arrow button down increases the speed in which the numbers
increase or decrease.
• Menu button. Each time you press the menu button, it takes you back one
menu level. The menu button also prompts you to save if you’ve made
changes to any options within that menu structure.
• Enter button. Use the enter button to select an option on a menu or select
a value to be edited.
• Contrast button. Press the contrast button to darken or lighten the
display. On the LCD model, press any button once to activate the back
light.
63230-300-212Chapter 3—Operation
April 2 001Operating the Display
Display Menu Conventions
Selecting a Menu Option
This section explains a few conventions that were developed to streamline
instructions in this chapter. Figure 3–3 shows the parts of a menu.
Menu
DISPLAY
LanguageEnglish
Date MM/DD/YYYY
Time Format2400hr
Menu Option
VFD Sensitivity3
Display Timer 1 Min
Value
Custom Quantity
Custom Screen
Figure 3–3: Parts of a menu
Each time you read “select” in this manual, choose the option from the menu
by doing this:
1. Press the arrowsto highlight the menu option.
2. Press the enter buttonto select that option.
Changinga Value
To change a value, the procedure is the same on every menu:
1. Use the arrow buttonsto scroll to the menu option you want to
change.
2. Press the enter buttonto select the value. The value begins to blink.
3. Press the arrow buttons to scroll through the possible values. To select
the new value, press the enter button.
4. Press the arrow buttons to move up and down the menu options. You can
change one value or all of the values on a menu. To save the changes,
press the menu buttonuntil the circuit monitor displays:
“Save changes? No”
NOTE: Pressing the menu button while a value is blinking will return that
value to its most current setting.
5. Press the arrow to change to “Ye s, ” then press the enter button to save
the changes.
Chapter 3—Operation63230-300-212
Main Menu OverviewApril 2001
MAIN MENU OVERVIEW
MAIN MENU
Meters
Min/Max
View Alarms
I/O Display
Resets
Setup
Diagnostics
METERS
Summary
Powe r
Power Quality
Energy
Power Demand
Current Demand
Custom
MIN / MAX
Current
Voltage
Frequency
Powe r
Power Factor
THD
VIEW ALARMS
Active Alarms List
High Priority Log
I/O DISPLAY
Digital Inputs
Analog Inputs
Digital Outputs
Analog Outputs
RESETS
Energy
Demand
Min/Max
The Main Menu on the display contains the menu options that you use to set
up and control the circuit monitor and its accessories and view metered data
andalarms.Figure3–4 on the left shows the options on the Main Menu. The
menus are briefly described below:
• Meters. This menu lets you view metered values that provide information
about power usage and power quality.
• Min/Max. This menu lets you view the minimum and maximum metered
values since the last reset of the min/max values with their associated
dates and times.
• View Alarms. This menu lets you view a list of all active alarms,
regardless of the priority. In addition, you can view a log of high priority
alarms, which contains the ten most recent high priority alarms.
• I/O Display. From this menu, you can view the designation and status of
each input or output. This menu will only display the I/Os present, so you
might not see all of the available menu items if you do not have a particular
I/O installed.
• Resets. This menu lets you reset energy, peak demand, and minimum/
maximum values.
• Setup. From this menu, you define the settings for the display such as
selecting the date format to be displayed. Creating custom quantities and
custom screens are also options on this menu. In addition, use this menu
to set up the circuit monitor parameters such as the CT and PT ratios. The
Setup menu is also where you define the communications, alarms, I/Os
and passwords.
• Diagnostics. From this menu, you can initiate the wiring error test. Also,
use this menu to read and write registers and view information about the
circuit monitor such as its firmware version and serial number.
SETUP
Date & Time
Display
Communications
Meter
Alarm
I/O
Passwords
DIAGNOSTICS
Meter Information
CVM Information
Read/Write Regs
Wiring Error Test
63230-300-212Chapter 3—Operation
April 2 001Configuring the Circuit Monitor Using the Setup Menu
CONFIGURINGTHE CIRCUIT
MONITOR USING THE
SETUP MENU
Setting Up the Display
Before you can access the Setup menu from the Main Menu, you must enter
the Setup password. Thedefault password is 0. To change the password, see
“Setting Up Passwords” on page 27. The Setup menu has the following
options:
• Date & Time
• Display
• Communications
• Meter
• Alarm
• I/O
• Passwords
Each of these options is described in the sections that follow.
Setting up the display involves, for example, choosing a date and time format
that you want to be displayed. To set up the display, follow these steps:
1. From the Main Menu, select Setup > Display.
The Display Setup menudisplays. Table 3–1 describes the options on this
2. Use the arrow buttons to scroll to the menu option you want to change.
3. Press the enter button to select the value.The value begins to blink. Use
the arrow buttons to scroll through the available values. Then, press the
enter button to select the new value.
4. Use the arrow buttons to scroll through the other options on the menu, or
if you are finished, press the menu button to save.
13
Chapter 3—Operation63230-300-212
Configuring the Circuit Monitor Using The Setup MenuApril 2001
Table 3–1: Factory Defaults for the Display Settings
1=0–6ft(0–15 m)
2=0–12 ft (0–31 m)
3=0–20 ft (0–51 m)
Display Timer1, 5, 10, or 15 minutesNumber of minutes the display remains illuminated
Custom QuantityCreating custom quantities is an advanced feature that is not required for basic setup. To learn more about this
feature, see “Creating Custom Quantities to be Displayed” on page 28.
Custom ScreenCreating custom screens is an advanced feature that is not required for basic setup. To learn more about this
feature, see “Creating Custom Screens” on page 31.
Language used by the display.English
Data format for all date-related values of the circuit
monitor.
Time format can be 24-hour military time or 12-hour
clock with AM and PM.
Sensitivity value for the proximity sensor (for the VFD
display only).
after inactivity.
MM/DD/YYYY
2400hr
2
5
Setting Up the Communications
Setting the Device Address
The Communications menu lets you set up the following communications:
•
RS-485
monitor and other
RS-232
•
the circuit monitor and a host device, such as a
Infrared Port
•
computer (available only on the
•
Ethernet Options
communications for daisy-chain communication of the circuit
RS-485 devices.
communications for point-to-point communication between the
PC or modem.
communications between the circuit monitor and a laptop
VFD display).
for Ethernet communications between the circuit
monitor and your Ethernet network when an Ethernet Communications
Card (
ECC)ispresent.
Each of these options is described in the sections that follow.
Each
POWERLOGIC device on a communications link must have a unique
device address. The term communications link refers to 1–32
POWERLOGIC
compatible devices daisy-chained to a single communications port. If the
communications link has only a single device, assign it address 1. By
networking groups of devices,
63230-300-212Chapter 3—Operation
April 2 001Configuring the Circuit Monitor Using The Setup Menu
RS-485, RS-232, and Infrared Port
Communications Setup
To se t up RS-485, RS-232, or the infrared port communications, set the
address, baud rate, and parity. Follow these steps:
1. From the Main Menu, select Setup > Communications.
The Communications Setup screen displays.
COMMUNICATIONS
RS-485
RS-232
Infrared Port
Ethernet Option
NOTE: You can set up infrared communications only if the circuit monitor
is equipped with a VFD display. Also, you can set up Ethernet
communications only if the circuit monitor is equipped with an
ECC
card.
2. From the Comms Setup menu, select the type of communications that
you are using. Depending on what you select, the screen for that
communications setup displays, as shown below.Table 3–2 describes the
options on this menu.
RS-485
ProtocolModbus
Address1
Baud Rate9600
ParityEven
3. Use the arrow buttons to scroll to the menu option you want to change.
4. Press the enter button to select the value.The value begins to blink. Use
5. Use the arrow buttons to scroll through the other options on the menu, or
Chapter 3—Operation63230-300-212
Configuring the Circuit Monitor Using The Setup MenuApril 2001
Table 3–2: Options for Communications Setup
ParityEven, Odd, or
None
Parity at which the circuit monitor will
communicate.
Even
EthernetCommunications Card (ECC)
Setup
Setting Up the Metering
Functions of the Circuit Monitor
Ethernet communications is available only if you have an optional Ethernet
Communications Card (
ECC) that fits into slot A on the top of the circuit
monitor. See “Option Cards” on page 28 in Chapter 4—Installation of the
installation manual for more information. To set up the Ethernet
communications between the circuit monitor and the network, refer to
instruction bulletin no. 63230-304-200 provided with the
ECC.
To set up the metering within the circuit monitor, you must configure the
following items on the Meter setup screen for basic setup:
• CT and PT ratios
• System type
• Frequency
The power demand method, interval and subinterval, and advanced setup
options are also accessible from the Meter Setup menu, but are not required
for basic setup if you are accepting the factory defaults already defined in the
circuit monitor. Follow these steps to set up the circuit monitor:
1. From the Main Menu, select Setup > Meter.
The Meter setup screen displays. Table 3–3 describes the options on this
menu.
METER
Ø CT Primary5
Ø CT Secondary5
N CT Primary5
N CT Secondary5
PT Pri Scalex1
PT Primary120
PT Secondary120
Sys Type3Ø4W3CT
Required for
basic setup
Frequency (Hz)60
Pwr Dmd MethSlide
Pwr Dmd Int15
Pwr Dmd Sub Int1
Advanced
2. Use the arrow buttons to scroll to the menu option you want to change.
3. Press the enter button to select the value. The value begins to blink. Use
the arrow buttons to scroll through the available values. Then, press the
enter button to select the new value.
4. Use the arrow buttons to scroll through the other options on the menu, or
if you are finished, press the menu button to save.
CT Primary1–32,767Set the rating for the CT primary. The circuit monitor supports two primary CT
ratings: one for the phase CTs and the other for the neutral CT.
CT Secondary1 or 5Set the rating for the CT secondaries.5
PT Pri Scalex1
x10
x100
No PT
PT Primary1–32,767Set the rating for the PT primary.120
PT Secondary100
110
115
120
Sys Type3Ø3W2CT
3Ø3W3CT
3Ø4W3CT
3Ø4W4CT
3Ø4W3CT2PT
3Ø4W4CT2PT
Frequency (Hz)50, 60, or 400 Hz Frequency of the system.60
Pwr Dmd MethSelect the power demand calculation method. The circuit monitor supports several methods to calculate
average demand of real power. See “Demand Power Calculation Methods” on page 57 for a detailed
description.
Slide—Sliding Block Demand
Slave—Slave Block Demand
Therm—Thermal Demand
RComms—Command-Synchronized Rolling Block Demand
Comms—Command-Synchronized Block Demand
RInput—Input-Synchronized Rolling Block Demand
Input—Input-Synchronized Block Demand
RClock—Clock-Synchronized Rolling Block Demand
Clock—Clock-Synchronized Block Demand
RBlock—Rolling Block Demand
Block—Fixed Block Demand
IncEngy—Synch to Incremental Energy Interval
Pwr Dmd Int1–60Power demand interval—set the time in minutes in which the circuit monitor
Pwr Dmd Sub Interval 1–60Power demand subinterval—period of time within the demand interval in which the
AdvancedSee “Advanced Meter Setup” on page 34 in this chapter for more information.
Set the value to which the PT Primary is to be scaled if the PT Primary is larger
than 32,767. For example, setting the scale to x10 multiplies the PT Primary
number by 10.
For a direct-current installation, select “No PT.”
Set the rating for the PT secondaries.120
3Ø3W2CT is system type 30
3Ø3W3CT is system type 31
3Ø4W3CT is system type 40
3Ø4W4CT is system type 41
3Ø4W3CT2PT is system type 42
3Ø4W4CT2PT is system type 43
Set the system type. A system type code is assigned to each type of system
connection. See Table 5–2 on page 38 of the installation manual for a description
of system connection types.
calculates the demand.
demand calculation is updated. Set the subinterval only for methods that will
accept a subinterval. The subinterval must be evenly divisible into the interval.
Chapter 3—Operation63230-300-212
Configuring the Circuit Monitor Using The Setup MenuApril 2001
Setting Up Alarms
This section describes how to setup alarms and create your own custom
alarms. For a detailed description of alarm capabilities, see Chapter 6—Alarms on page 83. The circuit monitor can detect over 100 alarm
conditions, including over/under conditions, status input changes, phase
unbalance conditions, and more. Some alarms are preconfigured and
enabled at the factory. See “Factory Defaults” on page 11 in Chapter 3—Getting Started of the installation manual for information about
preconfigured alarms. You can edit the parameters of any preconfigured
alarm from the display.
For each alarm that you set up, do the following:
• Select the alarm group that defines the type of alarm:
—
Standard speed
alarms have a detection rate of one second and are
useful for detecting conditions such as over current and under voltage.
Up to 80 alarms can be set up in this group.
—
High speed
alarms have a detection rate of 100 milliseconds and are
useful for detecting voltage sags and swells that last a few cycles. Up
to 20 alarms can be set up in this group.
—
Disturbance monitoring
alarms have a detection rate of one cycle and
are useful for detecting voltage sags and swells. Up to 20 alarms can
be set up in this group.
—
Digital
alarms are triggered by an exception such as the transition of a
status input or the end of an incremental energy interval. Up to 40
alarms can be set up in this group.
—
Boolean
alarms have a detection rate of the alarms used as inputs.
They are used to combine specific alarms into summary alarm
information.
• Select the alarm that you want to configure. Keep the default name or
enter a new name with up to 15 characters.
• Enable the alarm.
• Assign a priority to the alarm. Refer to “Viewing Alarms” on page 41 for
information about the alarm priority levels.
• Define any required pickup and dropout setpoints, and pickup and dropout
time delays (for standard, high speed, and disturbance alarm groups only,
refer to “Setpoint-Driven Alarms” on page 85 in Chapter 6—Alarms).