Samson 3785 series Mounting And Operating Instructions

PROFIBUS Positioner Type 3785
PA device profile version 2.0
Mounting and Operating Instructions
EB 8382-1 EN
Firmware version R 1.4x/K 1.6x Edition July 2004
Fig. 1 · Type 3785 PROFIBUS Positioner
Contents Page
1 Design and principle of operation . . . . . . . . . . . . . . . . . . . 8
1.1 Optional accessories . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Attaching the positioner. . . . . . . . . . . . . . . . . . . . . . . . 10
2.1 Direct attachment to Type 3277 Actuator . . . . . . . . . . . . . . . . 10
2.2 Attachment according to IEC 60534-6 . . . . . . . . . . . . . . . . . 14
2.2.1 Mounting sequence . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.2 Presetting the valve travel . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Attachment to rotary actuators . . . . . . . . . . . . . . . . . . . . . 18
2.3.1 Mounting the cam follower roll lever . . . . . . . . . . . . . . . . . . 18
2.3.2 Mounting the intermediate piece . . . . . . . . . . . . . . . . . . . . 18
2.3.3 Aligning and mounting the cam disk . . . . . . . . . . . . . . . . . . 20
2.3.4 Reversing amplifiers for double-acting actuators . . . . . . . . . . . . 22
2.4 Fail-safe position of the actuator . . . . . . . . . . . . . . . . . . . . 22
3 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1 Pneumatic connections. . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1.1 Pressure gauges. . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1.2 Supply air pressure . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2.1 Forced venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.2.2 Limit switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.2.3 Establishing communication (bus address) . . . . . . . . . . . . . . . 28
3.2.4 Local interface (SSP) . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.1 LED controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.2 Write protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3 Activate/deactivate forced venting . . . . . . . . . . . . . . . . . . . 31
4.4 Default settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.4.1 Adjusting mechanical zero. . . . . . . . . . . . . . . . . . . . . . . 32
4.4.2 Initialization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.5 Adjusting the inductive limit switches . . . . . . . . . . . . . . . . . . 34
5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6 Servicing explosion-protected devices . . . . . . . . . . . . . . . . . 35
2 EB 8382-1 EN
Contents
7 How to implement a Class 1 PROFIBUS Master . . . . . . . . . . . . 36
7.1 Device database files (GSD) . . . . . . . . . . . . . . . . . . . . . . 36
7.2 Data exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.3 Parameter description . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.4 Coding of measured value status . . . . . . . . . . . . . . . . . . . . 42
7.5 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
8 List of parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9 Messages and diagnostics. . . . . . . . . . . . . . . . . . . . . . . 61
9.1 Diagnostic messages . . . . . . . . . . . . . . . . . . . . . . . . . 61
9.2 Extended diagnostic messages . . . . . . . . . . . . . . . . . . . . . 63
9.3 CHECKBACK messages . . . . . . . . . . . . . . . . . . . . . . . . 64
9.4 Messages during initialization . . . . . . . . . . . . . . . . . . . . . 66
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . 69
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
EB 8382-1 EN 3
Contents
4
The device is to be assembled, started up or operated only by trained and ex­perienced personnel familiar with the product. According to these mounting and operating instructions, trained personnel is referred to as individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowl­edge and experience as well as their knowledge of the applicable standards.
4
Explosion-protected versions of this device are to be operated only by person­nel who have undergone special training or instructions, or who are autho­rized to work on explosion-protected devices in hazardous areas.
4
Any hazards that could be caused in the positioner by the process medium, the operating pressure, the signal pressure or by moving parts are to be pre­vented by means of the appropriate measures. If inadmissible motions or forces are produced in the pneumatic actuator as a result of the supply air pressure level, the pressure must be restricted using a suitable supply pressure reducing station.
4
Proper shipping and storage are assumed.
4
Note! Devices with a CE marking fulfil the requirements of the Directives 94/9/EC and 89/336/EEC. The declaration of conformity is available at http://www.samson.de and on request.
!
Modifications of the firmware compared to the previous version
Old New Control R 1.23 R 1.31
Firmware adaptation for a new hardware version Hardware version device index .01
Control R 1.31 R 1.4
Actuator type When the actuator type is switched from "linear actuator" to "rotary actua-
tor", the following applies: Initialization method . . . Based on maximum range
Transmission code . . . . 590
Nominal angle . . . . . 90°
End position for w < . . . 1 % End position for w > . . . 99 % Rot. angle range starts at 0° Rot. angle range ends at 90°
When the actuator type is switched from "rotary actuator" to "linear actua­tor", the following applies:
Attachment . . . . . . . Integral . . . . . . . . . NAMUR
Initialization method . . . Based on nominal range . Based on nom. range
Mounting position: arrow Towards actuator . . . . Away from actuator
Transmission code . . . . D1 . . . . . . . . . . . –
Pin position . . . . . . . – . . . . . . . . . . . . A
Rated travel . . . . . . . 15 mm . . . . . . . . . 15 mm
End position for w < . . . 1 % . . . . . . . . . . . 1 %
End position for w > . . . 125 % . . . . . . . . . 125 %
Lower travel range value. 0 mm . . . . . . . . . . 0 mm
Upper travel range value 15 mm . . . . . . . . . 15 mm
Lever length . . . . . . . – . . . . . . . . . . . . 42 mm
Initialization method When the initialization method is switched from "maximum range" to "nomi-
nal range", the following applies: End position for w < 1% End position for w > 125 %
When the initialization method is switched from "nominal range" to "maxi­mum range", the following applies: End position for w < 1% End position for w > 99 %
Desired transit time open/closed
The adjustment range of the desired transit time is now limited to 75 s.
Initialization During initialization, the minimum control pulses are determined for 20 % to
80 % of the manipulated variable range and saved in the EEPROM.
Proportional-action coefficients KP_Y1 and KP_Y2
The coefficients are adapted to the selected actuator type and the measured transit times.
4 EB 8382-1 EN
Firmware modifications
Control R 1.41 R 1.42
Correction when zero calibration was triggered by communication.
Communication K 1.34 K 1.41
Firmware adaptation for new hardware version Hardware version device index .01
Communication 1.41 K 1.51
Bit 7 of the CHECKBACK parameter indicates the current status of control loop monitoring. In contrast to bit 13, bit 7 is automatically reset when control loop monitoring detects no further errors. The function of bit 13 remains un­changed. Messages issued by bit 7 are only supported with firmware version R 1.41 and higher.
The "warm start" message indicated by bit 11 of the DIAGNOSIS parameter is automatically reset after 10 s.
In Local Override mode, bit 2 of the CHECKBACK parameter is activated.
Communication 1.51 K 1.60
A bad set point status no longer causes the positioner to move the valve to fail-safe position in any case. Rather, the positioner's behavior is determined by the FSAVE_TYPE parameter.
Using the serial interface, the positioner can be configured and operated with SAMSON's TROVIS-VIEW Configuration and Operator Interface software.
EB 8382-1 EN 5
Firmware modifications
Positioner
Travel
Direct attachment Type 3277 Acc. to IEC 60534-6 (NAMUR)
Adjustable 5 mm to 30 mm 5 mm to 255 mm or 30° to 120° for rotary actuators
Bus connection Fieldbus interface according to IEC 61158-2
Field unit according to FISCO (Fieldbus Intrinsically Safe Concept)
Permissible operating voltage 9 to 32 V DC; the specifications in the EC type examination certifi-
cate additionally apply to explosion-protected devices. Voltage supplied over bus cable
Static destruction limit 35 V
Max. operating current 10 mA
Current in case of fault 0 mA
Auxiliary energy Supply pressure of 1.4 to 6 bar (20 to 90 psi)
Air quality according to ISO 8573-1:2001, i.e. max. particle size and density: Class 4; oil content: Class 3; pressure dew point: Class 3 or at least 10 K above lowest ambient temperature to be expected
Signal pressure (output) 0 bar up to supply air pressure
Adjustable characteristic Linear, equal percentage, reverse equal percentage, user-defined
Deviation from characteristic≤1 %
Dead band Adjustable from 0.1 to 10.0 %, default 0.5 % (based on rated
travel/angle)
Resolution < 0.05 % (internal measurement)
Desired transit time Up to 75 s, separately adjustable for exhaust and supply air
Direction of action Reversible, adjusted using software
Air consumption Independent of supply air < 90 l
n
/h
Air supply
Actuator pressurized for Δp = 6 bar: 9.3 mn³/h, for Δp = 1.4 bar: 3.5 mn³/h Actuator vented for Δp = 6 bar: 15.5 m
n
³/h, for Δp = 1.4 bar: 5.8 mn³/h
Permissible ambient tempera­ture
–40 °C to 80 °C, the specifications in the EC type examination certificate additionally apply to explosion-protected devices
Influences Temperature:≤0.15 %/10 K, auxiliary energy: none
Vibration: none up to 250 Hz and 4 g
Explosion protection II 2 G EEx ia IIC T6 acc. to ATEX, see EC type examination certificate
Degree of protection IP 65 using the included filter check valve
Electromagnetic compatibility Requirements acc. to EN 61000-6-2, EN 61000-6-3 and NE 21 met
Binary input Internal power supply 5 V DC,
R
i
= 100 kΩfor alarm function, e.g. connection of pressure switch
6 EB 8382-1 EN
Technical data
Forced venting
Input
K
V
coefficient
To be activated using switch inside the positioner 6 to 24 V DC, static destruction limit 45 V R
i
approx. 6 kΩat 24 V DC (depending on voltage) Switching point for "1" signal at≥3 V, switching point for "0" signal only at 0 V
0.17
Communication Data transmission acc. to PROFIBUS-PA, Profile Class B, version 2.0
acc. to DIN EN 50170 and DIN 19245, Part 4 (version 3.0 also available)
Local interface SAMSON SSP interface for configuration and start-up
Bus address Adjustable using software or microswitch, default upon delivery: 126
Accessories
Inductive limit switches Two Type SJ2SN proximity switches
For connection to switching amplifier according to EN 60947-5-6
Materials
Housing Die-cast aluminum, chromated and plastic-coated
External parts Stainless steel 1.4571 and 1.4301
Weight Approx. 1.3 kg
Positioner versions
Type 3785– XXXXX
3
X
Explosion protection
Without Ex II 2 G Ex ia IIC T6 acc. to ATEX With Ex ia CSA/FM Ex II 3 G Ex nA II T6 acc. to ATEX
0 1 3 8
Accessories Limit switches Without
2 inductive
0 22
Forced venting Without
With
0 12
PA device profile Version 2.0
Version 3.0
0 1
Pneumatic connections
NPT ¼-18 ISO 228/1-G ¼
1 2
Electrical connections
Cable gland M 20 x 1.5 with shielding, nickel-plated brass Quantity: 1 Quantity: 2
1 2
EB 8382-1 EN 7
Technical data
1 Design and principle of opera-
tion
The digital PROFIBUS-PA positioner is de­signed for attachment to pneumatic control valves. It is used to assign the valve stem po­sition (controlled variable) to the control sig­nal (reference variable). It compares the digi­tal output signal to the travel of the control valve and generates a corresponding pres­sure signal as the output variable. As a re­sult, the positioner requires auxiliary supply air with a pressure of 1.4 to 6 bar. The nec­essary electrical power is supplied by the bus of the PROFIBUS-PA segment based on IEC 61158-2 standard transmission technol­ogy.
The positioner consists of an inductive, contactless travel pick-off system and an electrically controlled valve block comprising two on/off valves and an electronic unit. This unit contains two microcontrollers for pro­cessing the control algorithm and managing PROFIBUS communication. If a deviation between the actual valve travel (actual value) and the reference variable (set point) occurs, the microcontroller produces binary pulse-pause modulated signals to control the two on/off valves, each of which is assigned a downstream amplifier. One of these valves controls the exhaust air, the other the supply air.
The supply air valve (3) controls the connec­tion between the supply air (7, supply air pressure 1.4 to 6 bar) and the actuator (pressurizing). The exhaust air valve (4) con­trols the air exhausted from the actuator to the atmosphere (venting). The on/off valves can either have the switching states ("perma­nently open", "permanently closed" or gen-
erate single pulses of changing widths). The two valves cause the plug stem to move to a position corresponding to the reference vari­able. If there is no system deviation, both the supply air valve and the exhaust air valve are closed.
By default, the positioner is equipped with a binary input for floating contacts, which ad­ditionally signals the switching state of a further field device via PROFIBUS. Activating the write protection switch, which is located next to the bus address in the hinged lid, prevents the positioner settings from being overwritten by PROFIBUS com­munication.
Positioner with forced venting function:
The positioner is controlled by a 6 to 24 V signal, causing the signal pressure to be ap­plied to the actuator. If this voltage signal de­creases, the signal pressure is shut off and the actuator is vented. The springs in the ac­tuator move the valve to its fail-safe position. The forced venting function is included in all positioners and can be activated/deactivated as required over a switch. Refer to sec­tion 4.3 for details.
1.1 Optional accessories
As a supplement to the standard positioner version, the positioner can be equipped with limit switches. Two proximity switches can be used to indicate the valve's end positions in safety-related circuits.
1.2 Communication
The positioner is completely controlled by digital signal transmission according to the PROFIBUS-PA Profile Class B based on
8 EB 8382-1 EN
Design and principle of operation
DIN EN 50170 and DIN 19245, Part 4. Data is transmitted as bit-synchronous cur­rent modulation at a transmission rate of
31.25 kbit/s over twisted-pair cables ac­cording to IEC 61158-2. Positioners are gen­erally set up using a PC. One or more positioners are connected to the PC's PROFIBUS segment via segment coupler. After mechanically resetting the positioner to zero, it can be automatically started up using an initialization routine. During initialization, zero is automatically adjusted and the preset span is checked.
The positioner is delivered with a standard configuration for a control valve with a rated travel of 15 mm designed for integral positioner attachment.
Customized configuration to adapt the positioner to other actuators can only be car­ried out using communication.
Configuration
The positioner is configured and operated on the PC over the SSP interface (13) using TROVIS-VIEW. Alternatively, it can be con­figured and operated via a segment coupler, e.g. using the COMMUWIN II user interface (by Endress + Hauser) or the SIMATIC PDM user interface (by SIEMENS). During configuration, parameters such as control characteristic, direction of action, travel limitation, travel range, transit time and alarms, can be entered.
EB 8382-1 EN 9
Design and principle of operation
11
10
1
12
e
p
3
4
2
5
9
7
6
1
G
μC
61158-2 IEC
e
p
G
μC
PROFIBUS-PA
8
Serial Interface
13
Fig. 2 · Functional diagram
Binary input
Forced venting
Supply
air
Exhaust air
1 Inductive travel pick-off 2 Microcontroller 3 On/off valve for supply air 4 On/off valve for exhaust air 5 Microcontroller 6 Switch for bus address and
write protection 7 Binary input 8 Forced venting 9 IEC 61158-2 interface module 10 Actuator stem 11 Lever 12 Clamp 13 SSP interface
2 Attaching the positioner
The positioner can be attached either directly to a SAMSON Type 3277 Actuator or ac­cording to NAMUR (IEC 60534-6) to control valves with cast yokes or rod-type yokes. In combination with an intermediate piece, the positioner can also be attached as a ro­tary positioner to rotary actuators.
Since the standard positioner unit is deliv­ered without accessories, refer to the corre­sponding tables for required mounting parts and their order numbers.
Note!
For fast control valves with small travels (transit time < 0.6 s), replace the filter in the signal pressure output with a screw-in restric­tion, if necessary, to improve the control properties. See also sections 2.1, 2.2 and
2.3.
Important!
The positioner does not have its own vent plug so that the air is exhausted to the atmo­sphere through vent plugs located on the ac­cessories (see also Figs. 3, 5 and 6). A filter check valve for the exhaust air is in­cluded with each positioner (underneath the transparent cover on the back of the positioner). Replace the standard vent plug included in the accessories with this filter check valve. This is necessary to achieve degree of protec­tion IP 65 by preventing dirt and moisture from entering the device.
2.1 Direct attachment to Type 3277 Actuator
For selection of the required mounting parts, refer to Tables 1, 2 and 3 on page 13.
When looking at the signal pressure connec­tion or the switchover plate (120 cm² actua­tor) from the top, the positioner must be at­tached to the left side of the actuator. The arrow on the black housing cover (Fig. 11) points towards the diaphragm
chamber. Exception: control valves in which the plug
closes the seat area when the actuator stem retracts. In this case, the positioner has to be attached to the right side of the actuator, i.e. with the arrow pointing away from the dia­phragm chamber.
1. Screw clamp (1.2) to the actuator stem,
ensuring that the fastening screw is lo­cated in the groove of the actuator stem.
2. Screw associated lever D1 or D2 (for
700 cm² actuator) to the transmission le­ver of the positioner.
3. Fasten distance plate (15) with the seal
pointing towards the actuator yoke.
4. Place positioner on the plate so that the
pick-off lever D1 or D2 slides centrically over the pin of the clamp (1.2). Screw positioner to the distance plate (15).
5. Mount cover (16).
10 EB 8382-1 EN
Attaching the positioner
EB 8382-1 EN 11
Attaching the positioner
SUPPLY
1817 19
1.2 D2
D1
17
16
15
1.2
16
17
15
Fig. 3 · Attachment and signal pressure connection for Types 3277 (top) and 3277-5 with 120 cm² (bottom)
1.2 Clamp D1 Lever D2 Lever 15 Distance plate 16 Cover 17 Seal 18 Cover plate 19 Switch plate
Actuator stem
extends
Actuator stem
retracts
Switchover plate Signal pressure input
Marking
Signal pressure input with brass restriction, if required
Signal pressure bore Switchover plate
Vent
Connection block
Side view of connection block
with seal (new) with switch plate (old)
Actuator stem extends Actuator stem retracts
Internal signal pressure connection
Signal pressure connection over piping
Symbol "Actuator stem extends"
Marking
Symbol "Actuator stem retracts"
240, 350 and 700 cm² actuators
6. Check whether the tongue of the seal (17) is properly aligned at the side of the connection block with the actuator symbol "Actuator stem extends" or "Actu­ator stem retracts" to match the actuator version used. If it does not match, remove the three fastening screws and the cover plate (18), turn the seal (17) by 180° and reinsert it. When the old connection block is used, turn the switch plate (19) to align the ar­row with the actuator symbol.
7. Place connection block with the associ­ated sealing rings against the positioner and the actuator yoke and screw it tight using the fastening screw. For actuators with fail-safe position "Ac­tuator stem retracts", additionally mount the prefabricated signal pressure line.
120 cm² actuator
For Type 3277-5 Actuators with 120 cm², the signal pressure is transmitted to the dia­phragm chamber over the switchover plate (see Fig. 3, bottom). For a rated travel of 7.5 mm, a brass restric­tion (see Accessories table on page 13) must be pressed into the seal located in the signal pressure input on the actuator yoke. With 15 mm rated travel, this is only re­quired if the supply pressure exceeds 4 bar
6. Remove screw at the back of the positioner and close the signal pressure output (output 38) at the side with the as­sociated plug included in the accessories kit.
7. Mount positioner so that the bore in the distance plate (15) is aligned with the seal located in the bore of the actuator yoke.
8. Align switchover plate with the corre­sponding symbol for attachment on the left. Screw the plate to the actuator yoke.
Important!
If, in addition to the positioner, a solenoid valve or a similar device is attached to the 120 cm² actuator, the rear M3 screw must not be removed. In this case, the signal pres­sure has to be fed from the signal pressure output to the actuator over the required con­necting plate (see Table 2). The switchover plate is no longer required.
Note!
For faster control valves with a transit time < 0.6 s, replace the filter in the signal pres­sure output (output 38) with a screw-in restriction (see Accessories table), if neces­sary.
Filling the spring chamber with air
If the Type 3277 Actuator's spring chamber must be pressurized with the air exhausted from the positioner, the spring chamber (ver­sion "Actuator stem extends") can be con­nected to the connection block using a tube (Table 3). To do so, remove the plug on the connection block.
With the Type 3277-5, version "Actuator stem retracts", the spring chamber is con­stantly pressurized with the air exhausted from the positioner through an internal bore.
12 EB 8382-1 EN
Attaching the positioner
Table 1
Required lever with associated clamp and distance plate
Actuator size
cm²
Mounting kit
Order no.
D1 (33 mm in length with clamp, 17 mm in height) 120 (G ¼)
120 (¼ NPT)
1400-6790 1400-6791
D1 (33 mm in length with clamp, 17 mm in height) 240 and 350 1400-6370
D2 (44 mm in length with clamp, 13 mm in height) 700 1400-6371 Table 2 Order no. Switchover plate for 120 cm² actuator Actuator 3277-5xxxxxx.00 (old) 1400-6819 Switchover plate new Actuators with index .01 or higher (new) 1400-6822
Connecting plate for additional attachment of, e.g. a solenoid valve
3277-5xxxxxxxx.00 G
1
8
(old)
1
8
NPT
1400-6820 1400-6821
Connecting plate new Actuators with index .01 or higher (new) 1400-6823 Note! Only new switchover plates and connecting plates can be used with the new actuators (modifica-
tion index .01). Old and new plates are not interchangeable.
Connection block required for actuator sizes 250, 350 and 700 cm² (including seals and fastening screw)
G ¼
¼ NPT
1400-8811 1400-8812
Table 3 Actuator size cm² Material Order no.
Required tubes including fittings 240 Steel 1400-6444
240 Stainless steel 1400-6445
For version "Actuator stem retracts" or when pressurizing the upper diaphragm chamber
350 Steel 1400-6446
350 Stainless steel 1400-6447
700 Steel 1400-6448
700 Stainless steel 1400-6449
Accessories Order no.
Pressure gauge mounting kit for supply air and signal pressure St. steel/brass
St. steel/St. steel
1400-6957 1400-6958
Signal pressure restrictions (screw-in and brass restriction) 1400-6964
Filter check valve, replaces vent plug and increases degree of protection to IP 65 (one included with every positioner delivered)
1790-7408
EB 8382-1 EN 13
Attaching the positioner
2.2 Attachment according to IEC 60534-6
For selection of the required mounting parts, refer to Tables 4 and 5 on page 17.
For positioner attachment according to NAMUR as shown in Fig. 4, an adapter housing is required. The valve travel is trans­mitted over the lever (18) and shaft (25) to the bracket (28) of the adapter housing and then to the pin (27) located on the positioner lever. To attach the positioner, the mounting parts listed in Table 4 are required. Which lever is to be used depends on the rated valve travel. The positioner must be attached to the adapter housing so that the arrow on the black housing cover points away from the di­aphragm actuator towards the valve. Exception: control valves in which the plug closes the seat area when the actuator stem retracts. In this case, the arrow must point to­wards the diaphragm actuator.
If the adapter housing cannot be mounted between the actuator and the valve (e.g. non-SAMSON actuators), make sure the ar­row on the housing cover points towards the control valve.
Note!
For faster control valves with a transit time < 0.6 s, replace the filter in the signal pres­sure output (output 38) with a screw-in re­striction (see Accessories table), if necessary.
2.2.1Mounting sequence
Important!
Before mounting the parts, apply a signal pressure to the actuator so that the valve is set to 50 % of its travel. It is only in this posi­tion that the lever (18) and bracket (28) can be aligned exactly.
Control valve with cast yoke
1. Use countersunk screws to attach the plate (20) to the coupling that connects the plug and actuator stem. For 2100 and 2800 cm² actuators, use additional mounting bracket (32).
2. Remove rubber plug from the adapter housing and fasten the housing to the NAMUR rib using the hexagon head screw.
Control valve with rod-type yoke
1. Screw plate (20) to the follower clamp of the plug stem.
2. Screw studs (29) into the adapter hous­ing.
3. Place housing with the plate (30) on ei­ther the right or left side of the valve rod and screw the housing tight using nuts (31). Align the height of the housing so that the lever (18) to be mounted sub­sequently is horizontal.
4. Move clamp (21) to surround the pin (19). Screw pin in the center row of bores in the plate (20) and lock it so that it will be located above the correct lever marking (1 to 2) for the assigned travel (see Table 5). Intermediate values must be interpolated.
14 EB 8382-1 EN
Attaching the positioner
EB 8382-1 EN 15
Attaching the positioner
2
1,5
1
2826
AB
24 25 22
32
31
20 19
19 21 2023 18
27b
27a
29 30
Fig. 4 · Attachment according to IEC 60534-6 (NAMUR)
Mounting position
Attachment to NAMUR rib
Attachment to rods
18 Lever N1, N2 19 Pin 20 Plate 21 Clamp 22 Clamping plate 23 Screw 24 Pointer 25 Shaft 26 Lever of positioner 27a Transmission pin 27b Lock nut 28 Bracket 29 Studs 30 Plate 31 Nuts 32 Mounting bracket
5. Measure distance between the center of the shaft (25) and the center of the pin (19). This value must later be entered when configuring the positioner.
2.2.2Presetting the valve travel
1. Adjust shaft (25) in the adapter housing so that the black pointer (24) is aligned with the cast marking on the adapter housing.
2. Screw clamping plate (22) tight in this position using a screw (23).
3. Screw in pin (27) at the positioner le­ver (26) on the side of the insert nuts and secure it with a hex nut on the opposite side. Observe mounting position A or B according to Table 5 and Fig. 5.
4. Place positioner on the adapter housing such that the transmission pin (27a) lies properly within the arms of the bracket (28). To do so, insert a 2.5 mm Allen wrench or screwdriver from the front into the bore located below the ob­long hole on the cover plate and push the positioner lever to the required position.
5. Screw positioner to the adapter housing.
6. Relieve actuator of the signal pressure.
16 EB 8382-1 EN
Attaching the positioner
Table 4 Attachment IEC 60534-6
Control valve Travel [mm] With lever Order no.
NAMUR mounting kit
Parts, see Fig. 4
Valve with cast yoke
7.5 to 60
N1 (125 mm)
1400-6787
30 to 120
N2 (212 mm)
1400-6789
Valve with
rod-type
yoke,
rod diame
-
ter [mm]
20 to 25 N1 1400-6436
20 to 25 N2 1400-6437
25 to 30 N1 1400-6438
25 to 30 N2 1400-6439
30 to 35 N1 1400-6440
30 to 35 N2 1400-6441
Attachment to linear Fisher and Masoneilan actuators (one each of both mounting kits is needed per actuator)
1400-6771
and
1400-6787
Accessories Order no.
Pressure gauge mounting block G ¼
¼ NPT
1400-7106 1400-7107
Pressure gauge mounting kit (output and supply) Order with every pressure gauge kit: 2 restrictions (1790-6121)
St. st./Brass St. st./St. st.
1402-0938 1402-0939
Signal pressure restrictions (screw-in and brass restrictions) 1400-6964
Filter check valve, replaces vent plug and increases degree of protection to IP 65 (one included with every positioner delivered)
1790-7408
Table 5 Attachment acc. to IEC 60534-6
Travel in mm*
7.5 15 15 30 30 60 30 60 60 120
Pin on marking* 1 1 2 1 2 1 2 1 2
Corresp. distance pin to lever fulcrum 42 42 84 42 84 84 168 84 168
With lever N1 (125 mm long) N2 (212 mm long)
Transmission pin (27) on position A A B A B
* Deviating travel values (intermediate values) are to be interpolated accordingly
EB 8382-1 EN 1
7
Attaching the positioner
2.3 Attachment to rotary actuators
For selection of the required mounting parts, refer to Table 6 on page 21.
The positioner can also be attached to rotary actuators in accordance with VDI/VDE 3845 using the mounting parts and accessories listed in Table 6. In this arrangement, the ac­tuator's rotary motion is converted via the cam disk on the actuator shaft and the fol­lower roll of the positioner lever to a linear motion required by the positioner's inductive travel pick-off system. Each cam disk is suitable for two curves: for angles of rotation from 0° to 90° (for all an­gles smaller than 90°) and for 0° to 120° (for all angles of 90° and larger). For double-acting, springless rotary actua­tors, it is necessary to connect a reversing amplifier to the connection side of the positioner (see section 2.3.4). If the positioner is attached to a SAMSON Type 3278 Rotary Actuator, the positioner's exhaust air is routed to the inside of the actu­ator and the chamber behind the dia­phragm. No additional tubing is required. If the positioner is attached to non-SAMSON actuators (NAMUR), the air is applied to the chamber behind the diaphragm through a tube assembly and a tee, connected between the actuator and the exhaust connection of the intermediate piece.
Note!
For faster control valves with a transit time < 0.6 s, replace the filter in the signal pres­sure output (output 38) with a screw-in re­striction (see Accessories table), if necessary.
2.3.1Mounting the cam follower roll lever
1. Place lever with the attached roll (35) on
the transmission lever (37) and secure it with the enclosed screws (38) and wash­ers.
2.3.2Mounting the intermediate piece
SAMSON Type 3278 Actuator
1. Screw adapter (36) to the free end of the
rotary actuator shaft using two screws.
2. Place the positioner's intermediate
piece (34) on the actuator housing and secure it using two screws. Align interme­diate piece so that the air connections of the positioner face towards the dia­phragm case side.
Non-SAMSON actuators
1. Position complete intermediate piece (34,
42, 44 and 45) on the bracket (fixing level 1, VDI/VDE 3845) delivered with the actuator and fasten it with screws.
2. Align cam disk (40) and scale according
to section 2.3.3 and fasten them with screws.
With springless actuators, the reversing am­plifier (45) must be screwed to the side of the positioner housing. Refer to section 2.3.4 for details.
18 EB 8382-1 EN
Attaching the positioner
EB 8382-1 EN 19
Attaching the positioner
33
3835
39
39 40
34
36
40
34
44
45
42
43
37
Fig. 5 · Attachment to rotary actuators
Attachment to
SAMSON Type 3278 Actuator
Attachment acc. to VDI/VDE 3845
Vent plug or filter check valve
33 Positioner 34 Intermediate piece 35 Lever with cam follower roll 36 Adapter 37 Transmission lever 38 Screws 39 Scale 40 Cam disk 41 Actuator shaft 42 Plate 43 Bracket 44 Coupling 45 Seal
2.3.3Aligning and mounting the cam disk
In rotary actuators with spring-return mecha­nism, the built-in actuator springs determine the fail-safe position and the direction of ro­tation of the control valve (clockwise, counterclockwise). With double-acting, springless rotary actua­tors, the direction of rotation depends on both the actuator and the valve model used.
Close the valve before making any adjust-
ments.
The positioner's direction of action, i.e. whether the valve opens or closes when the reference variable increases, has to be soft­ware-adjusted using communication (in­creasing/increasing or increasing/decreas­ing).
1. Position cam disk with scale on the
adapter (36) or the coupling (34) and fasten the screw loosely at first.
The cam disk carries two cam sections. The starting point of each section is marked by a small bore.
Important!
With the valve closed, the starting point (bore hole) of the respective curve is to be aligned so that the center of rotation of the cam disk, the 0° position on the scale, and the arrow mark on the plate are aligned. The starting point for the closing position must not be below 0° position!
In actuators with fail-safe position "Control valve open" (OPEN), pressurize the actuator with the max. signal pressure before aligning the cam disk. In springless actuators, connect the supply air.
2. On aligning the cam disk, the dou­ble-sided scale disk must be clipped on so that the value on the scale corre­sponds to the control valve's direction of rotation. Tightly secure the cam disk with the fastening screws now.
Securing the aligned cam disk
If you want to additionally secure the cam disk to prevent it from being turned, proceed as follows: Four bore holes are located centrically around the center bore on the cam disk. Se­lect a suitable hole to secure the cam disk. Through this hole, drill a hole in the adapter (36) or coupling (44) and insert a 2 mm dowel pin.
3. Attach positioner to the intermediate piece (34) so that the lever (35) contacts the cam disk with its cam follower roll. To do so, insert a 2.5 mm Allen wrench or screwdriver from the front into the bore located below the oblong hole on the cover plate and push the positioner lever to the required position.
4. Screw positioner to the intermediate piece.
20 EB 8382-1 EN
Attaching the positioner
Table 6 Rotary actuators (complete mounting parts, but without cam disk)
Attachment acc. to
VDI/VDE 3845,
level 1
SAMSON Type 3278 Actuator Attachment to Masoneilan actuators
160 cm²
actuator
320 cm²
actuator
Camflex I
DN 25 to 100
Camflex I
DN 125 to 250
Camflex II
Order no.
1400-8815 1400-7103 1400-7104 1400-7118 1400-7119 1400-7120
Piping kit, 8 x 1 stainless steel
G: 1400-6670 G: 1400-6672
NPT: 1400-6669 NPT: 1400-6671
Accessories Order no. Reversing amplifier for springless double-acting actuators G: 1079-1118 NPT: 1079-1119 Cam disk (0050-0089) with accessories, angle of rotation 0° to 90° and 0° to 120° 1400-6959 Cam disk (0050-0089) esp. for VETEC, adjustable by software from 0° to 75° 1400-6960 Cam disk (0050-0090) esp. for Camflex, adjustable by software from 0° to 50° 1400-6961 Pressure gauge mounting block G ¼: 1400-7106 ¼ NPT: 1400-7107 Pressure gauge set Stainl. steel/Br:
1400-6957
St. steel/st. steel:
1400-6958
Signal pressure restrictions (screw-in and brass restrictions) 1400-6964
Filter check valve, replaces vent plug and increases degree of protection to IP 65 (one included with every positioner delivered)
1790-7408
EB 8382-1 EN 21
Attaching the positioner
Fig. 6 · Aligning the cam disk
Cam follower roll
Starting point
Bore holes to secure the cam disk
Insert clip and press tongues outward.
View onto actuator shaft from positioner
Control valve opens counterclockwise Control valve opens clockwise
2.3.4Reversing amplifiers for dou­ble-acting actuators
For the use with double-acting actuators, the positioner must be fitted with a reversing am­plifier. The reversing amplifier is listed as an accessory in Table 6 on page 21.
The signal pressure of the positioner is sup­plied at output A1 of the reversing amplifier. An opposing pressure, which equals the re­quired supply pressure when added to the pressure at A
1
, is applied at output A2. The
rule A
1
+ A2= Z applies.
Mounting
1. Screw special nuts (1.3) from the acces-
sories of the reversing amplifier into the threaded connections of the positioner.
2. Remove sealing plug (1.5) from the re-
versing amplifier. The rubber seal (1.4) must remain installed.
3. Insert gasket (1.2) into recess of the re-
versing amplifier and push both hollow special screws (1.1) into the connection bores A1 and Z.
4. Place reversing amplifier onto the
positioner and screw tight using both special screws (1.1).
5. Replace vent plug in the reversing ampli-
fier with the included filter check valve.
Signal pressure connections A
1
: Connect output A1to the signal pressure
connection at the actuator that opens the valve when the pressure increases.
A
2
: Connect output A2to the signal pressure
connection at the actuator that closes the valve when the pressure increases.
4
Set up the actuator as "Double-acting without spring-return mechanism" in the user interface under Start-up -> Actuator type.
2.4 Fail-safe position of the actua­tor
Important!
If the fail-safe position of the actuator is changed subsequently by modifying the actu­ator springs from "Actuator stem extends" to "Actuator stem retracts", readjust mechanical zero and re-initialize the positioner.
22 EB 8382-1 EN
Attaching the positioner
EB 8382-1 EN 23
Attaching the positioner
1.3 1.2 1.1 1
Output 38 Supply 9
A
1
1.5 1.6
Z
A
2
1.4
A
1
A
2
Output 38 Supply 9
1.3 1.21.1
1.6
Z
A
1
Fig. 7 · Mounting a reversing amplifier
From the positioner
Control signals
to the actuator
1 Reversing amplifier
1.1 Special screws
1.2 Gasket
1.3 Special nuts
1.4 Rubber seal
1.5 Plug
1.6 Filter
3 Connections
3.1 Pneumatic connections
The air connections are either ¼ NPT or G ¼ tapped holes. Common fittings for metal and copper tubes or plastic hoses can be used.
Important!
The supply air must be dry and free of oil and dust. The maintenance instructions for upstream pressure reducing stations must be observed. Carefully purge all air tubes and hoses before connecting them.
If the positioner is attached directly to the Type 3277 Actuator, the connection of the signal pressure to the actuator is fixed. For NAMUR attachment, the signal pressure can be applied to either the upper or lower dia­phragm chamber of the actuator, depending on the actuator's fail-safe action (either "Ac­tuator stem retracts" or "stem extends").
Exhaust air: The exhaust air connection of the positioner is located on the mounting kit. For direct attachment, a vent plug is located on the plastic cover of the actuator. For NAMUR attachment, the vent plug can be found at the adapter housing. For attachment to rotary actuators, it is either located either on the intermediate piece or the reversing amplifier. To guarantee degree of protection IP 65, the vent plug must be replaced with the filter check valve included with the positioner. Refer to section 2 on page 10 (Important!) for details.
3.1.1Pressure gauges
To monitor positioner operation, it is recom­mended to connect pressure gauges for the supply air and signal pressure. The required gauges are listed as accessories in Tables 3, 4 or 6.
24 EB 8382-1 EN
Connections
2...3mm
Fig. 8 · Mounting pressure gauges
Nut Restriction with filter
Order no. 1790-6121
3.1.2Supply air pressure
The required supply air pressure depends on the bench range and the operating direction (fail-safe action) of the actuator. The bench range is indicated on the nameplate as a spring range or signal pressure range.
Actuator stem extends:
Required supply air pressure = upper bench range value + 0.2 bar, at least 1.4 bar
Actuator stem retracts:
The required supply air pressure for tight-closing valves is estimated on the basis of the maximum signal pressure p
st max
:
p
st max
= F +
d² p p
4A
⋅⋅⋅Δ
[bar]
d = Seat diameter [cm] Δp = Differential pressure across the valve [bar] A = Actuator area [cm²] F = Upper bench range value of actuator [bar]
If there are no specifications, calculate as follows:
Required supply air pressure = upper bench range value + 1 bar
3.2 Electrical connections
For electrical installation, you are re­quired to observe the relevant electrotechnical regulations and the accident prevention regulations that apply in the country of use. In Ger­many, these are the VDE regulations and the accident prevention regula­tions of the employers’ liability insur­ance. The following regulations apply for installation in hazardous areas: EN 60079-14:2003; VDE 0165 Part 1:1998 ”Electrical apparatus for explosive gas atmospheres”, and EN 50281-1-2: VDE 0165 Part 2:1999 ”Electrical apparatus for use in the presence of combustible dust”. For intrinsically safe electrical equip­ment approved in accordance with Directive 79/196/EEC, the data specified in the certificate of confor­mity apply for the connection of in­trinsically safe circuits. For intrinsi­cally safe electrical equipment ap­proved in accordance with Directive 94/9/EC, the data specified in the EC type examination certificate apply for the connection of intrinsically safe circuits. Caution! The terminal assignment specified in the certificate must be observed! Switching the assignment of the electrical terminals may cause the explosion protection to become ineffective! Do not loosen enameled screws in or on the housing.
EB 8382-1 EN 25
Connections
!
Note on the selection of cables and wires
To run several intrinsically safe circuits in one multi-core cable, observe section 12 of EN 60079-14; VDE 0165:1998. Note especially that, for commonly used in­sulating materials such as polyethylene, the radial thickness of the conductor insulation must be at least 0.2 mm. The diameter of a single wire of a flexible conductor must not be smaller than 0.1 mm. The conductor ends must be protected against unlaying, e.g. by using wire-end fer­rules. When two separate cables are used for connection, an additional cable gland can be installed. Cable entries left unused must be sealed with plugs. Positioners used in ambient temperatures down to –40 °C must be fitted with metal ca­ble entries.
For terminal assignment, refer to Fig. 9 or to the designations on the cover plate inside the lid.
Cable entries
Cable entry with M20x1.5 cable gland, 7 to 12 mm clamping range.
There is a second M20x1.5 cable gland in the housing that can be used for additional connection, if required.
The screw terminals are designed for wire cross-sections of 0.2 to 2.5 mm² (tightening torque at least 0.5 Nm).
Bus line
The shielded PROFIBUS connecting cable must be routed over the EMC-proof brass ca­ble gland (standard) of the positioner to the terminals. The shield, which is placed over the clamping insert, is connected over a large area to the gland and housing.
1. To connect the bus line, remove coupling
nut and clamping insert from the positioner. Also remove the dust cap.
2. Slide coupling nut and clamping insert
over the connecting cable.
3. Strip insulation off the end of the bus line
to the required connecting length. Cut off the wire shield up to a length of approx. 13 mm. If necessary, cut off any filling cable cores as well.
4. Disentangle the braided shield and pull it
over the clamping insert.
5. Press clamping insert into connecting
screw gland. Tighten coupling nut until the connecting cable is clamped tightly.
6. Route two-wire bus line to the screw ter-
minals marked "IEC 1158-2"; when do­ing so, no polarity has to be observed.
In exceptional cases, if the plant does not permit such a connection, feed the cable shield through the cable gland and connect it to be capacitive over terminal "S". However, make sure that no conducting connection oc­curs from the shield to the cable gland or housing.
26 EB 8382-1 EN
Connections
Refer to PROFIBUS-PA User and Installation Guideline (PROFIBUS User Organization document 2.091) for further information.
At the binary input, a passive floating con­tact can be used. The positioner signals the circuit's state using the bus protocol.
Important!
The connection of limit switches, binary input and forced venting function requires an ad­ditional cable gland that must replace the cap fitted on the housing. Accessories: M20 x 1.5 cable gland, nickel-plated brass, order no. 8808-0143
3.2.1Forced venting
For positioners with forced venting function, a voltage of 6 to 24 V DC must be applied to the associated terminals.
The forced venting function can be activated or deactivated over an internal switch. See section 4.3 for details.
Note!
If there is no voltage connected or when the voltage signal is interrupted, the positioner vents the actuator and does not respond to the reference variable.
EB 8382-1 EN 27
Connections
Fig. 9 · Electrical connections (terminal assignment according to DIN 45140)
GW2 GW1
PE
S
NC
-52
+51
-42
+41 -86
+85
-82 +81
IEC 1158-2
PROFIBUS-PA
6...24 VDC
Brass cable gland Shielding Clamping insert Coupling nut
Switching amplifier
acc. to EN 60947-5-6
Bus line
Limit switches Binary input Forced venting
3.2.2Limit switches
Switching amplifiers have to be connected in the output circuit to operate limit switches. To ensure operational safety of the positioner, these switching amplifiers must comply with the limits of the control circuit according to NAMUR. Observe the relevant regulations if the positioner is installed in hazardous ar­eas.
3.2.3Establishing communication (bus address)
Communication between positioner, pro­grammable logic controller or automation system, i.e. between PC or workstation and the positioner(s), is established using a seg­ment coupler (see Fig. 10) in accordance with the PROFIBUS guidelines. If the positioner is used in hazardous areas, exlosion-protected PROFIBUS-PA segment couplers must be used. A maximum of 32 positioners can be oper­ated in parallel on a segment coupler in one PROFIBUS-PA segment. In hazardous areas, fewer positioners can be connected. Each positioner in a segment must be as­signed a unique bus address between 0 and 125. Seven microswitches located on the inside of the positioner's hinged lid serve to enter the bus address either directly by switch numbers 1, 2, 4 etc. or by adding up several switch positions. The positioner is de­livered with the default address set to 126. Make absolutely sure that the switches are adjusted all the way to either 1 or 0, not set to an intermediate position.
Note!
Start the positioner up again for a new bus address to be adopted.
3.2.4Local interface (SSP)
The local interface is located on the inside of the positioner's hinged lid. It is connected to a PC over the serial interface adapter (order no. 1400-7700). The positioner can be started up using the interface and SAMSON's TROVIS-VIEW software.
It is no longer necessary to connect the de­vice to a PROFIBUS DP/PA segment. Only the power supply needs to be connected over the bus terminals of the positioner (any DC voltage supply unit between 9 and 32 V).
The TROVIS-VIEW software and the device module 3785 in version 2.02 are required.
The positioner can also be accessed over the SSP interface when it is connected to a bus segment.
Cyclic and acyclic data exchange are not af­fected. The value written last is always valid for the device parameters.
28 EB 8382-1 EN
Connections
EB 8382-1 EN 29
Connections
PROFIBUS-DP(E) RS 485
3785
3785
3785
3785
PROFIBUS-PA IEC 61158-2
PROFIBUS-DP RS 485
3785-1
3785-1
3785-1
3785-1
PROFIBUS-PA IEC 61158-2
PROFIBUS-DP(E) RS 485
PROFIBUS-DP RS 485
Fig. 10 · PROFIBUS connection
Controller/PLC/control system (Class 1 Master)
Display and control component (Class 2 Master)
Segment coupler
Termination
Termination
Fig. 10.1 · Connection of Type 3785 Positioners
Fig. 10.2 · Connection of Type 3785-1 Positioners in hazardous areas
Controller/PLC/control system (
Class 1 Master)
Display and control component (
Class 2 Master)
Termination
Ex-proof segment coupler
Termination
Non-haz­ardous area
Hazard­ous area
4 Operation
Warning!
Before putting the positioner into op­eration, carefully move the control valve to its end position by covering the hole (manually) on the cover plate (Fig. 11). Check whether the lever mechanism functions properly. If the maximum angle of rotation is exceeded by selecting the wrong le­ver mechanism or sizing the lever mechanism incorrectly, the positioner may be destroyed.
4.1 LED controls
Two LEDs located inside the cover serve to monitor the positioner, indicating the positioner's status during start-up, operation and in the event of defects.
The colors indicate the following: Red Start-up or error, no control
operation possible
Green No error recognized, control
operation or fail-safe position (e.g. if not initialized)
Red + Green Error recognized, control
operation possible
For details, refer to the table below.
30 EB 8382-1 EN
Operation
!
Description LED
Positioner start-up Red ON
No errors Positioner connected to bus, cold start performed, initial­ization required When initializing or adjusting zero Positioner initialized, no valid set point Positioner initialized, valid set point, control operation
Green, generally Green blinks slowly
Green blinks quickly Green blinks 3 times quickly + long pause Green ON
Errors during control operation Zero point error Control loop error
Red and green Red and green blink slowly Red and green blink quickly
Errors causing the first initialization to be canceled (positioner does not start standard operation) Zero point error Error in mechanics/pneumatics section Control loop error
Red, generally
Red blinks slowly Red ON Red blinks quickly
Errors causing the positioner to stop control operation Positioner recognized an internal error Red blinks 3 times quickly + long pause
4.2 Write protection
A microswitch marked "write protection" is located to the right of the seven bus address selector switches inside the hinged cover. When it is activated (position ON), the positioner settings are write-protected so that they cannot be overwritten by the PROFIBUS communication protocol. If you want to change the settings via communication, set the switch to position OFF.
4.3 Activate/deactivate forced venting
For model index .03 and higher:
1. Remove four screws from the cover inside
the hinged lid and remove the cover.
2. Remove screw in the middle of the
printed circuit board and turn the PCB to one side.
3. Set switch to desired position: 1 ENABLED > function activated 2 DISABLED > function deactivated
4.4 Default settings
All parameters are set to their default values. Refer to section 8 for descriptions of the pa­rameters.
Caution!
Manual operation and activated end position function can cause the actua­tor to be pressurized with the maxi­mum supply pressure. If this causes inadmissible forces, restrict the supply pressure using a suitable pressure re­ducing station.
EB 8382-1 EN 31
Operation
GW1
GW2
3785
PE
IEC 1158-2
S
NC -52
+51
-42
+41
-86
+85
-82
+81
LED 1
LED 2
1
2
4
8
16
32
64
Write protection
Caution!
Valve
actuates
Init/Zero
Bus address
10
0N0FF
0
Fig. 11 · Inside view of the cover plate
Arrow for mounting position Pointer Manual operation Bus address Write protection switch
Zero point lever Metal tags Adjustment screws LEDs Key for initialization
for limit switches or zero adjustment
!
4.4.1Adjusting mechanical zero
Important!
Zero must be adjusted with the valve closed (for three-way valves with the actuator stem extended).
4
Firmly push the zero point lever, which is located on the cover plate of the positioner, once in the direction indicated by the arrow as far as it will go. The yel­low pointer will then be on the white marking.
For control valves with starting position OPEN, e.g. an actuator with fail-safe action "Actuator stem retracts", feed supply air to the positioner first. As soon as the manual operation function is activated, the signal pressure builds up and the valve moves to closed position. Subse­quently, the zero point lever can be oper­ated.
4.4.2Initialization
After the electric reference variable and the supply air have been connected to the positioner, the initialization process can be started. During initialization, the positioner is optimally adapted to the friction conditions and signal pressure demands of the control valve.
Warning!
The initialization process takes sev­eral minutes. During that time, the valve changes its position. Therefore, never initialize the positioner during a running process; only perform ini­tialization during the start-up cycle
when the shut-off valves in the plant are closed or when the control valve with the positioner has been removed from the plant and is used on a test bench.
4
Enter data for valve and actuator in the Start-up section of the operating software.
4
Set "Type of initialization" to "Rated range". Select "Maximum range" for three-way valves only.
4
Start initialization.
A successful initialization is indicated in the operating software and over the LEDs (see section 4.1).
4
Carry out the configuration suitable for the valve type.
The following settings are recommended:
4
Fail-safe position "Actuator stem ex­tends":
Direction of action: increasing/increasing (>>), a globe valve opens with increasing reference variable End position at a reference variable be­low 1 % (tight closing) End position at a reference variable above 125 % (function deactivated).
4
Fail-safe position "Actuator stem re­tracts":
Direction of action: increasing/decreas­ing (<>), a globe valve closes with in­creasing reference variable End position at a reference variable below –2.5 % (function deactivated) End position at a reference variable above 99 % (tight closing).
32 EB 8382-1 EN
Operation
!
4
Set delay time to at least 30 s.
4
Enter tag identification.
4
If necessary, configure the positioner further, e.g. special characteristics for ro­tary valves.
If no communication can be established on the valve, the positioner can also be initial­ized directly on the device itself.
4
Connect positioners that are not mounted on a valve to a power supply and initial­ize the positioner as described in section
4.4.2. If communication cannot be established, the default settings must be used.
4
Mount positioner and adjust mechanical zero as described in section 4.4.1.
4
Start initialization by pressing the Init/Zero key on the positioner's hinged lid using a suitable tool.
Initialization is completed when the positioner moves to the position predeter­mined by the reference variable.
Note!
Once the positioner has been initialized suc­cessfully for the first time, pressing the Init/Zero key only starts a zero calibration.
After a successful initialization, the positioner can be re-initialized when communication is established.
A completed initialization routine can be canceled using communication with the "Re­set to default values" command. After that, the Init/Zero key can be pressed again to start a complete initialization.
Electric zero calibration
If mechanical zero has shifted during the valve's operation, an electric zero calibration can be carried out. To do so, press the Init/Zero key located on the inside of the lid (Fig. 11).
Caution!
The control valve moves to its end po­sition.
4
Firmly push the zero point lever, which is located on the cover plate of the positioner, once in the direction indicated by the arrow as far as it will go. The yel­low pointer will then be on the white marking.
4
Press key again to start electric calibra­tion.
After the key has been pressed for the sec­ond time, it is locked for approximately one minute. Electric calibration is completed when the positioner moves to the position predeter­mined by the reference variable.
EB 8382-1 EN 33
Operation
!
4.5 Adjusting the inductive limit switches
The positioner version with inductive limit switches has two adjustable metal tags that are mounted on the shaft of the positioner le­ver and operate the associated proximity switches. Connect appropriate switching amplifiers to the output circuit to operate the inductive limit switches (see section 3.2.2).
If the tag is inside the inductive field of the proximity switch, the switch assumes a high resistance. If the tag is outside the field, the switch assumes a low resistance.
Normally, the limit switches are adjusted such that they will provide a signal in both end positions of the valve. These switches, however, can also be adjusted to signal in­termediate valve positions.
The desired switching function, i.e. whether the output relay is to be pulled in or dropped out when the tag has entered the field, has to be determined at the switching amplifier, if required.
Adjusting the switching point
The limit switches are marked GW1 and GW2 on the inside of the housing cover. Yel­low tags and the associated adjustment screws (Fig. 11) are located below these markings.
Each switching position can optionally be signaled when the tag has entered or left the field.
4
Move the valve to the switching position and adjust the tag of the desired limit switch GW1 or GW2 by turning the re­lated adjustment screw until the switching point is reached. This is indicated by the LED at the transistor relay.
When doing so, one edge of the yellow tag is aligned with the white, horizontal line on the housing cover. This indicates the side from which the tag enters the inductive field of the proximity switch.
To ensure safe switching under all ambient conditions, the switching point is to be ad­justed to a value approx. 5 % before the me­chanical stop (OPEN - CLOSED).
34 EB 8382-1 EN
Operation
5 Maintenance
The positioner is maintenance free. Pneumatic connection 9/Supply contains a filter with a mesh size of 100 µm. Remove and clean the filter, if required.
Observe the maintenance instructions for up­stream pressure reducing stations for supply air, if applicable.
6 Servicing explosion-protected
devices
If a part of the positioner on which the explo­sion protection is based needs to be serviced, the positioner must not be put back into op­eration until an expert has inspected it ac­cording to explosion protection requirements, has issued a certificate stating this or given the device a mark of conformity.
Inspection by an expert is not required if the manufacturer performs a routine test on the device prior to putting it back into operation. The passing of the routine test must be docu­mented by attaching a mark of conformity to the device.
EB 8382-1 EN 35
Maintenance
7 How to implement a Class 1 PROFIBUS Master
7.1 Device database files (GSD)
The device data are provided as a text file (SAMS3785.GSD). It is available from SAMSON AG under order no. 1400-7417 on a 3½" 1.44 MB floppy disk or on the Internet at http://www.samson.de or http: //www.profibus.com. The device database file permit the standardized implementation of the SAMSON Type 3785 PROFIBUS Positioner as a PROFIBUS slave unit in the programming and configu­ration environment of a Class 1 master (example: SIEMENS Simatic Step 7, HWConfig). Using the device database file, the Class 1 master is informed about the basic possibilities of cyclic data exchange with the slave unit – in this case, the Type 3785 Positioner.
7.2 Data exchange
According to the PROFIBUS PA device profile for electropneumatic actuators, a total of seven cyclic parameter combinations is available for the exchange of data. One of the combina­tions is to be selected in the programming and configuration environment of the Class 1 master. The terms "Output" and "Input" refer to the control system/Class 1 master.
Variant 1: Module = SP; 0xA4
Output value (Output)
Byte 0 1234
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
SP, value
(floating point, IEEE)
Status
Variant 2: Module = RCAS_OUT, RCAS_IN; 0xB4
Input value (Input)
Byte 0 1234
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
RCAS_OUT, value
(floating point, IEEE)
Status
36 EB 8382-1 EN
How to implement a Class 1 PROFIBUS Master
Output value (Output)
Byte 0 1234
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
RCAS_IN, value
(floating point, IEEE)
Status
Variant 3: Module = READBACK + POS_D, SP; 0x96, 0xA4
Input value (Input)
Byte 0 123456
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5 Octet 1 Octet 2
READBACK, value
(floating point, IEEE)
Status POS_D
value
POS_D
status
Output value (Output)
Byte 0 1234
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
SP, value
(floating point, IEEE)
Status
Variant 4: Module = CHECKBACK, SP; 0x92, 0xA4
Input value (Input)
Byte 0 1 2
Octet 1 Octet 2 Octet 3
CHECK_ BACK[0]
CHECK_
BACK[1]
CHECK_ BACK[2]
EB 8382-1 EN 37
How to implement a Class 1 PROFIBUS Master
Output value (Output)
Byte 0 1234
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
SP, value
(floating point, IEEE)
Status
Variant 5: Module = READBACK + POS_D + CHECKBACK, SP; 0x99, 0xA4
Input value (Input)
Byte 0 123456789
Octet 1
Sign, ex-
ponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5 Octet 1 Octet 2 Octet 1 Octet 2 Octet 3
READBACK, value
(floating point, IEEE)
Status POS_D
value
POS_D
status
CHECK_ BACK[0]
CHECK_ BACK[1]
CHECK_
BACK[2]
Output value (Output)
Byte 0 1234
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
SP, value
(floating point, IEEE)
Status
Variant 6: Module = RCAS_OUT + CHECKBACK, RCAS_IN; 0x97, 0xA4
Input value (Input)
Byte 0 1234567
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5 Octet 1 Octet 2 Octet 1
RCAS_OUT, value
(floating point, IEEE)
Status CHECK_
BACK[0]
CHECK_
BACK[1]
CHECK_ BACK[2]
38 EB 8382-1 EN
How to implement a Class 1 PROFIBUS Master
Output value (Output)
Byte 0 1234
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
RCAS_IN, value
(floating point, IEEE)
Status
Variant 7:
Module = READBACK + RCAS_OUT + POS_D + CHECKBACK, SP + RCAS_IN; 0x9E, 0xA9
Input value (Input)
Byte 0 123456789
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5 Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
READBACK, value
(floating point, IEEE)
Status RCAS_OUT, value
(floating point, IEEE)
Status
Byte 10 11 12 13 14
Octet 1 Octet 2 Octet 1 Octet 2 Octet 3
POS_D
value
POS_D
status
CHECK_ BACK[0]
CHECK_ BACK[1]
CHECK_ BACK[2]
Output value (Output)
Byte 0 123456789
Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5 Octet 1
Sign,
exponent
Octet 2
Exponent,
fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
SP, value
(floating point, IEEE)
Status RCAS_IN, value
(floating point, IEEE)
Status
EB 8382-1 EN 39
How to implement a Class 1 PROFIBUS Master
7.3 Parameter description
SP – Set point with status: Reference variable w in "Auto" operating mode
The reference variable w of the positioner is preset by SP in automatic mode (AUTO). SP consists of a floating point value (4 bytes) and the associated status (1 byte). Value and status must be transferred together (data consistency = 5 bytes). If the status of the reference variable is "bad" (value < 64 dec.), the positioner remains in the fail-safe position deter­mined by the actuator.
RCAS_IN/RCAS_OUT: Reference variable w in RCAS operating mode
The reference variable w of the positioner is preset in REMOTE CASCADE (RCAS) operating mode by RCAS_IN/RCAS_OUT. RCAS_IN/RCAS_OUT both consist of one floating point value (4 bytes) and the associated status (1 byte). Value and status must be transferred together (data consistency = 5 bytes). If the status of the reference variable is "bad" (value < 64 dec.), the positioner remains in the fail-safe position determined by the actuator.
Note! RCAS operating mode is implemented in version K1.60 and higher. READBACK – Current position with status: Controlled variable x
Position feedback is provided by the READBACK parameter and consists of a floating point value (4 bytes) and the associated status (1 byte).
POS_D – Discrete valve position feedback with status: End position indication
The final valve position is indicated by the POS_D parameter and consists of one message value (1 byte) and the associated status (1 byte). The message value is encoded as follows:
0 = not initialized, 1 = closed (x < 0.5 %), 2 = open (x > 99.5 %), 3 = intermediate position
CHECK_BACK – Device status: Detailed device information, bit-wise encoded
Bit no. Name Description Byte
0 CB_FAIL_SAFE Fail-safe position (mode = Out of Service)
0
1 CB_REQ_LOC_OP Request for local operation
2 CB_LOCAL_OP Device in local mode
3 CB_OVERRIDE Emergency operation / forced venting active
4, 5, 6 Not used
7 CB_TRAV_TIME Status of travel monitoring (reset automatically) 0
8, 9 Not used
1
10 CB_UPDATE_EVT Indicates change to static device data
40 EB 8382-1 EN
How to implement a Class 1 PROFIBUS Master
11 CB_SIMULATE
Simulation mode, i.e. value are not derived from the process
1
12 CB_DISTURBANCE Error, refer to DIAGNOSIS parameter for cause
13 CB_CONTR_ERR
Error in internal positioner control loop (to be con­firmed by Class 2 master), indicated by LED, reset au­tomatically when control loop monitoring no longer detects any errors
14 CB_CONTR_INACT Positioner inactive (mode = Out of Service)
15 CB_SELFTEST Positioner in self-test mode (mode = Out of Service)
16 CB_TOT_VALVE_TRAV Limit for total valve travel exceeded
2
17 to 23 Not used
Diagnostic messages of the positioner (slave diagnostic information)
In addition to the standard diagnostic messages, the positioner can provide further messages as "Ext_Diag_Data". These are bit-wise encoded as well and correspond to the PROFIBUS PA profile DIAGNOSIS parameter.
Bit no. Name Description
0 DIA_HW_ELETR Hardware error, electronics
1 DIA_HW_MECH Hardware error, mechanics
4 DIA_MEM_CHKSUM Checksum error, memory
5 DIA_MEASUREMENT Measurement error
6 DIA_NOT_INIT Positioner not initialized (no auto-initialization performed)
7 DIA_INIT_ERR Auto-initialization error
8 DIA_ZERO_ERR Zero point error (end position)
10 DIA_CONF_INVAL Invalid configuration
11
DIA_WARMSTART Restart (warm start) completed, refer to Profile A for definition of
warm start
12
DIA_COLDSTART New start (cold start) completed, refer to Profile A for definition of
cold start
13 DIA_MAINTENANCE Maintenance required
14 DIA_CHARACT Invalid characteristic
31 EXTENSION_AVAILABLE Further information available
EB 8382-1 EN 41
How to implement a Class 1 PROFIBUS Master
7.4 Coding of measured value status
Measured value status
The following status codes are used by the Type 3785 Positioner:
Bad Value is valid
Substatus Condition Decimal value
Configuration error Error in device configuration, value cannot be
determined
4
Device failure Device error: memory, electronics 12
Sensor failure Error in travel measurement, limit bits indicate
which measured value limits were exceeded*
16/17/18/19
No communication (last usable value)
Internal communication error, device operates with last usable value
20
No communication (no usable value)
Internal communication error, no usable error available
24
Out of service Transducer block in Out of Service mode
(e.g. device not initialized)
28
* Limit bits: The two lowest bits of the measuring value status indicate that the limits for the measuring value have been exceeded.
Bit 0 = Low limited – lower limit value not reached Bit 1 = High limited – upper limit value exceeded Bit 0 and 1 = Constant (high and low limited) – value is blocked
Uncertain Value is valid, but not derived from the process
Substatus Condition Value
Non-specific Initialization or zero calibration running 64
Initial value Initial value during device start-up (temporary) 76
42 EB 8382-1 EN
How to implement a Class 1 PROFIBUS Master
Good (non-cascade) Value is valid
Substatus Condition Value
OK Everything OK, no other status available 128
Maintenance required Transit time monitoring active, zero point error ac-
tive or total valve travel exceeded
164
Set point status
Good (non-cascade)
Substatus Condition Value
OK Everything OK 128 (80)
Good_INITIATE_FAIL_SAFE Positioner's defined fail-safe action activated 160 (AO)
Good (cascade)
Substatus Condition Value
Good_CAS_Init_Acknowledge Status required for transition to RCAS mode 196 (C4)
EB 8382-1 EN 43
How to implement a Class 1 PROFIBUS Master
7.5 Operating modes
Possible operating modes
The following operating modes are defined in the AO (Analog Output) profile:
4
Automatic (Auto)
4
Manual (Man)
4
Remote Cascade (RCas)
4
Local Override (LO)
4
Out of Service (OS)
The Type 3785 Positioner supports the following operating modes:
Up to firmware version K 1.20: OS, AUTO
Firmware version K 1.30 and higher: OS, LO, MAN, AUTO
Automatic (Auto) mode
In this operating mode, the positioner follows the set point that is cyclically or acyclically pre­set by the SP (w) parameter according to the scale and unit preset by PV_SCALE (reference variable range).
Local Override (LO) or Manual (Man) mode
In these operating modes, the positioner follows the acyclic set point preset by the OUT pa­rameter (correction value) according to the scale and unit (mm or degrees) entered as OUT_SCALE (travel/angle of rotation range). With the characteristic deactivated, this value corresponds to the actual valve position in mm or degrees. The INCREASE_CLOSE parameter (direction of action), however, is not processed. Neither are the communication monitoring parameters (FSAFE_TIME, _TYPE, _VALUE) processed.
Remote cascade (Rcas) mode
In this operating mode, the positioner follows the set point cyclically preset by the RCAS_IN (w_rcas) parameter according to the scale and unit preset by PV_SCALE (reference variable range).
Out of Service (OS) mode
In this operating mode, the valve is automatically moved to its fail-safe position.
44 EB 8382-1 EN
How to implement a Class 1 PROFIBUS Master
EB 8382-1 EN 45
w_man
Configuration block diagram
Start
End
Reference
variable
range
Direction
of action
Correction
value
Speed
limit
Travel
limit
Travel
adapt.
> end
pos.
at
< end
pos.
at
End position function
Supply
valve
Exhaust
valve
Fail-safe position
Control
characteristic
Fail-safe action
"Stem extends"
"Stem
retracts"
Travel
range
relation
Travel
convers.
Filter
Forced venting,
optional
Hardware or system
software failure
Initialization
parameter
Transit time
Upper, lower
Travel range
Rated travel
Travel
Start-up (warm start)
The response of the positioner to a warm start is determined by the FSAFE_TYPE parameter (fail-safe action).
If FSAFE_TYPE is set to "control to fail-safe value", the positioner switches to automatic oper­ating mode and adjusts to the value determined by the FSAFE_VALUE parameter.
If FSAFE_TYPE is set to "control to last set point" or "fail-safe position determined by spring action", the device remains in fail-safe position. As soon as a valid set point SP is transmitted to the positioner, the operating mode changes to automatic.
If the status of the transmitted set point is "bad" or the positioner has not been successfully in­itialized, it remains in fail-safe position (Out of Service) up to firmware version K1.51. With version K1.6 and higher, the behavior for a bad set point status is determined by the FSAFE_TYPE parameter.
Monitoring parameters FSAFE_TIME, FSAFE_TYPE, FSAFE _VALUE
The action determined by the FSAFE_TYPE (fail-safe action) parameter is triggered by the fol­lowing events:
4
Start-up of the positioner (warm start)
4
Elapsing of DP-Watchdog through interruption of the cyclic communication with a Class 1 master (not applicable when communication is terminated properly).
4
Elapsing of FSAFE_TIME in Automatic or Remote Cascade operating modes, when the status of the reference variable valid in this operating mode (SP or RCAS_IN) is set to "initiate fail-safe"
4
Receipt of a DP-Global Control service for which the clear bit is set (not yet applicable for version K1.30)
By setting the status of the reference variable used in the valid operating mode to "bad", the actuator always moves to the fail-safe position determined by the spring action (for firmware versions K1.30 to K1.51). In version K1.6 and higher, the behavior for a bad set point status is determined by the FSAFE_TYPE parameter.
46 EB 8382-1 EN
How to implement a Class 1 PROFIBUS Master
8 List of parameters
Below is an overview of parameters ordered by their fields of application. The list of parameters following the overview is in alphabetical order and describes all positioner parameters that can be displayed or modified using PROFIBUS communication, e.g. on a PC. Manufacturer-specific parameters of the SAMSON Type 3785 PROFIBUS-PA Positioner are marked with (M).
Parameter overview Device identification
Tag identification . . . . . . . . . . . . . . . . . . TAG_DESC
Firmware version, communication/control . . . . . . SW_REVISION
Hardware version, electronics/mechanics . . . . . . . HW_REVISION
Manufacturer, positioner . . . . . . . . . . . . . . . DEVICE_MAN_ID
Manufacturer, valve . . . . . . . . . . . . . . . . . VALVE_MAN
Manufacturer, actuator. . . . . . . . . . . . . . . . ACTUATOR_MAN
Type number, positioner . . . . . . . . . . . . . . . DEVICE_ID
Serial number, positioner. . . . . . . . . . . . . . . DEVICE_SER_NUM
Serial number of corresponding actuator . . . . . . . ACTUATOR_SER_NUM
Serial number of corresponding valve. . . . . . . . . VALVE_SER_NUM
Type of protection . . . . . . . . . . . . . . . . . . DEVICE_CERTIFICATION
Description . . . . . . . . . . . . . . . . . . . . . DESCRIPTOR
Message . . . . . . . . . . . . . . . . . . . . . . DEVICE_MESSAGE
Date of installation . . . . . . . . . . . . . . . . . . DEVICE_INSTALL_DATE
Identification, forced venting . . . . . . . . . . . . . IDENT_FORCED_VENTING (M)
Binary input . . . . . . . . . . . . . . . . . . . . . IDENT_BINARY_INPUT (M)
Identification, limit switches. . . . . . . . . . . . . . IDENT_LIMIT_SWITCHES (M)
Product number, positioner . . . . . . . . . . . . . . DEVICE_PRODUCT_NUM (M)
Text fields . . . . . . . . . . . . . . . . . . . . . . TEXT_INPUT_1…TEXT_INPUT_3 (M)
Date of last maintenance . . . . . . . . . . . . . . . VALVE_MAINT_DATE
Date of last calibration . . . . . . . . . . . . . . . . DEVICE_CALIB_DATE
Date of last configuration. . . . . . . . . . . . . . . DEVICE_CONFIG_DATE
EB 8382-1 EN 47
List of parameters
Start-up
Security locking . . . . . . . . . . . . . . . . . . . SECURITY_LOCKING
Cold start . . . . . . . . . . . . . . . . . . . . . . FACTORY_RESET
Warm start . . . . . . . . . . . . . . . . . . . . . DEVICE_RESET_CMD
Actuator type . . . . . . . . . . . . . . . . . . . . ACTUATOR_TYPE
Valve type. . . . . . . . . . . . . . . . . . . . . . VALVE_TYPE
Fail-safe position. . . . . . . . . . . . . . . . . . . ACTUATOR_ACTION
Attachment . . . . . . . . . . . . . . . . . . . . . ATTACHMENT (M)
Actuator version . . . . . . . . . . . . . . . . . . . ACTUATOR_VERSION (M)
Mounting position . . . . . . . . . . . . . . . . . . MOUNTING_POSITION (M)
Transit time, minimum OPEN . . . . . . . . . . . . . ACT_STROKE_TIME_INC
Transit time, minimum CLOSED. . . . . . . . . . . . ACT_STROKE_TIME_DEC
Calibration, command . . . . . . . . . . . . . . . . SELF_CALIB_CMD
Calibration, status . . . . . . . . . . . . . . . . . . SLF_CALIB_STATUS
Transmission, code. . . . . . . . . . . . . . . . . . TRANSM_CODE (M)
Transmission, length . . . . . . . . . . . . . . . . . TRANSM_LENGTH (M)
Transmission, pin position . . . . . . . . . . . . . . TRANSM_PIN_POS (M)
Initialization method . . . . . . . . . . . . . . . . . INIT_METHOD (M)
Device settings Configuration
Write protection . . . . . . . . . . . . . . . . . . . WRITE_PROTECTION_SWITCH (M)
Reference variable range. . . . . . . . . . . . . . . PV_SCALE
Fail-safe value, reference variable . . . . . . . . . . FSAFE_VALUE
Fail-safe action . . . . . . . . . . . . . . . . . . . FSAFE_TYPE
Fail-safe time . . . . . . . . . . . . . . . . . . . . FSAFE_TIME
Travel/angle of rotation range . . . . . . . . . . . . OUT_SCALE
Direction of action . . . . . . . . . . . . . . . . . . INCREASE_CLOSE
Local operation enabled . . . . . . . . . . . . . . . LOCAL _OP_ENA
Rated travel/nominal angle . . . . . . . . . . . . . RATED_TRAVEL
Travel/angle limit, lower . . . . . . . . . . . . . . . TRAVEL_LIMIT_LOW
Travel/angle limit, upper. . . . . . . . . . . . . . . TRAVEL_LIMIT_UP
Transit time, desired CLOSED. . . . . . . . . . . . . TRAVEL_RATE_DEC
Transit time, desired OPEN. . . . . . . . . . . . . . TRAVEL_RATE_INC
48 EB 8382-1 EN
List of parameters
End pos. when reference variable is below limit value . SETP_CUTOFF_DEC End pos. when reference variable is above limit value . SETP_CUTOFF_INC
Selection of characteristic . . . . . . . . . . . . . . CHARACT
Type of characteristic . . . . . . . . . . . . . . . . CHARACT_TYPE
Control parameters
Proportional-action coefficient KP_Y1 . . . . . . . . . SERVO_GAIN
Derivative-action coefficient KD. . . . . . . . . . . . SERVO_RATE
Deadband Xtot . . . . . . . . . . . . . . . . . . . DEADBAND
Proportional-action coefficient KP_Y2 . . . . . . . . . KP_Y2
Tolerated overshoot . . . . . . . . . . . . . . . . . TOL_OVERSHOOT (M)
Operation
Operating mode, desired/current . . . . . . . . . . MODE_BLK/TARGET_MODE
Controlled variable x. . . . . . . . . . . . . . . . . READBACK
Reference variable w. . . . . . . . . . . . . . . . . SP
Reference variable w_rcas . . . . . . . . . . . . . . RCAS_IN/RCAS_OUT
Valve position feedback, discrete . . . . . . . . . . . POS_D
Set point deviation e . . . . . . . . . . . . . . . . . SETP_DEVIATION
Correction value . . . . . . . . . . . . . . . . . . . OUT
Transducer state . . . . . . . . . . . . . . . . . . . TRANSDUCER_STATE (M)
Diagnostics
Diagnostics . . . . . . . . . . . . . . . . . . . . . DIAGNOSIS
Diagnostics extension . . . . . . . . . . . . . . . . DIAGNOSIS_EXTENSION
Simulation. . . . . . . . . . . . . . . . . . . . . . SIMULATE
Device status. . . . . . . . . . . . . . . . . . . . . CHECK_BACK
Total valve travel, absolute . . . . . . . . . . . . . . TOTAL_VALVE_TRAVEL
Total valve travel, limit . . . . . . . . . . . . . . . . TOT_VALVE_TRAV_LIM
Delay time. . . . . . . . . . . . . . . . . . . . . . DELAY_TIME (M)
Tolerance band . . . . . . . . . . . . . . . . . . . TOLERANCE_BAND (M)
Calibration, alarm message . . . . . . . . . . . . . SELF_CALIB_WARNING (M)
Binary input, status. . . . . . . . . . . . . . . . . . BINARY_INPUT (M)
Travel/angle of rotation, max. permissible . . . . . . MAX_HUB (M)
EB 8382-1 EN 49
List of parameters
Actuator type
ACTUATOR_TYPE States:
Default:
Identifies the actuator design Read-only parameter, determined by actuator 0 = Electropneumatic 1 = Electric
2 = Electrohydraulic 3 = Other 0
Actuator version
ACTUATOR_VERSION (M) States:
Default:
Specifies the actuator version with/without spring return mechanism
0 = Single-acting with spring return mechanism 1 = Double-acting without spring return mechanism
0
Attachment
ATTACHMENT (M)
States:
Default:
Defines positioner attachment to control valves with linear actuators. For rotary actuators, only attachment according to VDI/VDE 3845 (NAMUR) is possible. For details, refer to sections 2.1 and 2.2.
0 = Integral – attachment with SAMSON Type 3277 Linear Actuator 1 = NAMUR – attachment acc. to IEC 60534-6 (NAMUR)
0
Binary input
IDENT_BINARY_INPUT (M) States:
Default:
Describes whether and how the binary switch option is evaluated
0 = Not evaluated 1 = Actively open 2 = Actively closed
0
Binary input, status
BINARY_INPUT (M) States:
Default:
Indicates state of the binary switch
0 = Deactivated 1 = Activated 254 = Not evaluated
0
Calibration, alarm message
SELF_CALIB_WARNING (M) States:
Default:
Indicates additional alarm messages of started calibration procedure
0 = Not determined 13 = Improper selection of rated travel or transmission 15 = Air leakage of pneumatic system (during initialization) 254 = Successful 255 = No valid data in application
0
Calibration, command
SELF_CALIB_CMD States:
Starts manufacturer-specific procedures in the field device
0 = No test, standard control operation 1 = Zero calibration 2 = Initialization 7 = Reset total valve travel 10 = Reset control loop error 255 = Cancel current action
50 EB 8382-1 EN
List of parameters
Calibration, status
SELF_CALIB_STATUS States:
Indicates manufacturer-specific status of calibration procedure started with SELF_CALIB_CMD
0 = Not determined 2 = Canceled 4 = Error in mechanics/pneumatics 11 = Timeout 17 = Initialization status: determining mechanical stops 19 = Initialization status: determining minimum transit times 20 = Initialization canceled by activating forced venting 30 = Zero point error 254 = Successful
Characteristic selection
CHARACT States:
Default:
Selects characteristic to assign the reference variable to the valve travel/angle range
0 = Linear 1 = Equal percentage 2 = Reverse equal percentage 3 = User-defined (will be supported in future firmware version) 4 = SAMSON butterfly valves: linear 5 = SAMSON butterfly valves: equal percentage 6 = VETEC rotary plug valves: linear 7 = VETEC rotary plug valves: equal percentage
0
Characteristic type
CHARACT_TYPE
Text field to describe the adjusted characteristic Length: 32 characters
Cold start
FACTORY_RESET States:
Default:
Resets the positioner to its default values
0 = No action 1 = Resets application to default values. All positioner data are reset to their default values. Positioner moves to fail-safe position and must be re-initialized. Only device identification parameters are retained. 2 = Resets device identification parameters to their default values. Application parameters are retained.
0
Controlled variable x
READBACK
Indicates current valve position with status Controlled variable x in % of travel/angle of rotation range
Correction value
OUT
Calculated by the function block from the set point in [mm] or [de­gree]. Value can be preset in Local Override mode
Date of installation
DEVICE_INSTALL_DATE
Indicates when the field device was installed
Date of last calibration
DEVICE_CALIB_DATE
Indicates when the field device was last calibrated
Date of last configuration
DEVICE_CONFIG_DATE
Indicates when the field device was last configured
EB 8382-1 EN 51
List of parameters
Date of last maintenance
VALVE_MAINT_DATE
Indicates when the last maintenance was performed on the field device
Dead band Xtot
DEAD_BAND Default:
Indicates dead band of the control characteristic between 0.1 and
10.0 % of the rated travel/nominal angle
0.5 %
Delay time
DELAY_TIME (M)
Range:
Default:
Specifies reset criterion for active control loop monitoring. If the en­tered delay time is exceeded and the system deviation is outside the limits of the entered tolerance band, a control loop error is issued.
0 to 240 s Determined during initialization from min. transit time; can be
adapted 10 s
Derivative-action coefficient KD
SERVO_RATE
Range: Default:
Specifies gain factor of derivative element. We recommend incre­menting the value in steps of 0.02. Incrementing the value causes an increased deceleration before the reference variable is reached.
0.0 to 1.00
0.12
Description
DESCRIPTOR
Text field to describe the application, saved in field device Length: 32 characters
Device status
CHECK_BACK Message type:
States:
Provides detailed, bitwise-encoded device information, which permits several simultaneous messages; see also section 9
A: Dynamic messages, automatically reset when read R: Static messages, retained as long as event exists in the field device
0 = No message 1 = Device status message active
Diagnostic extension
DIAGNOSIS_EXTENSION
Message type:
States:
Provides additional, detailed manufacturer-specific device informa­tion; bitwise-encoded, which allows for several simultaneous mes­sages; see also section 9
A: Dynamic messages, automatically reset when read R: Static messages, remain active while error persists in field unit
0: No message 1: Diagnostic message active
Diagnostics
DIAGNOSIS Message type:
States:
Provides detailed, bitwise-encoded device information, which permits several simultaneous messages; see also section 9
A: Dynamic messages, automatically reset when read R: Static messages, remain active while error persists in field unit
0 = No message 1 = Diagnostic message active
52 EB 8382-1 EN
List of parameters
Direction of action
INCREASE_CLOSE (M) States:
Default:
Determines the assignment of reference variable to travel/angle
0 = Increasing/increasing, valve opens when reference variable
increases (for rotary plug valves, the actuator stem retracts)
1 = Increasing/decreasing, valve closes when reference variable
increases (for rotary plug valves, the actuator stem extends)
0
End position when reference variable is above limit value
SETP_CUTOFF_INC
Default:
If the reference variable exceeds the entered limit, the valve moves to­wards its end position that corresponds to 100 % of the reference variable; hysteresis: 1 % Function is deactivated when the value is 125 %
1 % Caution! Since the actuator is fully pressurized or vented when this
function is active, the valve moves to its absolute end positions. Re­strictions specified by the "travel range" or "travel limit" functions do not apply. Deactivate the function if excessive positioning forces are created by fully pressurizing or venting the actuator.
End position when reference variable is below limit value
SETP_CUTOFF_DEC
Default:
If the reference variable exceeds the entered limit, the valve moves to­wards its end position that corresponds to 0 % of the reference vari­able; hysteresis: 1 % Function is deactivated when the value is –2.5 %
99 % Caution! Since the actuator is fully pressurized or vented when this
function is active, the valve moves to its absolute end positions. Restrictions specified by the "travel range" or "travel limit" functions do not apply. Deactivate the function if excessive positioning forces are created by fully pressurizing or venting the actuator.
Fail-safe action
FSAFE_TYPE States:
Default:
Defines response when communication failure or device start-up is detected
0 = Control to fail-safe value 1 = Control to/save last valid set point 2 = Move to fail-safe position determined by spring action
1
Fail-safe position
ACTUATOR_ACTION
States:
Indicates actuator's fail-safe position upon air/power supply failure or device start-up; read-only value; automatically detected during ini­tialization
0 = Not initialized 1 = Opening in direction of 100 % position 2 = Closing in direction of 0 % position 3 = None/saving (position is retained)
Fail-safe time
FSAFE_TIME Range: Default:
When DP-Watchdog detects a communication failure, fail-safe action is triggered after the fail-safe time has elapsed.
0 to 3600 s 10 s
EB 8382-1 EN 53
List of parameters
Fail-safe value, reference var.
FSAFE_VALUE Default:
Functions as replacement value for set point (reference variable w or w_cas) when communication failure was detected
0
Firmware version
SW_REVISION
Firmware version, communication/control
Hardware version
HW_REVISION
Hardware version, electronics/mechanics
Identification, forced venting
IDENT_FORCED_VENTING (M) States:
Indicates whether the optional forced venting function is installed Read-only parameter, automatically set by the device
0 = Not installed 1 = Installed
Identification, limit switches
IDENT_LIMIT_SWITCHES (M) States:
Default:
Indicates whether optional inductive limit switch function is installed; not detected automatically
0 = Not installed 1 = Installed
0
Initialization method
INIT_METHOD (M)
States:
Default:
Specifies Initialization method based on nominal or maximum range. For initialization in nominal range, only the manipulated variable range entered under rated travel/nominal angle is considered (e.g. globe valve with mechanical stop on one side). For initialization in maximum range, the max. possible manipulated variable range is used (e.g. three-way valve with mechanical stops on both sides).
0 = Initialization based on maximum range 1 = Initialization based on nominal range
0
Local operation enabled
LOCAL_OP_ENA States:
Default:
Unlocks local operation (zero/initialization button). Local operation is enabled when communication fails for longer than 30 s.
0 = Disabled 1 = Enabled
1
Manufacturer, actuator
ACTUATOR_MAN
Clearly identifies the manufacturer of the actuator Length: 16 characters
Manufacturer, positioner
DEVICE_MAN_ID
Clearly identifies the manufacturer of the field device Read-only parameter
Manufacturer, valve
VALVE_MAN
Clearly identifies the manufacturer of the valve Length: 16 characters
Message
DEVICE_MESSAGE
Text field to enter any desired text, saved in the field device Length: 32 characters
54 EB 8382-1 EN
List of parameters
Mounting position
MOUNTING_POSITION (M) (linear actuator)
States:
Default:
An arrow on the positioner's cover plate indicates how to attach the positioner to the actuator. For direct attachment, the arrow must point towards the actuator. For NAMUR attachment, the arrow must point away from the actuator.
0 = Arrow points away from actuator 1 = Arrow points towards actuator
1
Operating mode, current Operating mode, desired
MODE_BLK / TARGET_MODE
Positioner operating modes for firmware versions: K 1.20 and earlier: OS, AUTO K 1.30 and higher: OS; LO, MAN, AUTO
Operating modes of the positioner: Automatic (AUTO): In AUTO mode, the positioner follows the set
point defined by the SP (w) parameter, which is preset cyclically or acyclically, according to the scale and unit determined by PV_SCALE (reference variable range).
Manual (MAN): In MAN mode, the positioner also follows the set point defined by the SP (w) parameter, which is preset cyclically or acyclically, according to the scale and unit determined by PV_SCALE (reference variable range). The INCREASE_CLOSE (direction of ac­tion) parameter, however, is not processed; neither are the communi­cation monitoring parameters (FSAFE_TIME, _TYPE, _VALUE).
Local Override (LO): In LO mode, the positioner follows the set point defined by the OUT parameter (correction value), which is refreshed acyclically, according to the scale and unit (mm or degree) preset by OUT_SCALE (travel/angle of rotation range). With the characteristic deactivated, this value corresponds to the actual valve position in mm or degrees. The INCREASE_CLOSE parameter (direction of action), however, is not processed; neither are the communication monitoring parameters (FSAFE_TIME, _TYPE, _VALUE).
Out of Service (OS): In this mode, the valve is automatically moved to fail-safe position.
Remote Cascade (RCas): In RCas mode, the positioner follows the set point defined by the RCAS_IN (w_rcas) parameter, which is re­freshed cyclically, according to the scale and unit preset by PV_SCALE (reference variable range).
Operating mode during start-up (warm start)
The positioner's response to a warm start is determined by the FSAFE_TYPE parameter (fail-safe action). If FSAFE_TYPE is set to "control to fail-safe value", the positioner switches to automatic operating mode and controls to the value pre­set by FSAFE_VALUE. If FSAFE_TYPE is set to "control to last set point" or "fail-safe position determined by spring action", the positioner remains in fail-safe posi­tion. The positioner switches to automatic operating mode as soon as a valid set point SP is transmitted to the device.
If the status of the transmitted set point is "bad" or if the positioner has not been successfully initialized, the positioner remains in fail-safe position (Out of Service).
EB 8382-1 EN 55
List of parameters
Operating mode, current Operating mode, desired
MODE_BLK / TARGET_MODE (continued)
The action determined by the FSAFE_TYPE parameter (fail-safe ac­tion) is triggered by the following events: – Start-up of the positioner (warm start) – Elapsing of DP watchdog by interrupting the cyclic communica-
tion with a Class 1 master (not applicable when communication is properly terminated)
Elapsing of FSAFE_TIME (fail-safe time) in automatic or remote
cascade operating mode when the status of the reference vari­able valid in this operating mode, SP or RCAS_IN, is set to "Initi­ate fail-safe"
Receipt of a DP "Global Control" service for which the CLEAR bit
is set (not in K 1.30)
By setting the reference variables tatus, which is used in the current operating mode, to "bad", the actuator always moves to the fail-safe position determined by the spring action (version K 1.30 and higher).
Product number, positioner
DEVICE_PRODUCT_NUM (M)
Indicates the manufacturer's product number of the positioner
Proportional-action coefficient KP_Y1
SERVO_GAIN
Proportional-action coefficient for supply air: When writing, the value is written to KP_Y1 (supply air) and KP_Y2 (exhaust air).
Proportional-action coefficient KP_Y2
Range: Default:
Proportional-action coefficient for exhaust air: When writing, the value is written to KP_Y2 (exhaust air). KP_Y1 (sup­ply air) remains unchanged.
Between 0.01 to 10.0, we recommend incrementing the value in steps of 0.1. When increasing the value, the set point is reached faster.
0.01 to 10.0
1.2
Note!
The proportional-action coefficients KP_Y1 and KP_Y2 are deter­mined when the positioner is initialized for the first time. The initial­ization values listed in the table on page 57 may have to be adapted to the changed operating conditions to achieve optimum control be­havior.
Rated travel/nominal angle
RATED_TRAVEL Default:
Specifies rated travel [mm] or nominal angle [degree] of the valve Nominal operating range 5 to 255 mm or 0.0° to 120.0°
15 mm
Reference variable range
PV_SCALE Default:
Specifies scale and unit of reference variable w/w_cas (SP or RCAS_IN)
0 to 100 %
Reference variable w
SP
Specifies the set point with status. Reference variable in AUTO / MANUAL mode. See also "Reference variable range"
Reference variable w_rcas
RCAS_IN / RCAS_OUT
Specifies the set point with status. Reference variable in RCAS mode See also Reference variable range
56 EB 8382-1 EN
List of parameters
Security locking
SECURITY_LOCKING Default:
Memory position for a password to be used by the host, serves to check access rights (format: 16 bit unsigned integer)
0x2457
Serial no., actuator
ACTUATOR_SER_NUM
Indicates serial number of the actuator associated with the positioner Length: 16 characters
Serial no., positioner
DEVICE_SER_NUM
Indicates positioner's serial number. Clearly identifies the field unit together with the manufacturer ID and type number.
Serial no., valve
VALVE_SER_NUM
Indicates serial number of the valve associated with the positioner Length: 16 characters
Set point deviation e
SETP_DEVIATION
Indicates the system deviation in percent
Simulation
SIMULATE
Allows operators to specify a simulation value for the current READBACK position including status
Tag identification
TAG_DESC
Indicates tag number of the positioner Length: 32 characters
Text fields
TEXT_INPUT_1 to TEXT_INPUT_3 (M)
Text fields to enter any desired text Length: 32 characters
EB 8382-1 EN 57
List of parameters
Type of actuator
Rated travel/
nom. angle
Transit time
KD
KP_Y1 Supply
KP_Y2
Exhaust
Min Fail-safe action OPEN CLOSED
Rotary
actuator
> 0.7 s > 0.7 s
0.12
0.5 0.5
Closing > 0.7 s < 0.7 s 0.5 0.1
Closing < 0.7 s > 0.7 s 0.1 0.5
< 0.7 s < 0.7 s 0.1 0.1
Opening > 0.7 s < 0.7 s 0.1 0.5
Opening < 0.7 s > 0.7 s 0.5 0.1
Linear
actuator
60 mm
< 10 s 0.5 0.5
10 s 3.0 4.0
< 60 mm
< 10 s
> 0.7 s > 0.7 s 0.5 1.2
Stem extends > 0.7 s < 0.7 s 0.5 0.8
Stem extends < 0.7 s > 0.7 s 0.3 1.2
< 0.7 s < 0.7 s 0.3 0.8
Stem retracts > 0.7 s < 0.7 s 0.3 1.2
Stem retracts < 0.7 s > 0.7 s 0.5 0.8
10 s 3.0 4.0
Tolerance band
TOLERANCE_BAND (M) Range: Default:
Reset criterion for active control loop monitoring. Enter permissible de­viation for control loop monitoring. See also DELAY_TIME parameter.
0.1 to 10.0 % 5 %
Tolerated overshoot
TOL_OVERSHOOT (M)
Adjustment range: Default:
If the set point deviation e exceeds the tolerated overshoot, pulse adaptation re­duces the minimal pulses in operating direction that caused the overshooting. If the set point deviation e exceeds the dead band Xtot, but stays within the toler­ated overshooting range, pulse adaptation reduces the minimal pulses in both moving directions after two complete amplitudes with the overshooting range.
0.01 to 10.00 % of rated travel/opening angle
0.5 %
Total valve travel, absolute
TOTAL_VALVE_TRAVEL
Specifies absolute total valve travel, i.e. sum of nominal duty cycles (e.g. valve travels from fully open to fully closed position and back) Maximum value: 16,500,000
Total valve travel, limit
TOT_VALVE_TRAV_LIM Default:
Specifies limit for the total valve travel. Range: 0 to 16,500,000
1,000,000
Transducer state
TRANSDUCER_STATE (M) States:
Indicates current state of control
0 = See current operating mode 1 = Forced venting active 2 = Lower travel limit active 3 = Upper travel limit active 4 = End position at < active 5 = End position at > active
Transit time, desired CLOSED
TRAVEL_RATE_DEC Range:
Default:
Specifies the adjustable min. time in seconds that the valve needs to move through the manipulated variable range towards 0 % position.
0 to 75 s 0 s
Transit time, desired OPEN
TRAVEL_RATE_INC
Default:
Specifies the adjustable minimum time in seconds that the valve needs to move through the manipulated variable range towards 100 % position. Range: 0 to 75 s
0 s
Transit time, minimum CLOSED
ACT_STROKE_TIME_DEC
The minimum transit time to CLOSE the valve (towards 0 % position) specifies the actual time in seconds that the system (positioner, actua­tor, valve) needs to move through the rated travel/angle and close the valve. This parameter is measured during start-up.
Read-only value
Transit time, minimum OPEN
ACT_STROKE_TIME_INC
The minimum transit time to OPEN the valve (towards 100 % posi­tion) specifies the actual time in seconds that the system (positioner, actuator, valve) needs to move through the rated travel/angle and open the valve. This parameter is measured during start-up.
Read-only value
58 EB 8382-1 EN
List of parameters
Transmission code
TRANSM_CODE (M) States:
States:
Default:
For linear actuators with integrally attached positioner: determine geometrical dimensions of the travel pick-off with integral attachment
1 = D1, lever length 64 mm 2 = D2, lever length 106 mm
For rotary actuators:
Max. opening angle of selected segment of the installed cam disk 3 = S90, 90° segment 4 = S120, 120° segment
1
Transmission length
TRANSM_LENGTH (M)
Range: Default:
Only for linear actuators with positioner attached acc. to NAMUR
Lever length, distance between travel pick-off and fulcrum of pick-off lever
0.0 to 1023.0 mm
42.0 mm
Transmission pin position
TRANSM_PIN_POS (M) States: Default:
Only for linear actuators with positioner attached acc. to NAMUR
Position of pin on positioner lever, see marking on positioner lever 0 = A 1 = B 0
Travel/angle limit, lower
TRAVEL_LIMIT_LOW Default:
Allows you to enter the lower limit of the valve travel/angle Range: –20.0 to 99.9 %. The characteristic is not adapted.
0.0 %
Travel/angle limit, upper
TRAVEL_LIMIT_UP Default:
Allows you to enter the upper limit of the valve travel/angle Range: 0.0 to 120.0 %. The characteristic is not adapted.
100.0 %
Travel/angle of rotation range
OUT_SCALE
Range: Default:
Specifies the adjusted upper and lower values of the actual operating range in mm or degrees. For non-linear characteristics, the charac­teristic is adapted to the reduced travel.
If the positioner is initialized based on the maximum range, the travel/angle range is always relative to the entered rated travel/angle. The operating range must not be smaller than ¼ of the rated travel/angle.
0.0 to 255.9 mm / 0.0° to 120.0° Lower limit: 0 Upper limit: 15 mm/90°
Travel/angle of rotation, max. permissible
MAX_HUB (M)
Specifies the maximum permissible travel/opening angle determined during initialization in percent of the rated travel/opening angle
Note! If initialization was successful with regard to the nominal range, the maximum permissible travel/angle is not determined.
Type number, positioner
DEVICE_ID
Specifies the type number of the field unit
Type of protection
DEVICE_CERTIFICATION
Specifies the field unit's type of protection
Valve position feedback, discrete
POS_D States:
Indicates the discrete valve position feedback with status
0 = Not initialized 1 = Closed (x < 0.5 %) 2 = Open (x > 99.5 %) 3 = Intermediate
EB 8382-1 EN 59
List of parameters
Valve type
VALVE_TYPE States:
Default:
Specifies the valve design
0 = Control valve with linear motion of the connecting element 1 = Control valve with rotary or part-turn motion of the element
0
Warm start
DEVICE_RESET_CMD States: Default:
Resets the field device (warm start)
0 = No action 1 = Reset the device 0
Write protection
WRITE_PROTECT_SWITCH (M)
States:
Indicates state of the write-protection switch in the positioner When write protection is activated, device data can only be read, but not overwritten. Write protection can only be activated on the switch in the positioner.
0 = Write enabled 1 = Write protected
60 EB 8382-1 EN
List of parameters
9 Messages and diagnostics
The Type 3785 PROFIBUS-PA Positioner provides the best opportunities for diagnostics dur­ing the initialization phase. The positioner automatically conducts detailed tests to check the mounting position and valve response as well as to evaluate them based on the entered or preset parameters. When running routine tests or when unclear diagnostic/error messages occur during opera­tion, we recommend to re-initialize the positioner to better assess the control system.
9.1 Diagnostic messages
Hardware error in electronics
This message is issued when the cyclic check detects a defect in the electronics module. Requires repair.
Hardware error in mechanics
This message is issued when the cyclic check detects a defect in the mechanics module. Requires repair.
Error in data memory
This message is issued when the cyclic check detects that a storage cell was changed without verification. The static message remains active while the error persists in the field unit.
Measurement error
This message indicates that the internal analog/digital converter does not work properly within its time frame or the measured values are outside the physical measuring range limits of the analog/digital converter. Repair is required if resetting the positioner fails after performing a warm start. The static message remains active while the error persists in the field unit.
Device not initialized (no auto-initialization performed)
This message indicates that the device has not been initialized yet or a cold start was per­formed. The message is automatically reset when initialization has been competed successfully.
Auto-initialization error
This message indicates that initialization could not be completed successfully. Detailed error messages will be issued (see section 9.4). The message is automatically reset when initializa­tion has been competed successfully.
EB 8382-1 EN 61
Messages and diagnostics
Zero point error (end position)
This message indicates any change that exceeds the value determined during initialization or zero adjustment by more than ±5 %. Possible sources of error: – Worn-out valve seat or plug – Foreign particles between seat and plug
The message is automatically reset when zero adjustment has been competed successfully.
Incorrect configuration
This message indicates that incorrect values have been entered. When receiving an incorrect value, the positioner indicates that the received value is outside the permissible range. The previous value remains valid. The message is reset by confirmation.
Restart (warm start) completed
This message indicates that the positioner was reset by performing a warm start. The reset is triggered by a restart after an electrical power failure or by the DEVICE_RESET_CMD = 1 command. The message is automatically reset when it is read.
New start (cold start) completed
This message indicates that the positioner was reset by performing a cold start and that it is started up again with the default control values. The reset is triggered by the FACTORY_RESET = 2 command. The positioner needs to be re-initialized. The message is automatically reset when it is read.
Maintenance required
This message indicates that the current total valve travel value exceeds the entered or preset limit. If the limit is adjusted slightly below the value determined for a reference valve, the positioner automatically signals that the valve needs to be serviced so that a possible failure is prevented. The message is reset by the SELF_CALIB_CMD = 7 command (reset total valve travel).
Invalid characteristic
This message indicates that: – An error occurred while the characteristic was transmitted to the positioner, or – The input values for a user-defined characteristic were not entered in ascending order, or – The gradient of a user-defined characteristic exceeds 16.
If an Invalid characteristic error occurs, the positioner automatically switches from a user-de­fined characteristic to a linear characteristic after receiving the values. The message is automatically reset when a correct characteristic has been received.
62 EB 8382-1 EN
Messages and diagnostics
Further information available
This message indicates that extended diagnostic messages have been generated.
9.2 Extended diagnostic messages
Binary input active
This message indicates that the condition for activating the binary input has been fulfilled.
Invalid start values for min. pulses in range 1
This message indicates that the pulse search for the 0 to 20 % range of the rated travel/an­gle by adapting the pulse-pause ration has not been completed yet. The message is automatically reset after supply and exhaust air pulses have successfully been adapted.
Invalid start values for min. pulses in range 2
This message indicates that the pulse search for the 20 to 80 % range of the rated travel/an­gle by adapting the pulse-pause ration has not been completed yet. The message is automatically reset after supply and exhaust air pulses have successfully been adapted.
Invalid start values for min. pulses in range 3
This message indicates that the pulse search for the 80 to 100 % range of the rated travel/angle by adapting the pulse-pause ration has not been completed yet. The message is automatically reset after supply and exhaust air pulses have successfully been adapted.
Error in optional forced venting function
This message indicates that either the optional module is not screwed on tightly or that the coding jumper is not set when the optional forced venting function is missing.
EB 8382-1 EN 63
Messages and diagnostics
9.3 CHECKBACK messages
Fail-safe position (mode = Out of Service)
This message indicates that fail-safe position was triggered by the positioner. This can be caused by selecting Out of Service mode, by activating the optional forced venting function or by a communication failure. The positioner switches to Out of Service mode.
Request for Local Operation mode
This message indicates that local operation was requested, but not enabled (LOCAL_OP_ENA = 0). The message is automatically reset when it is read.
Positioner in Local Operation mode Forced venting active
This message indicates that forced venting was triggered, i.e. the signal at terminals +81 and –82 is smaller than 3 V. The valve is moved to fail-safe position regardless of the control loop. The message is automatically reset when a 6 to 24 V DC signal is applied to terminals +81 and –82.
Static data changed
This message indicates that positioner data have been changed, which allows operators to detect (unintentional/unauthorized) changes of the originally adjusted values. The message is automatically reset when it is read.
Simulation mode (values not derived from the process)
This message indicates that the positioner is in simulation mode. In this case, the controlled variable x is preset.
Error (refer to section on diagnostic messages for possible causes)
This message indicates that the positioner is defective. Diagnostic messages indicate specific causes.
64
Messages and diagnostics
Control loop error
This message indicates that the positioner fails to control within the adjusted tolerance band for error monitoring within the specified delay time.
Possible sources of error: – Oscillation caused by the actuator working too fast (small travel volume)
Remedy: reduce supply pressure (see section 3.1.2) or install signal pressure restriction. – Supply air failure/insufficient supply air – Clogged filter – Oiled-up solenoid valves – Ruptured actuator diaphragm – Broken actuator springs – Considerable increase in friction on the control valve – Blocked control valve
The message is indicated by bit 7 and bit 13 of the Checkback parameter (see table on pages 38/39). The state of bit 7 is automatically reset; bit 13 is reset by the SELF_CALIB_CMD = 10 command (reset Control Loop Error).
Positioner inactive (mode = Out of Service)
This messages indicates that the positioner is in Out of Service mode.
Positioner in self-test mode (mode = Out of Service)
This message indicates that the positioner is going through the initialization process or elec­tric zero calibration.
Limit for total valve travel exceeded
This message indicates that the current total valve travel value exceeds the entered/preset limit. If the limit is adjusted slightly below the value determined for a reference valve, the positioner automatically signals that the valve needs to be serviced so that a possible failure is prevented. The message is reset by the SELF_CALIB_CMD = 7 command (reset total valve travel).
EB 8382-1 EN 65
Messages and diagnostics
9.4 Messages during initialization
Not defined
This message indicates that the positioner has not yet been initialized or that a cold start was performed. The message is reset by confirmation.
Canceled
This message indicates that the initialization routine was aborted by the user. The message is reset by confirmation. If the positioner had already been initialized successfully and no cold start has been trig­gered, the positioner returns to control operation.
Error in mechanics/pneumatics section
This message indicates that the initialization routine detects no or a constant change of the value measured for the controlled variable travel/angle. Initialization is canceled.
Possible sources of error: – Insufficient/unstable supply pressure – Insufficient air capacity – Improper mechanical attachment – Pick-off lever improperly mounted – With NAMUR attachment: lever incorrectly secured to the shaft of the adapter housing – Connecting cable between logic unit and PCB for travel pick-off removed
Timeout
This message indicates that the valve could not be moved to its end position within max. 240 seconds. Initialization is canceled.
Possible sources of error: – Large difference between static and sliding friction on the control valve (oscillation) triggers
separate message – Unstable supply pressure – Insufficient air capacity
66 EB 8382-1 EN
Messages and diagnostics
Incorrect selection of rated travel or transmission
This message indicates that the maximum travel determined, which is issued in percent of the rated travel/angle, is smaller than the selected rated travel/angle. Warning! Initialization is not canceled.
Possible sources of error: – Improper mechanical attachment – Improper transmission entered – With NAMUR attachment: wrong pin position selected – Valve blocked – Insufficient supply pressure. Adjust the supply pressure to be at least 0.4 bar above the
upper spring range value (see section 3.1.2).
Leakage in pneumatic system
When initially determining the minimum control pulse, the actuator must stall for a few sec­onds. This period of time is used to leak-test the pneumatic system. If the control valve moves from its rest position by more than 9.3 % within seven seconds, the associated message is generated. Additionally, an initialization warning is issued. Warning! initialization is not canceled.
Possible sources of error: – Leakage in actuator – Leakage in signal pressure connection
Initialization state: determining mechanical stops
When determining the mechanical stops, the initialization routine detects the spring action and zero point by completely pressurizing and venting the actuator. In addition, the routine checks whether the positioner can move through 100 % of its rated travel/angle.
Initialization state: determining the minimum transit times
When determining the transit time, the time required by the valve to move through its rated travel/angle from 0 % to 100 % and back is measured.
Initialization canceled by activating the forced venting function
Initialization is canceled if the optional forced venting function is activated. When the op­tional forced venting function is included, make sure a voltage between 6 and 24 V DC is applied to terminals +81 and –82.
EB 8382-1 EN 67
Messages and diagnostics
Zero point error
This message indicates that the zero point determined is outside the permissible tolerance of max. ±5 % around the absolute internal value for measurement. Initialization is canceled. To remove the error, adjust mechanical zero (see section 4.4.1). After that, make sure that the yellow position pin of the travel pick-off is roughly aligned with the white line marking zero on the cover plate.
Proportional band excessively restricted
This message indicates that even the smallest permissible pulses cause excessive changes in travel. Initialization is canceled.
Possible sources of error: – Excessive supply pressure – Missing signal pressure restriction for small-volume actuators – Error in mechanics section, particularly with NAMUR attachment (acc. to IEC 60534-6) – Bypass not opened far enough with booster valve mounted on large-volume actuator
Successful
This message indicates that initialization was completed without any errors.
68 EB 8382-1 EN
Messages and diagnostics
EB 8382-1 EN 69
Dimensional drawing
39
35
14
198
78.5
40
86
30.5
164
150
27
14
28
56 58
N1=113
N2=200
39
50
78.5
45
50
82
150
164
27
75
56
50
86
46
28.5
28.5
Output 1 (A1)
Output 2 (A2)
Supply (Z)
Output (38)
Supply (9)
M20 x1.5
G ¼ or ¼ NPT pneumatic connections
Direct attachment
Reversing amplifier
(optional)
Attachment using intermediate piece for rotary actuators Fulcrum of
actuator shaft
IEC 60534-6 attachm.with adapter housing
Pneumatic connection, reversing amplifier
(old PG 13.5)
70 EB 8382-1 EN
EB 8382-1 EN 71
72 EB 8382-1 EN
EB 8382-1 EN 73
74 EB 8382-1 EN
EB 8382-1 EN 75
76 EB 8382-1 EN
EB 8382-1 EN 77
78 EB 8382-1 EN
EB 8382-1 EN 79
80 EB 8382-1 EN
EB 8382-1 EN 81
82 EB 8382-1 EN
EB 8382-1 EN 83
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 8382-1 EN
S/Z 2017-07 · (version 3785-xxx0...)
Loading...