Samson 373 Series, 3730-2, 3730-3, 3731-3, 3730-4 Operating Instructions Manual

...
Page 1
Series 373x Positioners
EXPERT+Valve Diagnostics
Operating Instructions
EB 8388 EN
Firmware version 1.4x Edition November 2006
Fig. 1 · Valve diagnostics with SAMSON TROVIS-VIEW Operator Interface, e.g. for Type 3730-3 Positioner
Page 2
Contents Page
1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Diagnostic tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Activating EXPERT
+
. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Actuator and valve specification data . . . . . . . . . . . . . . . . . . 5
1.5 Start the reference test . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 SUb initialization mode, double-acting actuator and booster . . . . . . . 6
1.7 Activation, analysis and presentation of diagnostic data . . . . . . . . . 7
1.7.1 Printing the diagnostic/ESD log . . . . . . . . . . . . . . . . . . . . . 8
2 Statistical information AUTO . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Data logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Travel histogram . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Setpoint deviation histogram. . . . . . . . . . . . . . . . . . . . . . 12
2.4 Cycle counter histogram . . . . . . . . . . . . . . . . . . . . . . . . 13
2.5 Drive signal diagram . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.1 Steady-state drive signal. . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.2 Hysteresis test (d5) . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.6 End position trend. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 Tests MAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.1 Drive signal diagram steady-state (d1) . . . . . . . . . . . . . . . . . 22
3.2 Drive signal diagram hysteresis (d2) . . . . . . . . . . . . . . . . . . 23
3.3 Static characteristic (d3) . . . . . . . . . . . . . . . . . . . . . . . . 25
3.4 Step response (d4) . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4 Status and diagnostic alarms . . . . . . . . . . . . . . . . . . . . . 28
4.1 Standard EXPERT diagnostic alarms . . . . . . . . . . . . . . . . . . 28
4.2 Extended EXPERT
+
diagnostic alarms . . . . . . . . . . . . . . . . . . 28
4.3 Logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.4 Classification of the status alarms . . . . . . . . . . . . . . . . . . . 29
4.5 Condensed state . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.6 Status modification . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 Resetting diagnostic parameters. . . . . . . . . . . . . . . . . . . . 31
6 Diagnostic parameters saved in non-volatile memory . . . . . . . . . 34
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8 EXPERT
+
without TROVIS-VIEW . . . . . . . . . . . . . . . . . . . . 38
2 EB 8388 EN
Contents
Page 3
1 Description
1.1 General
These instructions EB 8388 EN supplement the standard mounting and operating in
-
structions of the positioners:
Type Standard EB
3730-2 EB 8384-2 EN
3730-3 EB 8384-3 EN
3730-4 EB 8384-4 EN
3730-5 EB 8384-5 EN
3731-3 EB 8387-3 EN
EXPERT+is an optional diagnostic firmware integrated in the positioner which allows the predictive, status-oriented maintenance of pneumatic control valves. Refer to section
1.3 on how to activate this option.
EXPERT
+
upgrades the standard EXPERT di­agnostics firmware incorporated in the positioner. The upgraded version provides extended functions to pinpoint valve param­eters that have worsened, allowing the user to plan predictive maintenance and service work before malfunctions can affect the pro
-
cess, causing unscheduled plant shutdowns.
EXPERT
+
records the valve faults in auto
­matic mode while the process is running and issues alarms on the required mainte
­nance work. In addition, numerous tests can be performed in manual mode to pinpoint emerging faults. Owing to the numerous diagnostic tests, EXPERT
+
is able to generate classified status
alarms on the state of the control valve.
The EXPERT
+
diagnostics are completely in
­tegrated in the positioner. Data required for diagnostics are compiled automatically and the test data are analyzed in automatic or manual mode in the positioner itself. The re
-
sulting data are used to issue classified sta
­tus alarms.
The diagnostics data, results and status alarms are available over the DD (Device Description). All the necessary reference graphs are automatically plotted after the positioner has been initialized and are available when required.
After performing the basic settings at the positioner using the rotary pushbutton, the TROVIS-VIEW3 or DTM software allow the parameters to be viewed and set conveniently.
Type Integration
3730-2 TROVIS-VIEW3
373x-3 TROVIS-VIEW3, DD, DTM
3730-4 TROVIS-VIEW3, DD, DTM
3730-5 TROVIS-VIEW3, DD
The following sections contain a description on how to operate the diagnostics over the TROVIS-VIEW3 software.
Note!
All the parameter settings that are changed over the operator interface must also be downloaded onto the positioner to allow them to become effective.
EB 8388 EN 3
Description
Page 4
Note!
The optional integrated solenoid valve is implemented by a forced venting function in Types 3731-x Positioners.
1.2 Diagnostic tests
There are two main groups of diagnostic tests available.
Statistical information AUTO
These tests are performed while the process is running (automatic mode) without disrupt
­ing the process. Activated tests are automatically performed when they are triggered by their start condi­tion (e.g. data logger and drive signal dia­gram hysteresis). Other tests are already performed in the background without being activated (e.g. histograms, cycle counter, drive signal steady-state and end position trending).
Tests MAN
These tests should not be performed while the process is running (i.e. in manual mode instead) as the positioner cannot follow the reference variable at the same time. The valve is moved to a certain position de
­fined by the test settings and the valve may move through its full range.
1.3 Activating EXPERT
+
The extended EXPERT
+
diagnostics can be activated later at the positioner when EXPERT
+
is not already activated on delivery
of the positioner.
The required activation code can be ordered (order number 1400-9318). On ordering this option, specify the serial number of the positioner (see nameplate or in the soft
-
ware).
To activate EXPERT
+
, proceed as follows:
Enable configuration at the positioner:
Turn
Code
3
, press ,
turn
ON
, press .
After enabling configuration:
Turn
Code
48
, press
Code
48
blinks.
Turn to select
d
, press ,
turn to select
d8, press .
d8
blinks
Turn and set the activation code XXXX.
Press to confirm the entered code.
4 EB 8388 EN
Description
Page 5
After the activation has been successfully completed,
YES
appears on the display.
Note!
On entering the wrong activation code, the display returns to Code 0. The activation of EXPERT
+
has been unsuccessful. After an incorrect activation code has been entered three times, Err appears on the display after selecting Code 48 and d8. An activation code can only be entered again after the positioner has been reset to its default settings (Code 36).
1.4 Actuator and valve
specification data
To correctly analyze the diagnostic data, several actuator and valve specifications need to be entered for the EXPERT
+
diagnos
­tics. Enter the required data in the
Identification
folder (>
Positioner > Actuator
) as well as
(>
Positioner > Valve
). Download the data to the positioner. The
Model
and
Booster
parameters in the
Actuator
folder and
Stuffing box
parameter
in the
Valve
folder need to be entered.
The default settings of these parameters are:
4
Model
> Single-acting
4
Booster
> Not present
4
Stuffing box
> Self-adjustable
These parameters do not need to be changed if the control valve also has these default settings.
1.5 Start the reference test
After EXPERT+has been activated properly, the reference graphs for future diagnostic purposes need to be plotted to allow the di
-
agnostics to function in their full scope.
The reference graphs are plotted automati
­cally after the positioner has been initialized when the EXPERT
+
has been activated (e.g. already on delivery). On activating EXPERT
+
at later time, the ref­erence graphs are plotted after the positioner is re-initialized. If reference graph plotting is to be started sep­arately in an initialized positioner or if graphs are to be replotted, proceed as follows:
Set the positioner to manual mode:
Turn
Code
0
, press ,
Code
0
blinks.
Turn
MAN
, press , the positioner
moves to manual mode.
Manual operating mode
You can activate the reference test either by selecting the
Diagnosis
folder (>
Start refer
-
EB 8388 EN 5
Description
Page 6
ence test
) and right-click the parameter to
select
Execute
, or, alternatively, start the ref
-
erence test at the positioner itself by select
-
ing Code
48
as follows:
Enable configuration at the positioner:
Turn
Code
3
,
turn
ON
, press .
After enabling configuration:
Turn
Code
48
, press
Code
48
blinks.
Turn until
d
appears, press ,
turn to select
d7, press .
d7
blinks.
Turn
ON
,
press to start the reference test.
Caution!
The control valve moves through its travel range during the reference test.
The tests
d1
(drive signal diagram
steady-state) and
d2
(drive signal diagram
hysteresis) are performed during the diag
-
nostic reference test. During the reference test,
tESt
and
d1
or
d2
appear in alternating sequence on the positioner display. The measured data are used as reference data and any existing reference graphs are overwritten. If the reference graphs could not be plotted correctly or are incomplete, Code 81 is is
­sued and saved in a non-volatile memory. The positioner can function properly after it has been initialized successfully without the reference data.
1.6 SUb initialization mode,
double-acting actuator and booster
The following points need to be observed when the positioner is initialized in
SUb
mode or when a double-acting actuator and/or booster is used:
Positioner initialization in SUb mode:
4
Analysis in automatic or manual mode is deactivated.
4
All tests for both statistical information AUTO and tests MAN of drive signal di
­agrams steady-state and hysteresis are inactive.
4
The reference test is inactive.
4
The automatic test to start all tests MAN is inactive.
Double-acting actuator with reversing amplifier:
4
All tests for both statistical information AUTO and tests MAN of drive signal diagrams steady-state and hysteresis are inactive.
4
The reference test is inactive.
6 EB 8388 EN
Description
Page 7
Booster:
4
The analysis of the tests for both statisti
­cal information AUTO and tests MAN of drive signal diagrams is inactive.
1.7 Activation, analysis and presentation of diagnostic data
All diagnostic tests which do not compile data automatically in the background (data logger, drive signal diagram hysteresis) must be activated to start them. To start these tests, select the corresponding test order (>
Start data loggerorStart test
)
and right-click the parameter to select
Exe-
cute
to activate the test.
Note!
The tests in statistical information AUTO in automatic mode can only be activated when the positioner is in automatic operating mode.
To activate the tests MAN in manual mode, the positioner must first be set to manual mode over Code 0.
Canceling diagnostic tests
There are two ways to cancel an active test:
4
On the TROVIS-VIEW operator interface, select the corresponding folder (>
Stop
test
) to cancel the test. The positioner
then moves to the previously set operat
-
ing mode and to the travel value previ
­ously set (manual mode) or returns to the reference variable (automatic mode).
4
Press once to cancel the tests MAN
d1
(drive signal diagram steady-state)
d2
(drive signal diagram hysteresis)
d3
(static characteristic)
d4
(step response), and the test in statistical information AUTO
d5
(drive signal diagram hysteresis) as well as the reference test over Code
48
.
On canceling a test (d1 to d4), the positioner moves to the fail-safe position. The positioner only goes into automatic mode on canceling test
d5
. The reference graphs must be plotted before the tests for drive signal diagrams steady-state and hysteresis in manual mode can be analyzed.
Note!
The analysis of raw data in automatic mode is started after the positioner has been in controlled operation for over one hour (after initialization). This does not apply to the end position trend test and the dynamic stress factor in the cycle counter histogram as their analysis starts directly after controlled operation begins.
Alarms generated from the tests MAN are marked
TEST
. If the electrical auxiliary power is too low, the test being performed is ended and the positioner moves to the fail-safe position. Upon failure of the auxiliary power, tests in tests MAN and statistical information AUTO must be restarted due reasons of safety.
EB 8388 EN 7
Description
Page 8
However, the test in statistical information AUTO drive signal diagram hysteresis re
­mains activated. In the event that the solenoid valve (Type 3730-x) is triggered or the forced venting function (Type 3731-x) is activated, active tests are stopped and the positioner moves to the fail-safe position.
However, the test in statistical information AUTO drive signal diagram hysteresis re
­mains activated. In the event that the solenoid valve (Type 3730-x) is triggered or the forced venting function (Type 3731-x) is activated, active tests are stopped and the positioner moves to the fail-safe position.
1.7.1 Printing the diagnostic/ESD
log
The Print command allows you to print out a diagnostic log of individual tests or the en­tire diagnosis.
The diagnostic log includes a title page and a list of all the data points including all their values and properties.
The title page contains all key information for clear identification of the printed log (de
-
vice type, file name, time and date of cre
­ation, time and date of the last change and TROVIS-VIEW version).
Select Print in the File menu to add further information.
1. In the File menu, select Print Options to
choose the scope of the diagnostic log. After installing/updating the TROVIS-VIEW software, customer data (Customer data in the Edit menu) and
summary (table of contents) are listed in the diagnostic log by default.
Check the check boxes for the Comments and Graphics options to add these op
-
tions to the diagnostic log.
2. Right-click the [Diagnosis] folder or the required subfolder and select Print from the context-sensitive menu to print the di­agnostic log. The printout contains the contents of the folder and its subfolders.
8 EB 8388 EN
Description
Page 9
2 Statistical information AUTO
The signals x, w and y need to be analyzed on a more precise basis to obtain advanced diagnostic information also over the valve, actuator and pneumatic air supply. The positioner compiles raw data for this pur
­pose. The signals are plotted, stored and analyzed while the process is running. In addition, an additional underlayed hysteresis test detects any changes in friction. The diagnostic tests do not have any affect on the positioner’s control performance.
2.1 Data logger
The data logger allows the reference vari­able w, controlled variable x in relation to the working range, drive signal y and setpoint deviation e to be plotted over time. The measured data are saved in an FIFO memory with a capacity to save 100 data points in the positioner. In addition to the permanent plotting of
data, the plotting can be automatically trig
­gered when a start condition is fulfilled. The travel condition (setpoint) or the optional in
­tegrated solenoid valve (optional integrated forced venting) can be used to trigger the data logger. The data logger is completely integrated into the positioner. The software is only necessary for activation and to set the parameters. In addition, the measured data can be viewed as a graph or in a list by selecting
Upload from Device
in the
Device
menu or
by clicking on the device toolbar.
Note! Upon disconnection of the auxiliary power or upon changing the operating mode, the test is inactive and must be reacti­vated.
Data logging
Select
Data logger
folder (>
Selection
) and
select
PermanentorTrigger
and set the
Scan
rate
parameter. Right-click the
Start data
EB 8388 EN 9
Statistical information AUTO
Fig. 2 · Statistical information AUTO
Page 10
logger
parameter and select
Execute
to start
data logging.
Permanent data logging
The variables w, x, y, and e are logged ac
­cording to the adjusted scan rate and saved in the FIFO memory which always stores the last 100 measured data points of each vari
-
able.
Triggered data logging
On selecting
Trigger
in the
Selection
param
­eter, the data logger records the measured data permanently in the background. A trig
­gering event leads to the last 100 measured data points being stored together with the pretrigger time and leads to the data log­ging of the triggering condition. The following parameters can be changed for this function:
4
Trigger status: Triggered by the travel condition (setpoint) and/or solenoid valve condi
-
tion (forced venting)
4
Start value: Limit indicating from which travel condi
­tion (setpoint) the data logger should be triggered
4
Logging limit: Indicating whether data logging should start when the travel condition (setpoint) exceeds or falls below the start value.
Travel condition (setpoint)
Note!
The valve position is used as the travel condition in positioners in ESD version.
Select
Trigger status
parameter and select
Start trigger via travel condition (setpoint)
.
Activate data logging by selecting
Start data
10 EB 8388 EN
Statistical information AUTO
Fig. 3 · Data logger
Page 11
logger
parameter and select
Execute
. The triggering event starts data logging when the start value exceeds or falls below an entered value. Enter the required value at which data log
­ging should be triggered in relation to the setpoint in the
Start value
parameter. Select whether data logging should start when the entered value exceeds or falls be
-
low the start value in the
Logging limit
pa
­rameter. After being triggered, the variables w, x, y and e are logged at the adjusted scan rate and saved in the FIFO memory. Additionally, there is a pretrigger time avail
­able to allow the variables to be stored that were logged before the triggered event. Enter the required pretrigger time by right-clicking the parameter and selecting
Modify
. However, the pretrigger time en­tered may not be higher than the maximum pretrigger time determined by the positioner. This maximum pretrigger time is shown in the
Max. pretrigger time
parame­ter. The data logging finishes automatically as soon as the maximum memory capacity of 100 measured data points for each vari
­able including the pretrigger time is reached.
Solenoid valve condition (forced venting)
Select
Trigger status
parameter and select
Start via solenoid valve condition (forced venting)
. Activate data logging by selecting
Start data logger
parameter and select
Exe
-
cute
to start data logging as soon as the in
­tegrated solenoid valve is triggered or the forced venting function is activated. Similar to the travel condition (setpoint), the variables w, x, e and y are logged at the adjusted scan rate and saved in the FIFO
memory on triggering. Additionally, there is a pretrigger time avail
­able to allow the variables to be stored that were logged before the triggered event. Enter the required pretrigger time by right-clicking the parameter and selecting
Modify
. However, the pretrigger time en
­tered may not be higher than the maximum pretrigger time determined by the positioner. The data logging finishes auto
­matically as soon as the maximum memory capacity of 100 measured data points for each variable including the pretrigger time is reached.
Travel (setpoint) or solenoid valve condition (forced venting)
Select
Trigger status
parameter and select
Start via travel (setpoint)/solenoid valve condition (forced venting)
. Activate data
logging by selecting
Start data logger
pa-
rameter and select
Execute
. The triggering event starts data logging when the valve travel (setpoint)/solenoid valve conditions (forced venting) are met. The measured data are plotted over time in graphs. In addition, the compiled measured data are stored in the
Measured values
folder (see Fig. 3).
2.2 Travel histogram
The valve travel histogram is a statistical analysis of the plotted valve travel. The histogram provides information, for ex
­ample, about where the valve mainly works during its service life and whether it shows a recent trend concerning changes in its work
­ing range. The valve travel is recorded and assigned to valve travel classes. The distribution showing
EB 8388 EN 11
Statistical information AUTO
Page 12
how often the valve travel remains within a class is shown in per cent. The result is pre
-
sented as a bar graph.
The
Travel histogram
folder contains
long-term data, i.e. measured data are up
-
dated cyclically (scan rate 1 s) over the en
­tire positioner service life and stored every 24 hours in the positioner’s non-volatile memory for long-term monitoring. The
Number of measurement values
param
­eter shows the total amount of classified measured data points previously recorded. The
Average value x long
parameter con
­tains the class in which the travel remained on average the most. In order to be able to recognize any short-term changes in valve travel properly, the last 100 measured data points are stored at a scan rate (default: 1 s) in a non-volatile memory. The scan rate can be changed in the
Scan rate short time
param-
eter. On changing the scan rate, old data in the short-term histogram are deleted.
The
Average values x short
parameter con
­tains the average class assignment for the last 100 measured data points stored in the non-volatile memory. Data can be reset in the
Status messages
folder.
2.3 Setpoint deviation histogram
The setpoint deviation histogram contains a statistical analysis of any setpoint deviations recorded. This provides a summary of how often and to which level a setpoint deviation has occurred during the positioner service life and whether it shows a recent trend con­cerning the setpoint deviation. The setpoint deviation is recorded and as­signed to predetermined level classes. The percentages showing how often the setpoint deviation remains within a class is presented
12 EB 8388 EN
Statistical information AUTO
Fig. 4 · Travel histogram
Page 13
as a bar graph. Ideally, the setpoint devia
-
tion should be as small as possible.
Similar to the valve travel histogram, the
Setpoint deviation histogram
folder contains
long-term data, i.e. measured data are up
-
dated cyclically (scan rate 1 s) over the en
-
tire positioner service life and stored every 24 hours in the positioner’s non-volatile memory for long-term monitoring. Additional information determined from this long-term histogram are shown in Fig. 5. The minimum and maximum setpoint devia
­tions are also indicated. In order to obtain a summary of recent setpoint deviations, the last 100 setpoint de­viations are logged at an adjustable scan rate (default: 1 s) and saved in an FIFO memory. The scan rate can be changed in the
Scan
rate short time
parameter. On changing the scan rate, old data in the short-term histo­gram are deleted.
The
Average values e short
parameter indi
-
cates the class in which the last 100 mea
-
sured setpoint deviations were stored on av
­erage in the FIFO memory. Data can be reset in the
Status messages
folder.
2.4 Cycle counter histogram
The histogram shows the span of cycles the valve has moved through and the frequency of the cycles. A valve cycle starts at the point where the valve stroke changes direction until the point where it changes direction again. The valve stroke between these two changes in direc­tion is the cycle span. The cycle counter histogram provides a sta­tistical analysis of the cycles. As a result, the cycle counter also provides information on the dynamic stress of a bellows seal or packing.
EB 8388 EN 13
Statistical information AUTO
Fig. 5 · Setpoint deviation histogram
Page 14
The
Dynamic stress factor
parameter is spec
­ified as a percentage reflecting the stress of the packing. An alarm is issued if the dy
­namic stress factor exceeds 90 %. The
Dynamic stress factor
is determined from the cycle span and how often the cycle spans occurred (frequency) depending on which packing has been selected (see section 1.4) self-adjusting, adjustable or bellows seal. To ensure this factor is correctly determined, make sure the correct packing is selected in the
Stuffing box
parameter in the
Identifica
-
tion
folder (>
Positioner>Valve
).
The cycle counter records the number of cy
­cles and the cycle spans which are assigned to cycle classes. The calculated percentages on how often a cycle occurs within a class are shown as a bar graph. The
Cycle counter histogram
folder contains long-term data, i.e. measured data points are updated cyclically over the entire
positioner service life and stored every 24 hours in the positioner’s non-volatile mem
­ory for long-term monitoring. The
Average value z long
parameter con
­tains the cycle class in which the average cycle spans were found.
The
Counter of all measured values
parame
­ter contains the total of classified measured data points previously recorded. In order to obtain a summary of recent cy
­cles, the last 100 cycles measured are stored in an FIFO memory. The
Short
folder contains this additional cy
­cle counter histogram. The
Average value z short
parameter con­tains the average cycle class for the last 100 measured data points stored in the FIFO memory. Data can be reset in the
Status messages
folder.
14 EB 8388 EN
Statistical information AUTO
Fig. 6 · Cycle counter histogram
Page 15
2.5 Drive signal diagram
2.5.1 Steady-state drive signal
The signature diagram plotting drive signal versus valve position is based upon the drive signal y being the internal control signal of the i/p converter. This signal runs linear in relation to the valve position, similar to the signal pressure in the pneumatic actuator. This graph is plotted after initialization and is stored as a reference in the positioner. A pressure drop across the valve while the process is running causes the signal pres
­sure in the actuator to change by the same amount as the valve travel because the flow forces have an affect on the equilibrium of forces at the valve stem. A similar effect arises when the actuator springs loose their compression due to one or more springs failing. As a result, a change in the correlation between the inter­nal drive signal y and the valve travel also
pinpoints to one of these events having oc
­curred. A reduced spring force or a control valve with the fail-safe position ”Fail-to-close” leads to the drive signal y shifting down
­wards with an ever smaller gradient. In contrast, the pressure drop across the valve while the process is running does cause the drive signal y to drop, but the gradient rises irrelevant of the valve travel. If significant leakage in the pneumatics arises due to screw fittings that are not tight
-
ened properly or due to a tear in the dia
­phragm, the drive signal even starts to rise steadily at a certain valve opening com
­pared to the reference graph. The drive signal y starts to rise almost un­steadily at the restricted valve position if the positioner supply pressure is insufficient. The steady-state drive signal diagram con­tains recent data to allow recent changes to be recognized. Furthermore, long-term data are also analyzed to be able to detect prob­lems due to supply pressure changes or air
EB 8388 EN 15
Statistical information AUTO
Fig. 7 · Steady-state drive signal diagram
Page 16
leaks in the pneumatics before they have an impact on the process. The measured data allows the following problems to be detected and the associated alarms to be issued:
4
Air leakage in the pneumatics
4
Spring force reduced
4
Changes in supply pressure
The valve position and its associated drive signal y are measured after the pressure conditions have settled (steady-state). Each pair of measured data points recorded is assigned to a valve position class. The average drive signal y is calculated for each class. The stored data can be read.
The reference data required are plotted and stored after initialization.
Long-term monitoring
The long-term monitoring involves the aver­age drive signal y for each valve position class being determined from all measured data points per valve position class. The
Long-term
folder contains a table of the valve position classes with the associated average drive signal y.
Short-term monitoring
The short-term monitoring involves the aver
­age drive signal y determined from the last measured data points per valve position class. This allows short-term changes in ac
­tuator pressure to be pinpointed at various valve positions. The
Differential drive signal
and
Valve posi
-
tion
s folders contain a table of the last ten
measured data points.
Graphs
The
Steady-state
folder contains a common
graph for long-term, short-term and refer
-
ence data. The graph plotted using the ref
­erence data covers the full range of the valve. The data for long-term and short-term moni
­toring are recorded online while the process is running, and therefore, the graphs do not necessarily cover the full range of the valve. Reference values are used in cases where no data could be compiled for valve positions x as the valve did not move to those positions or a steady-state could not be reached. The diagram allows changes in drive signal y at the corresponding valve positions to be easily recognized. Changes in pressure are also evident as the drive signal y is propor­tional to the actuator pressure. Data can be reset in the
Status messages
folder.
Test requirements:
A successfully plotted reference graph is necessary to record and analyze the data. Refer to section 1.6 in case a double-acting actuator with reversing amplifier or a booster is used or SUb initialization mode is set.
Note!
The valve can be moved through its travel range in manual mode, during plant shut
-
down or when the process allows it by se
-
lecting
Drive signal diagram steadyinTest
MAN
to check the results or statements de
-
termined in automatic mode in the
Status
message
folder (> Extended).
16 EB 8388 EN
Statistical information AUTO
Page 17
2.5.2 Hysteresis test (d5)
The hysteresis test allows changes in friction to be analyzed and an alarm is issued when a significant change in friction is detected.
If the diagnostic test d5 is activated and the condition for the
Minimum time between
tests
parameter is met and the pressure con
­ditions have settled, the test is performed with a change in travel < 1% to find∆y.
tESt
and
d5
appear on the positioner dis
­play in alternating sequence and for manual mode appears while the test is run
-
ning.
The test is immediately canceled and the positioner returns to automatic mode if the valve travel leaves the tolerance band or a change in the reference variable occurs which is greater than the tolerance band set. If the test was interrupted due to a change in the reference variable, the test is started
again after waiting 30 seconds using the new operating point. If the test is canceled again at this point due to a change in the reference variable∆w, the test is started again after waiting 60 sec
­onds with the operating point. This can happen ten times, during which the time between tests is increased by 30 sec
-
onds each time (30 s x Number of tests re
­peated). After the test is canceled for the tenth time (due to∆w), the time entered in
Minimum
time between tests
parameter is kept again.
The hysteresis test is deactivated by default. We recommend activating the test after en­tering
Minimum time between tests
by select-
ing
Start now
.
The
Minimum time between tests
and the control parameters are stored in the non-volatile memory of the positioner.
EB 8388 EN 17
Statistical information AUTO
Fig. 8 · Hysteresis test diagram
Page 18
Long-term monitoring
The measured results∆y are classified ac
­cording to the valve position x in the valve position classes. The average value∆y per valve position class is determined from all the measured data. The
Long-term
folder contains a table of the
results.
Short-term monitoring
To provide a short-term trend, the last ten valve positions x and the associated∆y val
-
ues are saved in the
Short-term
folder
(>
Valve position
and
Difference signal
drive
).
Graphs
The
Hysteresis
folder contains a graph with
two curves plotted. The
Measurement
curve shows the measured data recorded for long-term monitoring and the
Reference
curve shows the reference data recorded af­ter initialization. The graph plotted using the reference data covers the full range of the valve. The data for long-term monitoring are re
­corded online while the process is running, and therefore, the graphs do not necessarily cover the full range of the valve. Reference values are used in cases where no data could be compiled for valve classes. If the test has not yet been activated, the graph for the reference data is represented by a straight line.
The diagram allows changes in∆y with the corresponding valve positions to be recognized. Changes in friction are highlighted as∆y is proportional to the actuator pressure which, in turn, is a measurement for friction. A
change in friction leads to an alarm being issued.
Test requirements:
The test is possible in relation to the travel range between 2 and 98 %.
4
A successfully plotted reference graph is necessary in order to analyze the fric
-
tion.
4
The test can only be started when the tol
-
erance band (Code 19) or
Positioner
folder (>
Error control>Tolerance band
)
is greater than 1 %.
4
The characteristic type (Code20) must be set to
Linear
in order to record the
data.
4
Refer to section 1.6 in case a double-act­ing actuator with reversing amplifier or a booster is used or the SUb initialization mode is set.
Note!
The valve can be moved through its travel range in manual mode, during plant shutdown or when the process allows it by selecting
Drive signal diagram hysteresis
in
Test MAN
to check the results or statements determined in automatic mode in the Status message folder (> Extended).
18 EB 8388 EN
Statistical information AUTO
Page 19
The following parameters are changed dur
-
ing hysteresis test/d5 correspondingly:
4
Lower x-range value (Code 8): 0 %
4
Upper x-range value (Code 9): 100 %
4
Lower/upper x-limit (Code 10/11): OFF
4
Setpoint cutoff w decrease/increase (Code 14/15): OFF
4
Pressure limit (Code 16): Active pressure limit is raised one stage higher
4
W-ramp OPEN/CLOSED (Code 21/22): Variable
Data can be reset in the
Status messages
folder.
2.6 End position trend
The end position trend is used to detect a creeping zero point shift due to seat and plug wear or dirt between the seat and plug. A fluctuating zero point also causes an alarm to be issued. To accomplish this function, the valve posi-
tion x and the drive signal y are automati
-
cally logged and time-stamped by the oper
­ating hours counter in automatic mode when the valve moves to the lower end posi
­tion. The measured data are stored in an FIFO memory that always stores 30 mea
­sured data points. The measured data are first stored in a ring buffer if the valve position x differs by ±0.25 % from the measured value previ
­ously recorded. To allow the test to run automatically in the background, activate the tight-closing func
-
tion (over Code 14 or in the
Positioner
folder (>
Reference variable>Setpoint cut
-
off decrease
) and make sure the positioner
is in AUTO operating mode.
When the valve moves to the zero point for the first time in controlled operation, this measured value serves as a reference. The reference value is stored in a non-volatile memory independent from the ring buffer.
EB 8388 EN 19
Statistical information AUTO
Fig. 9 · End position trend with zero point shift at measuring point 1
Page 20
An alarm is generated after a change in zero point or when a zero point shift outside of the zero point limit is detected. Enter the zero point limit in the
Positioner
folder (>
Error control>Zero point limit
) or over Code 48 in the positioner, selecting d5 (default setting 5 %).
Note!
The valve end position is also logged when the valve moves to the fail-safe position over the forced venting option and with an actuator with AIR TO OPEN.
Graph versions
Select
Trend of valve end position
folder to view a graph of the recorded end positions. The reference value is represented by a straight line in the graph. The graph highlights a trend and a change in the end position.
The
Lower end position
folder contains a table of the measured data (valve position x, drive signal y) with time stamp. Data and the reference value can be reset in the
Status messages(> Reset
) folder.
20 EB 8388 EN
Statistical information AUTO
Page 21
3 Tests MAN
These tests are performed when the process in not running (i.e. manual operation). The positioner does not follow its reference vari
-
able.
In all the following tests, the control valve moves through the full range of the valve af
-
ter the test is started. Therefore, before start
­ing the test, it is absolutely important to make sure whether the process and plant conditions allow it.
In contrast to the tests in statistical informa
­tion AUTO, the corresponding test MAN covers the full range of the valve and also serves to detect errors within the travel range.
The tests MAN provide a trend showing the current control valve state, any possible ex­isting malfunctions and help to pinpoint faults and to schedule predictive mainte­nance work. For reasons of safety, the tests MAN can only be started when the positioner is in manual operating mode.
Select the operating mode over Code 0 on the positioner or in
Positioner
folder (>
Op
-
erating mode
).
Select the
Start all tests parameter
to start all
tests automatically in sequence.
During the test, the following parameters are changed for all tests MAN (d1 to d4):
4
Lower x-range value (Code 8): 0 %
4
Upper x-range value (Code 9): 100 %
4
Lower/upper x-limit (Code 10/11): OFF (not in a step response test)
4
Setpoint cutoff w decrease/increase (Code 14/15): OFF
4
Pressure limit (Code 16): Active pressure limit is raised one stage higher
4
Characteristic (Code 20): Linear
4
W-ramp OPEN/CLOSED (Code 21/22): Variable
Note!
The tests MAN can only be activated in manual operating mode.
EB 8388 EN 21
Tests MAN
Fig. 10 · Tests MAN
Page 22
3.1 Drive signal diagram steady-state (d1)
As described in detail in section 2.5 on the drive signal diagram, the drive signal y plot
-
ted versus valve position x allows the follow
-
ing changes at the control valve to be recog
-
nized (and an alarm issued):
4
Air leakage in the pneumatics
4
Spring force reduced
4
Changes in the supply pressure
This test (
tESt d1
) causes the valve to move through the travel range to allow the results and alarms issued in automatic mode to be accurately checked. After starting the test, the valve is moved to various fixed valve positions x distributed over the full range of the valve.
The drive signal y is measured for each valve position x and stored in the positioner memory. The necessary data set for the ref
­erence graph is automatically plotted and stored directly after initialization. The start time for the reference graph is stored with a reference time stamp in the positioner’s non-volatile memory. Any further measurement is stored as a re
­peated measurement. Previously recorded repeated measurements stored in the positioner are overwritten. However, note that you can upload previous repeated mea
­surements to a PC before starting a new test. While the test is active,
d1
and
tESt
appear on the positioner display in alternating se­quence and indicates manual operating mode.
22 EB 8388 EN
Tests MAN
Fig. 11 · Drive signal diagram steady-state
Page 23
Viewing the recorded parameters:
The
Drive signal diagram steady-state
folder
contains the reference and repeated mea
­surements plotted in a graph. The individual measured points are saved in the corresponding subfolders: > Reference valve position > Reference drive signal > Repetition value of valve position > Repetition value of drive signal.
Test requirements:
4
A successfully plotted reference graph and repetition lines are necessary in or
­der to analyze the data. If a reference graph still has not been plotted on starting the test, this test is adopted as the reference.
4
Refer to section 1.6 in case a double-act­ing actuator with reversing amplifier or a booster is used or SUb initialization mode is set.
3.2 Drive signal diagram hysteresis (d2)
Similar to the corresponding test in auto
-
matic mode, this test (
tESt d2
) is used to an
­alyze the change in friction forces. However, unlike the test in automatic mode, this test causes the valve to move to defined valve positions over the full range of the valve, and determines∆y for each valve po
­sition. The valve is made to move to fixed nodes of the valve position x and the valve position is ramped up (< 1 %) correspondingly. The drive signal y and the change in valve opening are analyzed during this test phase concerning changes in∆y for changes in di­rection, to precisely check the results or alarms issued in automatic mode.
To enable a test, the tolerance band (Code 19 or in
Positioner
folder (>
Error control
)
must be greater than 1 % (default: 5 %).
If the valve cannot move to a certain valve position node or the setpoint leaves the tol­erance band during the test, an alarm is generated in
Test information
and the test is canceled. The necessary data set for the reference graph is automatically plotted and stored di
­rectly after initialization. The start time for the reference graph is stored with a refer
­ence time stamp in the non-volatile memory of the positioner. Any further measurement is stored as a re
­peated measurement. Previously recorded repeated measurements stored in the positioner are overwritten. However, you can upload previous repeated measure
-
ments to a PC before you start a new test.
EB 8388 EN 23
Tests MAN
Page 24
While the test is active,
d2
and
tESt
appear
on the positioner display in alternating se
­quence. indicates manual operating mode.
Viewing the recorded parameters:
The
Drive signal diagram hysteresis
folder contains a graph with reference measurements and the last measurement performed plotting the change in drive sig
-
nal∆y versus the valve position x. The
Refer
-
ence valve position
subfolder contains a list of the valve positions that the valve moved to. The recorded∆y are saved in the corre
­sponding subfolders: > Reference hysteresis > Repetition value of hysteresis.
Test requirements:
4
A successfully plotted reference graph and repeated measurements are neces
­sary in order to analyze the data. If a reference graph still has not been plotted on starting the test, this test is adopted as the reference.
4
Refer to section 1.6 in case a double-act
­ing actuator with reversing amplifier or a booster is used or the SUb initialization mode is set.
24 EB 8388 EN
Tests MAN
Fig 12 · Drive signal diagram hysteresis
Page 25
3.3 Static characteristic (d3)
The static performance of the control valve is affected by the friction hysteresis and the elastic processes in the valve stem packing. The static characteristic is plotted to check the static performance. The analysis of minimum, maximum and average dead band parameters allows the control loop to be evaluated. To accomplish this, the reference variable w is commanded in small steps and the re
­sponse of the controlled variable x is plotted after waiting a predetermined period of time. This test
(tESt d3)
allows the full range of the
valve to be recorded in manual mode.
It is also possible to define a test range by selecting the
Start
and
End
parameters. The ascendent and descendent are plotted within the test range. 100 measured points are plotted at the maximum, i.e. max. 50 measured points are available for the ascendent and the descen
­dent. The step height and the number of measur
­ing points are determined automatically by the adjusted test range. The dead zone is analyzed by a step height smaller than
0.2 %. The setpoint difference that causes a mini
­mal change in the valve position x is termed dead band. It is recorded and analyzed in the positioner for each step.
EB 8388 EN 25
Tests MAN
Fig. 13 · Static characteristic
Page 26
Fig. 13 lists the settings and information pa
-
rameters.
While the test is active,
d3
and
tESt
appear
on the positioner display in alternating se
­quence. indicates manual operating mode.
Viewing the recorded parameters:
The
Static characteristic
folder contains a graph of the measured points, plotting the valve position x versus the reference vari
­able. The
Measured values
subfolder (>
Valve po
-
sition x
) and (>
Reference variable w
) con
­tain a table of the individual corresponding measured points.
Data can be reset in the
Status messages
folder.
Test requirements:
4
The starting point must be smaller than the final point. The dead band is analyzed if the step height is smaller than 0.2 %.
3.4 Step response (d4)
The dynamic valve performance can be ex
­amined by recording the step responses. Usually, two steps in reference variable are performed and the course of the valve posi
­tion x and the drive signal y are plotted until a steady state is reached. This test is stored and analyzed in the positioner. The reference variable w, the setpoint devia
-
tion e and time t are also stored and ana
­lyzed. The default setting is two steps with the first step usually starting at a defined start value and ending at a defined end value. After a certain delay, the second step is per­formed, starting at the end value of the first step and ending at the defined start value of the first step. The data are automatically analyzed in the positioner after the test is completed. Param­eters such as overshoot, dead time, T63, T98, rise time and settling time are deter­mined separately for each step.
Refer to Fig. 14 for the setting and informa­tion parameters.
The following analysis parameters are deter
-
mined separately for each step:
> Overshoot (relative to the step height) in % > Dead time > T63 > T98 > Rise time > Settling time.
While the test is active,
d4
and
tESt
appear
on the positioner display in alternating se
­quence. indicates manual operating mode.
26 EB 8388 EN
Tests MAN
Page 27
Viewing the recorded parameters:
The parameters required to analyze the step response test such as reference variable w, valve position x, setpoint deviation e and drive signal y are plotted in graphs over time in the
Step response
folder.
The
Measured values
subfolder contains all measured and analyzed parameters such as valve position, setpoint, drive signal, setpoint deviation and the points in time at which they were recorded.
Data can be reset in the
Status messages
folder.
EB 8388 EN 27
Tests MAN
Fig. 14 · Step response test
Page 28
4 Status and diagnostic alarms
4.1 Standard EXPERT diagnostic alarms
The standard EXPERT diagnostics provides information about positioner states such as operating hours counter, process monitor
­ing, number of zero calibrations and initializations, total valve travel, tempera
­ture, initialization diagnostics, zero/control loop errors, etc.
In addition, the standard EXPERT diagnostics generates diagnostic and status alarms which allow faults to be pinpointed quickly when a fault occurs. The diagnostic and status alarms issued by EXPERT appear on the positioner display and can also be viewed in TROVIS-VIEW software in the
Diagnosis
folder (>
Status
messages
). Alarms are classified in the following main groups:
4
Status
4
Operation
4
Hardware
4
Initialization
4
Data memory
4
Temperature
Further information on the positioner status (e.g. limit switches, tight-closing function) and the parameters (e.g. characteristics) are displayed in the
Positioner
folder).
The following folders contain particularly in
-
formative data for valve diagnostics:
4
Positioner
folder (process data)
Information on the current process vari
­ables, condensed status, operating mode, limit switch, temperature.
The Trend Viewer function (activate Trend Viewer in the
View
menu) allows process variables to be shown in one or more graphs. To proceed, drag and drop the required process variable into the graph.
4
Positioner
folder (>
Error control
) Information on total travel with a freely defined limit
4
Positioner
folder (>
Start-up>Initializa-
tion
) List of initialization errors which can also be found in the
Diagnosis
folder (>
Sta-
tus messages
).
4.2 Extended EXPERT+diagnostic alarms
Further status alarms are generated from the extensive information gained in the diagnos
-
tic tests of EXPERT
+
which provide the user with information covering the whole control valve (see table below).
These status alarms can be viewed in the
Di
-
agnosis
folder (>
Extended
). An active diagnostic alarm issued by EXPERT
+
appears on the positioner display
over Code
79.
28 EB 8388 EN
Status and diagnostic alarms
Page 29
4.3 Logging
The last thirty alarms (EXPERT/ EXPERT+) are stored in the positioner with a time-stamp (logged by the operating hours counter). However, it is important to note that the same alarm is only logged once when it first occurs.
The alarms stored can be viewed in the
Log
-
ger
folder.
Entries can be reset in the
Reset
folder.
4.4 Classification of the status alarms
Any event or alarm is assigned a status. The following states listed in the table below are possible:
4.5 Condensed state
To provide a better overview, the state of the positioner is summarized in a condensed status which is made up from a summary of all classified positioner alarms.
Note!
If an event is classified as “No message”, this event does not have any affect on the condensed status of the positioner.
The condensed status is displayed in the en
­gineering tool as well as on the positioner display as in the table below. Furthermore, the condensed state is issued at the fault alarm output. Refer to the mount­ing and operating instructions of the positioner for further details.
EB 8388 EN 29
Status and diagnostic alarms
Individual status alarm
Engineering tool
TROVIS-VIEW/DTM
Inactive status_ok.ico
Active · “No message” classification
status_on.ico
Active · “Maintenance required/Maintenance demanded“ classification
status_main.ico
Active · “Function check“ classification
status_funct.ico
Active · “Maintenance alarm“ classification
status_critic.ico
Status alarm
Engineering tool
TROVIS-VIEW/DTM
Device
display
“Maintenance alarm”
status_critic.ico
“Maintenance required/ Maintenance demanded
status_main.ico
“Function check“
status_funct.ico Text
“No message”
status_ok.ico
Page 30
4.6 Status modification
The classification of the status alarms can be changed as required. The following assign
-
ment of the states are:
4
Maintenance alarm
4
Maintenance required/Maintenance demanded
4
No message possible
Select
Positioner
folder (>
Error control
>
Status classification
) to modify the classifica
-
tion of standard alarms issued by EXPERT.
Select
Positioner
folder (>
Error control
>
Status classification > Extended)
to modify the classification of alarms issued by EXPERT+.
Note!
All additional alarms generated by EXPERT
+
have the status “No message” by default.
On resetting the positioner parameters to their default settings (Code 36), the status classification is also reset to the default set
-
ting.
If modifications that have already been made should be kept, we recommend uploading them on a PC before performing a reset and then downloading them onto the positioner again afterwards.
Note!
In the Type 3730-5 Positioner (Foundation Fieldbus), block error alarms as well as the condensed states can be assigned to events . Refer to EB 8384-5 EN for further instructions.
30 EB 8388 EN
Status and diagnostic alarms
Page 31
5 Resetting diagnostic
parameters
When an alarm is issued, the source of the error should be first located and the error remedied. In the case of an EXPERT alarm, we recom
­mend reading the corresponding remedy notes listed in the error code list (refer to the Operating Instructions of the positioner). Remedy notes on EXPERT
+
alarms are listed
in the table in section 7.
EXPERT
Alarms generated by EXPERT which are indicated on the positioner display by an er­ror code can be confirmed by pressing the
rotary pushbutton after selecting the corre
­sponding error code. Resetting error codes as well as resetting op
­tions such as logging or the total valve travel can be performed using an engineering tool, for example, TROVIS-VIEW3 software.
EXPERT
+
Extended alarms generated by EXPERT+are based upon the statistical information AUTO and tests MAN. An active EXPERT
+
alarm is indicated by Code 79 at the positioner. Select
Diagnosis
folder (>
Status messages
>
Reset
) to reset data from statistical infor
-
mation AUTO and tests MAN (see Fig. 15).
EB 8388 EN 31
Resetting diagnostic parameters
Fig. 15 · Resetting diagnostic parameters
Page 32
Note that the corresponding short-term his
­togram/short-term monitoring is also reset on resetting long-term histogram/long-term monitoring.
On performing the tests MAN, the measur
­ing data of the last measurement as well as the reference measurements (for d1 and d2) are stored in the positioner. On restarting a test MAN, the existing data are updated by the repeated measurement data. In addition, the repeated measurements of the tests MAN such as drive signal diagram steady-state and drive signal diagram hys
­teresis can be reset by selecting the
Status
messages
folder (>
Reset
).
Note!
Resetting the measured data does not cause the reference graphs to be reset:
4
Drive signal diagram steady-state
4
Drive signal diagram hysteresis
4
Reference value for the end position trend
However, the existing data set is replaced by the new reference data when the refer
­ence graphs for steady-state and hysteresis graphs (see section 1.5) are replotted. The data sets from already existing mea
­surements of steady-state and hysteresis graphs recorded in both statistical informa
­tion AUTO and tests MAN are reset when both reference graphs are updated.
Initialization
After an initialization has been successfully completed, new reference measurements are automatically plotted and the existing refer
-
ence data are overwritten. The new refer
-
ence data and the optimized control param
-
eters cause the following statistical informa
-
tion AUTO and MAN tests to be reset:
4
Drive signal diagram steady-state (AUTO and MAN tests)
4
Drive signal diagram hysteresis (AUTO and MAN tests)
4
Setpoint deviation histogram (long-term and short-term)
4
End position trend
Resetting over Code 36 (EXPERT/EXPERT
+
)
Activate Code 36 or select
Operation unit
folder (> Start with default settings) to reset the positioner parameters to their default settings (see code list in the mounting and operating instructions of the positioner).
The following diagnostic functions of EXPERT/EXPERT
+
diagnostics are reset:
4
Settings and activated statistical informa­tion AUTO and tests MAN in EXPERT
+
4
Status classification settings (EXPERT/EXPERT
+
)
4
Operating hours counter: (>
Device
switched on since initialization
) and
(>
Device since initialization in control
loop
) (EXPERT)
4
Total valve travel (EXPERT)
4
All short-term histograms (EXPERT+) Drive signal diagram steady-state and diagram hysteresis Statistical information AUTO and tests MAN (EXPERT
+
)
4
Static characteristic and step response (EXPERT
+
)
4
End position trend (EXPERT+)
32 EB 8388 EN
Resetting diagnostic parameters
Page 33
If the same status classification is to be used in future, you can upload the settings onto a PC over, for example, the TROVIS-VIEW software.
Mounting the positioner onto another con
-
trol valve
As the EXPERT
+
extended diagnostics pro
­vides statements about the entire control valve, the data from statistical information AUTO and tests MAN need to be reset when the positioner is attached to a different control valve. After mounting the positioner on the new control valve, perform a reset over Code 36 and re-initialize the positioner. This leads to the most of the diagnostic functions being reset. We recommend additionally to manually re­set the long-term travel histogram and the long-term cycle counter histogram as well as the logging by selecting the
Diagnosis
folder
(>
Reset
).
EB 8388 EN 33
Resetting diagnostic parameters
Page 34
6 Diagnostic parameters saved in non-volatile memory
The following parameters are saved in a non-volatile memory to prevent their loss:
Which data are saved if a parameter change is detected
Cyclic saving (24 h)
Statistical information AUTO
Data logger
Data logging, scan rate, start value, logging limit, trigger status
Travel histogram
Scan rate of short-term monitoring
Data for long-term histogram
Setpoint deviation histogram
Cycle counter histogram
Drive signal histogram (steady-state)
Data for short-term and long-term histograms
Drive signal histogram (hysteresis) (d5)
Minimum time between tests, start test
Data for long-term monitoring
End position trend Measured values when end
position changes
Tests MAN
Drive signal diagram (steady-state) (d1)
Reference test, reference time stamp
Drive signal diagram (hysteresis) (d2)
Static characteristic (d3)
Step response (d5)
Scan rate, step start, step end, delay time after step, number of step responses, analysis parameters
General
Details on actuator and valve data
Yes
Logging Save when a new alarm is issued
Classification of status alarms
Yes
34 EB 8388 EN
Diagnostic parameters saved in non-volatile memory
Page 35
7 Troubleshooting
Fault category Alarm Remedy Resetting alarm
Supply pressure Possibly changed (test)
Check supply pressure. Refer to the section on
supply pressure in the EB of the positioner.
Reset y-x signature measured data
Possibly at full capacity (test)
Possibly insufficient
Reset over Code 57. Reset y-x long-term and
short-term monitoring
Trend concerning full range of valve
Working range shift CLOSED position
Check the valve working range.
Reset x long-term and short-term histograms
Working range shift max. OPEN
Air leakage in the pneumatics
Possibly exists (test)
Check pneumatic actuator and connections for leakage.
Reset y-x signature measured data
Possibly too much (test)
Possibly too much
Reset y-x long-term and short-term monitoring Reset over Code 57.
Possibly exists
Restriction of full range of valve
Downwards Check pneumatic
accessories and connections for leakage.
Check supply pressure and increase it, if necessary.
Refer to the section on supply pressure in the EB of the positioner.
Check plug stem for problems caused by an external source.
Reset over Code 57.
Reset e short-term histogram
Reset e long-term histogram
Upwards
No change possible (terminals)
EB 8388 EN 35
Troubleshooting
Page 36
End position trend
Zero point shift downwards monotonic
Average value above the reference line
Check plug and seat
Reset lower end position trend
Zero point shift upwards monotonic
Average value above the reference line
Zero point fluctuates Average value above the
reference line
Zero point shift downwards monotonic
Average value below the reference line
Zero point shift upwards monotonic
Average value below the reference line
Zero point fluctuates Average value below the reference line
Mechanical connection linking positioner/ control valve
Possible restriction of the full range of valve
Check attachment
Reset e short-term histogram
Full range of valve
Mainly near to CLOSED position
Reconsider whether the working range is suitable
Reset x long-term histogram
Mainly near to max. OPEN
Mainly CLOSED position
Mainly max. OPEN
36 EB 8388 EN
Troubleshooting
Page 37
Friction Much higher over the full
range of valve
Check packing
Reset hysteresis long-term and short-term monitoring
Much lower over the full range of valve
Much higher over part of the range
Much lower over part of the range
Much higher/lower over the full range of valve (test)
Reset hysteresis measured data
Much higher/lower over part of the range (test)
Actuator springs Spring rigidness possible
reduced (spring failure)(test)
Check springs in the actuator
Reset y-x signature measured data
Compression possible reduced (test)
Seat leakage
Possibly different Check plug and seat
Reset y-x signature measured data
Reset e short-term histogram
Leakage to the atmosphere
Maybe to be expected soon Check packing
Reset hysteresis long-term and short-term monitoring
Reset hysteresis measured data
Reset z long-term histogram
Dynamic stress factor*
Percentage as information on packing load Leakage to the atmosphere alarm active when greater than 90 %
Check packing
Reset z long-term histogram
* This value is included in the Cycle counter histogram in statistical information AUTO
EB 8388 EN 37
Troubleshooting
Page 38
8 EXPERT+without TROVIS-VIEW
The EXPERT+valve diagnostics are displayed in different ways depending on the type of communication and the connected engineering tool.
The TROVIS-VIEW software with communication over the SSP interface provides full access to EXPERT
+
diagnostic functions:
4
Numerical display of parameters
4
Display of parameters in the form of graphs
4
Parameterization, where applicable
The representation may differ in other engineering tools. The table below illustrates the differ
-
ences.
Communication HART – DD HART-DTM HART-EDD FF – DD Profibus-EDD
Engineering tool e.g. PACTWare e.g. Siemens PDM
Various Siemens PDM
Start reference test (section 1.5)
•• • ••
Statistical information AUTO (refer to section 2 for description)
Data logger
No numerical
display
No graphical
display
No numerical
display
No graphical
display
No numerical
display
No graphical
display
Travel histogram · long-term
1)
No graphical
display
••
No graphical
display
Travel histogram · short-term
No graphical
display
No parame
-
terization
••–
Setpoint deviation histogram · long-term
1)
No graphical
display
••–
Setpoint deviation histogram · short-term
No graphical
display
No parame
-
terization
••–
Cycle counter histogram · long-term
1)
No graphical
display
••
No graphical
display
Cycle counter histogram · short-term
1)
No graphical
display
••–
Steady-state drive signal · long-term
1)
No graphical
display
••–
38 EB 8388 EN
EXPERT+without TROVIS-VIEW
Page 39
Communication HART – DD HART-DTM HART-EDD FF – DD Profibus-EDD
Engineering tool e.g. PACTWare e.g. Siemens PDM
Various Siemens PDM
Steady-state drive signal · short-term
1)
No graphical
display
–•–
Hysteresis test · long-term
No graphical
display
••
No numerical
display
No graphical
display
End position trend
1)
No graphical
display
••–
Tests MAN (refer to section 3 for description)
Drive signal diagram steady-state (d1)
No graphical
display
••
No numerical
display
No graphical
display
Drive signal diagram hysteresis (d2)
No graphical
display
••
No numerical
display
No graphical
display
Static characteristic (d3)
Restricted
numerical
display
2)
No graphical
display
••
Restricted
numerical
display
2)
No graphical
display
Step response (d4)
Restricted numerical
display
2)
No graphical
display
••
Restricted
numerical
display
2)
No graphs
displayed
Diagnostics – Status alarms (refer to section 4 for description) Extended EXPERT
+
status alarms
•• • ••
Logging • Classification of status
alarms
•• • ••
Resetting diagnostic parameters (refer to section 5 for description) Resetting diagnostic
parameters
•• • ••
• Full scope of functions = all functions that are available with TROVIS-VIEW
1)
EXPERT+functions cannot be parameterized
2)
Only analyzed data are shown; the measured data are not shown.
3)
With Siemens PDM full functionality with numerical and graphical display
EB 8388 EN 39
EXPERT+without TROVIS-VIEW
Page 40
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: + 49 69 4009-1507 Internet: http://www.samson.de
EB 8388 EN
S/Z 2007-10
Loading...