Samson 373 Series, 3730-2, 3730-3, 3731-3, 3730-4 Operating Instructions Manual

...
Series 373x Positioners
EXPERT+Valve Diagnostics
Operating Instructions
EB 8388 EN
Firmware version 1.4x Edition November 2006
Fig. 1 · Valve diagnostics with SAMSON TROVIS-VIEW Operator Interface, e.g. for Type 3730-3 Positioner
Contents Page
1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Diagnostic tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Activating EXPERT
+
. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Actuator and valve specification data . . . . . . . . . . . . . . . . . . 5
1.5 Start the reference test . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 SUb initialization mode, double-acting actuator and booster . . . . . . . 6
1.7 Activation, analysis and presentation of diagnostic data . . . . . . . . . 7
1.7.1 Printing the diagnostic/ESD log . . . . . . . . . . . . . . . . . . . . . 8
2 Statistical information AUTO . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Data logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Travel histogram . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Setpoint deviation histogram. . . . . . . . . . . . . . . . . . . . . . 12
2.4 Cycle counter histogram . . . . . . . . . . . . . . . . . . . . . . . . 13
2.5 Drive signal diagram . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.1 Steady-state drive signal. . . . . . . . . . . . . . . . . . . . . . . . 15
2.5.2 Hysteresis test (d5) . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.6 End position trend. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 Tests MAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.1 Drive signal diagram steady-state (d1) . . . . . . . . . . . . . . . . . 22
3.2 Drive signal diagram hysteresis (d2) . . . . . . . . . . . . . . . . . . 23
3.3 Static characteristic (d3) . . . . . . . . . . . . . . . . . . . . . . . . 25
3.4 Step response (d4) . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4 Status and diagnostic alarms . . . . . . . . . . . . . . . . . . . . . 28
4.1 Standard EXPERT diagnostic alarms . . . . . . . . . . . . . . . . . . 28
4.2 Extended EXPERT
+
diagnostic alarms . . . . . . . . . . . . . . . . . . 28
4.3 Logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.4 Classification of the status alarms . . . . . . . . . . . . . . . . . . . 29
4.5 Condensed state . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.6 Status modification . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 Resetting diagnostic parameters. . . . . . . . . . . . . . . . . . . . 31
6 Diagnostic parameters saved in non-volatile memory . . . . . . . . . 34
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8 EXPERT
+
without TROVIS-VIEW . . . . . . . . . . . . . . . . . . . . 38
2 EB 8388 EN
Contents
1 Description
1.1 General
These instructions EB 8388 EN supplement the standard mounting and operating in
-
structions of the positioners:
Type Standard EB
3730-2 EB 8384-2 EN
3730-3 EB 8384-3 EN
3730-4 EB 8384-4 EN
3730-5 EB 8384-5 EN
3731-3 EB 8387-3 EN
EXPERT+is an optional diagnostic firmware integrated in the positioner which allows the predictive, status-oriented maintenance of pneumatic control valves. Refer to section
1.3 on how to activate this option.
EXPERT
+
upgrades the standard EXPERT di­agnostics firmware incorporated in the positioner. The upgraded version provides extended functions to pinpoint valve param­eters that have worsened, allowing the user to plan predictive maintenance and service work before malfunctions can affect the pro
-
cess, causing unscheduled plant shutdowns.
EXPERT
+
records the valve faults in auto
­matic mode while the process is running and issues alarms on the required mainte
­nance work. In addition, numerous tests can be performed in manual mode to pinpoint emerging faults. Owing to the numerous diagnostic tests, EXPERT
+
is able to generate classified status
alarms on the state of the control valve.
The EXPERT
+
diagnostics are completely in
­tegrated in the positioner. Data required for diagnostics are compiled automatically and the test data are analyzed in automatic or manual mode in the positioner itself. The re
-
sulting data are used to issue classified sta
­tus alarms.
The diagnostics data, results and status alarms are available over the DD (Device Description). All the necessary reference graphs are automatically plotted after the positioner has been initialized and are available when required.
After performing the basic settings at the positioner using the rotary pushbutton, the TROVIS-VIEW3 or DTM software allow the parameters to be viewed and set conveniently.
Type Integration
3730-2 TROVIS-VIEW3
373x-3 TROVIS-VIEW3, DD, DTM
3730-4 TROVIS-VIEW3, DD, DTM
3730-5 TROVIS-VIEW3, DD
The following sections contain a description on how to operate the diagnostics over the TROVIS-VIEW3 software.
Note!
All the parameter settings that are changed over the operator interface must also be downloaded onto the positioner to allow them to become effective.
EB 8388 EN 3
Description
Note!
The optional integrated solenoid valve is implemented by a forced venting function in Types 3731-x Positioners.
1.2 Diagnostic tests
There are two main groups of diagnostic tests available.
Statistical information AUTO
These tests are performed while the process is running (automatic mode) without disrupt
­ing the process. Activated tests are automatically performed when they are triggered by their start condi­tion (e.g. data logger and drive signal dia­gram hysteresis). Other tests are already performed in the background without being activated (e.g. histograms, cycle counter, drive signal steady-state and end position trending).
Tests MAN
These tests should not be performed while the process is running (i.e. in manual mode instead) as the positioner cannot follow the reference variable at the same time. The valve is moved to a certain position de
­fined by the test settings and the valve may move through its full range.
1.3 Activating EXPERT
+
The extended EXPERT
+
diagnostics can be activated later at the positioner when EXPERT
+
is not already activated on delivery
of the positioner.
The required activation code can be ordered (order number 1400-9318). On ordering this option, specify the serial number of the positioner (see nameplate or in the soft
-
ware).
To activate EXPERT
+
, proceed as follows:
Enable configuration at the positioner:
Turn
Code
3
, press ,
turn
ON
, press .
After enabling configuration:
Turn
Code
48
, press
Code
48
blinks.
Turn to select
d
, press ,
turn to select
d8, press .
d8
blinks
Turn and set the activation code XXXX.
Press to confirm the entered code.
4 EB 8388 EN
Description
After the activation has been successfully completed,
YES
appears on the display.
Note!
On entering the wrong activation code, the display returns to Code 0. The activation of EXPERT
+
has been unsuccessful. After an incorrect activation code has been entered three times, Err appears on the display after selecting Code 48 and d8. An activation code can only be entered again after the positioner has been reset to its default settings (Code 36).
1.4 Actuator and valve
specification data
To correctly analyze the diagnostic data, several actuator and valve specifications need to be entered for the EXPERT
+
diagnos
­tics. Enter the required data in the
Identification
folder (>
Positioner > Actuator
) as well as
(>
Positioner > Valve
). Download the data to the positioner. The
Model
and
Booster
parameters in the
Actuator
folder and
Stuffing box
parameter
in the
Valve
folder need to be entered.
The default settings of these parameters are:
4
Model
> Single-acting
4
Booster
> Not present
4
Stuffing box
> Self-adjustable
These parameters do not need to be changed if the control valve also has these default settings.
1.5 Start the reference test
After EXPERT+has been activated properly, the reference graphs for future diagnostic purposes need to be plotted to allow the di
-
agnostics to function in their full scope.
The reference graphs are plotted automati
­cally after the positioner has been initialized when the EXPERT
+
has been activated (e.g. already on delivery). On activating EXPERT
+
at later time, the ref­erence graphs are plotted after the positioner is re-initialized. If reference graph plotting is to be started sep­arately in an initialized positioner or if graphs are to be replotted, proceed as follows:
Set the positioner to manual mode:
Turn
Code
0
, press ,
Code
0
blinks.
Turn
MAN
, press , the positioner
moves to manual mode.
Manual operating mode
You can activate the reference test either by selecting the
Diagnosis
folder (>
Start refer
-
EB 8388 EN 5
Description
ence test
) and right-click the parameter to
select
Execute
, or, alternatively, start the ref
-
erence test at the positioner itself by select
-
ing Code
48
as follows:
Enable configuration at the positioner:
Turn
Code
3
,
turn
ON
, press .
After enabling configuration:
Turn
Code
48
, press
Code
48
blinks.
Turn until
d
appears, press ,
turn to select
d7, press .
d7
blinks.
Turn
ON
,
press to start the reference test.
Caution!
The control valve moves through its travel range during the reference test.
The tests
d1
(drive signal diagram
steady-state) and
d2
(drive signal diagram
hysteresis) are performed during the diag
-
nostic reference test. During the reference test,
tESt
and
d1
or
d2
appear in alternating sequence on the positioner display. The measured data are used as reference data and any existing reference graphs are overwritten. If the reference graphs could not be plotted correctly or are incomplete, Code 81 is is
­sued and saved in a non-volatile memory. The positioner can function properly after it has been initialized successfully without the reference data.
1.6 SUb initialization mode,
double-acting actuator and booster
The following points need to be observed when the positioner is initialized in
SUb
mode or when a double-acting actuator and/or booster is used:
Positioner initialization in SUb mode:
4
Analysis in automatic or manual mode is deactivated.
4
All tests for both statistical information AUTO and tests MAN of drive signal di
­agrams steady-state and hysteresis are inactive.
4
The reference test is inactive.
4
The automatic test to start all tests MAN is inactive.
Double-acting actuator with reversing amplifier:
4
All tests for both statistical information AUTO and tests MAN of drive signal diagrams steady-state and hysteresis are inactive.
4
The reference test is inactive.
6 EB 8388 EN
Description
Booster:
4
The analysis of the tests for both statisti
­cal information AUTO and tests MAN of drive signal diagrams is inactive.
1.7 Activation, analysis and presentation of diagnostic data
All diagnostic tests which do not compile data automatically in the background (data logger, drive signal diagram hysteresis) must be activated to start them. To start these tests, select the corresponding test order (>
Start data loggerorStart test
)
and right-click the parameter to select
Exe-
cute
to activate the test.
Note!
The tests in statistical information AUTO in automatic mode can only be activated when the positioner is in automatic operating mode.
To activate the tests MAN in manual mode, the positioner must first be set to manual mode over Code 0.
Canceling diagnostic tests
There are two ways to cancel an active test:
4
On the TROVIS-VIEW operator interface, select the corresponding folder (>
Stop
test
) to cancel the test. The positioner
then moves to the previously set operat
-
ing mode and to the travel value previ
­ously set (manual mode) or returns to the reference variable (automatic mode).
4
Press once to cancel the tests MAN
d1
(drive signal diagram steady-state)
d2
(drive signal diagram hysteresis)
d3
(static characteristic)
d4
(step response), and the test in statistical information AUTO
d5
(drive signal diagram hysteresis) as well as the reference test over Code
48
.
On canceling a test (d1 to d4), the positioner moves to the fail-safe position. The positioner only goes into automatic mode on canceling test
d5
. The reference graphs must be plotted before the tests for drive signal diagrams steady-state and hysteresis in manual mode can be analyzed.
Note!
The analysis of raw data in automatic mode is started after the positioner has been in controlled operation for over one hour (after initialization). This does not apply to the end position trend test and the dynamic stress factor in the cycle counter histogram as their analysis starts directly after controlled operation begins.
Alarms generated from the tests MAN are marked
TEST
. If the electrical auxiliary power is too low, the test being performed is ended and the positioner moves to the fail-safe position. Upon failure of the auxiliary power, tests in tests MAN and statistical information AUTO must be restarted due reasons of safety.
EB 8388 EN 7
Description
However, the test in statistical information AUTO drive signal diagram hysteresis re
­mains activated. In the event that the solenoid valve (Type 3730-x) is triggered or the forced venting function (Type 3731-x) is activated, active tests are stopped and the positioner moves to the fail-safe position.
However, the test in statistical information AUTO drive signal diagram hysteresis re
­mains activated. In the event that the solenoid valve (Type 3730-x) is triggered or the forced venting function (Type 3731-x) is activated, active tests are stopped and the positioner moves to the fail-safe position.
1.7.1 Printing the diagnostic/ESD
log
The Print command allows you to print out a diagnostic log of individual tests or the en­tire diagnosis.
The diagnostic log includes a title page and a list of all the data points including all their values and properties.
The title page contains all key information for clear identification of the printed log (de
-
vice type, file name, time and date of cre
­ation, time and date of the last change and TROVIS-VIEW version).
Select Print in the File menu to add further information.
1. In the File menu, select Print Options to
choose the scope of the diagnostic log. After installing/updating the TROVIS-VIEW software, customer data (Customer data in the Edit menu) and
summary (table of contents) are listed in the diagnostic log by default.
Check the check boxes for the Comments and Graphics options to add these op
-
tions to the diagnostic log.
2. Right-click the [Diagnosis] folder or the required subfolder and select Print from the context-sensitive menu to print the di­agnostic log. The printout contains the contents of the folder and its subfolders.
8 EB 8388 EN
Description
2 Statistical information AUTO
The signals x, w and y need to be analyzed on a more precise basis to obtain advanced diagnostic information also over the valve, actuator and pneumatic air supply. The positioner compiles raw data for this pur
­pose. The signals are plotted, stored and analyzed while the process is running. In addition, an additional underlayed hysteresis test detects any changes in friction. The diagnostic tests do not have any affect on the positioner’s control performance.
2.1 Data logger
The data logger allows the reference vari­able w, controlled variable x in relation to the working range, drive signal y and setpoint deviation e to be plotted over time. The measured data are saved in an FIFO memory with a capacity to save 100 data points in the positioner. In addition to the permanent plotting of
data, the plotting can be automatically trig
­gered when a start condition is fulfilled. The travel condition (setpoint) or the optional in
­tegrated solenoid valve (optional integrated forced venting) can be used to trigger the data logger. The data logger is completely integrated into the positioner. The software is only necessary for activation and to set the parameters. In addition, the measured data can be viewed as a graph or in a list by selecting
Upload from Device
in the
Device
menu or
by clicking on the device toolbar.
Note! Upon disconnection of the auxiliary power or upon changing the operating mode, the test is inactive and must be reacti­vated.
Data logging
Select
Data logger
folder (>
Selection
) and
select
PermanentorTrigger
and set the
Scan
rate
parameter. Right-click the
Start data
EB 8388 EN 9
Statistical information AUTO
Fig. 2 · Statistical information AUTO
logger
parameter and select
Execute
to start
data logging.
Permanent data logging
The variables w, x, y, and e are logged ac
­cording to the adjusted scan rate and saved in the FIFO memory which always stores the last 100 measured data points of each vari
-
able.
Triggered data logging
On selecting
Trigger
in the
Selection
param
­eter, the data logger records the measured data permanently in the background. A trig
­gering event leads to the last 100 measured data points being stored together with the pretrigger time and leads to the data log­ging of the triggering condition. The following parameters can be changed for this function:
4
Trigger status: Triggered by the travel condition (setpoint) and/or solenoid valve condi
-
tion (forced venting)
4
Start value: Limit indicating from which travel condi
­tion (setpoint) the data logger should be triggered
4
Logging limit: Indicating whether data logging should start when the travel condition (setpoint) exceeds or falls below the start value.
Travel condition (setpoint)
Note!
The valve position is used as the travel condition in positioners in ESD version.
Select
Trigger status
parameter and select
Start trigger via travel condition (setpoint)
.
Activate data logging by selecting
Start data
10 EB 8388 EN
Statistical information AUTO
Fig. 3 · Data logger
logger
parameter and select
Execute
. The triggering event starts data logging when the start value exceeds or falls below an entered value. Enter the required value at which data log
­ging should be triggered in relation to the setpoint in the
Start value
parameter. Select whether data logging should start when the entered value exceeds or falls be
-
low the start value in the
Logging limit
pa
­rameter. After being triggered, the variables w, x, y and e are logged at the adjusted scan rate and saved in the FIFO memory. Additionally, there is a pretrigger time avail
­able to allow the variables to be stored that were logged before the triggered event. Enter the required pretrigger time by right-clicking the parameter and selecting
Modify
. However, the pretrigger time en­tered may not be higher than the maximum pretrigger time determined by the positioner. This maximum pretrigger time is shown in the
Max. pretrigger time
parame­ter. The data logging finishes automatically as soon as the maximum memory capacity of 100 measured data points for each vari
­able including the pretrigger time is reached.
Solenoid valve condition (forced venting)
Select
Trigger status
parameter and select
Start via solenoid valve condition (forced venting)
. Activate data logging by selecting
Start data logger
parameter and select
Exe
-
cute
to start data logging as soon as the in
­tegrated solenoid valve is triggered or the forced venting function is activated. Similar to the travel condition (setpoint), the variables w, x, e and y are logged at the adjusted scan rate and saved in the FIFO
memory on triggering. Additionally, there is a pretrigger time avail
­able to allow the variables to be stored that were logged before the triggered event. Enter the required pretrigger time by right-clicking the parameter and selecting
Modify
. However, the pretrigger time en
­tered may not be higher than the maximum pretrigger time determined by the positioner. The data logging finishes auto
­matically as soon as the maximum memory capacity of 100 measured data points for each variable including the pretrigger time is reached.
Travel (setpoint) or solenoid valve condition (forced venting)
Select
Trigger status
parameter and select
Start via travel (setpoint)/solenoid valve condition (forced venting)
. Activate data
logging by selecting
Start data logger
pa-
rameter and select
Execute
. The triggering event starts data logging when the valve travel (setpoint)/solenoid valve conditions (forced venting) are met. The measured data are plotted over time in graphs. In addition, the compiled measured data are stored in the
Measured values
folder (see Fig. 3).
2.2 Travel histogram
The valve travel histogram is a statistical analysis of the plotted valve travel. The histogram provides information, for ex
­ample, about where the valve mainly works during its service life and whether it shows a recent trend concerning changes in its work
­ing range. The valve travel is recorded and assigned to valve travel classes. The distribution showing
EB 8388 EN 11
Statistical information AUTO
how often the valve travel remains within a class is shown in per cent. The result is pre
-
sented as a bar graph.
The
Travel histogram
folder contains
long-term data, i.e. measured data are up
-
dated cyclically (scan rate 1 s) over the en
­tire positioner service life and stored every 24 hours in the positioner’s non-volatile memory for long-term monitoring. The
Number of measurement values
param
­eter shows the total amount of classified measured data points previously recorded. The
Average value x long
parameter con
­tains the class in which the travel remained on average the most. In order to be able to recognize any short-term changes in valve travel properly, the last 100 measured data points are stored at a scan rate (default: 1 s) in a non-volatile memory. The scan rate can be changed in the
Scan rate short time
param-
eter. On changing the scan rate, old data in the short-term histogram are deleted.
The
Average values x short
parameter con
­tains the average class assignment for the last 100 measured data points stored in the non-volatile memory. Data can be reset in the
Status messages
folder.
2.3 Setpoint deviation histogram
The setpoint deviation histogram contains a statistical analysis of any setpoint deviations recorded. This provides a summary of how often and to which level a setpoint deviation has occurred during the positioner service life and whether it shows a recent trend con­cerning the setpoint deviation. The setpoint deviation is recorded and as­signed to predetermined level classes. The percentages showing how often the setpoint deviation remains within a class is presented
12 EB 8388 EN
Statistical information AUTO
Fig. 4 · Travel histogram
Loading...
+ 28 hidden pages