Samson 36-8 Mounting And Operating Instructions

Page 1
Safety Excess Pressure Valve (SEV) Type 36-8
Fig. 1 · Type 36-8 Excess Pressure Valve
Mounting and Operating Instructions
EB 2546-2 EN
Edition April 2007
Page 2
Design and principle of operation
1 Design and principle of
The excess pressure valve consists of a spring-loaded globe valve with a balanced plug and an actuator with an operating dia phragm and a safety diaphragm.
The excess pressure valve is used to maintain the pressure upstream of the valve to an ad justed set point value. The valve opens when the upstream pressure rises.
The process medium flows through the valve between the seat(2)andthe plug (3) in the di rection indicated by the arrow. The position of thevalveplug determines the flow rate.The upstream pressure p control line (12) to the operating diaphragm (11.1) and is converted into a positioning force which is used to move the valve plug, opposing the force of the positioning springs (7). The spring force is adjustable at the set point adjuster (6).
4
4
4
is transmitted via the
1
The regulators must be mounted, started up and serviced by fully trained and qualified personnel only, observing the accepted industry codes and practices. Make sure employees or third persons are not exposed to any danger. All safety instructions and warnings in these instructions, particularly those concerning installation, start-up, and maintenance, must be observed. Any hazards which could be caused in the excess pressure valve by the process medium or operating pressure are to be prevented by means of appropriate measures. For appropriate operation, make sure that the regulator is only used in applications where the operating pressure and temperatures do not exceed the operating values based on the valve sizing data submitted in the order. Proper shipping and appropriate storage are assumed.
The regulator has two diaphragms (11.1) op erating independently from one another. Continued operation is possible even should one diaphragm fail. To recognize a ruptured diaphragm, a diaphragm rupture indicator or optionally a pressure switch to signalize a
­rupture is installed in the intermediate ring
(11.3 ).
Typetestng:
­The regulator has been typetested as a safety
excess pressure valve (SEV) by the German Technical Inspectorate (TÜV) according to AGFW specifications.
­The test mark is available on request.
-
2 EB 2546-2 EN
Page 3
Design and principle of operation
1
p
1
12
Drawn turned by 90° into the plane of projection
1 Valve body 2 Seat 3 Plug 4 Plug stem 5 Balancing bellows 6 Set point adjuster 7 Positioning springs 8 Bellows 9 Fastening nut 10 Support 11 Actuator housing
11.1 Diaphragms
11.2 Diaphragm rupture indicator
11.3 Intermediate ring
12 Control line
3
p
2
2
4
6
5
7
8
9
10 11
11.1
11.2
11.3
Fig. 2 · Sectional drawing
EB 2546-2 EN 3
Page 4
Installation
2 Installation
2.1 Position of installation
Note!
Flush the pipeline thoroughly prior to installa tion of the regulator, ensuring that sealing particles and other impurities carried along by the process medium do not impair proper operation, especially tight shut-off.
Install the excess pressure valve in horizontal pipelines with the actuator suspended down wards.
On installing the valve,checkthatthemedium flows in the same directionasindicatedbythe arrow on the valve body.
On choosing the point of installation, it is im­portant to make sure that the regulator can still be easily accessed after completion of the plant.
The regulator must be installed free ofstress.If necessary, support the piping near the con­necting flanges.
2.2 Shut-off valve, pressure gauge
Ideally hand-operated shut-off valves should be installed both upstream and downstream of the regulator. This allows the plant to be
-
shut down forcleaning and maintenance rou tines, or when the plant is not operated for long periods of time.
To monitor the pressuresintheplant,pressure gauges should be installed upstream and downstream of the regulator.
-
12 451
1 Shut-off valve 2 Upstream pressure gauge 3 Strainer 4 Pressure reducing valve 5 Downstream pressure gauge
-
Note!
Never attach supports to the valve or actua tor.
4 EB 2546-2 EN
Fig. 3 · Installation example
-
Page 5
Operation
3 Operation
3.1 Start up
Open the hand-operated shut-off valve downstream of the excess pressure valve. Then open slowly the shut-off valve upstream of the excess pressure valve.
3.2 Set point adjustment
The excess pressure required (upstream pres
) is set by turning the set point adjust
sure p
1
ment (6) with an open-end wrench, up to DN 50 with flats across width SW 19 and from DN 65 upwards with SW 22.
Turning it clockwise increases the upstream pressure and turning it counterclockwise re­duces it.
The pressure gauge located on the upstream pressure side allows the adjusted set point to be monitored.
4 Troubleshooting
Should the excess pressure (pressure gauge located on the upstream pressure side) devi ate significantly from the adjusted set point value, check first the control line (12) for any blockages (section 4.1).
If the diaphragms are damaged, the actuator can be disassembled and the diaphragms (11.1) can be replaced (section 4.2).
If other causes such as a damaged seat or
­plug are found, we recommend that you con
­tact our customer service center or return the
regulator to the manufacturer for repair.
Caution!
If the repair is to be performed by the plant operator, it is important to take into account when assembling and disassembling the reg­ulator that thevalve springs (7) for valve nom­inal sizes DN 15to50arepreloadedby up to 70 mm. To remove the springs, only use a suitable tool, for example,SAMSON disassembly tool 9129-2747. Additionally it is important to make sure that no torque is transmitted to the bellows (8), otherwise the metal bellows will be irrepara bly damaged. Remove the regulator from the pipeline be fore performing any repair work on it!
-
-
-
-
5 EB 2546-2 EN
Page 6
Troubleshooting
Prior to disassembling the excess pressure valve, shut down the plant by slowly closing the shut-off valves. Relieve the corresponding part of the plant from pressure and drain it, if necessary.
4.1 Cleaning the control line
1. Loosen the screw joints connecting the control line to the actuator and the valve body, and remove the control line.
2. Blow through the control line to remove any blockages and clean it. Reattach it to the actuator and the valve body.
4.2 Replacing the diaphragms
Note!
When the bottom diaphragm fails, the atmo­spheric pressure in the intermediate chamber between the diaphragms rises to the level of the upstream pressure. A red mark becomes visible in the mechanical rupture indicator. For versions with an installedpressure switch, a visual or acoustic signal is triggered. When the rupture indicator is activated, the bottom diaphragm must be replaced.
1. Unscrew the control line and clean.
2. Unscrew the nuts (9) on the support (10) and remove the actuator housing (11).
3. Disassemble the actuator housing andre place the diaphragm(s).
To reassemble the regulator, proceed in the reverse order. To start up, proceed as de scribed in section 3.1.
-
-
EB 2546-2 EN 6
Page 7
Nominal size, set point range and spare parts for actuator
Dimensions and weights
Set point range
DN 15...25 DN 32...50 DN 65...100
Nominal valve size DN Actuator
bar
Required spring(s)
Order no. 0270-
2 to 4.4
2.4 to 6.6 6 to 11
2166 2167 2166 2167 1410 2203 2166 2168 2166 2199 1410 1417 2200 2201 2200 2201 1416 2204
5 Dimensions and weights
Nominal size DN
Length L Height H Weight
approx. kg
1)
Weights for PN 16,
+10 % for spheroidal graphite iron PN 25 and cast steel PN 40
15 20 25 32 40 50 65 80 100
130 150 160 180 200 230 290 310 350
415 470 600 615
1)
13 14 14.5 20 22 22.5 41.5 48.5 57.5
Diaphragm material
EPDM FKM
Sur
-
Act-
Diaph
Act-
face cm²
uator
gram
uator
Diaph gram
Order no.
1070- 0520- 1070- 0520-
80 9500 0868 9508 0869
L
H
ØD 30
EB 2546-2 EN 7
Page 8
6 Customer inquiries
Please submit the following details: (see also name plate)
Type and nominal size
4
Order number and model number
4
Upstream and downstream pressure
4
Flow rate in m³/h
4
Has a strainer been installed?
4
Installation drawing
4
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 2546-2 EN
S/Z 2007-04
Page 9
Conversion from chromate coating to iridescent passivation
Conversion from chromate coating to iridescent passivation
We at SAMSON are converting the surface treatment of passivated steel parts in our production. As a result, you may receive a device assembled from parts that have be­en subjected to different surface treatment methods. This means that the surfaces of so­me parts show different reections. Parts can have an iridescent yellow or silver color. This has no effect on corrosion protection. For further information, go to u www.samson.de/chrome-en.html
Loading...