Samson 3430, 430 Series, 3431, 3434-1, 3434-2 Operating Instructions Manual

...
Page 1
Series 430
Pneumatic Indicating Controllers Type 3430
– with Type 3435 Transmitter Module for Pressure – with Type 3436 Transmitter Module for Temperature – with Type 3438 Transmitter Module for Temperature (Pt 100) – for standardized signals
Version shown with lockable door and integrated Type 3436 Transmitter Module for Temperature
Fig. 1 · Controller stations
Mounting and Operating Instructions
EB 7030 EN
Edition October 2010
– for standardized signals
Page 2
Contents
Contents Page
1 Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Settings at the controller modules . . . . . . . . . . . . . . . . . . . . 4
2.1.1 Operating action . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2 Air supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.3 Proportional-action coefficient Kp . . . . . . . . . . . . . . . . . . . . 6
2.1.4 Reset time Tn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.5 Rate time Tv. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.6 Operating point. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Setting the limit switches. . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 Tuning the controller . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1.1 Setting the operating point in P and PD controllers . . . . . . . . . . . . 9
3.2 Smooth automatic/manual mode changeover . . . . . . . . . . . . . 10
3.3 Smooth changeover between the internal and external reference variable 10
3.4 Readjusting the controller’s zero point . . . . . . . . . . . . . . . . . 10
4 Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Transmitter modules . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Controller station . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3 Controller modules. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 Type 3433 Controller Modules . . . . . . . . . . . . . . . . . . . . . 14
5.3.2 Type 3434 Controller Modules . . . . . . . . . . . . . . . . . . . . . 17
5.4 Additional modules . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.4.1 Type 6112 i/p Converter . . . . . . . . . . . . . . . . . . . . . . . 18
5.4.2 w
selector switch . . . . . . . . . . . . . . . . . . . . . . . . 18
int/wext
5.4.3 Supply pressure regulators . . . . . . . . . . . . . . . . . . . . . . . 18
5.4.4 Inductive limit switches . . . . . . . . . . . . . . . . . . . . . . . . . 19
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.1.1 Changing scales. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.2 Installing the temperature sensor . . . . . . . . . . . . . . . . . . . . 22
7 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1 Pneumatic connections . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1.1 Typical applications . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1.2 Adjusting the supply air for version with supply pressure regulator. . . . 25
7.2 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2 EB 7030 EN
Page 3
Contents
8 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.1 Checking the air supply . . . . . . . . . . . . . . . . . . . . . . . . 27
9 Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.1 Changing the controller function . . . . . . . . . . . . . . . . . . . . 28
9.2 Exchanging the transmitter module . . . . . . . . . . . . . . . . . . . 30
9.3 Checking the controller function . . . . . . . . . . . . . . . . . . . . 30
10 Use in hazardous areas . . . . . . . . . . . . . . . . . . . . . . . . 31
10.1 Servicing explosion-protected devices . . . . . . . . . . . . . . . . . 31
11 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
General safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. According to these mounting and operating instructions, trained personnel is referred to as individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the relevant standards. Explosion-protected versions may only be operated by personnel who have
4
undergone special training or instructions or who are authorized to work on explosion-protected devices in hazardous areas. Any hazards that could be caused by the signal pressure are to be
4
prevented by means of the appropriate measures. Proper shipping and appropriate storage of the device are assumed.
4
EB 7030 EN 3
Page 4
Application
1 Application
The Series 430 Pneumatic Indicating Con trollers are used for applications in process automation and industrial plants. The controllers directly measure the con trolled variables (pressure, temperature, electric or pneumatic standardized signal) and display the value. They compare the measured variable with the set point and is sue a corresponding pneumatic control sig nal from 0.2 to 1 bar (3 to 15 psi).
A supply pressure of 1.4 bar±0.1 bar (20 psi±1.5 psi) is required or an operat ing pressure of 2 to 12 bar (30 to 180 psi) when a supply pressure regulator is in­stalled.
-
2 Operation
-
2.1 Settings at the controller modules
The controller module in the station can be accessed after the lock (Fig. 2) has been re leased and the indicating unit (5) has been opened out.
-
The settings for operating action (turnboard
-
A) and air supply (turnboard B) must be performed prior to commissioning.
Unscrew the mounting screw (6) on the
4
-
controller module. Pull it off its self-seal ing hose fittings and lift out of the con­troller station.
2.1.1 Operating action
The operating action for the control loop is set at the turnboard A (Fig. 2), where the position of its arrow symbol according to the arrow symbol on the controller module de­termines the operation action of the control­ler.
34 Arrow tips facing opposite
directions: Operating direction: Increasing/decreasing = As the controlled variable x increases, the output signal pressure y decreases.
44 Arrow tips facing the same direction:
Operating direction: Increasing/increasing As the controlled variable x increases, the output signal pressure y increases.
-
-
4 EB 7030 EN
Page 5
Operation
Setting or modifying the operating direction:
Unfasten the screw in turnboard A (Fig. 2) and lift it off together with the turnboard. If necessary, lever the board at the side. Do not lose the rubber seal.
Turn the board by 90° so that the re
4
quired arrow is aligned with the arrow on the base plate. Insert board and tighten screw.
4
Reassemble the controller module in the
4
controller station.
1 Controller station (Type 3432)
1
1.1 Scale
1.3
1.3 Actual value pointer (red)
1.1
1.4 Set point adjuster
4
2 Transmitter module
1.4
3 Controller module
5
3.1 Comparator
3.2 Connecting plate
3.3 Hex screws
2
Air supply
B
Oper. action
A 3.2 3.4 8 9 3.1
3.4 Screws (inside)
2.1.2 Air supply
(only with Type 3433 Controller Module) The position of the turnboard B (Fig. 2) with its arrow symbol determines the air supply to the feedback bellows. It can be accessed
-
after the comparator (3.1) has been re moved.
4yA Normal air supply, approx. 1 m
4R Large air supply, approx. 3 m
or connecting base
-
³/h
n
per % of the system deviation
³/h
n
per % of the system deviation (not with P or PD controller modules)
4 Lock 5 Indicating unit 6 Mounting screw 7 Restriction 8 Zero adjuster 9 Kp adjuster 10 Tn adjuster 11 Tv adjuster (only in
PD or PID controller)
12 Operating point adjuster
(only in P or PD controller)
63109
Type 3432 Contr. Module
Side view without comparator
Fig. 2 · Turnboards and adjusters
3.3 3 6
7
Type 3433-2 (PI) Controller Module
10 12
11
Type 3434-2 (PI) Controller Module
Oper. action
A
8
EB 7030 EN 5
Page 6
Operation
Unfasten screws (3.3) and pull off the
4
connecting plate (3.2) together with nuts and bolts from the controller module. Unscrew the hexagonal socket-head
4
screws (3.4) at the side and lift the com parator (3.1) out of the controller mod ule.
Setting or modifying the air supply:
Unfasten screw in turnboard B and lift it
4
off together with the turnboard. If neces sary, lever the board at the side. Do not lose the rubber seal. Turn the board so that the arrow is
4
aligned with the mark yA or R on the controller module. Insert board and tighten screw. Reassemble the controller module in the
4
controller station.
2.1.3 Proportional-action coefficient Kp
2.1.5 Rate time Tv
For Type 3433 Controller versions with de rivative-action component, the rate time Tv needs to be set at the restriction (11). The
­setting depends on the controlled system that
­is being tuned (section 3.1).
2.1.6 Operating point
­Controller modules without integral-action
component such as P or PD controllers have an operating point. In Type 3433 Controller Module, it can be adjusted between 0 and 100 % which corresponds to 0.2 to 1 bar by an operating point adjuster (12). The setting depends on the manipulated variable y (sec­tion 3.1.1). In Type 3434 P Controller Module, the oper­ating point is fixed at 0.6 bar.
-
The setting of the KP(adjuster 9) determines the controller gain and is related to the con­trolled system that is being tuned (section
3.1).
2.1.4 Reset time Tn
Controller versions with integral-action com ponent require the reset time to be set at the restriction (10). The setting depends on the controlled system that is being tuned (section 3.1).
6 EB 7030 EN
-
Page 7
2.2 Setting the limit switches
Only applies to controller stations with the limit switch option: To set the limit switches, first release the lock (4, Fig. 2) and open out the indicating unit (5). The contacts can be accessed at the back.
Adjust proximity switches by placing a screwdriver in the clamps between 0 and 100 % of the reference scale and move until a contact is made over the connected switch ing amplifier.
Clamps with proximity switch
Operation
-
Fig. 3 · Limit switches
EB 7030 EN 7
Page 8
Commissioning
3 Commissioning
Prior to commissioning the control loop, check all devices to make sure they are con nected correctly, do not leak and function properly. Release lock (4) and open out the indicating unit (5) to enable easy access to the operat ing controls at the controller. Check the turnboard to make sure the cor
­rect operating action is set at the controller (see section 2.1.1).
3.1 Tuning the controller
The controller needs to be tuned to the char­acteristics of the controlled system using the
and Tnand/or Tvadjusters at the control-
K
P
ler module to ensure that the controller can keep any system deviations for all set points caused by the disturbance variables to zero or at least to minimize them.
In case of controller stations which have a manual/ automatic switch (1.6), the plant must be started up manually.
We recommend to determine the settings by using a tuning test (following the Ziegler and Nichols method) which produces sufficient results in most cases:
1. Apply supply air (1.4 ±0.1 bar).
2. Set the proportional-action coefficient K
to a low value at the comparator.
3. Set T
restrictor to its maximum value
n
and T
to its lowest value (applies only to
v
PI and PID controllers).
1.8
1.6
-
1.5
1.7
-
1.3 Actual value pointer (red)
1.4 Set point adjuster with green pointer
1.5 Signal pressure display
1.6 Manual/automatic switch
1.7 Adjuster for signal pressure (manual)
1.8 Differential pressure indicator 4 Lock 5 Indicating unit
Fig. 4 · Front view
Setting in manual mode:
4. Set manual/automatic switch to Manual.
5. Operate manual adjuster (1.7) for the control signal so that the controlled vari­able (actual value pointer 1.3) slowly settles on the adjusted set point (set point pointer 1.4). Should the differential pressure indicator (1.8) move to zero, set the manual/auto matic switch (1.6) to Automatic.
P
Proceed as described in points 6 and 7.
Setting in automatic mode:
4. Set the set point to the required value at the rotary knob (1.4) on the indicating unit.
5. Set the T
restriction briefly to its lowest
n
value (completely open) to move the red
1.3
1.4 4 5
-
8 EB 7030 EN
Page 9
Commissioning
actual value pointer to the green set point pointer. Close the T
restriction
n
again.
6. Starting from a low value, increase the proportional-action coefficient K
P
until the actual value pointer displays an har monic oscillation pattern (uniform oscil lation amplitudes as shown in Fig. 5) of the controlled variable. If oscillations do not arise with a large K
setting, turn the rotary knob to
P
change the set point slightly and then re turn it to its former setting. It may be necessary to increase the gain (K
)
P
slightly until an harmonic oscillation pat­tern arises.
7. Write down the adjusted value of the K scale you have just adjusted as the criti­cal proportional-action coefficient K
Pkrit
Use a stopwatch to time the oscillation time for one entire oscillation as T
krit
(PI
and PID controller only).
Controlled variable (actual value)
Tkrit
+
Tkrit
Cntr. K
P 0.50 · K
PI 0.45 · K
PID 0.59 · K
Fig. 5 · Harmonic oscillation, settings
P
P,krit
P,krit
P,krit
T
n
0.85 · T
0.50 · T
T
v
krit
0.12 · T
krit
Multiply both values with the values in the table (Fig. 5) and set as the favor able settings for K
, Tn, and Tvat the
P
controller. Should oscillations still occur despite these settings, slightly reduce K
­Repeat these steps, if necessary, until the
­control loop shows a satisfactory perfor
and increase Tn.
P
mance. Leave enough time in between set ting to allow the controller to stabilize.
3.1.1 Setting the operating point in
-
P and PD controllers
(Type 3433 Controller Module only) After setting the proportion-action coefficient
as described previously, set the operating
K
P
P
point for P and PD controllers instead of the
.
reset time T
Read off the controlled variable yA of the
4
.
n
controller at the display (1.5) when the plant is in a steady-state condition and set this value directly at the operating point adjuster (12, Fig. 2). (Setting 0.2 to 1 bar = 0 to 100 %). Recorrect slightly until the system devia
4
tion is zero. In case the signal pressure display deviates, average the value.
Note!
On changing set point or reference variable, the operating point must be set again as de scribed above. If the reference variable is changed more of ten, set the operating point to 0.6 bar = 50 % (average value).
krit
-
-
-
-
-
-
EB 7030 EN 9
Page 10
Commissioning
Note!
restriction must be completely opened
The T
n
with a P/PI controller is switched over to P action to allow the operating point adjuster to work without delay.
Version with w-dependent operating point
This version does not need to be adjusted since the operating point automatically fol lows the set point w.
-
3.2 Smooth automatic/manual mode changeover
(only for controller station with manual/au­tomatic changeover, Fig. 4)
The smooth switchover ensures that no pres­sure surges can reach the valve when the manual/automatic switch is activated as fol­lows:
Changeover from automatic to manual
Use the manual adjuster (1.7) to adjust signal pressure manual yH until the differen tial pressure indicator (1.8) is zero. Switch over to manual at the switch.
Differential pressure indicator
With Without deviation
adjuster (1.4). The switch (1.6) can only be set to automatic after the differential pressure indicator (1.8) is at zero.
Set the set point again to the required value.
3.3 Smooth changeover between the internal and external re ference variable
When combining the fixed set point control and follower control, the Type 3432 Con troller Station is equipped with a w switch, a pressure adjuster and a differential pressure indicator (Fig. 10). The differential pressure indicator must first be brought to zero by activating the pres­sure adjuster in order to switch between the reference variables.
3.4 Readjusting the controller’s zero point
Should deviations arise between the actual value and set point during operation, the zero point adjustment can be readjusted by
­turning the zero screw at the back of the dis
play unit (5) until the actual value and set point on the front display are the same again.
Deviations between the actual value and set point can also be corrected at the zero point adjuster (8, Fig. 2) of the controller module.
-
-
int/wext
-
Changeover from manual to automatic
If the plant is to be controlled manually to the required value, the automatic signal pressure yA must be matched to the manual signal pressure yH by adjusting the set point
10 EB 7030 EN
Page 11
Construction
4 Construction
The controllers designed according to the modular principle form an entire automation unit consisting of a controller station, a con troller module tuned to the local conditions, and, where applicable, a transmitter as well as other additional modules.
Controllers with Type 3432 Controller Sta tion are mainly designed for installation of a Type 3435 Transmitter Module for Pressure or a Type 3436 Transmitter Module for Temperature with direct process fluid con nection. The Type 3431 Controller Station receives the controlled variable as a standardized signal from 0.2 to 1 bar or 3 to 15 psi. The controlled variable can also be supplied as a current signal from 4 or 0 to 20 mA or 1 to 5 mA over an integrated i/p converter.
The controller station can be equipped with the Type 3433 or Type 3434 Controller Module. For special control applications, the Type 3433 Controller Module can be combined with Type 3437 Additional Modules for pressure limitation, control mode switchover or smooth manual/automatic transfer. The controller station can also be upgraded, if required, with a manual/automatic trans fer, consisting of a selector switch, adjuster for manual mode, and differential pressure indicator. The controller station must be equipped with an additional module for w
int/wext
over when used for applications as a com bined fixed set point controller and follower controller. An additional pneumatic or elec tric output for the external reference variable
(e.g. 0.2 to 1 bar or 4 (0) to 20 mA)
w
ext
change
-
-
-
-
is likewise required when used as a follower controller. Additionally, inductive limit switches, that are adjustable at a scale, can be mounted on the indicating units 1 or 2.
-
Note! Refer to the corresponding Data Sheets for details about the controller sta tions and their controller modules.
T 7030 EN · Pneumatic Indicating Controllers - Information Sheet with product overview.
T 7032 EN · Pneumatic Indicating Controllers for Pressure
T 7034 EN · Pneumatic Indicating Controllers for Temperature with Capillary Sensor
T 7036 EN · Pneumatic Indicating Controllers for Temperature with Pt 100 Resistance Thermometer
T 7038 EN · Pneumatic Indicating Controllers for Standardized Signals
T 7040 EN · Type 3433 Pneumatic Controller Modules and Type 3437Additional Modules
T 7041 EN · Type 3434 Pneumatic Controller Modules
T 7045 EN · Type 6112 i/p Converter
-
Module
5 Principle of operation
5.1 Transmitter modules
Type 3435 for Pressure
The process fluid pressure p is transmitted to
-
the transmitter module (2) where it causes a deflection at the Bourdon tube measuring
-
EB 7030 EN 11
Page 12
Principle of operation
system (2.1). The deflection is converted by the pneumatic servo system (2.2) into a pneumatic signal (controlled variable x) which is proportional to the pressure p. The signal is transferred to the bellows measur ing system of the actual value display (1.3) as well as to the controller module (3).
Type 3436 for Temperature with capillary sensor
The temperature of the medium produces a pressure in the gas-filled sensor (2.3) of the transmitter module which is proportional to the temperature. This pressure is offset by a force on the beam (2.4) and converted into the output pressure p
at the feedback bel-
A
lows (2.6). The supply air flows over the restriction (2.9) and nozzle (2.8) and hits the flapper (2.7). As the temperature rises, the flapper moves closer to the nozzle. This results in an in­crease in output air pressure p
supplied to
A
the bellows (2.6) until a new state of equilib­rium is reached, i.e. until the output signal is proportional to the temperature measured. This signal is transmitted as the actual value signal (controlled variable x) to the bellows measuring system of the actual value display (1.3) and the controller module (3).
Type 3438 for Temperature with Pt 100 re sistance thermometer
The Type 3438 Transmitter Module consists of an electric transmitter and a downstream i/p converter to connect a Pt 100 sensor. The resistance value of the Pt 100 sensor is converted into a 4 to 20 mA current signal in the electric transmitter. Its output signal (4 to 20 mA) is converted into a pneumatic sig nal between 0.2 and 1 bar by the i/p con verter. The output pressure, which is propor tional to the temperature, is supplied to the
bellows measuring system of the controlled variable display and the controller module as a pneumatic controlled variable signal (controlled variable x).
-
5.2 Controller station
The actual value signal x causes a deflection at the bellows measuring system of the ac tual value display (1.3) which is transmitted to the pointer over a gear mechanism. The set point (reference variable w) can be adjusted at the scale (1.2) on the front. The position of the set point adjuster (1.4) is transmitted to the set point transmitter over a gear mechanism. This pneumatic servo sys­tem (1.41) converts the adjusted set point into a pneumatic set point signal (w) which is transmitted to the controller module. The controller module compares the actual value signal (x) with the set point signal (w) and controls using the control signal yA de­pending on the system deviation and the ad­justed control parameters. The control signal is connected to the signal pressure display (1.5) and the output port y. The controller station with manual/auto matic switchover (Figs. 2 and 4) additionally features a manual/automatic switch (1.6),
-
an adjuster for manual mode (1.7), and a differential pressure indicator (1.8). Signal pressure display (1.5) and output port y are connected to the automatic output signal y matic” and to the manual output signal y set at the adjuster (1.7) with a switch posi tion at “Manual”.
-
A smooth switchover from manual to auto
-
matic mode is possible when the differential
-
pressure indicator (1.8) shows that y y
H
with a switch position at “Auto
A
are identical.
-
-
-
H
-
-
and
A
12 EB 7030 EN
Page 13
Principle of operation
1.5 31.2
1
y
w
1.4 1.31.41 1.5 31.2 1.4 1.31.41
R w
PI
z
P
A
y
PPI
/
PID
S x
2.1
2
y
Z
2.2
Type 3432 with Type 3435 Transmitter for Pressure
1.5
1
y
w
1.2 1.4 1.3
3
R w
PI
z
P
A
y
PPI
/
S
PID
x
Zx
Type 3431 and 3432 for pneumatic standardized signals
1 Controller station
1.2 Scale
1.3 Actual value display with pointer, gear mechanism and bellows measuring system
1.4 Set point adjuster with pointer, gear mechanism and set point (1.41), set point display only for follower controllers
1.5 Signal pressure display
1.8 Differential pressure indicator for smooth manual/automatic switchover
1.9 Supply pressure regulator
2 Transmitter module
2.1 Bourdon tube meas. system
2.2 Pneumatic servo system
2.3 Temperature sensor
2.4 Beam
2.6 Feedback bellows
Fig. 6 · Principle of operation of controllers
1
2.4
2.6
2.3
wxwx
w
R w
PI
z
P
y
A
PPI
/
PID
S x
2.7
Z
y
2.9 2.8
Type 3432 with Type 3436 Transmitter for Temperature
y
A
w
1.21.41 1.4 1.3 3 w
xwx
R w
PI
z
P
A
y
PPI
S
PID
x
x
/
1.6
1.5
1.7
1.8
y
H
S
y
H
4
Z
1
1.9 P
B
y
x
Type 3432 with manual/automatic switch (1.6),
supply pressure regulator (1.9) and i/p converter
2.7 Flapper
2.8 Nozzle
2.9 Restriction 3 Controller module 4 Type 6112 i/p Converter
Z = Supply pressure 1.4 bar
= Output pressure
P
A
= Compressed air network
P
B
EB 7030 EN 13
Page 14
Principle of operation
5.3 Controller modules
The controller modules are designed as plug-in units. They are inserted into the self-sealing hose fittings of the controller sta tion and fastened in place by mounting screw.
5.3.1 Type 3433 Controller Modules
The controller modules consist of the com parator equipped with four metal bellows arranged in a square and the base plate with plug-in connections. The base plate contains the components necessary for the corresponding function such as relays and restrictors. The components can be ex­changed or retrofitted to upgrade a device (refer to section 9.1 for more details).
Type 3433-2 PI Controller (Fig. 7, top) The controlled variable x (actual value) and
the reference variable w (set point) are transmitted as pneumatic signals between
0.2 and 1 bar to metal bellows w und x
over the turnboard A. When x is greater than w, the actual value bellows tilts the swashplate at its pivot towards the set point bellows. This causes the pressure to rise downstream of the nozzle which is con nected to the swashplate over a pin and, as a result, the comparator increases the output pressure y
. The output pressure is fed back
A
over turnboard B to the bellows R2 on the swashplate. The pressure and the position of the swashplate continue changing until the dis tance between the nozzle and flapper achieve the initial value and the output pres
-
-
-
sure y
reaches the value related to the con
A
trolled variable x and the proportional-ac tion coefficient K
Outside of the controller module, y
­nected to R, meaning that the output pres
sure y
is also fed back to bellows R1 over
A
port R and the adjustable T
set at the screw.
p
restriction. As a
n
result, the effect caused by the pressures in bellows R1 and R2 is balanced and system deviation is eliminated.
Should a switching pressure exist at port S after switching the controller station to man ual mode, the T
start-up relay.
the T
n
restriction is bypassed by
n
Turnboard A determines the operating action of the controller which can be changed by turning the board. Refer to sec­tion 2.1.1.
Turnboard B determines the air supply to the feedback bellows. In delivered state, it is set to y
, i.e., the
A
output pressure is directly fed back to bel­lows R2, whereas, it is fed to bellows R1 over the manual control unit to port R. This arrangement provides the controller with a normal air supply and a damping of the out put pressure. Setting it to R results in the output pressure
being fed back to bellows R1 and R2
y
A
over port R which provides a higher air sup ply. This type of turnboard setting is suitable for applications where the distance to the final control element is long and the connected volume is large as well as where controlled systems react quickly. Refer to section 2.1.2 to set or change the air supply by turning the turnboard B.
-
is con
A
-
-
-
-
-
-
-
14 EB 7030 EN
Page 15
0.2
Kp
20
0.2
Kp
20
Principle of operation
Type 3433-2 PI Controller Module
The following versions of the controller mod ules are similar in most aspects to the Type 3433-2 PI Controller Module, how
­ever, they are fitted with, for example, an operating point adjuster, derivative element, or a selector switch, depending on the application.
Type 3433-1 P Controller Module
corresponds to Type 3433-2. An operating point adjuster is used in place of the integral element.
-
R Feedback R1/R2 Feedback bellows Z = Supply air 1.4 bar
Output pressure
Y
A
S Switching pressure
Fig. 7 · Type 3433 Controller Modules
A Operating action B Air supply
Turnboards
0.2
Kp
20
Type 3433-3 PID Controller Module
corresponds to Type 3433-2. Additionally, it contains a derivative element which produces the rate action with approx imately ten times the gain in the input branch of the controlled variable x. The rate time can be adjusted at the T
restriction.
V
EB 7030 EN 15
-
Page 16
Principle of operation
Type 3433-4 PD Controller Module
corresponds to Type 3433-1. Additionally, it contains a derivative element which produces the rate action with approx imately ten times the gain in the input branch of the controlled variable x. The rate time can be adjusted at the T
restriction.
V
Type 3433-5 P/PI Controller Module
with P/PI selector switch can optionally be used as a P controller with operating point adjustment or as a PI controller. The structure is the same as that of the PI and P controller module. Type 3433-6 PD/PID Controller Module with PD/PID selector switch can optionally be used as a PD or PID controller.
0.2
-
Kp
20
0.2
Kp
20
Type 3433-9 P Controller Module
with set point-dependent operating point corresponds to Type 3433-1 P Controller Module, except that the operating point shifts proportional to the set point w.
16 EB 7030 EN
0.2
Kp
20
Fig. 8 · Type 3433 Controller Modules
Page 17
Principle of operation
5.3.2 Type 3434 Controller Modules
The controller modules have a round com parator which operates according to the force-balance principle. The proportional-action coefficient K be adjusted in the range between 1 and 25.
Type 3434-2 PI Controller Module (Fig. 9) Controlled variable x and reference variable
w are transmitted as pneumatic excess pres sures between 0.2 and 1 bar or 3 and 15 psi to the diaphragm chambers (R1 and R2) over the turnboard A. When x is greater than w, the force switch (23) lowers and the plug opens. Supply air flows into the dia­phragm chamber R2 and the output pres­sure y ted over the T
increases. This pressure is transmit-
A
restriction (10) to the volume
n
of the 1:1 booster (24). Its output pressure is fed back to the diaphragm chamber R1.
24
10
R
w
Z
y
A
S
A
T
n
-
can
p
9 8
K
p
The effect caused by the pressures in the di aphragm chambers R1 and R2 is balanced. The position of the force switch continues to change until the controller output pressure reaches a value which is related to the con trolled variable x and the adjusted propor tional-action coefficient K
i.e. until the sys
p,
tem deviation is eliminated. The proportional-action coefficient K justed at the restriction (9) and the reset time
at the restriction (10). The zero point ad
T
n
juster (8) is used to tune the device.
-
The turnboard A determines the controller’s operating action which can be changed by turning the board (section 2.1.1).
Type 3434-1 P Controller Module
The design and principle of operation are the same in most aspects to Type 3434-2 PI Controller Module. However, a spring for an operating point fixed at 0.6 bar is used instead of the feed­back with T
restriction.
n
8 Zero point adjuster 9K
P
adjuster
10 T
n
21 Diaphragms
R1
23 Force switch 24 Booster
21 R2
R1 Diaphragm chamber
23
R2 Diaphragm chamber A Turnboard for operating
action
adjuster
p
is ad
-
-
-
-
-
-
x
Fig. 9 · Type 3434-2 Controller Module
EB 7030 EN 17
Page 18
Principle of operation
5.4 Additional modules
5.4.1 Type 6112 i/p Converter
External reference variable w
and/or con
ext
trolled variable x can be issued as a current signal of 4(0) to 20 mA or 1 to 5 mA and converted by the i/p converter into a pneu matic standardized signal of 0.2 to 1 bar. The i/p additional module with one or two converters is integrated into the controller station and can only be used in conjunction with the Type 3433 Controller Modules.
5.4.2 w
int/wext
selector switch
When used as a combination of fixed set point controller and follower controller, the controller is fitted with a w
int/wext
selector switch. The associated set point adjuster and differ­ential pressure indicator allow a smooth switchover when the indicator is at zero. Re­fer to section 3.3.
5.4.3 Supply pressure regulators
When a supply pressure regulator is mounted onto the Type 3432 Controller Sta tion, it is suitable for the connection to an operating pressure of 2.0 to 12 bar. The Type 3708-5003 Supply Pressure Regu lator (Var.-ID 1023317) reduces and con trols the operating pressure to the required supply pressure of 1.4 bar.
-
-
-
Connecting plate with two i/p converters
for controlled variable x and external set point
Adjuster for internal set point
w
selector switch
-
int/wext
-
18 EB 7030 EN
Supply pressure regulator
Fig. 10 · Additional modules
Page 19
5.4.4 Inductive limit switches
The inductive limit switches indicate when the controlled variable x exceeds and/or falls below an adjustable limit value.
Two metal tags are mounted to the pointer shaft of the controlled variable x which acti vate associated proximity switches. When the metal tag moves into the field of the inductive pick-up, it is highly resistive and when the metal tag moves outside of the field, it is low resistive.
The proximity switches are located in adjust able brackets. The required switching point can be adjusted by turning the brackets. Re­fer to section 2.2 for more details.
Principle of operation
-
-
EB 7030 EN 19
Page 20
Installation
6 Installation
6.1 Mounting
The controller station is designed for mount ing onto pipes, walls or in panels. Refer to Figs. 11 and 12 for the correspond ing dimensions.
Active sensor length
Air sensor
Ø19.5
Ø12
300
400
Type 3432 with Type 3436 Temperature Transmitter
300
425
Ø7
192
303130 30 16
26278/938
124
Pipe mounting
Mounting to vertical or horizontal 2" pipes using a mounting part with bracket. Required mounting kit: Order no. 1400-6302.
­Protective roof (accessories):
-
Order no. 1400-6311
Mounting plate
Bracket
Pipe 2”
Cable gland M 20x1.5
10
Protective roof
16069
40
2845
13
Ports: 26 x Controlled variable 27 wext Ext. set point 8/9 Supply air Z 38 y Manipulated variable
Fig. 11 · Installation dimensions of Type 3432 Controller Station
241
36
10
Process fluid connection Type 3432 with Type 3435 Pressure Transmitter
29
5
26278/938
Tapped ports ISO 228/1-G 1/8
20 EB 7030 EN
Air connections
160
228 8 228 8
28
13
Page 21
Installation
Wall mounting
Mounting using three straps Required mounting kit: Order no.1400-6301
Panel mounting
Mounting using four mounting elements (DIN 43835). Distance between centers to door approx. 235 mm. Close arrangement in rows without door acc. to DIN IEC 61554 (DIN 43700).
192
30 30 30 16
Pipe 2”
Cable glands M20x1.5
Ø7
26278/9 38
124
Type 3432:
+1
Panel cut-out 188
x 255+1mm, Required panel mounting kit: Order no. 1400-6300.
Type 3431:
+1
Panel cut-out 188
x 138+1mm, Required panel mounting kit: Order no. 1400-6303
Protective roof (accessories): Order no. 1400-6311
Mounting plate
Bracket
Pipe 2”
16069
10
Protective roof
2845
13
Ports: 26 x Controlled variable 27 wext Ext. set point 8/9 Supply air Z 38 y Manipulated variable
Fig. 12 · Installation dimensions of Type 3431 Controller Station
5
26278/9 38
241
10
Air connections Tapped ports ISO 228/1-G 1/8
160
144 8 144 8
28
13
EB 7030 EN 21
Page 22
Installation
6.1.1 Changing scales
After unlocking the door (4, Fig. 4), the scale can be removed from the back of the display and, if necessary, replaced with a special scale. The scale division of the scale must match the measuring range of the connected or in tegrated transmitter.
Adhesive strips are attached to inside the casing for tag labeling on the scale.
Cut the strips to size and stick them on
4
the scale.
6.2 Installing the temperature sensor
Only applies to controller stations with Type 3436 Transmitter Module
Bulb sensor Ø 12 mm, length 425 mm (ac tive length 300 mm)
­The bulb sensor can be installed in any position. However, the entire length of the sensor must be immersed in the medium to be controlled.
Choose a point of installation where over heating or noticeable time delays cannot oc cur. Run the capillary tube in such a way that the large temperature deviations cannot occur (ambient temperature approx. 20 °C) and the tube cannot be damaged. The smallest possible bending radius is 50 mm.
A sleeve with G ½ or G ¾ female thread at the point of measurement is required to in­stall the sensor. Screw or seal one of the mounting parts shown in Fig. 13 into this sleeve.
-
-
-
22 EB 7030 EN
Note!
The mounting parts are not included with the sensor. They must be ordered separately. Select which mounting parts are needed de pending on the operating conditions at the point of measurement.
-
Page 23
Installation
Mounting parts for bulb sensor Ø 12 mm, length 425 mm
Clamping flange
For wall mounting, e.g. pressureless containers or ducts
Order no. 1090-9547
Mount flange to wall using two screws and attach temperature sensor with two other screws in the flange.
Screw gland (PN 10) G ½ Order no. 1080-4881
G ¾ Order no. 1080-4882
Fill screw fitting with sealant. Insert sensor with screw gland and coupling nut. Tighten coupling nut.
Screw gland (PN 40) with clamping nut G ½ Order no. 1080-4884
G ¾ Order no. 1080-4885
Install as described above. Tighten clamping nut instead of coupling nut.
Thermowell with thread (PN 63) G ½ Order no. 1080-4888
G ¾ Order no. 1080-4889 Use a thermowell when the nominal pressure is
exceeded, when corrosive media are involved or when the plant is to continue to run while the sensor is being replaced.
Insert sensor right to the bottom of the thermowell. Tighten coupling nut.
32
8 Ø50
Ø26
G
G
Ø16
385
Ø21.3
Ø12
Ø9.5
SW 32
SW 32
136
12
30
G SW 32
SW 32
55
75
Thermowell for welding (PN 63) Order no. 1080-4890
Thermowell with flange
Order no. 1080-4891 (PN 40)
1080-4892 (PN 100)
Note: All wetted parts of the screw gland and thermo wells are made of stainless steel 1.4571.
Fig. 13 · Mounting parts for bulb sensor
375
SW 32
-
Ø21.3
335 40
EB 7030 EN 23
Page 24
Connections
7 Connections
7.1 Pneumatic connections
The air connections underneath the device are designed as bores with ISO 228/1­G 1/8 thread. The customary fittings for pipes or plastic hoses can be used.
Note!
The supply air must be dry and free from oil and dust. The maintenance instructions for upstream pressure reducing stations must be observed. Blow through all air tubes and hoses thor­oughly prior to connecting them.
The connection designations with codes are cast underneath the housing. They can additionally be marked on the back of the housing using the adhesive label supplied with the controller station.
38 Output y – Manipulated variable, Output signal of the controller to operate the control valve or positioner.
8/9 Supply – Supply air , Supply air 1.4 ±0.1 bar or 2 to 12 bar for the version with supply pressure regulator (see section 5.4.3).
27 Input w Closed with fixed set point controller and open for the connected external set point
with follower controller.
26 Input x – Controlled variable, Closed with pressure or temperature control
ler (controlled variable is recorded by the transmitter module). Open with standardized controllers.
– External reference variable,
ext
7.1.1 Typical applications
Controller for standardized signals
26MU8/9
Z
x
0.2...1 bar
Temperature controller (with Type 3436)
Sensor
Pressure controller (with Type 3435)
Process fluid connection
-
to measure pressure: Connection to pipe, pressure vessel, etc.
Fig. 14 · Standard applications
Supplyy0.2 ...1 bar
8/9
Z
Supplyy0.2 ...1 bar
8/9
Z
Supplyy0.2 ...1 bar
MU – Transmitter STR – Positioner
38
STR
38
STR
38
STR
24 EB 7030 EN
Page 25
7.1.2 Adjusting the supply air for version with supply pressure regulator
Connections
Only applies to Type 3432 Controller Sta tions with supply pressure regulator (1.9).
Hose connections for supply air are located directly above the corners of the supply pressure regulators on the bridge of the connecting plate (inside housing). The con nections are sealed by the hose end fittings.
Pull left end fitting off and use a hose to
4
connect it to a test pressure gauge. Controller stations with a manual/auto
4
matic selector switch have a test connec­tion (yellow) inside the indicating unit. Use the enclosed test connector for this version (Fig. 15). Unscrew cap of the pressure controller.
4
Undo the lock nut on the spindle and ad­just the spindle:
Turn the spindle clockwise to increase the
4
supply pressure and counterclockwise to reduce it.
Secure the position of the spindle with
4
the lock nut and screw the cap back on when the supply pressure at the test pres sure gauge indicates a pressure of
1.4 ±0.1 bar (20 ±1.5 psi).
-
-
Fig. 15 · Test connection with test connector
-
-
EB 7030 EN 25
Page 26
Connections
7.2 Electrical connection
The electrical components only apply to controller stations with i/p converter addi tional modules for controlled variable x, ex ternal reference variable wext and/or with inductive limit switches.
Caution!
For electrical installation, you are re quired to observe the relevant elec trotechnical regulations and the acci dent prevention regulations that ap ply in the country of use. In Germa ny, these are the VDE regulations and the accident prevention regula­tions of the employers' liability insu­rance association. The following standards apply for assembly and installation in hazar­dous areas: EN 60079-14: 2003 (VDE 0165 Part 1/8.98) "Electrical
apparatus for explosive gas atmo­spheres" and EN 50281-1-2: 1999 (VDE 0165 Part 2/11.99) "Electrical apparatus for use in the presence of combustible dust".
For the interconnection of intrinsical ly safe electrical equipment, the per missible maximum values specified in the EC type examination certifica te apply (U or C0, and Lior L0). Note! The terminal assignment spe cified in the Mounting and Opera ting Instructions must be adhered to. Reversing the assignment of the elec trical terminals may cause the explo sion protection to become ineffective. Do not tamper with painted screws.
or U0; Iior I0; Pior P0; C
i
Note on the selection of cables and wires: To install intrinsically safe circuits, observe section 12 of the standard EN 60079-14:
-
2003 (VDE 0165 Part 1).
-
To run multi-core cables or lines with more than one intrinsically safe circuit, section
12.2.2.7 of this standard applies. Devices used at ambient temperatures down to –40 °C must have metal cable entries.
-
-
The terminals on the base plate can be ac
-
cessed after unscrewing the front cover be
-
neath the display. For operation of the limit
-
switches, switching amplifiers which comply with EN 60947-5-6 must be connected in the output circuit.
Type 3432
Controller Station
i/p converter
12 11 21 22 42 41 52 51
–+
+– –+ –+
w
x
ext
4(0)...20 mA
Sw. amplifier
-
-
Type 3431
Controller Station
-
i
-
-
-
-
Fig. 16 · Connecting i/p converters and limit switches
+ –
+ –
Sw. amplifier
Limit switches
42 41 52 51
Limit switches
i/p converter
– +
+ –
22 21 11 12
w
ext
4(0)...20 mA
-
-
x
26 EB 7030 EN
Page 27
Maintenance
Type 3438
–++
T
I
4...20 mA
+–
43
11 12 13
+
L
~
N
24V– EEx i
PE
14
W
Y
H
Y
A
PID
I
X
P
Y38W
Z 8/9
Supply Output External
Setpoint
Sensor connection: No line compensation is required
ϑ
+–34
+
Safe area Ex zone 1
Fig. 17 · Electrical wiring of Type 3432 Controller Station with Type 3438 Transmitter Module
EEx i
+
Pt 100
8 Maintenance
with four-wire connection. The resistance of the wires must be identical and the
permissible line resistance of 50Wper wire is not to be exceeded.
The sensor lines are to be routed separately from relay or contactor lines.
This filter needs to be cleaned or replaced when the display for the controlled variable
8.1 Checking the air supply
The modules of the pneumatic controllers normally do not require any maintenance. However, the air supply should be checked regular intervals. The proper functioning of the device can only be guaranteed when the compressed air supplied to the device is always in a clean condition. Check the air filter and traps of the reducing station at regular intervals. If necessary, when the performance worsens, clean or re place the appropriate filters.
Transmitter module:
A hose grommet fitted on the hose for sup
does not work (order no. 0550-0193).
Type 3433 Controller Module:
In case the controller module does not con trol properly or there is no output signal, un screw the restriction (7, Figs. 2 and 17) on the left side underneath the comparator and clean or replace it (order no.1390-0183). Pull out the filter, if need be, and replace it (order no. 0550-0193). The hose connections of the controller mod ule are also fitted with filters (order no. 0550-0186).
-
Additionally, the ports underneath the hous ing are fitted with plastic-rimmed filters which can be unscrewed and cleaned (order no. 0550-0189).
-
ply air which includes a filter.
ext
27
-
-
-
-
EB 7030 EN 27
Page 28
Conversion
Undo bolts (3.3) and pull connecting
9 Conversion
4
plate (3.2) together with bolts and hex
9.1 Changing the controller function
The controller function can be changed ei ther by exchanging the entire module (Type 3434-1 or Type 3434-2) or by up grading or altering (Type 3433) components such as adjusters, restrictions or differential amplifier.
-
-
nuts off the controller module. Detach and mount the corresponding
4
cover plates and adjusters by unfasten ing the M3 hexagon socket head screws inside the housing.
P into PI: Unscrew adjuster for operating point (12) and replace it with T
restriction
n
(10).
P into P/PI: Unscrew adjuster for operating
Type 3433 Controller Module:
Unscrew the mounting screw (6) at the
4
controller module and pull it off the self-sealing hose fittings. Remove it from the controller station.
point (12) and replace it with a selector switch with operating point adjuster (13)
restriction (10).
and T
n
P into PD: Unscrew cover plate (14.1). Take out O-ring (14.3) and insert two O-rings (14.4) in its place. Screw on differential
Part Quantity Designation Order no.
10
10.1
10.2
11
11.1
11.2
11.3
12 12
12.1
12.2
13
13.1
13.2
14
14.1
14.2
14.3
14.4
15 1 Plate with restriction for set point-dependent operating point 1590-1089
1
Tnrestriction
2
Screws M3x8
3
O-rings 1.78 x 1.02
1
Tvrestriction
1
Cover plate
2
Screws M3x8
4
O-rings 2 x 1.5
1
Operating point adjuster 1.4 bar 1 2
Screws M3x8 4
O-rings 1.78 x 1.02
1
Selector switch with operating point adjuster 2
Screws M3x30 4
O-rings 1.78 x 1.02
1
Differential amplifier 1
Cover plate 1
Screws M3x16 1
O-ring 14 x 1.5 for plate
4 (2)
O-rings 2 x 15
20 psi
1070-4584 8333-0479 8421-0010
1070-4585 0360-1597 8333-0479 8421-0023
1070-4583 1070-6413 8333-0479 8421-0010
1180-3615 8333-0482 8421-0010
1080-6924 0360-1598 8333-0476 8421-0070 8421-0023
-
28 EB 7030 EN
Page 29
Conversion
amplifier (14). Unscrew cover plate (11.1) and mount T
restriction (11).
v
P into PID: Modify as described for P into PD. Additionally, replace adjuster (12) with
restriction (10).
T
n
P controller with set point-dependent oper ating point: Fasten the plate with restriction
P in PI
6
3.2
3.3 10 12 (15)
14.1, 14.2 11.1, 11.2
(15) in place of the adjuster for operating point (12).
Note!
We recommend replacing old O-rings as well as the filter in the restriction (7) with
-
new ones.
P/PI
14.1, 14.2 11.1, 11.2
P in PD
13 10
12
10 12
14 11
Filter
Restriction (7)
14.3 14.4 10.2
Fig. 18 · Changing the controller function of Type 3433
14.4 10.2
EB 7030 EN 29
Page 30
Conversion
9.2 Exchanging the transmitter module
The Type 3435 and Type 3436 Transmitter Module are fastened to the Type 3432 Con troller Station over six screws. The supply air x is connected over two sili cone hoses.
The transmitter module can be replaced when a measuring element is defective or the measuring range is to be changed. When you order a new module, you need to provide information on the sensor version and the required measuring range. In addi tion, please state the specifications con­tained on the nameplate of the old transmit­ter module.
1 Unscrew the front plate located under-
neath the display. Unfasten the corre­sponding terminals for modules with electrics.
2 Pull off the hoses for controlled variable
x and supply air Z on the housing connecting plate.
3 Unfasten the six mounting screws on the
bottom of the controller station and re move the transmitter module.
4 Mount the new transmitter in the reverse
order.
On attaching the hoses to ports x and Z, it is important not to get them confused. The supply air hose is fitted with a hose grommet which contains a restriction and filter.
-
-
-
Hose grommet
-
Controlled variable x Supply air Z
Fig. 19 · Connecting plate
9.3 Checking the controller function
To check the controller, the controlled vari­able and the manipulated variable must be bypassed at the ports x (26) and y (38) on the bottom of the controller station.
Set the turnboard A to 34 increasing/decreasing,
restriction to “fully open” and
the T
n
restriction to “closed”.
the T
v
Change the reference variable at the set
4
point knob over the entire range. If the controller works properly, the controlled variable pointer (red) and the manipu lated variable pointer (small pressure gauge) follow the reference variable over the whole display range.
-
30 EB 7030 EN
Page 31
Use in hazardous areas
10 Use in hazardous areas
The Type 3430 Controller Station is suitable for use in potentially explosive atmospheres in Zones 1 and 2, even though it does not have its own EC-type examination certifi cate. The controller station does not require an EC-type examination certificate accord ing to 94/9/EC (ATEX).
Conditions for use in hazardous areas:
The controller station is not marked as an
4
explosion-protected device with the cor responding approval mark. All installed explosion-protected modules
4
possess their own EC-type examination certificate. The maximum values specified in the as-
4
sociated EC-type examination certificate apply to the connection to intrinsically safe circuits. The installation, wiring, terminals, cable
4
entry and other components relevant for explosion protection comply with DIN EN 50014, DIN EN 50020 and DIN EN 60079-14 (VDE 0615). The transparent door or window of the
4
controller station has a conductive coating to prevent electrostatic charging. The measuring circuit of the transmitter
4
model TTH200-E1H has a protection level corresponding to “ia” and can be connected to sensors which are routed into Zone 0. The transmitter itself must be installed in areas of Zone 1 or Zone 2.
Caution!
Observe the following for installations in po tentially explosive atmospheres: On install ing and performing service work on the de
-
vice, ensure that no electrostatic charging can arise due to the high surface resistivity
= 1012ohm).
(R
-
insul.
-
-
-
10.1 Servicing explosion-protected devices
­If a part of the apparatus on which the ex
plosion protection is based needs to be ser viced, it must not be put back into operation until an expert has inspected the device ac­cording to explosion protection require­ments, has issued a certificate stating this or given the device a mark of conformity.
Inspection by an expert is not required if the manufacturer performs a routine check on the device prior to putting it back into oper­ation. The passing of the routine check must be documented by attaching a mark of con­formity to the device.
Explosion-protected components may only be replaced by original, checked compo nents from the manufacturer.
Devices that have already been used outside of hazardous areas and are intended for use in hazardous areas in future must com ply with the safety demands placed on re paired devices. Prior to operation, they must be tested according to the specifications stip ulated for "Repairing explosion-protected devices".
-
-
-
-
-
-
EB 7030 EN 31
Page 32
Technical data
11 Technical data
Type 3432 and Type 3431 Controller Station
Actual value display Measuring range 0.2 to 1.0 bar (3 to 15 psi) · Accuracy class 1.6 · Scale length 212 mm Set point adjustment Output 0.2 to 1.0 bar (3 to 15 psi) · Scale length 212 mm · Accuracy class 1.6 Adjuster for
manual mode
Limit switches
i/p converter
Output 0.2 to 1.0 bar (3 to 15 psi) · Max. 0.02 to 1.35 bar · Max. air supply: >1.5m
1 or 2 SC 3,5-NO-YE proximity switches acc. to DIN EN 60947-5-6 (NAMUR)
Type of protection II 2 G EEx ia IIC T6 (PTB 99 ATEX 2219 X)
Input 4 (0)...20 mA, output 0.2 to 1 bar or 3 to 15 psi for controlled variable x or
external set point w
ext
Upgradable with
Contr. Module Type 3434-1 3434-2 3433-1 3433-2 3433-3 3433-4 3433-5 3436-6 3433-9
Controller function P PI P PI PID PD P/PI PD/PID P Proportional-action Kp= 1 to 20 Kp= 0.2 to 20 (0.4 to 40) Reset time Tn[min] 0.05...20 0.03 to 50 Rate time [min] 0.01 to 10 · Derivative-action gain of x: approx. 10 Optionally with
Additional Module Type
Signal Limiter
3437-1
Control Mode
Selector Switch
3437-2
Manual/auto Transfer Switch
3437-3
Output 0.2 to 1 bar (3 to 15 psi) · Max. 0.02 to 1.35 bar
Supply air
Air quality acc. to ISO 8573-1
Standard version: Supply air 1.4 bar±0.1 bar (20 psi±1.5 psi)
Air consumption < 0.6 m
With supply pressure regulator: Operating air 2.0 to 12 bar (30 to 180 psi)
Air consumption < 0.75 m
With i/p converter: w
Max. particle size and density: Class 3 · Oil content: Class 2 · Pressure dew point: Class 3 or
at least 10 K beneath the lowest ambient temperature to be expected
: +0.13 m
ext
3
/h
n
3
/h
n
3
/h
n
Perm. ambient temp. –20 °C to +60 °C (–40 °C to +60 °C on request) Degree of protection IP 40, IP 65 front with door Total weight, approx. 6 kg Type 3435 Transmitter Module for Pressure Measuring range [bar]
(set point range)
0 to 1.6 0 to 2.5 0 to 4 0 to 6 0 to 16 0 to 25 0 to 40
Overloadable up to 1.25 times the upper measuring range value Ultimate strength up to Double times the upper measuring range value (max. 63 bar at 0 to 40 bar)
Performance
Deviation from terminal-based linearity:£0.3 % with terminal-based conformity
Hysteresis:£0.5 % · Overloading to permissible value:£0.1 %
Ambient temperature:£0.04 %/°C
Influence
Supply air:£0.25 %/0.1 bar
Overload on permissible value£0.1 %
3
n
/h
32 EB 7030 EN
Page 33
Technical data
Type 3436 Transmitter Module for Temperature
Measuring span °C 50 100 150 200
Measuring limit °C
–40 to +200 or
150 to 300 Standard ranges °C –20 to +30 0 to 100 50 to 100 0 to 200 Overload limit 350 °C Perm. pressure at sensor Without thermowell: PN 16 With thermowell PN 63 or PN 100 Supply air Supply air 1.4 ± 0.1 bar (20 ±1.5 psi) Output 0.2...1.0 bar (3...15 psi) Deviation from terminal-based
linearity
0.6 % with terminal-based conformity
Hysteresis < 0.25 % Influence Supply air: < 0.25 %/0.1 bar
Pressure at sensor < 0.6 %/10 bar < 0.25 %/10 bar < 0.15 %/10 bar Ambient temperature < 0.6 %/°C < 0.03 %/°C
Type 3438 Transmitter Module, consisting of Temperature Transmitter TTH200-E1H with Type 6112-22 i/p Converter Module
Electric Temperature Transmitter TTH200-E1H
Input Pt 100 resistance thermometer (RTD)
Measuring ranges
Connection Four-wire circuit, resistance per wire < 50 ohm Measuring current < 0.3 mA Output 4 to 20 mA, linear to temperature Current consumption < 3.5 mA Maximum output current 23.6 mA Supply voltage Two-wire system: Power supply lines = Signal lines
Use in safe area U Use in hazardous area U
Max. load R
B
Explosion protection II 2(1) G EEx [ia] ib IIC T6 acc. to ATEX EC-type examination
certificate
–30 to 60 °C, 0 to 40 °C, 0 to 100 °C, 0 to 150 °C, 0 to 200 °C, 0 to 400 °C,
other ranges on request
= 16 to 30 V
S
= 16.5 to 28 (25) VDC, see EC-type examination certificates
S
The supply voltage USdetermines the max. load: RB<
PTB 05 ATEX 2017 X
–40 to +300
DC
(U 16.5 V)
S -
0.022 mA
EB 7030 EN 33
Page 34
Technical data
Electric Temperature Transmitter TTH200-E1H
Fault indication
Sensor breakage > 22 mA Sensor short-circuit < 3.6 mA Sensor wire breaking < 3.6 mA or > 22 mA Supply voltage with reverse
poles
Deviation from terminal-based
0.1% or£0.2 K (whichever value is greater)
£
linearity Influence of ambient
0.08 %/10 K for lower measuring range value and measuring span,
£
temperature Influence of supply voltage < 0.5 %/10 V Output signal refreshment rate 0.4 s when the input signal changes < 0.25 K/s Electrical isolation (I/O) 3.5 kV Long-term stability
0.05 % or 0.1 K per year (whichever value is greater)
£
(approx. 2.5 kVAC), 60 s, input/output
DC
Type 6112- … i/p Transmitter Module
Type 6112-02 without explosion protection
Type 6112-22 with explosion protection
1)
Intrinsically safe input circuit · Input impedance 200Wand ~ 0 mH
Input impedance 200Wand ~ 5.9 mH
Explosion protection II 2 G EEx ia IIC T6 EC-type examination certificate PTB 00 ATEX 2021 Input 4 to 20 mA or 0 to 20 mA Output 0.2 to 1 bar or 3 to 15 psi Supply air 1.4 bar ± 0.1 bar (20 psi ± 1.5 psi), air consumption < 0.1 m Performance Characteristic: Output linear to input Influence Hysteresis£0.3 % · Deviation from terminal-based linearity£0.1 % (fixed set point)
Supply air 0.1 %/0.1 bar Ambient temperature < 0.03 %/K for lower measuring range value and measuring span, based on 20 °C
Perm. ambient temperature range
1)
Refer to attached EC-type examination certificates for details (on permissible temperatures, effective internal capacitance and inductance)
0 mA
based on 20 °C
–40 to +60 °C
3
/h
n
1)
34 EB 7030 EN
Page 35
EB 7030 EN 35
Page 36
36 EB 7030 EN
Page 37
EB 7030 EN 37
Page 38
38 EB 7030 EN
Page 39
EB 7030 EN 39
Page 40
40 EB 7030 EN
Page 41
EB 7030 EN 41
Page 42
42 EB 7030 EN
Page 43
EB 7030 EN 43
Page 44
44 EB 7030 EN
Page 45
EB 7030 EN 45
Page 46
46 EB 7030 EN
Page 47
EB 7030 EN 47
Page 48
48 EB 7030 EN
Page 49
EB 7030 EN 49
Page 50
50 EB 7030 EN
Page 51
EB 7030 EN 51
Page 52
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 7030 EN
S/Z 2010-11
Loading...