Samson 3430, 430 Series, 3431, 3434-1, 3434-2 Operating Instructions Manual

...
Series 430
Pneumatic Indicating Controllers Type 3430
– with Type 3435 Transmitter Module for Pressure – with Type 3436 Transmitter Module for Temperature – with Type 3438 Transmitter Module for Temperature (Pt 100) – for standardized signals
Version shown with lockable door and integrated Type 3436 Transmitter Module for Temperature
Fig. 1 · Controller stations
Mounting and Operating Instructions
EB 7030 EN
Edition October 2010
– for standardized signals
Contents
Contents Page
1 Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Settings at the controller modules . . . . . . . . . . . . . . . . . . . . 4
2.1.1 Operating action . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2 Air supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.3 Proportional-action coefficient Kp . . . . . . . . . . . . . . . . . . . . 6
2.1.4 Reset time Tn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.5 Rate time Tv. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.6 Operating point. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Setting the limit switches. . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 Tuning the controller . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1.1 Setting the operating point in P and PD controllers . . . . . . . . . . . . 9
3.2 Smooth automatic/manual mode changeover . . . . . . . . . . . . . 10
3.3 Smooth changeover between the internal and external reference variable 10
3.4 Readjusting the controller’s zero point . . . . . . . . . . . . . . . . . 10
4 Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Transmitter modules . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Controller station . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3 Controller modules. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 Type 3433 Controller Modules . . . . . . . . . . . . . . . . . . . . . 14
5.3.2 Type 3434 Controller Modules . . . . . . . . . . . . . . . . . . . . . 17
5.4 Additional modules . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.4.1 Type 6112 i/p Converter . . . . . . . . . . . . . . . . . . . . . . . 18
5.4.2 w
selector switch . . . . . . . . . . . . . . . . . . . . . . . . 18
int/wext
5.4.3 Supply pressure regulators . . . . . . . . . . . . . . . . . . . . . . . 18
5.4.4 Inductive limit switches . . . . . . . . . . . . . . . . . . . . . . . . . 19
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.1.1 Changing scales. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.2 Installing the temperature sensor . . . . . . . . . . . . . . . . . . . . 22
7 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1 Pneumatic connections . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1.1 Typical applications . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1.2 Adjusting the supply air for version with supply pressure regulator. . . . 25
7.2 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2 EB 7030 EN
Contents
8 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.1 Checking the air supply . . . . . . . . . . . . . . . . . . . . . . . . 27
9 Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9.1 Changing the controller function . . . . . . . . . . . . . . . . . . . . 28
9.2 Exchanging the transmitter module . . . . . . . . . . . . . . . . . . . 30
9.3 Checking the controller function . . . . . . . . . . . . . . . . . . . . 30
10 Use in hazardous areas . . . . . . . . . . . . . . . . . . . . . . . . 31
10.1 Servicing explosion-protected devices . . . . . . . . . . . . . . . . . 31
11 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
General safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. According to these mounting and operating instructions, trained personnel is referred to as individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the relevant standards. Explosion-protected versions may only be operated by personnel who have
4
undergone special training or instructions or who are authorized to work on explosion-protected devices in hazardous areas. Any hazards that could be caused by the signal pressure are to be
4
prevented by means of the appropriate measures. Proper shipping and appropriate storage of the device are assumed.
4
EB 7030 EN 3
Application
1 Application
The Series 430 Pneumatic Indicating Con trollers are used for applications in process automation and industrial plants. The controllers directly measure the con trolled variables (pressure, temperature, electric or pneumatic standardized signal) and display the value. They compare the measured variable with the set point and is sue a corresponding pneumatic control sig nal from 0.2 to 1 bar (3 to 15 psi).
A supply pressure of 1.4 bar±0.1 bar (20 psi±1.5 psi) is required or an operat ing pressure of 2 to 12 bar (30 to 180 psi) when a supply pressure regulator is in­stalled.
-
2 Operation
-
2.1 Settings at the controller modules
The controller module in the station can be accessed after the lock (Fig. 2) has been re leased and the indicating unit (5) has been opened out.
-
The settings for operating action (turnboard
-
A) and air supply (turnboard B) must be performed prior to commissioning.
Unscrew the mounting screw (6) on the
4
-
controller module. Pull it off its self-seal ing hose fittings and lift out of the con­troller station.
2.1.1 Operating action
The operating action for the control loop is set at the turnboard A (Fig. 2), where the position of its arrow symbol according to the arrow symbol on the controller module de­termines the operation action of the control­ler.
34 Arrow tips facing opposite
directions: Operating direction: Increasing/decreasing = As the controlled variable x increases, the output signal pressure y decreases.
44 Arrow tips facing the same direction:
Operating direction: Increasing/increasing As the controlled variable x increases, the output signal pressure y increases.
-
-
4 EB 7030 EN
Operation
Setting or modifying the operating direction:
Unfasten the screw in turnboard A (Fig. 2) and lift it off together with the turnboard. If necessary, lever the board at the side. Do not lose the rubber seal.
Turn the board by 90° so that the re
4
quired arrow is aligned with the arrow on the base plate. Insert board and tighten screw.
4
Reassemble the controller module in the
4
controller station.
1 Controller station (Type 3432)
1
1.1 Scale
1.3
1.3 Actual value pointer (red)
1.1
1.4 Set point adjuster
4
2 Transmitter module
1.4
3 Controller module
5
3.1 Comparator
3.2 Connecting plate
3.3 Hex screws
2
Air supply
B
Oper. action
A 3.2 3.4 8 9 3.1
3.4 Screws (inside)
2.1.2 Air supply
(only with Type 3433 Controller Module) The position of the turnboard B (Fig. 2) with its arrow symbol determines the air supply to the feedback bellows. It can be accessed
-
after the comparator (3.1) has been re moved.
4yA Normal air supply, approx. 1 m
4R Large air supply, approx. 3 m
or connecting base
-
³/h
n
per % of the system deviation
³/h
n
per % of the system deviation (not with P or PD controller modules)
4 Lock 5 Indicating unit 6 Mounting screw 7 Restriction 8 Zero adjuster 9 Kp adjuster 10 Tn adjuster 11 Tv adjuster (only in
PD or PID controller)
12 Operating point adjuster
(only in P or PD controller)
63109
Type 3432 Contr. Module
Side view without comparator
Fig. 2 · Turnboards and adjusters
3.3 3 6
7
Type 3433-2 (PI) Controller Module
10 12
11
Type 3434-2 (PI) Controller Module
Oper. action
A
8
EB 7030 EN 5
Operation
Unfasten screws (3.3) and pull off the
4
connecting plate (3.2) together with nuts and bolts from the controller module. Unscrew the hexagonal socket-head
4
screws (3.4) at the side and lift the com parator (3.1) out of the controller mod ule.
Setting or modifying the air supply:
Unfasten screw in turnboard B and lift it
4
off together with the turnboard. If neces sary, lever the board at the side. Do not lose the rubber seal. Turn the board so that the arrow is
4
aligned with the mark yA or R on the controller module. Insert board and tighten screw. Reassemble the controller module in the
4
controller station.
2.1.3 Proportional-action coefficient Kp
2.1.5 Rate time Tv
For Type 3433 Controller versions with de rivative-action component, the rate time Tv needs to be set at the restriction (11). The
­setting depends on the controlled system that
­is being tuned (section 3.1).
2.1.6 Operating point
­Controller modules without integral-action
component such as P or PD controllers have an operating point. In Type 3433 Controller Module, it can be adjusted between 0 and 100 % which corresponds to 0.2 to 1 bar by an operating point adjuster (12). The setting depends on the manipulated variable y (sec­tion 3.1.1). In Type 3434 P Controller Module, the oper­ating point is fixed at 0.6 bar.
-
The setting of the KP(adjuster 9) determines the controller gain and is related to the con­trolled system that is being tuned (section
3.1).
2.1.4 Reset time Tn
Controller versions with integral-action com ponent require the reset time to be set at the restriction (10). The setting depends on the controlled system that is being tuned (section 3.1).
6 EB 7030 EN
-
2.2 Setting the limit switches
Only applies to controller stations with the limit switch option: To set the limit switches, first release the lock (4, Fig. 2) and open out the indicating unit (5). The contacts can be accessed at the back.
Adjust proximity switches by placing a screwdriver in the clamps between 0 and 100 % of the reference scale and move until a contact is made over the connected switch ing amplifier.
Clamps with proximity switch
Operation
-
Fig. 3 · Limit switches
EB 7030 EN 7
Commissioning
3 Commissioning
Prior to commissioning the control loop, check all devices to make sure they are con nected correctly, do not leak and function properly. Release lock (4) and open out the indicating unit (5) to enable easy access to the operat ing controls at the controller. Check the turnboard to make sure the cor
­rect operating action is set at the controller (see section 2.1.1).
3.1 Tuning the controller
The controller needs to be tuned to the char­acteristics of the controlled system using the
and Tnand/or Tvadjusters at the control-
K
P
ler module to ensure that the controller can keep any system deviations for all set points caused by the disturbance variables to zero or at least to minimize them.
In case of controller stations which have a manual/ automatic switch (1.6), the plant must be started up manually.
We recommend to determine the settings by using a tuning test (following the Ziegler and Nichols method) which produces sufficient results in most cases:
1. Apply supply air (1.4 ±0.1 bar).
2. Set the proportional-action coefficient K
to a low value at the comparator.
3. Set T
restrictor to its maximum value
n
and T
to its lowest value (applies only to
v
PI and PID controllers).
1.8
1.6
-
1.5
1.7
-
1.3 Actual value pointer (red)
1.4 Set point adjuster with green pointer
1.5 Signal pressure display
1.6 Manual/automatic switch
1.7 Adjuster for signal pressure (manual)
1.8 Differential pressure indicator 4 Lock 5 Indicating unit
Fig. 4 · Front view
Setting in manual mode:
4. Set manual/automatic switch to Manual.
5. Operate manual adjuster (1.7) for the control signal so that the controlled vari­able (actual value pointer 1.3) slowly settles on the adjusted set point (set point pointer 1.4). Should the differential pressure indicator (1.8) move to zero, set the manual/auto matic switch (1.6) to Automatic.
P
Proceed as described in points 6 and 7.
Setting in automatic mode:
4. Set the set point to the required value at the rotary knob (1.4) on the indicating unit.
5. Set the T
restriction briefly to its lowest
n
value (completely open) to move the red
1.3
1.4 4 5
-
8 EB 7030 EN
Commissioning
actual value pointer to the green set point pointer. Close the T
restriction
n
again.
6. Starting from a low value, increase the proportional-action coefficient K
P
until the actual value pointer displays an har monic oscillation pattern (uniform oscil lation amplitudes as shown in Fig. 5) of the controlled variable. If oscillations do not arise with a large K
setting, turn the rotary knob to
P
change the set point slightly and then re turn it to its former setting. It may be necessary to increase the gain (K
)
P
slightly until an harmonic oscillation pat­tern arises.
7. Write down the adjusted value of the K scale you have just adjusted as the criti­cal proportional-action coefficient K
Pkrit
Use a stopwatch to time the oscillation time for one entire oscillation as T
krit
(PI
and PID controller only).
Controlled variable (actual value)
Tkrit
+
Tkrit
Cntr. K
P 0.50 · K
PI 0.45 · K
PID 0.59 · K
Fig. 5 · Harmonic oscillation, settings
P
P,krit
P,krit
P,krit
T
n
0.85 · T
0.50 · T
T
v
krit
0.12 · T
krit
Multiply both values with the values in the table (Fig. 5) and set as the favor able settings for K
, Tn, and Tvat the
P
controller. Should oscillations still occur despite these settings, slightly reduce K
­Repeat these steps, if necessary, until the
­control loop shows a satisfactory perfor
and increase Tn.
P
mance. Leave enough time in between set ting to allow the controller to stabilize.
3.1.1 Setting the operating point in
-
P and PD controllers
(Type 3433 Controller Module only) After setting the proportion-action coefficient
as described previously, set the operating
K
P
P
point for P and PD controllers instead of the
.
reset time T
Read off the controlled variable yA of the
4
.
n
controller at the display (1.5) when the plant is in a steady-state condition and set this value directly at the operating point adjuster (12, Fig. 2). (Setting 0.2 to 1 bar = 0 to 100 %). Recorrect slightly until the system devia
4
tion is zero. In case the signal pressure display deviates, average the value.
Note!
On changing set point or reference variable, the operating point must be set again as de scribed above. If the reference variable is changed more of ten, set the operating point to 0.6 bar = 50 % (average value).
krit
-
-
-
-
-
-
EB 7030 EN 9
Commissioning
Note!
restriction must be completely opened
The T
n
with a P/PI controller is switched over to P action to allow the operating point adjuster to work without delay.
Version with w-dependent operating point
This version does not need to be adjusted since the operating point automatically fol lows the set point w.
-
3.2 Smooth automatic/manual mode changeover
(only for controller station with manual/au­tomatic changeover, Fig. 4)
The smooth switchover ensures that no pres­sure surges can reach the valve when the manual/automatic switch is activated as fol­lows:
Changeover from automatic to manual
Use the manual adjuster (1.7) to adjust signal pressure manual yH until the differen tial pressure indicator (1.8) is zero. Switch over to manual at the switch.
Differential pressure indicator
With Without deviation
adjuster (1.4). The switch (1.6) can only be set to automatic after the differential pressure indicator (1.8) is at zero.
Set the set point again to the required value.
3.3 Smooth changeover between the internal and external re ference variable
When combining the fixed set point control and follower control, the Type 3432 Con troller Station is equipped with a w switch, a pressure adjuster and a differential pressure indicator (Fig. 10). The differential pressure indicator must first be brought to zero by activating the pres­sure adjuster in order to switch between the reference variables.
3.4 Readjusting the controller’s zero point
Should deviations arise between the actual value and set point during operation, the zero point adjustment can be readjusted by
­turning the zero screw at the back of the dis
play unit (5) until the actual value and set point on the front display are the same again.
Deviations between the actual value and set point can also be corrected at the zero point adjuster (8, Fig. 2) of the controller module.
-
-
int/wext
-
Changeover from manual to automatic
If the plant is to be controlled manually to the required value, the automatic signal pressure yA must be matched to the manual signal pressure yH by adjusting the set point
10 EB 7030 EN
Construction
4 Construction
The controllers designed according to the modular principle form an entire automation unit consisting of a controller station, a con troller module tuned to the local conditions, and, where applicable, a transmitter as well as other additional modules.
Controllers with Type 3432 Controller Sta tion are mainly designed for installation of a Type 3435 Transmitter Module for Pressure or a Type 3436 Transmitter Module for Temperature with direct process fluid con nection. The Type 3431 Controller Station receives the controlled variable as a standardized signal from 0.2 to 1 bar or 3 to 15 psi. The controlled variable can also be supplied as a current signal from 4 or 0 to 20 mA or 1 to 5 mA over an integrated i/p converter.
The controller station can be equipped with the Type 3433 or Type 3434 Controller Module. For special control applications, the Type 3433 Controller Module can be combined with Type 3437 Additional Modules for pressure limitation, control mode switchover or smooth manual/automatic transfer. The controller station can also be upgraded, if required, with a manual/automatic trans fer, consisting of a selector switch, adjuster for manual mode, and differential pressure indicator. The controller station must be equipped with an additional module for w
int/wext
over when used for applications as a com bined fixed set point controller and follower controller. An additional pneumatic or elec tric output for the external reference variable
(e.g. 0.2 to 1 bar or 4 (0) to 20 mA)
w
ext
change
-
-
-
-
is likewise required when used as a follower controller. Additionally, inductive limit switches, that are adjustable at a scale, can be mounted on the indicating units 1 or 2.
-
Note! Refer to the corresponding Data Sheets for details about the controller sta tions and their controller modules.
T 7030 EN · Pneumatic Indicating Controllers - Information Sheet with product overview.
T 7032 EN · Pneumatic Indicating Controllers for Pressure
T 7034 EN · Pneumatic Indicating Controllers for Temperature with Capillary Sensor
T 7036 EN · Pneumatic Indicating Controllers for Temperature with Pt 100 Resistance Thermometer
T 7038 EN · Pneumatic Indicating Controllers for Standardized Signals
T 7040 EN · Type 3433 Pneumatic Controller Modules and Type 3437Additional Modules
T 7041 EN · Type 3434 Pneumatic Controller Modules
T 7045 EN · Type 6112 i/p Converter
-
Module
5 Principle of operation
5.1 Transmitter modules
Type 3435 for Pressure
The process fluid pressure p is transmitted to
-
the transmitter module (2) where it causes a deflection at the Bourdon tube measuring
-
EB 7030 EN 11
Principle of operation
system (2.1). The deflection is converted by the pneumatic servo system (2.2) into a pneumatic signal (controlled variable x) which is proportional to the pressure p. The signal is transferred to the bellows measur ing system of the actual value display (1.3) as well as to the controller module (3).
Type 3436 for Temperature with capillary sensor
The temperature of the medium produces a pressure in the gas-filled sensor (2.3) of the transmitter module which is proportional to the temperature. This pressure is offset by a force on the beam (2.4) and converted into the output pressure p
at the feedback bel-
A
lows (2.6). The supply air flows over the restriction (2.9) and nozzle (2.8) and hits the flapper (2.7). As the temperature rises, the flapper moves closer to the nozzle. This results in an in­crease in output air pressure p
supplied to
A
the bellows (2.6) until a new state of equilib­rium is reached, i.e. until the output signal is proportional to the temperature measured. This signal is transmitted as the actual value signal (controlled variable x) to the bellows measuring system of the actual value display (1.3) and the controller module (3).
Type 3438 for Temperature with Pt 100 re sistance thermometer
The Type 3438 Transmitter Module consists of an electric transmitter and a downstream i/p converter to connect a Pt 100 sensor. The resistance value of the Pt 100 sensor is converted into a 4 to 20 mA current signal in the electric transmitter. Its output signal (4 to 20 mA) is converted into a pneumatic sig nal between 0.2 and 1 bar by the i/p con verter. The output pressure, which is propor tional to the temperature, is supplied to the
bellows measuring system of the controlled variable display and the controller module as a pneumatic controlled variable signal (controlled variable x).
-
5.2 Controller station
The actual value signal x causes a deflection at the bellows measuring system of the ac tual value display (1.3) which is transmitted to the pointer over a gear mechanism. The set point (reference variable w) can be adjusted at the scale (1.2) on the front. The position of the set point adjuster (1.4) is transmitted to the set point transmitter over a gear mechanism. This pneumatic servo sys­tem (1.41) converts the adjusted set point into a pneumatic set point signal (w) which is transmitted to the controller module. The controller module compares the actual value signal (x) with the set point signal (w) and controls using the control signal yA de­pending on the system deviation and the ad­justed control parameters. The control signal is connected to the signal pressure display (1.5) and the output port y. The controller station with manual/auto matic switchover (Figs. 2 and 4) additionally features a manual/automatic switch (1.6),
-
an adjuster for manual mode (1.7), and a differential pressure indicator (1.8). Signal pressure display (1.5) and output port y are connected to the automatic output signal y matic” and to the manual output signal y set at the adjuster (1.7) with a switch posi tion at “Manual”.
-
A smooth switchover from manual to auto
-
matic mode is possible when the differential
-
pressure indicator (1.8) shows that y y
H
with a switch position at “Auto
A
are identical.
-
-
-
H
-
-
and
A
12 EB 7030 EN
Principle of operation
1.5 31.2
1
y
w
1.4 1.31.41 1.5 31.2 1.4 1.31.41
R w
PI
z
P
A
y
PPI
/
PID
S x
2.1
2
y
Z
2.2
Type 3432 with Type 3435 Transmitter for Pressure
1.5
1
y
w
1.2 1.4 1.3
3
R w
PI
z
P
A
y
PPI
/
S
PID
x
Zx
Type 3431 and 3432 for pneumatic standardized signals
1 Controller station
1.2 Scale
1.3 Actual value display with pointer, gear mechanism and bellows measuring system
1.4 Set point adjuster with pointer, gear mechanism and set point (1.41), set point display only for follower controllers
1.5 Signal pressure display
1.8 Differential pressure indicator for smooth manual/automatic switchover
1.9 Supply pressure regulator
2 Transmitter module
2.1 Bourdon tube meas. system
2.2 Pneumatic servo system
2.3 Temperature sensor
2.4 Beam
2.6 Feedback bellows
Fig. 6 · Principle of operation of controllers
1
2.4
2.6
2.3
wxwx
w
R w
PI
z
P
y
A
PPI
/
PID
S x
2.7
Z
y
2.9 2.8
Type 3432 with Type 3436 Transmitter for Temperature
y
A
w
1.21.41 1.4 1.3 3 w
xwx
R w
PI
z
P
A
y
PPI
S
PID
x
x
/
1.6
1.5
1.7
1.8
y
H
S
y
H
4
Z
1
1.9 P
B
y
x
Type 3432 with manual/automatic switch (1.6),
supply pressure regulator (1.9) and i/p converter
2.7 Flapper
2.8 Nozzle
2.9 Restriction 3 Controller module 4 Type 6112 i/p Converter
Z = Supply pressure 1.4 bar
= Output pressure
P
A
= Compressed air network
P
B
EB 7030 EN 13
Principle of operation
5.3 Controller modules
The controller modules are designed as plug-in units. They are inserted into the self-sealing hose fittings of the controller sta tion and fastened in place by mounting screw.
5.3.1 Type 3433 Controller Modules
The controller modules consist of the com parator equipped with four metal bellows arranged in a square and the base plate with plug-in connections. The base plate contains the components necessary for the corresponding function such as relays and restrictors. The components can be ex­changed or retrofitted to upgrade a device (refer to section 9.1 for more details).
Type 3433-2 PI Controller (Fig. 7, top) The controlled variable x (actual value) and
the reference variable w (set point) are transmitted as pneumatic signals between
0.2 and 1 bar to metal bellows w und x
over the turnboard A. When x is greater than w, the actual value bellows tilts the swashplate at its pivot towards the set point bellows. This causes the pressure to rise downstream of the nozzle which is con nected to the swashplate over a pin and, as a result, the comparator increases the output pressure y
. The output pressure is fed back
A
over turnboard B to the bellows R2 on the swashplate. The pressure and the position of the swashplate continue changing until the dis tance between the nozzle and flapper achieve the initial value and the output pres
-
-
-
sure y
reaches the value related to the con
A
trolled variable x and the proportional-ac tion coefficient K
Outside of the controller module, y
­nected to R, meaning that the output pres
sure y
is also fed back to bellows R1 over
A
port R and the adjustable T
set at the screw.
p
restriction. As a
n
result, the effect caused by the pressures in bellows R1 and R2 is balanced and system deviation is eliminated.
Should a switching pressure exist at port S after switching the controller station to man ual mode, the T
start-up relay.
the T
n
restriction is bypassed by
n
Turnboard A determines the operating action of the controller which can be changed by turning the board. Refer to sec­tion 2.1.1.
Turnboard B determines the air supply to the feedback bellows. In delivered state, it is set to y
, i.e., the
A
output pressure is directly fed back to bel­lows R2, whereas, it is fed to bellows R1 over the manual control unit to port R. This arrangement provides the controller with a normal air supply and a damping of the out put pressure. Setting it to R results in the output pressure
being fed back to bellows R1 and R2
y
A
over port R which provides a higher air sup ply. This type of turnboard setting is suitable for applications where the distance to the final control element is long and the connected volume is large as well as where controlled systems react quickly. Refer to section 2.1.2 to set or change the air supply by turning the turnboard B.
-
is con
A
-
-
-
-
-
-
-
14 EB 7030 EN
0.2
Kp
20
0.2
Kp
20
Principle of operation
Type 3433-2 PI Controller Module
The following versions of the controller mod ules are similar in most aspects to the Type 3433-2 PI Controller Module, how
­ever, they are fitted with, for example, an operating point adjuster, derivative element, or a selector switch, depending on the application.
Type 3433-1 P Controller Module
corresponds to Type 3433-2. An operating point adjuster is used in place of the integral element.
-
R Feedback R1/R2 Feedback bellows Z = Supply air 1.4 bar
Output pressure
Y
A
S Switching pressure
Fig. 7 · Type 3433 Controller Modules
A Operating action B Air supply
Turnboards
0.2
Kp
20
Type 3433-3 PID Controller Module
corresponds to Type 3433-2. Additionally, it contains a derivative element which produces the rate action with approx imately ten times the gain in the input branch of the controlled variable x. The rate time can be adjusted at the T
restriction.
V
EB 7030 EN 15
-
Principle of operation
Type 3433-4 PD Controller Module
corresponds to Type 3433-1. Additionally, it contains a derivative element which produces the rate action with approx imately ten times the gain in the input branch of the controlled variable x. The rate time can be adjusted at the T
restriction.
V
Type 3433-5 P/PI Controller Module
with P/PI selector switch can optionally be used as a P controller with operating point adjustment or as a PI controller. The structure is the same as that of the PI and P controller module. Type 3433-6 PD/PID Controller Module with PD/PID selector switch can optionally be used as a PD or PID controller.
0.2
-
Kp
20
0.2
Kp
20
Type 3433-9 P Controller Module
with set point-dependent operating point corresponds to Type 3433-1 P Controller Module, except that the operating point shifts proportional to the set point w.
16 EB 7030 EN
0.2
Kp
20
Fig. 8 · Type 3433 Controller Modules
Loading...
+ 36 hidden pages