Integral Mount or Remote Mount Magnetic
Flowmeter System with F
OUNDATION
™
fieldbus
www.rosemount.com
Reference Manual
NOTICE
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
Integral Mount or Remote Mount
Magnetic Flowmeter System with
OUNDATION
F
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure you thoroughly understand the contents before
installing, using, or maintaining this product.
Rosemount Inc. has two toll-free assistance numbers:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
Europe/ Middle East/ Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Rosemount representative.
™
fieldbus
The products described in this document are NOT designed for nuclear-qualified
applications. Using non-nuclear qualified products in applications that require
nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Rosemount
Sales Representative.
sensor and transmitter, and measures volumetric flow rate by detecting the
velocity of a conductive liquid that passes through a magnetic field.
There are four Rosemount magnetic flowmeter sensors:
•Flanged Rosemount 8705
•Flanged High-Signal Rosemount 8707
•Wafer-Style Rosemount 8711
•Sanitary Rosemount 8721
There are two Rosemount magnetic flowmeter transmitters:
•Rosemount 8712
•Rosemount 8732
The sensor is installed in-line with process piping — either vertically or
horizontally. Coils located on opposite sides of the sensor create a magnetic
field. Electrodes located perpendicular to the coils make contact with the
process fluid. A conductive liquid moving through the magnetic field
generates a voltage at the two electrodes that is proportional to the flow
velocity.
The transmitter drives the coils to generate a magnetic field, and electronical ly
conditions the voltage detected by the electrodes to provide a flow signal. T he
transmitter can be integrally or remotely mounted from the sensor.
This manual is designed to assist in the installation and ope ration of the
Rosemount 8732 Magnetic Flowmeter Transmitter and the Rosemount 8700
Series Magnetic Flowmeter Sensors.
®
8700 Series Magnetic Flowmeter System consists of a
www.rosemount.com
Reference Manual
See “Safety Messages” on page D-1 for complete warning information.
00809-0100-4663, Rev BA
Rosemount 8732
January 2010
SAFETY MESSAGESProcedures and instructions in this manual may require special preca utions to
ensure the safety of the personnel performing the operations. Refer to the
safety messages listed at the beginning of each section before performing
any operations.
Attempting to install and operate the Rosemount 8705, 8707 High-Signal, 8711 or 8721
Magnetic Sensors with the Rosemount 8712 or 8732 Magnetic Flowmeter Transmitter
without reviewing the instructions contained in this manual could result in personal injury or
equipment damage.
SERVICE SUPPORTTo expedite the return process outside the United States, contac t the nearest
Rosemount representative.
Within the United States and Canada, call the North American Response
Center using the 800-654-RSMT (7768) toll-free number. The Response
Center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for product model and serial numbers, and will provide a
Return Material Authorization (RMA) number. The center will also ask for the
name of the process material to which the product was last exposed.
Mishandling products exposed to a hazardous subst ance may result in death
or serious injury. If the product being returned was exposed to a hazardous
substance as defined by OSHA, a copy of the required Material Safety Data
Sheet (MSDS) for each hazardous substance identified must be included with
the returned goods.
The North American Response Center will detail the additional information
and procedures necessary to return goods exposed to hazardous
substances.
This section covers the steps required to physically install the magnetic
flowmeter. Instructions and procedures in this section may require special
precautions to ensure the safety of the personnel performing the operations.
Please refer to the following safety messages before performing any
operation in this section.
Rosemount 8732
SAFETY MESSAGESThis symbol is used throughout this manual to indicate that special attention
to warning information is required.
Failure to follow these installation guidelines could result in death or serious injury:
Installation and servicing instructions are for use by qualified personnel only. Do not perform
any servicing other than that contained in the operating instructions, unless qualified. Verify
that the operating environment of the sensor and transmitter is consistent with the
appropriate hazardous area approval.
Do not connect a Rosemount 8732 to a non-Rosemount sensor that is located in an
explosive atmosphere.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review
the approvals section of the 8732 reference manual for any restrictions associated with a
safe installation.
Before connecting a handheld communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or non-incendive
field wiring practices.
Electrical shock can result in death or serious injury
Avoid contact with the leads and terminals. High voltage that may be present on leads can
cause electrical shock.
www.rosemount.com
Rosemount 8732
Reference Manual
00809-0100-4663, Rev BA
January 2010
The sensor liner is vulnerable to handling damage. Never place anything through the sensor
for the purpose of lifting or gaining leverage. Liner damage can render the sensor useless.
To avoid possible damage to the sensor liner ends, do not use metallic or spiral-wound
gaskets. If frequent removal is anticipated, take precautions to protect the liner ends. Short
spool pieces attached to the sensor ends are often used for protection.
Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must be
tightened in the proper sequence to the specified torque limits. Failure to observe these
instructions could result in severe damage to the sensor lining and possible sensor
replacement.
Emerson Process Management can supply lining protectors to prevent liner damage during
removal, installation, and excessive bolt torquing.
TRANSMITTER
SYMBOLS
Caution symbol — check product documentation for details
Protective conductor (grounding) terminal
PRE-INSTALLATIONBefore installing the Rosemount 8732 Magnetic Flowmeter Transmitter, there
are several pre-installation steps that should be completed to make the
installation process easier:
•Identify the options and configurations that apply to your application
•Set the hardware switches if necessary
•Consider mechanical, electrical, an d en vir onm en tal req uir eme nts
MECHANICAL
CONSIDERATIONS
The mounting site for the 8732 transmitter should provide enough room for
secure mounting, easy access to conduit ports, full openin g of the transmitter
covers, and easy readability of the LOI screen (see Figure 2-1). The
transmitter should be mounted in a manner that prevent s moisture in conduit
from collecting in the transmitter.
If the 8732 is mounted remotely from the sensor, it is not subject to limitations
that might apply to the sensor.
2-2
Reference Manual
5.82
(148)
6.48 (165)
7.49 (190)
LOI Cover
4.97
(126)
8.81
(224)
3.00
(76)
3.07
(78)
4.97
(126)
1
/2”-14 NPT Electrical
Conduit Connections
(2 places with a 3rd
optional)
1
/2”-14 NPT Remote Junction
Box Conduit Connections (2
places)
00809-0100-4663, Rev BA
January 2010
Figure 2-1. Rosemount 8732 Dimensional Drawing
Rosemount 8732
ENVIRONMENTAL
CONSIDERATIONS
To ensure maximum transmitter life, avoid temperature extremes and
vibration. Typical problem areas include:
•high-vibration lines with integrally mounted transmitters
•warm-climate installations in direct sunlight
•outdoor installations in cold climates.
Remote-mounted transmitters may be installed in the control room to protect
the electronics from a harsh environment and provides easy access for
INSTALLATION
PROCEDURES
configuration or service.
Rosemount 8732 transmitters require external power so there must be access
to a suitable power source.
Rosemount 8732 installation includes both detailed mecha nical and electrical
installation procedures.
Mount the TransmitterRemote-mounted transmitters may be mounted on a pipe up to two inches in
diameter or against a flat surface.
Pipe Mounting
To mount the transmitter on a pipe:
1.Attach the mounting bracket to the pip e using the m ounting har dware.
2.Attach the 8732 to the mounting bracket using the mounting screws.
2-3
Rosemount 8732
Reference Manual
00809-0100-4663, Rev BA
January 2010
Surface Mounting
To surface mount the transmitter:
1.Attach the 8732 to the mounting location using the mounting screws.
Identify Options and
Configurations
The standard application of the Rosemount 8732 includes a FOUNDATION
fieldbus output. Be sure to identify options and configurations that apply to
your situation, and keep a list of them nearby for consideration during the
installation and configuration procedures.
Hardware SwitchesThe 8732 electronics board is equipped with two user-selectable hardware
switches. These switches set the Transmitter Security and Simulate Mode.
The standard configuration for these switches when shipped from the factory
are as follows:
Transmitter Security:OFF
Simulate ModeOFF
Definitions of these switches and their functions are provided below. If you
determine that the settings must be changed, see below .
Transmitter Security
The security switch on the 8732 allows the user to lock out any configuration
changes attempted on the transmitter. No changes to the configuration are
allowed when the switch is in the ON position. The flow rate indication
function remains active at all times.
With the switch in the ON position, you may still access and review any of the
operating parameters and scroll through the available choices, but no actual
data changes are allowed. Transmitter security is set in the OFF position
when shipped from the factory.
Simulate Mode
The Simulate Mode switch is used in conjunction with the Analog Input (AI)
function block. The switch is used to enable flow measurement simulation. To
enable the simulate enable feature, the switch must transition from OFF to
ON after power is applied to the transmitter, preventing the transmitter from
being accidentally left in simulate mode. Simulate Mode is set in the OFF
position when shipped from the factory.
Changing Hardware Switch Settings
In most cases, it is not necessary to change the setting of the hardware
switches. If you need to change the switch settings, complete the steps
below:
NOTE
The hardware switches are located on the top side of the electronics board
and changing their settings requires opening the electronics housing. If
possible, carry out these procedures away from the plant environment in
order to protect the electronics.
2-4
Reference Manual
00809-0100-4663, Rev BA
January 2010
Figure 2-2. Rosemount 8732
Electronics Board and Hardware
Switches
Rosemount 8732
1.Disconnect power to the transmitter.
2.Remove electronics cover.
3.Remove display if applicable.
4.Identify the location of each switch (see Figure 2-2).
5.Change the setting of the desired switche s with a sm all scr ewd r iver.
6.Replace the electronics cover.
Conduit Ports and
Connections
Both the sensor and transmitter junction boxes have ports for 1/2-inch NPT
conduit connections, with optional CM20 and PG 13.5 connections available.
These connections should be made in accordance with national, local or plant
electrical codes. Unused ports should be sealed with metal plugs and PTFE
tape or other thread sealant. Connections should also be made in accordance
with area approval requirements, see examples below for details. Proper
electrical installation is necessary to prevent errors due to electrical noise and
interference. Separate conduit s are not necessary for the coil drive and signa l
cables connecting the transmitter to the sensor, but a dedicated conduit line
between each transmitter and sensor is required. A shielded cable must be
used.
Example 1: Installing flanged sensors into an IP68 area. Sensors must be
installed with IP68 cable glands and cable to maintain IP68 rating. Unused
conduit connections must be properly sealed to prevent water ingress. For
added protection, dielectric gel can be used to pot the sensor terminal block.
Example 2: Installing flowmeters into explosion proof/flameproof areas.
Conduit connections and conduit must be rated for use in the hazardous area
to maintain flowmeter approval rating.
2-5
Reference Manual
NOTE
Dimensions are in
inches
(millimeters).
1.00
(26)
Cable Shield
00809-0100-4663, Rev BA
Rosemount 8732
January 2010
Conduit CablesRun the appropriate size cable through the conduit connections in your
magnetic flowmeter system. Run the power cable from the power source to
the transmitter . Do n ot run power cab les and outpu t signal cables in the same
conduit. For remote mount installations, run the coil drive and electrode
cables between the flowmeter and transmitter. Refer to Electrical
Considerations for wire type. Prepare the ends of the coil drive and electrode
cables as shown in Figure 2-3. Limit the unshielded wire length to 1-in. on
both the electrode and coil drive cables. Excessive lead length or failure to
connect cable shields can create electrical noise resulting in unstable meter
readings.
Figure 2-3. Cable Preparation
Detail
Electrical ConsiderationsBefore making any electrical connections to the Rosemount 8732, consider
the following standards and be sure to have th e proper power supply, conduit,
and other accessories. When prepar ing all wir e conne ctions, remove only the
insulation required to fit the wire completely under the terminal connection.
Removal of excessive insulation may result in an unwanted electrical short to
the transmitter housing or other wire connections.
Transmitter Input Power
The 8732 transmitter is designed to be powered b y 90-250 V AC, 50–60 Hz or
12–42 V DC. The eighth digit in the transmitter model number designates the
appropriate power supply requirement.
Model NumberPower Supply Requirement
190-250 V AC
212-42 V DC
Supply Wire Temperature Rating
Use 12 to 18 AWG wire. For connections in ambient temperatures
exceeding 140 °F (60 °C), use wire rated to at least 194 °F (90 °C).
Disconnects
Connect the device through an external disconnect or circuit breaker.
Clearly label the disconnect or circuit breaker and locate it near the
transmitter.
Requirements for 90-250 V AC Power Supply
2-6
Wire the transmitter according to national, local, and plant electrical
requirements for the supply voltage. In addition, follow the supply wire and
disconnect requirements on page2-7.
I = 10/V
I = Supply current requirement (Amps)
V = Power supply voltage (Volts)
Supply Current (Amps)
1218
24
30
36
42
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
00809-0100-4663, Rev BA
January 2010
Figure 2-4. Supply Current
versus Input Voltage
Rosemount 8732
Requirements for 12-42 V DC Power Supply
Units powered with 12-42 V DC may draw up to 1 amp of cu rren t. As a result,
the input power wire must meet certain gauge requirements.
Figure 2-4 shows the supply current for each corresponding supply voltage .
For combinations not shown, you can calculate the maximum distance given
the supply current, the voltage of the source, and the minimum start-up
voltage of the transmitter, 12 V DC, using the following equation:
Installation CategoryThe installation category for the Rosemount 87 32 is (overvoltage) Category II.
Overcurrent ProtectionThe Rosemount 8732 Flowmeter Transmitter requires overcurrent protection
of the supply lines. Maximum ratings of overcurrent devices are as follows:
Power SystemFuse RatingManufacturer
110 V AC250 V; 1 Amp, Quick ActingBussman AGCI or Equivalent
220 V AC250 V; 2 Amp, Quick ActingBussman AGCI or Equivalent
42 V DC50 V, 3 Amp, Quick ActingBussman AGCI or Equivalent
Connect Transmitter
Power
To connect power to the transmitter, complete the following steps.
1.Ensure that the power source and connecting cable meet the
requirements outlined on page 2-8.
2.Turn of f the power source.
3.Open the power terminal cover.
4.Run the power cable through the conduit to the transmitter.
5.Connect the power cable leads as shown in Figure 2-5.
a. Connect AC Neutral or DC- to terminal 9.
b. Connect AC Line or DC+ to terminal 10.
c. Connect AC Ground or DC Ground to the ground screw mounted
inside the transmitter enclosure.
2-7
Rosemount 8732
AC Line or DC +
Transmitter
Power Cable
AC Neutral or DC –
AC or DC
Ground
See “Safety Messages” on page 2-1 for complete warning information.
Figure 2-5. AC Transmitter
Power Connections
Reference Manual
00809-0100-4663, Rev BA
January 2010
Connect FOUNDATION
fieldbus Wiring
Transmitter
Communication Input
Power ConditioningEach fieldbus power supply requires a power conditioner to decouple the
Field WiringPower independent of the coil power supply must be supplied for FOUNDATION
Table 2-1.
Ideal Cable Specifications for
Fieldbus Wiring
The FOUNDATION fieldbus signal provides the output information from the
transmitter.
The FOUNDATION fieldbus communication requires a minimum of
9 V dc and a maximum of 32 V dc at the transmitter communication terminals.
NOTES
•Do not exceed 32 V dc at the transmitter communication terminals.
•Do not apply ac line voltage to the transmitter
communication terminals.
Improper supply voltage can damage the transmitter.
power supply output from the fieldbus wiring segment.
fieldbus communications. Use shielded, twisted pair for best results. For new
installations or to get maximum performance, twisted pair cable designed
especially for fieldbus should be used. Table 2-1 details cable characteristics
and ideal specifications.
CharacteristicIdeal Specification
Impedance100 Ohms ± 20% at 31.25 kHz
Wire Size18 AWG (0,8 mm2)
Shield Coverage90%
Attenuation3 db/km
Capacitive Unbalance2 nF/km
2-8
Reference Manual
–FF signal
+FF signal
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
NOTE
The number of devices on a fieldbus segment is limited by the power supply
voltage, the resistance of the cable, and the amount of current drawn by
each device.
Transmitter Wiring
Connection
Figure 2-6. F
Signal Connections
OUNDATION fieldbus
To connect the 8732 to the FOUNDATION fieldbus (FF) segment, complete
the following steps.
1.Ensure that the power source and connecting cable meet the
requirements outlined above and in “Field Wiring” on page 2-8.
2.Turn of f the transmitter and power sources.
3.Run the F
4.Connect -FF to Terminal 1.
5.Connect +FF to Terminal 2.
NOTE
Foundation fieldbus signal wiring for the 8732 is not polarity sensitive.
Refer to Figure 2-6 on page 2-9.
OUNDATION fieldbus cable into the transmitter.
2-9
Rosemount 8732
Integrated
Power
Conditioner
and Filter
Terminators
6234 ft (1900 m) max
(depending upon cable
characteristics)
Fieldbus
Segment
(Spur)
(Trunk)
(The power supply,
filter, first terminator,
and configuration tool
are typically located
in the control room.)
*Intrinsically safe installations may
allow fewer devices per I.S. barrier.
Power
Supply
FOUNDATION
Fieldbus
Configuration
Tool
(Spur)
Devices 1 through 11*
Figure 2-7. Rosemount 8732
Transmitter Field Wiring
Reference Manual
00809-0100-4663, Rev BA
January 2010
2-10
Reference Manual
Coil Drive
and
Electrode
Cables
Power
Power
Outputs
Outputs
Coil Drive
and
Electrode
Cables
Power
Outputs
Power
Outputs
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
SENSOR CONNECTIONSThis section covers the steps required to physically install the transmitter
including wiring and calibration.
Rosemount SensorsTo connect the transmitter to a non-Rosemount sensor, refer to the
appropriate wiring diagram in “Universal Sensor Wiring Diagrams” on
page E-1. The calibration procedure listed is not required for use with
Rosemount sensors.
Transmitter to Sensor
Wiring
Figure 2-8. Conduit Preparation
CorrectIncorrect
Flanged and wafer sensors have two conduit ports as shown in Figur e 2-8.
Either one may be used for both the coil drive and electrode cables. Use the
stainless steel plug that is provided to seal the unused conduit port. Use
Teflon tape or thread sealant appropriate for the installation when sealing the
conduit.
A single dedicated conduit run for the coil drive and electrode cables is
needed between a sensor and a remote transmitter. Bundled cables in a
single conduit are likely to create interference and noise problems in your
system. Use one set of cables per conduit run. See Figure 2-8 for proper
conduit installation diagram and Table 2-2 for recommended cable. For
integral and remote wiring diagrams refer to Figure 2-10.
Table 2-2. Cable Requirements
DescriptionUnitsPart Number
Signal Cable (20 AWG) Belden 8762, Alpha 2411 equivalentft
(1) Combination signal and coil drive cable is not recommended for high-signal magmeter system. For remote mount installa tions, combination signal and coil
(1)
drive cable should be limited to less than 330 ft. (100 m).
Rosemount recommends using the combination signal and coil drive for N5,
E5 approved sensors for optimum performance.
Remote transmitter installations require equal lengths of signal and coil drive
cables. Integrally mounted transmitters are factory wired and do not require
interconnecting cables.
Lengths from 5 to 1,000 feet (1.5 to 300 meters) may be specified, and will be
shipped with the sensor.
Conduit CablesRun the appropriate size cable through the conduit connections in your
magnetic flowmeter system. Run the power cable from the power source to
the transmitter. Run the coil drive and electrode cables between the sensor
and transmitter .
Prepare the ends of the coil drive and electrode cables as shown in Figure
2-9. Limit the unshielded wire length to 1-inch on both the electrode and coil
drive cables.
NOTE
Excessive lead length or failure to connect cable shields ca n create electrical
noise resulting in unstable meter readings.
Figure 2-9. Cable Preparation
Detail
2-12
Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
Sensor to Remote Mount
Transmitter Connections
Figure 2-10. Wiring Diagram
Connect coil drive and electrode cables as shown in Figure 2-10.
Do not connect AC power to the sensor or to terminals 1 an d 2 of the
transmitter, or replacement of the electronics board will be necessary.
INTRODUCTIONThis section covers basic operation, software functionality, and configuration
procedures for the Rosemount 8732 Magnetic Flowmeter Transmitter. For
information on connecting anothe r m anufacturer’s flowtube sensor, refer to
“Universal Sensor Wiring Diagrams” on page E-1.
The Rosemount 8732 features a full range of software functions for
configuration of output from the transmitter. Software functions are accessed
through the LOI, AMS, a Handheld Communicator, or a control system.
Configuration variables may be changed at any time and specific instructions
are provided through on-screen instructions.
The optional Local Operator Interface (LOI) provides an operator
communications center for the 8732. By using th e LO I, th e op er at or can
access any transmitter function for changing configuration parameter settings,
checking totalized values, or other functions. The LOI is integral to the
transmitter electronics.
BASIC FEATURESThe basic features of the LOI include 4 navigational arrow keys that are used
to access the menu structure. See Figure 3-1.
www.rosemount.com
Rosemount 8732
Figure 3-1. Local Operator
Interface Keypad
Reference Manual
00809-0100-4663, Rev BA
January 2010
Data EntryThe LOI keypad does not have numerical keys. Numerical data is entered by
the following procedure.
1.Access the appropriate function.
2.Use the RIGHT ARROW key to move to the value to change.
3.Use the UP and DOWN ARROWS to change the highlighted value.
For numerical data, toggle through the digits 0–9, decimal point, and
dash. For alphabetical data, toggle through the letters of the alphabet
A–Z, digits 0–9, and the symbols ,&, +, -, *, /, $, @,%, and the blank
space.
4.Use the RIGHT ARRO WS to highlight other digit s you want to change
and change them.
5.Press “E” (the lef t arrow key) when all cha nges are compl ete to save
the entered values.
LOI EXAMPLESUse the DOWN ARROW to access the menu structure in Table 3-2. Use the
ARROW KEYS to select the desired parameters to review/change.
Parameters are set in one of two ways, Table Values or Select Values.
Table Values:
Parameters such as units, that are available from a predefined list
Select Values:
Parameters that consist of a user-created number or character string, such
as calibration number; values are entered one character at a time using
the ARROW KEYS.
3-2
Reference Manual
00809-0100-4663, Rev BA
January 2010
Table Value ExampleSetting the TUBE SIZE:
1.Press the DOWN arrow to access the menu.
2.Select line size from the Basic set-up menu.
3.Press the UP or DOWN arrow to increase/decrease (incrementally)
the tube size to the next value.
4.When you reach the desired size, press “E” (the left arrow).
5.Set the loop to manual if necessary, and press “E” again.
After a moment, the LCD will display the new tube size and the maximum flow
rate.
Select Value ExampleChanging the ANALOG OUTPUT RANGE:
1.Press the DOWN arrow to access the menu.
2.Using the arrow keys, select PV URV from the Basic Setup menu.
3.Press RIGHT arrow key to posit ion the cursor.
4.Press UP or DOWN to set the number.
5.Repeat steps 2 and 3 until desired number is displayed.
6.Press “E”.
Rosemount 8732
After a moment, the LCD will display the new analog output range.
Display LockThe display can be locked to prevent unintentional configuration changes.
The display lock can be activated through a HART communication device, or
by holding the UP arrow for 10 seconds. When the display lock is activated,
DL will appear in the lower left hand corner of the display. To deactivate the
display lock (DL), hold the UP arrow for 10 seconds. Once deactivated, the
DL will no longer appear in the lower left hand corner of the display.
Start TotalizerTo start the totalizer, press the DOWN arrow to display the totalizer screen
and press “E” to begin totalization. A symbol will flash in the lower right
hand corner indicating that the meter is totalizing.
Stop TotalizerTo stop the totalizer, press the DOWN arrow to display the totalizer screen
and press “E” to end totalization. The flashing symbol will no longer display
in the lower right hand corner indicating that the meter has stopped totalizing.
Reset TotalizerTo reset the totalizer, press the DOWN arrow to display the totalizer screen
and follow the procedure above to stop totalization. Once totalization has
stopped, press the RIGHT arrow key to reset the NET total value to zero.
To reset the gross total value, you must change the line size. See “Line Size”
on page 3-9 for details on how to change the line size.
3-3
Rosemount 8732
Diag Controls
Basic Diag
A dvanced D iag
Variables
Trims
Status
E mpty P ipe
Process Noise
G round/W i ri ng
Elec Temp
Self Test
A O L oop Test
Pulse Out Test
E mpty P ipe
Elec Temp
G round/W i ri ng
Process Noise
8714i
4-20 mA V erif y
Licensing
R un 8714i
V iew Results
Tube Signature
Test Criteria
M easur ements
Values
R e-Signature
Recall V alues
Coil R esist
C oil S ignature
E lectr ode R es
No Flow
Flowing, Full
E mpty P ipe
Coil R esist
C oil S ignature
E lectr ode R es
E mpty P ipe
Elec Temp
L ine N oise
5Hz SN R
37Hz SN R
Signal Power
8714i R esults
D/A Trim
Digital Trim
A uto Z ero
Universal Trim
4-20 mA V erif y
View Results
Tag
Flow Units
L ine S ize
PV UR V
PV L R V
Cal Number
PV Damping
C oi l F requency
Proc Density
PV LSL
PV USL
PV Min Span
Analog
Pulse
DI/DO Config
Totalizer
Reverse Flow
HART
PV UR V
PV L R V
Alarm Type
Test
Pulse Scaling
Pulse W idth
Pulse M ode
Test
DI 1
DO 2
Totalize Units
Total Dis
play
Burst Mode
B urst C ommand
F lange T ype
F lange M atl
E lectr ode T ype
E lectr ode M atl
L iner Material
Software Rev
Final A smbl #
Tag
Description
Message
Device ID
PV Sensor S/N
Flowtube Tag
Revision Num
M ateri al s
Operating Mode
SP Config
C oi l F requenc y
PV Damping
Lo-Flow Cuto
Flow Display
Total Display
L anguage
More Params
Output C onfi g
LOI Config
Si g Processing
Device Info
PV Units
Special Units
Totalize Units
Diagnostics
Basic Setup
Detailed S etup
Ta ble 3-2. LOI Menu Tree
Reference Manual
00809-0100-4663, Rev BA
January 2010
3-4
Loading...
+ 160 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.