Rosemount 8600 Operating Manual

Rosemount™ 8600 Series Vortex Flowmeter

Reference Manual
00809-0100-4860, Rev BD
October 2016
00809-0100-4860, Rev BD
Contents

1Section 1: Introduction

2Section 2: Configuration

Table of Contents
October2016
1.1 How to use this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.3 System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1 Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.2 Process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2.1 Primary Variable (PV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2.2 PV% of range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2.3 Analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2.4 View other variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Basic setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.3.1 Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.3.2 Process configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.3.3 Reference K-factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.3.4 Flange type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3.5 Mating pipe ID (Inside Diameter) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.3.6 Variable mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.3.7 PV units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2.3.8 Range values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2.3.9 PV damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2.3.10 Auto adjust filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

3Section 3: Installation

3.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.2 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
3.2.1 General considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
3.2.2 Flowmeter sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
3.2.3 Flowmeter orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.2.4 Wetted material selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
3.2.5 Environmental considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3 Hazardous locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Table of Contents
3.4 Hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
iii
Table of Contents
October 2016
Reference Manual
00809-0100-4860, Rev BD
3.4.1 Failure mode vs. saturation output values . . . . . . . . . . . . . . . . . . . . . . . . 28
3.4.2 LCD indicator option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.5 Meter body installation tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.5.1 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.5.2 Flow direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3.5.3 Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3.5.4 Flange bolts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.5.5 Flanged-style flowmeter mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.5.6 Flowmeter grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.6 Electronics considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3.6.1 High-Temperature installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3.6.2 Conduit connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
3.6.3 High-Point installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
3.6.4 Cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
3.6.5 Grounding the transmitter case . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
3.6.6 Wiring procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.6.7 Remote electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.6.8 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.7 Software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
3.7.1 Installing the indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.8 Transient protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
3.8.1 Installing the Transient Protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44

4Section 4: Operation

4.1 Diagnostics/service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
4.1.1 Test/status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.1.2 Loop test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
4.1.3 Pulse output test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
4.1.4 Flow simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
4.1.5 D/A trim(Digital-to-Analog Trim) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.1.6 Scaled D/A trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.1.7 Shed freq at URV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
4.2 Advanced functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
4.3 Detailed set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
4.3.1 Characterize meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
4.3.2 Configure outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
4.3.3 Signal processing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.3.4 Device information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
iv
Table of Contents
00809-0100-4860, Rev BD

5Section 5: Troubleshooting

Table of Contents
October2016
5.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
5.2 Troubleshooting tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
5.3 Advanced troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
5.3.1 Diagnostic messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
5.3.2 Electronics test points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.3.3 TP1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.4 Diagnostic messages on LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
5.5 Testing procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
5.6 Hardware replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
5.6.1 Replacing the terminal block in the housing . . . . . . . . . . . . . . . . . . . . . . 76
5.6.2 Replacing the electronics boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
5.6.3 Replacing the electronics housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
5.6.4 Replacing the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
5.6.5 Remote electronics procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
5.6.6 Coaxial cable at the electronics housing . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.6.7 Changing the housing orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.6.8 Temperature sensor replacement (MTA option only). . . . . . . . . . . . . . . 87
5.7 Return of material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
AAppendix A: Specifications and Reference Data
A.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
A.2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
A.3 Typical flow ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
A.4 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
A.4.1 Flow accuracy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
A.5 Physical specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
A.6 Dimensional drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
BAppendix B: Product Certifications
B.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
B.2 Product certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
B.2.1 Approved manufacturing locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105
B.2.2 International certifications (IECEx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105
B.2.3 Chinese certifications (NEPSI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
B.2.4 European certifications (ATEX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
Table of Contents
B.2.5 EurAsian Conformity (EAC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
B.2.6 Canadian Standards Association (CSA) . . . . . . . . . . . . . . . . . . . . . . . . . .109
v
Table of Contents
October 2016
CAppendix C: Electronics Verification
DAppendix D: HART® Menu Tree
Reference Manual
00809-0100-4860, Rev BD
C.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
C.2 Electronics verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
C.2.1 Electronics verification using flow simulation mode. . . . . . . . . . . . . . .112
C.2.2 Fixed flow rate simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
C.2.3 Varying flow rate simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
C.2.4 Electronics verification using an external frequency generator . . . . .113
C.2.5 Calculating output variables with known input frequency . . . . . . . . .114
C.3 Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
C.3.1 English units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
C.3.2 SI units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120
D.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
vi
Table of Contents
Reference Manual
NOTICE
00809-0100-4860, Rev BD
Rosemount™ 8600D Smart Vortex Flowmeter
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
Within the United States, Emerson Process Management has two toll-free assistance numbers:
Customer Central Technical support, quoting, and order-related questions.
1-800-999-9307 (7:00 am to 7:00 pm CST) North American Response Center
Equipment service needs. 1-800-654-7768 (24 hours—includes Canada) Outside of the United States, contact your local Emerson Process Management
representative.
Title Page
October 2016
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative.
Title Page
vii
Title Page
October 2016
Reference Manual
00809-0100-4860, Rev BD
viii
Title Page
00809-0100-4860, Rev BD

Section 1 Introduction

1.1 How to use this manual

This manual provides installation, configuration, troubleshooting, and other procedures for the use of the Rosemount
information are also included.
Section 2: Configuration contains information on entering and verifying basic configuration
parameters.
Section 3: Installation contains mechanical and electrical installation instructions.
Section 4: Operation contains information on advanced configuration parameters and
functions that can aid in maintaining the 8600D.
Section 5: Troubleshooting provides troubleshooting techniques, diagnostic information,
and transmitter verification procedures.
8600D Vortex Flowmeter. Specifications and other important
Introduction
October 2016
Specifications and Reference Data provides reference and specification data.
Appendix B: Product Certifications provides specific information for approval codes.
Appendix C: Electronics Verification provides a short procedure for verification of electronic
output to assist in meeting the quality standards for ISO 9000 certified manufacturing processes.
Appendix D: HART
the Field Communicator when used in conjunction with the Rosemount 8600D.
®
Menu Tree provides command tree, and Fast Key Sequence tables for

1.2 Safety messages

Procedures and instructions in this manual may require special precautions to ensure the safety of the personnel performing the operations. Refer to the safety messages, listed at the beginning of each section, before performing any operations.

1.3 System description

The Rosemount 8600D Vortex Flowmeter consists of a meter body and transmitter and measures volumetric flow rate by detecting the vortices created by a fluid passing by the shedder bar.
Introduction
The meter body is installed in-line with process piping. A sensor is located at the end of the shredder bar and creates an alternating sine wave due to the passing vortices. The transmitter measures the frequency of the sine waves and converts it into a flowrate.
This manual is designed to assist in the installation and operation of the Rosemount 8600D Vortex Flowmeter.
1
Introduction
October 2016
Reference Manual
00809-0100-4860, Rev BD
2
Introduction
00809-0100-4860, Rev BD

Section 2 Configuration

Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Basic setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
This product is intended to be used as a flowmeter for liquid, gas, or steam applications. Any use other than for which it was intended may result in serious injury or death.

2.1 Review

Configuration
October 2016
FastKeys
Review the flowmeter configuration parameters set at the factory to ensure accuracy and compatibility with your particular application of the flowmeter. Once you have activated the Review function, scroll through the data list to check each variable in the configuration data list.
The last step of start-up and commissioning is to check the flowmeter output to ensure that the flowmeter is operating properly. Rosemount 8600D digital process variables include: primary variable, primary variable as a percent of range, analog output, vortex shedding rate, pulse frequency, mass flow, volumetric flow, velocity flow, totalizer, electronics temperature, calculated process density, cold junction temperature, and process temperature.
1, 5

2.2 Process variables

FastKeys
The process variables for the Rosemount 8600D provide the flowmeter output. When commissioning a flowmeter, review each process variable, its function and output, and take corrective action if necessary before using the flowmeter in a process application.
1, 1
Configuration
3
Configuration
October 2016

2.2.1 Primary Variable (PV)

Reference Manual
00809-0100-4860, Rev BD
FastKeys
The measured value of the variable mapped to the primary variable. This can be either Process Temperature (MTA option only) or Flow. Flow variables are available as mass, volume, or velocity. When bench commissioning, the flow values for each variable should be zero and the temperature value should be the ambient temperature.
If the units for the flow or temperature variables are not correct, refer to “View other variables”
on page 4. Use the Process Variable Units function to select the units for your application.

2.2.2 PV% of range

FastKeys
The primary variable as a percentage of range provides a gauge as to where the current measurement of the meter is within the configured range of the meter. For example, the range may be defined as 0 gal/min to 20 gal/min. If the current flow is 10 gal/min, the percent of range is 50 percent.

2.2.3 Analog output

FastKeys 1, 1, 3
The analog output variable provides the analog value for the primary variable. The analog output refers to the industry standard output in the 4–20 mA range. Check the analog output value against the actual loop reading given by a multi-meter. If it does not match, a 4–20 mA trim is required. See D/A Trim (Digital-to-Analog Trim).
1, 1, 1
1, 1, 2

2.2.4 View other variables

FastKeys 1, 1, 4
Allows for the viewing and configuration of other variables such as flow units, totalizer operation, and pulse output.
Volume flow
FastKeys 1, 1, 4, 1, 1
Allows the user to view the current volumetric flow value.
4
Configuration
00809-0100-4860, Rev BD
Volume flow units
FastKeys 1, 1, 4, 1, 2
Allows the user to select the volumetric flow units from the available list.
Volumetric Unit LCD Display Field Communicator
U.S. Gallons per second GAL/S gal/s
U.S. Gallons per minute GAL/M gal/m
U.S. Gallons per hour GAL/H gal/h
U.S. Gallons per day GAL/D gal/d
Actual Cubic Feet per second ACFS ACFS
Actual Cubic Feet per minute ACFM ACFM
Actual Cubic Feet per hour ACFH ACFH
Actual Cubic Feet per day ACFD ACFD
Standard Cubic Feet per minute
Standard Cubic Feet per hour SCFH N/A
Barrels per second BBL/S bbl/s
Barrels per minute BBL/M bbl/min
Barrels per hour BBL/H bbl/h
Barrels per day BBL/D bbl/d
Imperial Gallons per second IGAL/S Impgal/s
Imperial Gallons per minute IGAL/M Impgal/min
Imperial Gallons per hour IGAL/H Impgal/h
Imperial Gallons per day IGAL/D Impgal/d
Liters per second L/S L/s
Liters per minute L/MIN L/min
Liters per hour L/H L/h
Liters per day L/D L/D
Actual Cubic Meters per second
Actual Cubic Meters per minute
Actual Cubic Meters per hour ACMH ACMH
Actual Cubic Meters per day ACMD ACMD
Million Actual Cubic Meters per day
Normal Cubic Meters per minute
Normal Cubic Meters per hour NCMH N/A
Normal Cubic Meters per day NCMD N/A
Configuration
October 2016
SCFM N/A
ACMS ACMS
ACMM ACMM
MACMD MACMD
NCMM N/A
Configuration
5
Configuration
October 2016
Reference Manual
00809-0100-4860, Rev BD
Standard/Normal flow units
StdCuft/min
SCFH
NCMM
NmlCum/h
NCMD
Note
When configuring Standard or Normal Flow units to the volumetric flow, a density ratio must be provided. See the Density/Density Ratio on page 13.
Special units
FastKeys 1, 1, 4, 1, 3
Special Units allows you to create flow rate units that are not among the standard options. They can be volumetric only. Configuration of a special unit involves entry of these values: base volume unit, base time unit, user defined unit and conversion number. Suppose you want the Rosemount 8600D to display flow in barrels per minute instead of gallons per minute, and one barrel is equal to 31.0 gallons.
Base volume unit: gal
Base time unit: min
User defined unit: br
Conversion number:
1
/31.0
See the specific variables listed below for more information on setting special units.
Base volume unit
FastKeys 1, 1, 4, 1, 3, 1
Base Volume Unit is the unit from which the conversion is made. You must select one of the Field Communicator defined unit options:
Gallons (gal)
Liters (L)
Imperial gallons (Impgal)
Cubic meters (Cum)
Barrels (bbl) where 1 bbl=42 gal
Cubic Feet (Cuft)
6
Configuration
00809-0100-4860, Rev BD
Base time unit
FastKeys 1, 1, 4, 1, 3, 2
Provides the time unit from which to calculate the special units. For example, if your special units is a volume per minute, select minutes. Choose from the following units:
Seconds (s)
Minutes (min)
Hours (h)
Days (d)
User defined unit
FastKeys 1, 1, 4, 1, 3, 3
A format variable that provides a record of the flow units to which you are converting. The LCD display on the Rosemount 8600D will display the actual units you define. The Field Communicator will simply display “SPCL.” There are four characters available to store the new units designation.
Configuration
October 2016
Conversion number
FastKeys 1, 1, 4, 1, 3, 4
Used to relate base units to special units. For a straight conversion of volume units from one to another, the conversion number is the number of base units in the new unit.
For example, if you are converting from gallons to barrels and there are 31 gallons in a barrel, the conversion factor is 31. The conversion equation is as follows (where barrels is the new volume unit):
1 gallon = 0.032258 bbl.
Mass flow
FastKeys 1, 1, 4, 2
Allows the user to view the current mass flow value and units. Also allows the user to configure the mass flow units.
Mass flow
FastKeys 1, 1, 4, 2, 1
Displays the current mass flow value and units.
Mass units
Configuration
FastKeys 1, 1, 4, 2, 2
Allows the user to select the mass flow units from the available list. (1 STon = 2000 lb; 1 MetTon = 1000 kg)
7
Configuration
October 2016
Reference Manual
00809-0100-4860, Rev BD
Mass Flow Units
lb/s STon/min lb/min STon/h lb/h STon/d lb/d MetTon/mi
n kg/s MetTon/h kg/min MetTon/d kg/h g/s kg/d g/min
g/h
Note
If you select a Mass Units option, you must enter process density in your configuration. See the Density/Density Ratio section on page 13.
Velocity flow
FastKeys 1, 1, 4, 3
Allows the user to view the current velocity flow value and units. Also allows the user to configure the velocity flow units.
Velocity flow
FastKeys 1, 1, 4, 3, 1
Displays the current velocity flow value and units.
Velocity units
FastKeys 1, 1, 4, 3, 2
Allows the user to select the velocity units from the available list
ft/s
m/s
Velocity measured base
FastKeys 1, 1, 4, 3, 3
Determines if the velocity measurement is based on the mating pipe ID or the meter body ID.
Totalizer
FastKeys 1, 1, 4, 4
Tallies the total amount of liquid or gas that has passed through the flowmeter since the totalizer was last reset. It enables you to change the settings of the totalizer.
8
Configuration
00809-0100-4860, Rev BD
Total
FastKeys 1, 1, 4, 4, 1
Provides the output reading of the totalizer. Its value is the amount of liquid or gas that has passed through the flowmeter since the totalizer was last reset.
Start
FastKeys 1, 1, 4, 4, 2
Starts the totalizer counting from its current value.
Stop
FastKeys 1, 1, 4, 4, 3
Interrupts the totalizer count until it is restarted again. This feature is often used during pipe cleaning or other maintenance operations.
Reset
FastKeys 1, 1, 4, 4, 4
Configuration
October 2016
Returns the totalizer value to zero. If the totalizer was running, it will continue to run starting at zero.
Totalizer config
FastKeys 1, 1, 4, 4, 5
Used to configure the flow parameter (volume, mass, velocity) that will be totalled.
Note
The totalizer value is saved in the non-volatile memory of the electronics every three seconds. Should power to the transmitter be interrupted, the totalizer value will start at the last saved value when the power is re-applied.
Note
Changes that affect the density, density ratio, or compensated K-Factor will affect the totalizer value being calculated. These changes will not cause the existing totalizer value to be recalculated.
Pulse frequency
FastKeys 1, 1, 4, 5
Allows users to view the pulse output frequency value. To configure the pulse output, refer to the section on pulse output found on page 54.
Configuration
Vortex frequency
FastKeys 1, 1, 4, 6
Allows users to view the shedding frequency directly off of the sensor.
9
Configuration
October 2016
Reference Manual
00809-0100-4860, Rev BD
Electronics temperature
FastKeys 1, 1, 4, 7
Allows users to view the electronics temperature value and units. Also allows the user to configure the units for the electronics temperature.
Electronics temperature
FastKeys 1, 1, 4, 7, 1
Displays the current electronics temperature value and units.
Electronics temperature unit
FastKeys 1, 1, 4, 7, 2
Allows the user to select the units for electronics temperature from the available list.
deg C
deg F
deg R
Kelvin
Calculated process density
FastKeys 1, 1, 4, 8
Allows users to view the calculated process density value when the vortex is configured for temperature compensated steam applications. Also allows the user to configure the calculated density units.
Process density
FastKeys 1, 1, 4, 8, 1
Displays the current calculated process density value.
Density units
FastKeys
Allows the user to configure the units for the calculated process density from the available list.
g/Cucm (cm
g/L
kg/Cum (m
lb/Cuft (ft
lb/Cuin (in
1, 1, 4, 8, 2
3
)
3
)
3
)
3
)
10
Configuration
00809-0100-4860, Rev BD
Process temperature
FastKeys 1, 1, 4, 9
Allows users to view the process temperature value when the vortex transmitter has the temperature sensor option. Also allows the user to configure the process temperature units.
Process temperature
FastKeys 1, 1, 4, 9, 1
Displays the current process temperature value.
Process temperature units
FastKeys 1, 1, 4, 9, 2
Allows the user to configure the units for the process temperature from the available list.
deg C
deg F
Configuration
October 2016
deg R
Kelvin
T/C failure mode
FastKeys 1, 1, 4, 9, 3
Allows the user to configure the temperature sensor failure mode. In the event that the thermocouple sensor fails, the vortex can go either into an alarm output mode, or continue to operate normally using the Fixed Process Temperature value. See Fixed Process Temperature page 13. This mode is only relevant with the MTA option.
Note
If the Primary Variable is set to Process Temperature and there is an error, the output will always go to alarm and this setting will be ignored.
Cold Junction (CJ) temperature
FastKeys 1, 1, 4, Scroll to bottom of list
Allows users to view the thermocouple cold junction temperature value when the vortex has the temperature sensor option. Also allows the user to configure the CJ temperature units.
CJ temperature
Configuration
FastKeys 1, 1, 4, -, 1
Displays the current thermocouple cold junction temperature value.
11
Configuration
October 2016
CJ temperature units
FastKeys 1, 1, 4, -, 2
Allows the user to configure the units for the thermocouple cold junction temperature from the available list.
deg C
deg F
deg R
Kelvin

2.3 Basic setup

FastKeys 1, 3
The Rosemount 8600D must be configured for certain basic variables in order to be operational. In most cases, all of these variables are pre-configured at the factory. Configuration may be required if your Rosemount 8600D is not configured or if the configuration variables need revision.
Reference Manual
00809-0100-4860, Rev BD

2.3.1 Tag

FastKeys 1, 3, 1
The quickest way to identify and distinguish between flowmeters. Flowmeters can be tagged according to the requirements of your application. The tag may be up to eight characters long.

2.3.2 Process configuration

FastKeys 1, 3, 2
The flowmeter can be used for liquid or gas/steam applications, but it must be configured specifically for the application. If the flowmeter is not configured for the proper process, readings will be inaccurate. Select the appropriate Process configuration parameters for your application:
Transmitter mode
FastKeys 1, 3, 2, 1
For units with an integral temperature sensor, the temperature sensor can be activated here.
Without Temperature Sensor
12
With Temperature Sensor
Configuration
00809-0100-4860, Rev BD
Process fluid
FastKeys 1, 3, 2, 2
Select the fluid type: either Liquid, Gas/Steam, Tcomp Sat Steam. Tcomp Sat Steam requires the MTA Option and provides a temperature compensated mass flow output for saturated steam.
Fixed process temperature
FastKeys 1, 3, 2, 3
Process Temperature is needed for the electronics to compensate for thermal expansion of the flowmeter as the process temperature differs from the reference temperature. Process temperature is the temperature of the liquid or gas in the line during flowmeter operation.
Fixed process temperature may also be used as a back-up temperature value in the event of a temperature sensor failure if the MTA option is installed.
Note
The Fixed Process Temperature may also be changed under Calculate Density Ratio.
Configuration
October 2016
Density/Density ratio
FastKeys 1, 3, 2, 4
When configuring a meter for mass flow units, a density value needs to be entered. When configuring a meter for Standard and Normal Volumetric flow units a density ratio will be required.
Density ratio
FastKeys 1, 3, 2, 4, 1
Configure the Density Ratio in one of two ways:
1. Enter Density Ratio to convert from actual flow rate to standard flow rate.
2. Enter the process and base conditions. (The Rosemount 8600D electronics will then calculate the density ratio for you).
Note
Be careful to calculate and enter the correct conversion factor. Standard flow is calculated with the conversion factor you enter. Any error in the factor entered will result in an error in the standard flow measurement. If pressure and temperature changes over time, use actual volumetric flow units. The Rosemount 8600D does not compensate for changing temperature and pressure.
Configuration
Note
Changing the base process conditions will modify the density ratio. Likewise a change to the density ratio will lead to a change in the base process pressure (Pf).
13
Configuration
DensityRatio
densit y at actual (flowing) conditions
dens ity at s dard (base)tan conditions
--------------------------------------------------------------------------------------------------------=
DensityRatio
TbxPfxZ
b
TfxPbxZ
f
---------------------------=
DensityRatio
518.57 °R x100 psiax1.0006
629.67 °Rx14.7 psiax1.0036
---------------------------------------------------------------------------- 5 . 5 8 6==
October 2016
Reference Manual
00809-0100-4860, Rev BD
Density ratio
FastKeys 1, 3, 2, 4, 1, 1
Used to convert actual volumetric flow to standard volumetric flow rates based on the following equations:
Calculate density ratio
FastKeys 1, 3, 2, 4, 1, 2
Calculates the density ratio (shown above) based on user entered process and base conditions.
Operating conditions
FastKeys 1, 3, 2, 4, 1, 2, 1
Tf = absolute temperature at actual (flowing) conditions in degrees Rankine or Kelvin. (The transmitter will convert from degrees Fahrenheit or degrees Celsius to degrees Rankine or Kelvin respectively.)
P
= absolute pressure at actual (flowing) conditions psia or KPa absolute. (The transmitter
f
will convert from psi, bar, kg/sqcm, kpa, or mpa to psi or kpa for calculation. Note that pressure values must be absolute.)
Z
= compressibility at actual (flowing) conditions (dimensionless)
f
Base conditions
FastKeys 1, 3, 2, 4, 1, 2, 2
Tb = absolute temperature at standard (base) conditions degrees Rankine or Kelvin. (The transmitter will convert from degrees Fahrenheit or degrees Celsius to degrees Rankine or Kelvin respectively.)
= absolute pressure at standard (base) conditions psia or KPa absolute. (The transmitter
P
b
will convert from psi, bar, kg/sqcm, kpa, or mpa to psi or kpa for calculation. Note that pressure values must be absolute.)
= compressibility at standard (base) conditions (dimensionless)
Z
b
Example:
Configure the Rosemount 8600D to display flow in standard cubic feet per minute (SCFM). (Fluid is hydrogen flowing at conditions of 170 °F and 100 psia.) Assume base conditions of 59 °F and 14.696 psia.)
14
Configuration
00809-0100-4860, Rev BD
Fixed process density
FastKeys 1, 3, 2, 4, 2
Process Density is required only if you have designated mass units for your flow rate units. You will first be prompted for density units. It is required for the conversion from volumetric units to mass units. For example, if you have set flow units to kg/sec rather than gal/sec, a density is required to convert the measured volumetric flow into the desired mass flow. The Fixed Process Density must be entered even in temperature compensated Saturated Steam applications as this value is used to determine flow sensor limits in Mass Flow Units.
Note
If mass units are chosen, you must enter the density of your process fluid into the software. Be careful to enter the correct density. The mass flow rate is calculated using this user-entered density, and any error in this number will cause error in the mass flow measurement. If fluid density is changing over time, it is recommended that volumetric flow units be used.

2.3.3 Reference K-factor

Configuration
October 2016
FastKeys 1, 3, 3
The reference K-factor is a factory calibration number relating the flow through the meter to the shedding frequency measured by the electronics. Every Rosemount 8600 meter manufactured by Emerson is run through a water calibration to determine this value.

2.3.4 Flange type

FastKeys 1, 3, 4
Flange Type enables you to specify the type of flange on the flowmeter for later reference. This variable is preset at the factory but can be changed if necessary.
ANSI 150
ANSI 300
PN16
PN40
Spcl
Configuration
15
Configuration
October 2016

2.3.5 Mating pipe ID (Inside Diameter)

FastKeys 1, 3, 5
The Pipe ID (Inside Diameter) of the pipe adjacent to the flowmeter can cause entrance effects that may alter flowmeter readings. You must specify the exact inside diameter of the pipe to correct for these effects. Enter the appropriate value for this variable.
Pipe ID values for schedule 10, 40, and 80 piping are given in Table 2-1. If the piping in your application is not one of these, you may need to contact the manufacturer for exact Pipe ID.
f
Table 2-1. Pipe IDs for Schedule 10, 40, and 80 Piping
Reference Manual
00809-0100-4860, Rev BD
Pipe Size
Inches (mm)
1 (25) 1.097 (27.86) 1.049 (26.64) 0.957 (24.31)
1? (40) 1.682 (42.72) 1.610 (40.89) 1.500 (38.10)
2 (50) 2.157 (54.79) 2.067 (52.50) 1.939 (49.25)
3 (80) 3.260 (82.80) 3.068 (77.93) 2.900 (73.66)
4 (100) 4.260 (108.2) 4.026 (102.3) 3.826 (97.18)
6 (150) 6.357 (161.5) 6.065 (154.1) 5.716 (145.2)
8 (200) 8.329 (211.6) 7.981 (202.7) 7.625 (193.7)
Schedule 10
Inches (mm)

2.3.6 Variable mapping

FastKeys 1, 3, 6
Allows the user to select which variables the Rosemount 8600D will output.
Primary Variable (PV)
FastKeys 1, 3, 6, 1
Selections for this Variable are Mass Flow, Volumetric Flow, Velocity Flow, and Process Temperature. The Primary Variable is the variable mapped to the analog output.
Secondary Variable (SV)
Schedule 40
Inches (mm)
Schedule 80
Inches (mm)
16
FastKeys 1, 3, 6, 2
Selections for this Variable include all Variables that can be mapped to PV, and also Vortex Frequency, Pulse Output Frequency, Totalizer Value, Calculated Process Density, Electronics Temperature, and Cold Junction (CJ) Temperature.
Tertiary Variable (TV)
FastKeys 1, 3, 6, 3
Selections for this Variable are identical to those of the Secondary Variable.
Quaternary Variable (4V)
FastKeys 1, 3, 6, 4
Selections for this Variable are identical to those of the Secondary Variable.
Configuration
00809-0100-4860, Rev BD

2.3.7 PV units

FastKeys 1, 3, 7
Selections for this include all units available for the selection of PV. This will set the units for the flow rate or process temperature.

2.3.8 Range values

FastKeys 1, 3, 8
Range Values enables you to maximize resolution of analog output. The meter is most accurate when operated within the expected flow ranges for your application. Setting the range to the limits of expected readings will maximize flowmeter performance.
The range of expected readings is defined by the Lower Range Value (LRV) and Upper Range Value (URV). Set the LRV and URV within the limits of flowmeter operation as defined by the line size and process material for your application. Values set outside that range will not be accepted.
Primary Variable Upper Range Value (PV URV)
Configuration
October 2016
FastKeys 1, 3, 8, 1
This is the 20 mA set point for the meter.
Primary Variable Lower Range Value (PV LRV)
FastKeys 1, 3, 8, 2
This is the 4 mA set point for the meter, and is typically set to 0 when the PV is a Flow Variable.

2.3.9 PV damping

FastKeys 1, 3, 9
Damping changes the response time of the flowmeter to smooth variations in output readings caused by rapid changes in input. Damping is applied to the Analog Output, Primary Variable, Percent of Range, and Vortex Frequency. This will not affect the Pulse Output, Total, or other Digital Information.
The default damping value is 2.0 seconds. This can be reset to any value between 0.2 to 255 seconds when PV is a flow variable or 0.4 to 32 seconds when PV is Process Temperature. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the loop dynamics in your system.
Note
If the vortex shedding frequency is slower than the damping value selected, no damping is applied.
Configuration
17
Configuration
October 2016

2.3.10 Auto adjust filter

FastKeys 1,3, Scroll to
Bottom
The Auto Adjust Filter is a function that can be used to optimize the range of the flowmeter based on the density of the fluid. The electronics uses process density to calculate the minimum measurable flow rate, while retaining at least a 4:1 signal to the trigger level ratio. This function will also reset all of the filters to optimize the flowmeter performance over the new range. If the configuration of the device has changed, this method should be executed to ensure the signal processing parameters are set to their optimum settings. For a stronger signal select a density value that is lower than the actual flowing density.
Reference Manual
00809-0100-4860, Rev BD
18
Configuration
1. Device Setup
2. PV
3. AO
4. LRV
5. URV
1. Process
Variables
2. Diagnostics and Service
3. Basic Setup
4. Detailed
Setup
5. Review
1. PV
2. PV % Range
3. Analog Output
4. View Other
Variables
1. Volumetric Flow
2. Mass Flow
3. Velocity Flow
4. Totalizer
5. Pulse Frequency
6. Vortex Frequency
7. Electronics Temp
8. Calc Proc Density
9. Process Temp
- CJ Tem
p
erature
1. Volume Flow
2. Units
3. Special Units
1. Base Volume Unit
2. Base Time Unit
3. User Defined Unit
4. Conversion Number
1. Mass Flow
2. Mass Flow Unit
1. Total
2. Start
3. Stop
4. Reset
5. Totalizer Config
1. Electr Temp
2. Elec Temp Units
1. Test/Status
2. Loop Test
3. Pulse Output Test
4. Flow Simulation
5. D/A Trim
6. Scaled D/A Trim
7. Shed Fre
q
at URV
1. View Status
2. Config Status
3. Density Test Calc
4. Min/Max Temps
5. Self Test
6. Reset Xmt
r
1. PV
2. Shedding Frequency
3. Configure Flow Simulation
4. Enable Normal Flow
5. Mode
1. Tag
2. Process Config
3. Reference K Factor
4. Flange Type
5. Mating Pipe ID
6. Variable Mapping
7. PV Unit
8. Range Values
9. PV Damping
- Auto Ad
j
ust Filte
r
1. Transmitter Mode
2. Process Fluid
3. Fixed Process Temp
4. Density / Dens Ratio
1. Density Ratio
2. Fixed Process Density
1. Density Ratio
2. Calc Density Ratio
1. PV is
2. SV is
3. TV is
4. QV is
1. URV
2. LRV
3. PV Min Span
4. USL
5. LSL
1. Operating Conditions
2. Base Conditions
3. Exit
1.Characterize Meter
2. Configure Outputs
3. Signal Processing
4. Device Information
1. K Factor
2. Mating Pipe ID
3. Flange Type
4. Wetted Material
5. Meter Body #
6. Installation Effects
1. Reference K Factor
2. Compensated K Factor
1.Anlg Output
2. Pulse Output
3.HART Output
4. Local Display
1. Range Values
2. Loop Test
3. Alarm Jumper
4. D/A Trim
5. Alarm Level Select
6. Alarm/Sat Levels
7. Scaled D/A Trim
8. Recall Factor
y
Trim
1. Vel. Flow
2. Vel. Flow Unit
3. Velocity Meas Base
1. High Alarm
2. High Saturation
3. Low Saturation
4. Low Alarm
1. Pulse Output
2. Pulse Output Test
1. Off
2. Direct (Shedding)
3. Scaled Volume
4. Scaled Velocity
5. Scaled Mass
1. Poll Address
2. # of Req Preams
3. Num Resp P reams
4. Burst Mode
5. Burst Option
6. Burst Xmtr Vars
1.Xmtr Var, Slot 1
2.Xmtr Var, Slot 2
3.Xmtr Var, Slot 3
4.Xmtr Var, Slot 4
1. Optimize Flow Range
2. Manual Filter Adjust
3. Filter Restore
4. Damping
5. LFC Response
1. Manufacturer
2. Tag
3. Descriptor
4. Message
5. Date
6. Write Protect
8. Revision Numbers
7. Transmitter Options
1. PV
2. LFC
3. Sig/Tr
4. Auto Adjust Filter
1. PV
2. Sig/Tr
3. Low Flow Cutoff
4. Low Pass Filter
5. Trigger Level
1. Universal Rev
2. Transmitter Rev
3. Software Rev
4. Hardware Rev
5. Final Assembly #
6. Device ID
7. Board Serial #
1. Proc Density
2. Density Units
1. Proc Temp
2. Proc Temp Units
3. T/C Failure Mode
1. URV
2. LRV
3. PV Min Span
4. USL
5. LSL
1. CJ Temp
2. CJ Temp Units
1. Min Electr Temp
2. Max Electr Temp
1. PV Damping
2. Flow Damping
3. Temperature Damping
00809-0100-4860, Rev BD
Figure 2-1. Field Communicator Menu Tree for the Rosemount 8600D
Configuration
October 2016
Configuration
19
Configuration
October 2016
Reference Manual
00809-0100-4860, Rev BD
Table 2-2. Field Communicator Fast Key Sequences for the Rosemount 8600D
Function Fast Keys Function Fast Keys
Alarm Jumper 1, 4, 2, 1, 3 Message 1, 4, 4, 4 Analog Output (Config) 1, 4, 2, 1 Meter Body Number 1, 4, 1, 5 Analog Output (View) 1, 1, 3 Minimum Span 1, 3, 8, 3 Auto Adjust Filter 1, 4, 3, 1, 4 Num Req Preams 1, 4, 2, 3, 2 Base Time Unit 1, 1, 4, 1, 3, 2 Poll Address 1, 4, 2, 3, 1 Base Volume Unit 1, 1, 4, 1, 3, 1 Process Fluid Type 1, 3, 2, 2 Burst Mode 1, 4, 2, 3, 4 Process Variables 1, 1 Burst Option 1, 4, 2, 3, 5 Pulse Output 1, 4, 2, 2, 1 Burst Variable 1 1, 4, 2, 3, 6, 1 Pulse Output Test 1, 4, 2, 2, 2 Burst Variable 2 1, 4, 2, 3, 6, 2 PV Damping 1, 3, 9 Burst Variable 3 1, 4, 2, 3, 6, 3 PV Mapping 1, 3, 6, 1 Burst Variable 4 1, 4, 2, 3, 6, 4 PV Percent Range 1, 1, 2 Burst Xmtr Variables 1, 4, 2, 3, 6 QV Mapping 1, 3, 6, 4 Conversion Number 1, 1, 4, 1, 3, 4 Range Values 1, 3, 8 D/A Trim 1, 2, 5 Review 1, 5 Date 1, 4, 4, 5 Revision Numbers 1, 4, 4, 7 Descriptor 1, 4, 4, 3 Scaled D/A Trim 1, 2, 6 Density Ratio 1, 3, 2, 4, 1, 1 Self Test 1, 2, 1, 5 Device ID 1, 4, 4, 7, 6 Signal to Trigger Ratio 1, 4, 3, 2, 2 Electronics Temp 1, 1, 4, 7, 1 STD/Nor Flow Units 1, 1, 4, 1, 2 Electronics Temp Units 1, 1, 4, 7, 2 Special Units 1, 1, 4, 1, 3 Filter Restore 1, 4, 3, 3 Status 1, 2, 1, 1 Final Assembly Number 1, 4, 4, 7, 5 SV Mapping 1, 3, 6, 2 Fixed Process Density 1, 3, 2, 4, 2 Tag 1, 3, 1 Fixed Process Temperature 1, 3, 2, 3 Total 1, 1, 4, 4, 1 Flange Type 1, 3, 4 Totalizer Control 1, 1, 4, 4 Flow Simulation 1, 2, 4 Transmitter Mode 1, 3, 2, 1 Installation Effects 1, 4, 1, 6 TV Mapping 1, 3, 6, 3 K-Factor (reference) 1, 3, 3 Trigger Level 1, 4, 3, 2, 5 Local Display 1, 4, 2, 4 URV 1, 3, 8, 1 Loop Test 1, 2, 2 User Defined Units 1, 1, 4, 1, 3, 3 Low Flow Cutoff 1, 4, 3, 2, 3 USL 1, 3, 8, 4 Low Pass Filter 1, 4, 3, 2, 4 Shedding Frequency 1, 1, 4, 6 LRV 1, 3, 8, 2 Variable Mapping 1, 3, 6 LSL 1, 3, 8, 5 Velocity Flow 1, 1, 4, 3 Manufacturer 1, 4, 4, 1 Velocity Flow Base 1, 1, 4, 3, 3 Mass Flow 1, 1, 4, 2, 1 Volumetric Flow 1, 1, 4, 1 Mass Flow Units 1, 1, 4, 2, 2 Wetted Material 1, 4, 1, 4 Mating Pipe ID (Inside Diameter) 1, 3, 5 Write Protect 1, 4, 4, 6
20
Configuration
00809-0100-4860, Rev BD

Section 3 Installation

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Hazardous locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 27
Hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 27
Meter body installation tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
Electronics considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32
Software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 41
Transient protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 44
This section provides installation instructions for the Rosemount 8600D Vortex Flowmeter. Dimensional drawings for each Rosemount 8600D variation and mounting configuration are included in the Appendix on page 100.
The options available for the Rosemount 8600D flowmeter are also described in this section. The numbers in parentheses refer to the codes used to order each option.
Installation
October2016

3.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Refer to the following safety messages before performing any operation in this section.
Explosions could result in death or serious injury.
Do not remove the transmitter cover in explosive atmospheres when the circuit is
alive.
Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate
hazardous locations certifications.
Both transmitter covers must be fully engaged to meet explosion-proof
requirements.
Failure to follow these installation guidelines could result in death or serious injury.
Make sure only qualified personnel perform the installation.
Installation
21
Installation
Is
Configuration
OK?
Mount
Flowmeter
Wire
Flowmeter
Power
Flowmeter
DONE
Mount
Conduit
START HERE
FIELD
INSTALL
CONFIGURE
Tag
Process Config
• Transmitter Mode
• Process Fluid
• Fixed Process Temp.
•Dens/Dens Ratio
-Density Ratio
(Std. or Normal Volumetric Flow Units Only)
-Fixed Process Density (Mass Flow Units Only)
No
Bench
Commissioning?
Review
Configuration
Ye s
No
Ye s
Did you
Configure on
Bench?
No
Ye s
Configure if
Necessary
Go to
Review
Configuration
A
A
A
Go to
B
Go to
B
Reference
K-Factor
Mating Pipe ID
Variable Mapping
Flange Type
PV Unit
Range Values
PV Damping
Auto Adjust Filter
Using
LCD?
Yes
Configure
Local
Display
Using Pulse
Output
No
Using
Totalizer
Meter
Installed
Configure
Pulse
Output
Yes
No
Configure
Totalizer
Yes
No
Yes
No
DONE
October 2016
Figure 3-1. Installation Flowchart
Reference Manual
00809-0100-4860, Rev BD
22
Installation
Loading...
+ 106 hidden pages