This instruction is a supplement to the Rosemount 5300 Series Reference
Manual (Document No. 00809-0100-4530), and the Rosemount 5400 Series
Reference Manual (Document No. 00809-0100-4026).
www.rosemount.com
Manual Supplement
00809-0500-4530, Rev AA
Rosemount 5300/5400 Series
October 2010
SAFETY MESSAGESProcedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol (). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Failure to follow safe installation and service guidelines could result in death or
serious injury
• Make sure the transmitter is installed by qualified personnel and in accordance
with applicable code of practice.
• Use the equipment only as specified in the Rosemount 5300 Series Reference
Manual (Document No. 00809-0100-4530), the Rosemount 5400 Series
Reference Manual (Document No. 00809-0100-4026), and in this Manual
Supplement. Failure to do so may impair the protection provided by the
equipment.
• Do not perform any services other than those contained in this manual unless
you are qualified.
Explosions could result in death or serious injury
• Verify that the operating environment of the transmitter is consistent with the
appropriate hazardous locations specifications.
• To prevent ignition of flammable or combustible atmospheres, disconnect
power before servicing.
®
• Before connecting a HART
an explosive atmosphere, make sure the instruments in the loop are installed in
accordance with intrinsically safe or non-incendive field wiring practices.
• To avoid process leaks, only use o-ring designed to seal with the
corresponding flange adapter.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
• Make sure the main power to the Rosemount 5300 Series transmitter or
Rosemount 5400 Series transmitter is off and the lines to any other external
power source are disconnected or not powered while wiring the transmitter.
Probes with non-conducting surfaces
• Probes covered with plastic and/or with plastic discs may generate an
ignition-capable level of electrostatic charge under certain extreme conditions.
Therefore, when the probe is used in a potentially explosive atmosphere,
appropriate measures must be taken to prevent electrostatic discharge.
or FOUNDATION™ fieldbus based communicator in
1-2
Manual Supplement
5300/5400
transmitter
electronics
HART
signals
HART to
Modbus
Converter
Modbus and
Levelmaster
communication
Remote
Terminal
Unit
Rosemount
Radar Master/
Field
Communicator
HART signals
5300/5400 transmitter enclosure
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
INTRODUCTIONThe Rosemount 5300 Series and Rosemount 5400 Series transmitters are
Modbus compatible measurement devices that support commun ication with a
Remote Terminal Unit (RTU) using a subset of read, write, and diagnostic
commands used by most Modbus compatible host controllers. The
transmitters also support communication through Levelmaster and Modbus
ASCII protocols.
®
The HART
Rosemount 5300 and Rosemount 5400 transmitter enclosure and provides
power to and communicates with the transmitter through a HART interface.
Figure 1-1. System Overview
to Modbus Converter (HMC) module is located inside the
During normal operation, the HMC “mirrors” the conten t s of process var iables
from the 5300/5400 transmitter to the Modbus registers. To configure the
5300/5400 transmitter, it is possible to connect a configuration tool to the
HMC. See “Transmitter Configuration” on page 1-13 for more information.
WORKFLOWOverview of workflow for commissioning a Rosemount 5300 or a Rosemount
5400 transmitter with Modbus protocol:
1. Mount the transmitter on the tank.
2. Connect the power and communication wires.
3. Establish HART communication with the transmitter through Rosemount
Radar Master , or a Field Communicator. This is done by:
•Connecting to the HART terminals, or
•Connecting to the MA/MB terminals (tunneling mode)
4. Configure the transmitter.
5. Configure the Modbus communication.
6. Configure Modbus host.
7. Verify output values as reported by the transmitter.
1-3
Rosemount 5300/5400 Series
Manual Supplement
00809-0500-4530, Rev AA
October 2010
MECHANICAL
INSTALLATION
ELECTRICAL
INSTALLATION
For instructions on how to mount the Rosemount 5300/5 400 transmitter, refer
to the Rosemount 5300 Series Reference Manual (Document No.
00809-0100-4530), and the Rosemount 5400 Series Reference Manual
(Document No. 00809-0100-4026).
NOTE
For general electrical installation requirements, including grounding
requirements, refer to Rosemount 5300 Series Refere nce Manual (Document
No. 00809-0100-4530), and the Rosemo un t 54 00 Seri es Re fe re nc e Ma n ua l
(Document No. 00809-0100-4026).
To connect the Rosemount 5300/5400:
1. Disconnect/shut off the electrical power to transmitter head and then
open the instrument cover. Do not remove the cover in an explosive
atmosphere with a live circuit.
2. Pull the cable through the cable gland/conduit. For the RS-485 bus, use
shielded twisted pair wiring, preferably with an impedance of 120
(typically 24 AWG) in order to comply with the EIA-485 standard and
EMC regulations. The maximum cable length is 4000 ft/1200 m.
3. Make sure that the transmitter housing is grounded, then connect wires
according to Figure 1-2 and Table 1-1. Connect the lead that originates
from the “A” line from the RS-485 bus to the terminal marked MB, and
the lead that originates from the “B” line to the terminal marked MA.
4. If it is the last transmitter on the bus, connect the 120 termination resistor.
5. Connect the leads from the positive side of the power supply to the
terminal marked POWER +, and the leads from the negative side of the
power supply to the terminal marked POWER -. The power supply
cables must be suitable for the supply volt age and ambien t temperatur e,
and approved for use in hazardous areas, where applicable.
6. Attach and tighten the housing cover. Tighten the cable gland, then plug
and seal any unused terminals, and connect the power supply.
1-4
Manual Supplement
RS-485 Bus
B
A
Power
Supply
HART
+
HART -
120
120
In case it is the last
transmitter on the
bus, connect the
120
termination
resistor
v
120
00809-0500-4530, Rev AA
October 2010
Figure 1-2. Field Wiring Connections
Rosemount 5300/5400 Series
HART to Modbus Converter
-
HART
+
MODBUS
(RS-485)
POWER
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
erter
MB
MB
MA
-
+
MODBUS
(RS-485)
MA
-
1-5
Manual Supplement
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
-
-
+
+
HART +
HART -
00809-0500-4530, Rev AA
Rosemount 5300/5400 Series
Connection TerminalsThe connection terminals are described in Table 1-1 below:
Table 1-1. Connection Terminals
Connector labelDescriptionComment
HART +Positive HART connectorConnect to PC with RRM
software, Field
HART -Negative HART connector
MA
MB
Modbus RS-485 B connection
(RX/TX+)
Modbus RS-485 A connection
(RX/TX-)
(1)
(1)
POWER +Positive Power input terminal
POWER -Negative Power input terminal
(1) The designation of the connectors do not follow the EIA-485 standard, which states
that RX/TX- should be referred to as 'A' and RX/TX+ as 'B'.
Communicator, or other
HART configurators.
Connect to RTU
Apply +8 Vdc to +30 Vdc
(max. rating)
October 2010
Figure 1-3. Connection Terminals
for Rosemount 5300/5400 with
HART to Modbus Converter
1-6
Manual Supplement
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
Power
Supply
120
120
RS-485 Bus
BAModbus
Master
Z
External
Ground Screw
Internal
Ground Screw
External
Ground Screw
Internal
Ground Screw
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
RS-485 Bus•The 5300/5400 transmitters do not provide electrical isolation between
the RS-485 bus and the transmitter power supp ly
•Maintain a bus topology and minimize stub length
•Figure 1-4 identifies multidrop wiring topology, where up to 32 devices
may be wired on one RS-485 bus
•The RS-485 bus needs to be terminated once at each end, but should
not be terminated elsewhere on the bus
Installation casesInstall the Rosemount 5300/5400 Series Transmitters as shown in Figure 1-4.
•Use common ground for Modbus Master and Power Supply
•The Power cables and RS-485 Bus are in the same cable installation
•An ground cable is installed and shall be used (cable size ≥4 mm
according to IEC60079-14, or size according to applicable national
regulations and standards). A properly installed threaded conduit
connection may provide sufficient ground.
•The cable shielding is grounded at master site (optional)
NOTE
The HMC equipped transmitter contains intrinsically safe circuits that require
the housing to be grounded in accordance with national and local electrical
codes. Failure to do so may impair the protection provided by the equipment.
Figure 1-4. Multidrop Connection of
5300/5400 Transmitters
1-7
Rosemount 5300/5400 Series
Power
Supply
120
120
RS-485 Bus
BAModbus
Master
Z
External
Ground Screw
External
Ground Screw
Internal
Ground Screw
Internal
Ground Screw
v
For Star Topology
connection,
connect the 120
termination
resistor to the
transmitter with
the longest cable
run.
Alternatively, the Rosemount 5300/5400 Series Transmitters can be installed
as shown in Figure 1-5. If this wiring layout is used, there is an increased risk
for communication disturbances due to differences in potential between
grounding points. By using the same grounding point for Modbus Master and
Power Supply, this risk is reduced.
Figure 1-5. Alternative Multidrop
Connection of 5300/5400
Transmitters
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Figure 1-6. Star Topology
Connection of 5300/5400
Transmitters
HART to Modbus Converter
-
HART
+
HART to Modbus Converter
-
HART
+
MODBUS
(RS-485)
POWER
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
MB
MA
-
+
MODBUS
(RS-485)
MB
POWER
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
MA
-
+
Star Topology
For a St ar Topology Connection of the 5300/5400 transmitters, the transmitter
with the longest cable run needs to be fitted with a 120- termination resistor.
erter
HART to Modbus Converter
MB
MA
MODBUS
(RS-485)
-
-
+
POWER
Ambients > 60 ºC
HART
Use wiring rated
for min 90 ºC
HART to Modbus Converter
MB
MA
MODBUS
(RS-485)
-
-
+
POWER
Ambients > 60 ºC
HART
Use wiring rated
for min 90 ºC
+
+
HART to Modbus Converter
MB
MA
MODBUS
(RS-485)
MB
MA
MODBUS
(RS-485)
-
-
+
POWER
Ambients > 60 ºC
HART
Use wiring rated
for min 90 ºC
+
-
HART to Modbus Converter
MB
MA
MODBUS
(RS-485)
-
-
+
POWER
Ambients > 60 ºC
HART
Use wiring rated
for min 90 ºC
+
1-8
HART to Modbus Converter
MB
MA
MODBUS
(RS-485)
-
-
+
POWER
Ambients > 60 ºC
HART
Use wiring rated
for min 90 ºC
+
Manual Supplement
Power
Supply
RS-485
Bus
Up to four
external
devices
External HART
device 2
External HART
device 1
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
External HART Devices
(Slaves)
Table 1-2. Approximate update
rates for measurement values
The HMC supports up to four external HART devices. The external devices
are separated by using the HART address. The address must be different
between the external devices and only addr e sse s 1 to 5 are allo we d for
multiple slaves. Connect the devices one at a time and change the short
address prior to connecting the next device by using a HART Configuration
Tool such as RRM, or a Field Communicator.
NOTE
The power supply from the HMC to external HART devices is not intrinsically
safe. In a hazardous environment, any exter n al HA RT device conn ec te d to
the HMC must have Flameproof/Explosion-proof certification.
The HMC cyclically polls the HART devices for measurement values. The
update rate depends on the number of connected devices and is shown in
Table 1-2.
Figure 1-7. The HMC Module
supports up to four external devices
(slaves)
HART to Modbus Converter
-
+
MB
MA
MODBUS
(RS-485)
-
+
POWER
HART
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
1-9
Rosemount 5300/5400 Series
HART
20 seconds
Modbus RTU
20 seconds
Configured
protocol
(Modbus RTU,
Levelmaster,
or Modbus
ASCII)
20 seconds
HART
20 seconds
Time
0 s20 s40 s60 s80 s100 s
Configured
protocol
(Modbus RTU,
Levelmaster,
or Modbus
ASCII)
20 seconds
Manual Supplement
00809-0500-4530, Rev AA
October 2010
ESTABLISH HART
COMMUNICATION
Connect to the MA/MB
terminals
Figure 1-8. RS-485 Communication
after startup
The Rosemount 5300 Series and Rosemount 5400 Series can be configured
using the Rosemount Radar Master (RRM) PC software or a Field
Communicator. Configuration is done by sending HART commands through
the HART to Modbus Converter (HMC) to the 5300/5400 transmitter
electronics. To establish HART communication, connect to the MA/MB
terminals, or to the HART terminals. Both alternatives are desc rib ed belo w.
The 5300/5400 level transmitter can be configured with RRM using the MA,
MB terminals.
An RS-485 Converter is required to connect to the transmitter.
The transmitter will try to establish communication using different protocols
during 20 second timeslots from time of startup.
The transmitter will continue to use a communication protocol once
communication has been established.
1-10
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
To configure the 5300/5400 level transmitter using RRM and the MA, MB
terminals, do the following:
1. Connect the RS-485 Converter to the MA, MB connectors.
2. Start RRM and open Communication Preferences.
3. Enable HART communication and make sure the port for the RS-485
Converter is selected. Use the following settings:
4. Connect the power wires (or cycle power) to the transmitter.
5. Wait 20 seconds and then open the Sea rch Device windo w in RRM (also
see note below). Make sure HART address 1 is being scanned.
1-11
Rosemount 5300/5400 Series
6. Connect to the transmitter and perform the necessary configuration.
7. After completing the configuration, disconnect the RS-485 Converter,
connect the Modbus communication wires and cycle power to the
transmitter
8. Verify communication between the transmitter and the RTU is
established (can take up to 60 seconds from startup) .
NOTE
Take the following into consideration if there are multiple 5300/5400 Modbus
units on the bus:
By default, the transmitters have HART address 1. It will not be possible to
establish communication on HART address 1 if several transmitters have the
same address. In this case, there are alternative solutions to establish
communication:
1. Select the Scan by T ag option in the Search Device window in RRM and
enter the HART Device Tag of the transmitter. Communication can now
be established with an individual transmitter even if several devices have
the same HART address.
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Connect to the HART
terminals
1-12
2. Make sure the 5300/5400 transmitter is alone on bu s. Disconnect or tur n
off power from any other devices.
To configure the 5300/5400 transmitter, connect the communicator or PC to
the HART terminals using a HART modem, see Figure 1-3 on p a ge 1-6. Both
the configuration tool and the RS-485 bus can be connected simultaneously.
Configuration data is sent with HART commands through the HMC to the
5300/5400 transmitter electronics, as illustrated in Figure 1-1 on page 1-3.
Note that the power supply must be connected during configuration, see also
“Electrical Installation” on page 1-4.
NOTE
Measurement data is not updated to the Modbus Master when a configur ation
tool is connected.
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
TRANSMITTER
CONFIGURATION
Configuration data such as Tank Height, Upper Null Zone, dielectric
constants, and other basic parameters are configured in the same way as for
a standard Rosemount 5300/5400 transmitter. For more information, see the
Rosemount 5300 Series Quick Installation Guide (Document No.
00825-0100-4530), and the Rosemount 5400 Series Quick Installation Guide
(Document No. 00825-0100-4026).
Make sure that the measurement unit of the Primary Variable (PV) matches
the configuration of the Modbus Host since the transmitter output value does
not include any information on associated measurement units.
For further information on basic configuration, see the Rosemount 5300
Series Reference Manual (Document No. 00809-0100-4530), and the
Rosemount 5400 Series Reference Manual (Document No.
00809-0100-4026).
NOTE
The 5300/5400 transmitter with Modbus protocol is configured to HART
address 1 at factory. This reduces power consumption by locking the analog
output at 4 mA.
1-13
Loading...
+ 29 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.