Rockwell Automation MobileView Tethered Operator Terminal User Manual

MobileView Tethered Operator Terminal
Catalog Numbers 2711T-B10I1N1, 2711T-B10R1K1, 2711T-B10R1M1, 2711T-F10GIN1, 2711T-T10G1N1, 2711T-T10I1N1-TC, 2711T-T10R1N1, 2711T-BRACKET, 2711T-VMBRACKET, 2711T-JBIP20DC, 2711T­JBIP65DC1, 2711T-JBIP65DM1, 2711T-JBBKCOVER, 2711T­5MCABLE, 2711T-5MCABLE2, 2711T-10MCABLE, 2711T-10MCABLE2, 2711T-15MCABLE, 2711T-15MCABLE2, 2711T-JUMP, 2711T-22JUMP
Original Instructions
MobileView Tethered Operator Terminal User Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WA RN I NG : Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
2 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021

Table of Contents

Preface
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1
Features Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
MobileView 2711T Terminal Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
MobileView 2711T Terminal Component Description . . . . . . . . . . . . . . . 10
MobileView 2711T Terminal Dimensions and Weight . . . . . . . . . . . . . . . 11
Membrane Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Resistive Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
USB 2.0 Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 2 Safety Precautions and Elements
General Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Programmable Electronic Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Enabling Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Enabling Switch Connection Example with a Control Relay. . . . . . 14
Foreseeable Misuse of the Enabling Switch. . . . . . . . . . . . . . . . . . . . . 16
Emergency Stop (E-stop) Push Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Risk Assessment of Machinery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
MobileView 2711T Terminal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
MobileView Junction Box Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Chapter 3
Operate the Terminal Install a Connection Cable to a MobileView Terminal. . . . . . . . . . . . . . . 19
Remove the Back Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Install the Connection Cable to the MobileView 2711T Terminal . . 20
Relocate the Connection Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Adjust the Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Adjust the Display Brightness and GPU Energy Setting. . . . . . . . . . 25
Recalibrate the Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Shut Down the MobileView 2711T Terminal. . . . . . . . . . . . . . . . . . . . . . . . 28
Disconnect Power from the MobileView 2711T Terminal . . . . . . . . . 28
Install the Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 3
Table of Contents
Chapter 4
Install and Operate the Junction Boxes
Junction Box Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
The MobileView IP20 Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Mount and Connect the IP20 Junction Box. . . . . . . . . . . . . . . . . . . . . 32
Connect a First Generation MobileView Terminal to the IP20
Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Connect to an Ethernet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
The MobileView IP65 Junction Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Mount the IP65 Junction Box Back Plate . . . . . . . . . . . . . . . . . . . . . . . 36
Temporarily Mount the IP65 Junction Box . . . . . . . . . . . . . . . . . . . . . 37
Wire the 2711T-JBIP65DC1 Junction Box . . . . . . . . . . . . . . . . . . . . . . . 38
Configure the 2711T-JBIP65DC1 Junction Box. . . . . . . . . . . . . . . . . . . 41
Configure the 2711T-JBIP65DM1 Junction Box . . . . . . . . . . . . . . . . . . 43
Mount the IP65 Junction Box to Its Back Plate . . . . . . . . . . . . . . . . . . 44
Connect M12 On-Machine Connectors to the 2711T-JBIP65DM1
Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Connect Power to IP65 Junction Boxes. . . . . . . . . . . . . . . . . . . . . . . . . 46
IP65 Junction Box Status Indicator Lights. . . . . . . . . . . . . . . . . . . . . . 48
Connect a Second Generation MobileView Terminal to an IP65
Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Connect a Black Bridge Connector to an IP65 Junction Box . . . . . . 50
Set Up the BIOS Settings and Desktop Icons
Chapter 5
End User Setup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Desktop Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Buttons on the Task Bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Enhanced Write Filter (EWF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
FTView ME Station. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Transfer the MER File With a USB Storage Device . . . . . . . . . . . . . . 54
Transfer the MER File Through the Ethernet Network. . . . . . . . . . . 56
FactoryTalk View ME Station Software Patch. . . . . . . . . . . . . . . . . . . 59
KEPServer Enterprise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
VNC Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
System Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Update the Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Update the BIOS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Network Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Remote Desktop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Touch Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Rescue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Restore the Default BIOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Change the BIOS Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Back Up the Operating System Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Restore the Operating System Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 6
Table of Contents
Maintain and Troubleshoot the MobileView Terminal and IP65 Junction Box
Clean the MobileView 2711T Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Handle and Care for the MobileView 2711T Terminal and
IP65 Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Chemical Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Real-time Clock Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Troubleshoot the MobileView 2711T Terminal . . . . . . . . . . . . . . . . . . . . . . 80
Troubleshoot the IP65 Junction Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Provide Information to Technical Support. . . . . . . . . . . . . . . . . . . . . . . . . 82
Ship or Transport a MobileView Device . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Dispose of a MobileView Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Appendix A
Specifications MobileView Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
IP20 Junction Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
IP65 Junction Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
MobileView Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Standard and Agency Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 5
Table of Contents
Notes:
6 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021

Preface

This manual is a user guide for MobileView™ 2711T tethered operator terminals and MobileView junction boxes. It provides procedures to the following:
Install a MobileView 2711T terminal and junction box.
Make MobileView 2711T terminal and junction box connections.
Operate the MobileView 2711T terminal and junction box.
Troubleshoot MobileView 2711T terminals and IP65 junction boxes.
IMPORTANT
This publication must be kept throughout the entire service life of the MobileView 2711T terminal and junction box.
Summary of Changes This manual contains new and updated information as indicated in the
following table.
Top ic Pa ge
Added sentence to Adjust the Display Brightness and GPU Energy Setting to indicate Display Brightness should be set to 50% and instruction for adjusting GPU Energy Setting.
Corrected Desktop Overview screen showing Desktop as of May 2016 to include KEPServer icon.
Removed licensing requirement text from IMPORTANT statement in KEPServer Enterprise section.
Updated Operating Temperature in table in Appendix A. 86
25
52
61
Abbreviations This publication can use the following abbreviations.
Abbr Description Abbr Description
BIOS Basic input/output system LCD Liquid crystal display BSS Bootable service system OS Operating system DHCP Dynamic host configuration protocol PCB Printed circuit board DRAM Dynamic random access memory SD Secure Digital EEA European Economic Area TFT Thin film transistor EMC Electromagnetic Compatibility TFT Thin film transistor ESD Electrostatic discharge UPD Updated program data EWF Enhanced write filter USB Universal serial bus HMI Human machine interface VMDK Virtual machine disk IP Internet protocol VNC Virtual network computing
International Organization for
ISO
Standardization
ISP Internet service provider
WXGA Wide extended graphics array
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 7
Preface
Additional Resources These documents contain more information to related products from Rockwell
Automation.
Resource Description
FactoryTalk® View Machine Edition User Guide, publication VIEWME-UM004
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website,
rok.auto/certifications
Provides comprehensive information about FactoryTalk View Machine Edition, procedures to create and run an automation application, and reference information.
Provides general guidelines to install a Rockwell Automation® industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
rok.auto/literature.
8 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 1
Features
Overview The MobileView™ 2711T family of human machine interface (HMI) devices
have a rugged design with features that include a 3-position enable switch,
(a)
touch and function keys, and stop push buttons access the safety system of a machine and the general interface to its control system.
There are two generations of MobileView 2711T terminals. First generation terminals use a 20-pin connection cable with a silver connector to connect to an IP20 junction box. Second generation terminals use a 22-pin connection cable with a black connector to connect to one of two available IP65 junction boxes. Because of the pin differences, you cannot mix components between generations.
. These features let you
A second generation MobileView terminal, cat. no. 2711T-T10I1N1-TC, is a thin client model without an operating system but is set for PXE boot into a thin client server. This terminal is configured to work with ThinManager® software. To learn more about how to PXE boot into a ThinManager server, access the Rockwell Automation Knowledgebase link at
https://rockwellautomation.custhelp.com/
There are two IP65 junction boxes that work with second generation MobileView terminals. One junction box has cord grip connections, and the other junction box has M12 On-Machine™ connections. Both IP65 junction boxes have LED lights and a status indicator bar on their front plate that can signify different operating and error states.
and search for AID 1043685.
(a) Three of the first generation MobileView terminals are equipped with a red-yellow emergency stop (E-stop) push button, both
second generation MobileView terminals are equipped with an illuminated red E-stop push button, and two of the first generation MobileView terminals are equipped with a gray stop button that is not classified as an E-stop button.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 9
Chapter 1 Features
12 34 5 78
9
11
6
10
10
MobileView 2711T Terminal Options
The following tables summarize the options available for the 2711T MobileView tethered operator terminals. A comparative summary of features for the MobileView terminals is in Appendix A, MobileView Terminals
on page 85.
First Generation MobileView Terminal Options
Cat. No. (2711T-)
B10R1K1 B10R1M1 No Yes F10G1N1 No No Yes T10G1N1 No T10R1N1 Yes No
Display Size (in.)
10.1 Yes
Tou ch Screen
Function Keys
Yes
3-position Enabling Switch
Yes
3-position Key Switch
Yes No
Momentary Button
2-circuit Push Button E-stop
(red/ yellow)
Yes No
Stop (gray)
Second Generation MobileView Terminal Options
Cat. No. (2711T-)
B10I1N1 1 0 .1 Yes Yes Yes No N o Yes No T10I1N1-TC No
Display Size (in.)
Tou ch Screen
Function Keys
See MobileView Accessories
3-position Enabling Switch
3-position Key Switch
Momentary Button
on page 88 for what accessories are available for
2-circuit Push Button Illuminated
E-stop
Stop (gray)
each generation of MobileView terminals.
MobileView 2711T Terminal
The following illustration shows the location of key hardware components.
Component Description
First
Item Description
1 Membrane keypad with tactile feedback • 2 10 inch WXGA (1280 x 800 pixels) TFT color LCD display with analog-resistive touch screen
• Illuminated momentary push button, normally open OR
3
• 3-position key switch
• Red emergency stop (E-stop) button, twin-circuit, N.C. contacts, 24V DC, 500 mA max OR
4
• Illuminated red E-stop button, twin circuit, N.C. contacts, 24V DC, 500 mA max
5 Backside membrane keypad with tactile feedback • 6USB port •—
Generation Standard Option Standard
(2)
Second Generation
(1)
— —
(2)
10 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 1 Features
352 mm (13.86 in.)
274 mm
(10.79 in.)
108.5 mm (4.27 in.)
All MobileView 2711T terminals weigh 1550 g (3.42 lb).
1
2
3
4
5
6
First
Item Description (Continued)
7Product nameplate •—• 8 Handle to hold the terminal, to store the connection cable, and to attach to the mounting bracket • 9 3-position, twin circuit, enabling switch for safety system interface • 10 Plug for alternate cable outlet not used (meets degree protection IP65) • 11 Back cover to access connection compartment
(1) 2711T-T10I1N1-TC MobileView terminal does not have this feature. (2) 2711T-F10GIN1 and 2711T-T10G1N1 MobileView terminals are equipped with a gray push button that is classified as a stop button but not an E-stop button.
Generation Standard Option Standard
Second Generation
MobileView 2711T Terminal Dimensions and Weight
Membrane Keypad
The MobileView 2711T terminal has a membrane keypad with stainless steel dome switches for tactile feedback.
IMPORTANT The 2711T-T10I1N1-TC MobileView terminal does not have the function
keys shown in this section.
The keys on the MobileView 2711T terminal keypad operate similar to the keyboard of a Windows personal computer. Some 3-key combinations are
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 11
Chapter 1 Features
supported. The following table shows the corresponding keyboard shortcut for each function key.
IMPORTANT The following table applies to Microsoft® Windows® OS keyboard
shortcuts. All MobileView terminal keys are also mappable within a FactoryTalk®
Machine Edition (ME) application.
Function Key Keyboard Shortcut Function Key Keyboard Shortcut
F1 F1 2+ Right ALT+F3 F2 F2 2– Right ALT+F4 F3 F3 3+ Right ALT+F5 F4 F4 3– Right ALT+F6 F5 F5 4+ Right ALT+F7 F6 F6 4– Right ALT+F8 F7 F7 5+ Right ALT+F9 F8 F8 5– Right ALT+F10 1+ Right ALT+F1 6+ Right ALT+F11 1– Right ALT+F2 6– Right ALT+F12
Resistive Touch Screen The touch screen is calibrated before shipment. You can recalibrate the touch
screen. For more information, see Touch Calibration
Resistive touch screens are activated when you apply pressure to the touch screen with your finger. You can operate a resistive touch screen while gloves are worn.
Resistive touch screens accept only single finger input. Multi-finger input or ‘palm contact’ can cause an incorrect touch input.
ATTENTION: Do not use sharp objects, such as a screwdriver, on the touch screen. Scratching the surface of the touch screen can damage the display and compromise the IP rating.
on page 68.
USB 2.0 Port Use the USB 2.0 port on the back of the terminal to
perform the following tasks:
Connect a USB storage device for the following:
- Update or restore the BIOS settings
- Back up or restore the OS image
- Copy or move files to the internal Secure Digital (SD) card
Connect a USB keyboard or mouse
Connect a USB hub to use multiple USB devices simultaneously
IMPORTANT Any task that is performed through the USB port must be done
while the MobileView 2711T terminal is not used for operation. Do not use or keep a USB storage drive connected in the USB port
while the MobileView 2711T terminal is operated.
12 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 2
Safety Precautions and Elements
General Safety It is important to follow the instructions in this document in all circumstances.
Failure to do so can result in potential sources of danger or the possible override of safety features that are integrated in the terminal.
Besides the safety instructions in this document, you must also use safety precautions and accident prevention measures that are appropriate to the situation.
ATTENTION: Consider or perform the following as part of general safety.
• Verify that interrupted processes can be properly restarted after power failures or power dips. Do not allow any dangerous operating conditions to occur, even temporarily.
• In situations where faults that occur within the automation system could cause personal injury or significant damage to machinery and equipment, take extra safety measures to confirm that the system remains in an acceptable operating condition.
• When applying functional safety, restrict access to qualified, authorized personnel who are trained and experienced.
• Verify that unauthorized persons are not allowed to adjust settings or make memory modifications that can lead to dangerous situations.
• Test the functionality of the E-stop button and enabling switch at least once every six months. Verify that the machine or plant operation stops when the button is pushed.
• If the MobileView™ 2711T terminal and controller do not communicate with a point-to-point connection, then keypad data could transmit with a delay. An Ethernet switch that is used between the MobileView 2711T terminal and controller is recommended for a higher speed connection.
• When a MobileView 2711T terminal has been exposed to shock (for example, it is dropped on the ground), test to verify that the E-stop button and enabling switch still function properly.
• The USB port on the backside of the MobileView 2711T terminal is only for maintenance. Do not operate the terminal while a USB drive is connected to it.
• Risk assessment and risk reduction are important precautionary measures for machine safety. For more information, see ISO 12100.
Proper care and handling contribute to MobileView terminal and junction box safety. For more information on care and handling, see Handle and Care for
the MobileView 2711T Terminal and IP65 Junction Box on page 79.
Programmable Electronic Systems
ATTENTION: Personnel responsible for the application of safety-related
Programmable Electronic Systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 13
Chapter 2 Safety Precautions and Elements
Power Supply All MobileView 2711T terminals meet the Safety Class III requirements for
electrical shock in accordance with EN 61131-2. See Appendix A power supply requirements for a MobileView 2711T terminal, junction box, and connection cable.
SHOCK HAZARD: Supply the MobileView terminal and junction box exclusively from power sources with SELV or PELV circuit protection according to EN 61131-2. Only connect voltages and circuits that are separated from dangerous voltages (for example, by means of sufficient insulation) to connections, terminals or interfaces up to a rated voltage of 50V DC.
Specifications of power supply lines in the connection cables are:
2
Cross section: 26 AWG (0.126 mm
Material: zinc-coated copper strand
Line resistance: <136 Ω/km (<219 Ω/mi)
WA RN I NG : The 24V DC power supply to the control cabinet or operator panel must have a fuse that is rated 3.15A (max) and complies with UL 248. Failure to install a fuse can result in fire from component failure.
)
for the DC
Enabling Switch
On the MobileView 2711T terminal, the enabling switch consists of a 3-position operating element with two independent circuits.
WA RN I NG : Only the operator of the enabling device on the MobileView 2711T terminal is allowed in the dangerous area or zone. The enabling switch is only suitable as a safety device if the operator of the enabling switch on the MobileView 2711T terminal recognizes the dangerous situation and reacts in time to avoid the danger.
Consider reduced speed of movements as a precautionary measure, which can be done through the risk assessment of machinery.
Enabling Switch Connection Example with a Control Relay
Figure 1 on page 15 shows suggested wiring for the enabling switch with an
Allen-Bradley® safety control relay. If this wiring example is followed, then the safety function meets Category 4, Performance Level e (CAT. 4, PLe) in accordance with ISO 13849-1 or SIL 3 in accordance with EN 61508.
14 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 2 Safety Precautions and Elements
Table 1 - Callouts
Item Description
1 MobileView 2711T terminal 2 Enabling switches circuit board 3 Connection cable wires 4 Junction box input connection 5 Control cabinet 6 Junction box terminals
7
Allen-Bradley Guardmaster® safety relay
83-phase motor
Table 2 - Actuating Elements
Item Description
Voltage, nom
24V DC (typical) 30V DC (max)
Current, nom
500 mA (typical)
Inductive load, max
700 mA (DC13)
Figure 1 - Enabling Switch Wiring Example for a First Generation MobileView Terminal Connected to an IP20 Junction Box
1
2
CH1
CH2
3
4
6
5
+24 V DC
S1
1278910 1278910
X4
X1
1278910
+24 V
GND ED1+ ED1- ED2+ ED2-
K2K1
7
A1 A2
S11
S21
Y32
Reset
0
AM
MM
S12
S22
S34
13 14
23 24
L11
100S-C09EJ23BC
A1A1A2
K1
A2
K2
100S-C09EJ23BC
L1 L2 L3
External Switched
Stop/Start Circuit
K1
K2
8
M
Only if both channels (CH1 and CH2) of the enabling switch are activated ‘simultaneously’ do output contacts 13-14 and 23-24 close, and output relays K1 and K2 energize.
The output relays K1 and K2 do not energize if:
- Only one enabling channel is activated.
- The tolerance value for the simultaneity period is exceeded.
- The feedback control loop at S34 is open.
If one enabling channel is released after being simultaneously activated, the forced-guided output contacts 13-14 and 23-24 open, and output relays K1 and K2 return to their initial position. The output relays only energize again after both enabling channels have been released and operate simultaneously again.
In this way, the enabling switches avoid the one single error that makes the safety function inoperable. At the least, one error is recognized at the next cycle.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 15
Chapter 2 Safety Precautions and Elements
Foreseeable Misuse of the Enabling Switch
Foreseeable misuse is when the enabling switch is modified so it stays in the enabling position. The foreseeable misuse of the enabling switch must be restricted. The following measures are recommended, which cause the machine to stop in manual mode.
Inquiry of the enabling switch when you turn on the machine/plant, and inquiry of the enabling switch when you change the operating mode from automatic to manual (the enabling switch must not be in the enabling position).
The enabling switch must be released within a defined time period and pushed into the enabling position again, with the time length defined by the activity.
Emergency Stop (E-stop) Push Button
The E-stop push button of a MobileView 2711T terminal meets the requirements of ISO 13850. The button must be designed as a Category 0 or Category 1 emergency stop by the risk assessment for the machine. The connection of the force-guided contacts to an appropriate monitoring system must meet the safety level that results from the risk assessment of the machine. See Risk Assessment of Machinery
The E-stop has two potential-free, normally closed contacts to connect external peripherals, a nominal operating voltage of 24V (safety low voltage in accordance with EN 61131-2), and a maximum operating current of 500 mA at 24V DC.
WA RN I NG : E-stop push buttons (red-yellow in color) that are not fully functional can have fatal consequences. E-stop push buttons must be effective under all circumstances in all operating modes of a machine or plant.
• When the E-stop push button is not wired into an emergency stop circuit, the MobileView 2711T terminal must be stored where it is not visible to operators.
• The reset of an activated E-stop push button must not result in the uncontrolled startup of machines or installations.
• The E-stop push button does not replace other safety devices or E-stop buttons mounted directly on machines.
• Do not use MobileView 2711T terminals with red-yellow E-stop buttons in applications where the terminal is plugged in and out of junction boxes frequently or meant for temporary use. Only MobileView 2711T terminals with gray stop push buttons are meant for these applications.
• Test the functionality of the E-stop push button at least once every six months. Verify that machine or plant operation stops when the button is pushed.
• When a MobileView 2711T terminal has been exposed to shock (for example, it is dropped on the ground), test to verify that the E-stop push button still functions properly.
on page 16.
Risk Assessment of Machinery
For the risk assessment for the machinery, use the standards in ISO 12100, “Safety of machinery - General principles for design - Risk assessment and risk reduction.”
16 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 2 Safety Precautions and Elements
Figure 1 on page 15 shows how a first generation MobileView 2711T terminal
uses an Allen-Bradley control relay with the enabling switches. The control system must be designed for the safety level that results from the risk assessment of ISO 12100.
MobileView 2711T Terminal Operation
The MobileView 2711T terminal is a high-quality device that is equipped with state-of-the-art electronics.
ATTENTION: o avoid malfunctions or damage through improper handling, follow these instructions during operation.
• Do not operate the terminal if the cable is damaged or pinched. To avoid damaging the cable, do not place the cable over or around sharp objects.
• When the terminal is not in use, hang the terminal on the mounting bracket (ordered separately) or place inside a cabinet or enclosure.
• To avoid impact damage to the terminal, do not set the terminal on unstable surfaces and keep the cable clear of high traffic areas.
• If the terminal falls to the ground, verify that the emergency stop switch and enabling switch remain operable before you use the terminal on any machinery.
• To avoid damage to the operating elements, do not set the terminal on its operating side.
• Do not set the terminal near heat sources and avoid direct sunlight.
• Do not expose the terminal to strong magnetic fields or excessive vibrations, dust, or humidity.
• Use a soft, damp cloth with 50% water and 50% isopropyl alcohol to clean the operating panel and operating elements. Do not use solvents, scouring agents, or scrubbing sponges.
• Help prevent foreign objects or liquids from getting into the terminal. Check the protective covers of the device regularly. Verify that all screws are firmly tightened and that the housing and cable entrance are not damaged.
• Turn off the power supply before you remove the back cover of the MobileView 2711T terminal. When the back cover is removed, the terminal is sensitive to electrostatic discharge (ESD).
• If the terminal exhibits any anomaly, have the unit thoroughly and fully tested by the manufacturer or authorized repair dealer before you operate the terminal again.
• Do not use sharp objects, such as a screwdriver, on the touch screen. Scratching the surface of the touch screen can damage the display and compromise the IP rating.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 17
Chapter 2 Safety Precautions and Elements
MobileView Junction Box Operation
MobileView IP20 and IP65 junction boxes are high-quality devices that are equipped with state-of-the-art electronics.
ATTENTION: To avoid malfunctions or damage through improper handling, follow these instructions during operation.
• Do not operate a junction box if the cable is damaged or pinched. To avoid damaging the cable, do not place the cable over or around sharp objects.
• Do not mount a junction box near heat sources and avoid direct sunlight.
• Do not expose the a junction box to strong magnetic fields or excessive vibrations, dust, or humidity.
• Use a soft, damp cloth with water to clean IP65 junction boxes. Do not use solvents, scouring agents, or scrubbing sponges.
• Help prevent foreign objects or liquids from getting into a junction box. Check the protective covers of the device regularly. Verify that all screws are firmly tightened and that the housing and cable entrance are not damaged.
• Turn off the power supply before you remove an IP65 junction box from its cover plate. When the back plate is removed, the junction box is sensitive to ESD.
• If a junction box exhibits any anomaly, have the device thoroughly and fully tested by the manufacturer or authorized repair dealer before you operate the junction box again.
18 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Operate the Terminal
Chapter 3
Install a Connection Cable to a MobileView Terminal
This section provides details on the following topics:
Remove the Back Cover
Install the Connection Cable to the MobileView 2711T Terminal
Relocate the Connection Cable
IMPORTANT
20-pin connection cables work only with first generation MobileView™ 2711T terminals and IP20 junction boxes. Its cable connector (shown as S1 on page 23) is silver.
22-pin connection cables are meant for second generation MobileView 2711T terminals and IP65 junction boxes. Its cable connector (shown as S1 on page 24
The following installation instructions apply to either connection cable type.
) is black.
Remove the Back Cover
This section shows how to remove the back cover of the MobileView 2711T terminal. When the back cover is removed, you have access to the area that contains all connectors except the USB port.
SHOCK HAZARD: Disconnect all power to the MobileView 2711T terminal before you remove its back cover. When the back cover is removed, the MobileView 2711T terminal is sensitive to electrostatic discharge (ESD).
1. Place the MobileView 2711T terminal with the display side down on a stable, flat surface free of debris.
2. Use a Torx T10 screwdriver to remove the three screws that secure the back cover.
The ‘Image Applied’ label on the back cover was part of the manufacturing process. Therefore, you can remove and discard this label.
3. Carefully lift off the back cover and set it aside.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 19
Chapter 3 Operate the Terminal
Back Cover
Connection
Cable
Cable Connector S3 to PCB Connector ETH (Communication Interface)
SD Card™
(1)
Circuit Board Serial No. Label
Cable Channel
(1 of 2)
Cable Connec tor S2 Con nects to PCB Connector S1 (Power and Safety Connections)
Reset
Button
Cable channel that is used is only for example. Use channel that is best suited for your application.
Cable Channel
(2 of 2)
(1)
The 2711T-T10I1N1-TC MobileView terminal does not have this feature.
(2)
For first generation terminals, this connection is for a push button or key switch connection. For second generation terminals, this connection is for an illuminated push button.
Cable Connecto r S4 Connec ts to PCB Connector S2
(2)
Figure 2 shows the main circuit board of the MobileView 2711T terminal with
the back cover removed.
Figure 2 - Printed Circuit Board (PCB) with Back Cover Removed
IMPORTANT
Use the reset button when MobileView 2711T terminal functionality ‘locks up’ and you cannot restart from the terminal-desktop screen.
Install the Connection Cable to the MobileView 2711T Terminal
The connection cable can be attached on the right or left side of the MobileView 2711T terminal for right- or left-hand operation.
20 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
IMPORTANT
The MobileView 2711T terminal is shipped with the cable connection port open for right-hand operation. For more information, see
Figure 3.
Chapter 3 Operate the Terminal
Back Cover
Cable connection with open port (as factory shipped).
Cable connection
with hex plug
installed.
IMPORTANT
The MobileView 2711T terminal is shipped with the above cable­connection port open for right-hand operation.
When the cable is connected to this port, you can hold the terminal with your left arm, operate the enabling switch with your left hand, and operate the terminal touch screen with your right hand.
Strain Relief
Connector-cable Assembly
Gray Fitting
Use the following tools to install the connection cable.
19 mm open-end wrench or spanner
Torx T10 screwdriver
8 mm hex key
To install the cable, perform the following steps.
1. Decide on which cable-connection port of the terminal to install the cable; see Figure 3
Figure 3 - Cable Connections on MobileView 2711T Terminals
.
2. If you want left-hand operation, remove the plug with an 8 mm hex key.
Set the plug aside.
3. Remove the back cover as detailed on page
4. If present, unscrew and remove the gray fitting from
19.
the connector-cable
mounting assembly.
5. Unscrew the strain relief from the connector-cable mounting assembly to allow the red cable to slide freely.
6. Gently feed the three terminals at the end of the red cable into the chosen cable connection and up through the cable channel.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 21
Chapter 3 Operate the Terminal
IMPORTANT
Do not force the cable terminals through the channel. If you encounter resistance, slowly pull the cable towards you until it moves freely again.
If necessary, slide the connector-cable assembly farther down the cable to assist cable feed through the channel.
7. When the three terminals reach the main circuit board, carefully plug each terminal into its connection. See Figure 2 on page 20
for where each
terminal is connected.
IMPORTANT
Verify that there is a snap sound when you plug each terminal into its corresponding connection, which confirms that the terminal is properly connected.
8. After each terminal is securely connected, reinstall the back cover.
Use a Torx T10 screwdriver to reinstall the three cover screws.
9. Install the connector-cable mounting assembly into the cable connection of the MobileView 2711T terminal.
10. Reinstall the strain relief to the connector-cable mounting assembly.
11. Tighten the strain relief and the connector-cable mounting assembly with the 19 mm open-end wrench or spanner.
Torque the connector-cable mounting assembly to 1.2 N•m (10.6 lb•in.).
12. If you chose left-hand operation, reinstall the plug in the open cable­connection port with an 8 mm hex key.
Torque the plug to 1.2 N•m (10.6 lb•in.).
Relocate the Connection Cable
Use the following tools to relocate the connection cable.
19 mm open-end wrench or spanner
Torx T10 screwdriver
8 mm hex key
To relocate the cable, perform the following steps.
1. Remove the plug with the 8 mm hex key from the side where you are going to relocate the cable.
Set the plug aside.
See step 5 on page 21 to identify the components in steps 2 and 3.
2. Unscrew the strain relief from the connector-cable mounting assembly with the 19 mm open-end wrench or spanner.
3. Disconnect the connector-cable mounting assembly from the cable connection of the terminal with the 19 mm open-end wrench or spanner.
4. Remove the back cover as detailed on page 19
5. Disconnect the terminal connections at S2, S3, and S4. See Figure 2 on
page 20 for their locations.
6. Gently pull the cable while you guide the three disconnected terminals out through the cable channel and cable connection.
.
22 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 3 Operate the Terminal
2711T MobileView Te rm in al
PCB Connector
S1, Power and Safety Connection
ETH, Communication Interface
S2, Push Button or Key Switch Connection
(1) Shielded.
IMPORTANT
Do not force the disconnected terminals through the channel, or wires can be stripped from their connectors.
7. Follow step 6 through step 11 on page 21 to complete the cable relocation.
8. Reinstall the plug with the 8 mm hex key in the cable connection from which the cable was removed.
Torque the plug to 1.2 N•m (10.6 lb•in.).

The 20-pin MobileView Connection Cable

The 20-pin connection cable connects a first generation MobileView 2711T terminal to an IP20 junction box. The connection cable is 5, 10, or 15 meters (16.4, 32.8, or 49.2 feet) long. This cable withstands water, cleaning agents, motor oil, drilling oils, grease, lubricants, and condensates that contain hydrochloric acid.
ATTENTION: For the IP20 junction box terminals (X1…X4) listed in the following table, see Figure 4 on page 32.
Connection Cable IP20 Junction Box
Connector No.
S2
S3
S4
Connector Pin No.
11, 12 11 11 Not used
2
3
6
S1 Cable
Cable
Pin
Wire Color
No.
1 1 pink 1 24V DC X1, #1 22black 2GND_IN X1, #2 3 3 brown 3 E-stop, circuit 2 (+) X1, #5 4 4 white-green 4 E-stop, circuit 2 (-) X1, #6 5 5 gray 5 E-stop, circuit 1 (+) X1, #3 6 6 red-blue 6 E-stop, circuit 1 (-) X1, #4 7 7 green-brown 7 Enabling switch, circuit 1 (+) X1, #7 8 8 yellow 8 Enabling switch, circuit 1 (-) X1, #8
9 9 green 9
10 10 gray-pink 10 Enabling switch, circuit 2 (-) X1, #10
(1)
1
(1)
(1)
(1)
1 12 violet 12 External 1 X2, #1 2 17 white-pink 17 External 2 X2, #2 3 18 white 18 External 3 X2, #3 4 19 blue 19 External 4 X2, #4 5 20 white-blue 20 Not used
13 blue 13 TD+ (transmit) X3, #1
14 orange 14 TD- (transmit) X3, #2
15 white 15 RD+ (receive) X3, #3
16 red 16 RD- (receive) X3, #6
Junctio n Box Input (X4)
Signal Description
Enabling switch, circuit 2 (+)
Junction Box Output
X1, #9
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 23
Chapter 3 Operate the Terminal
50 mm ±2 (2 in. ±0.08)
10 mm ±2 (0.4 in. ±0.08)
60 mm ±3 (2.4 in. ±0.12)
40 mm ±3
(1.6 in. ±0.12)
5, 10, or 15 m
(16.4, 32.8, or 49.2 ft)
1
3
4
6
7
9
10
12
13
15
16
17
18
19
20 11
8
5
14
2
Connection Cable
S1 (cable connector)
S2
S3
S4
S2 Detail
11
9 7 5 3 1
12 10 8 6 4 2
50 mm ±2 (2 in. ±0.08)
10 mm ±2 (0.4 in. ±0.08)
60 mm ±3 (2.4 in. ±0.12)
5, 10, or 15 m
(16.4, 32.8, or 49.2 ft)
Connection Cable
S1 (cable connector)
S2
S2 Detail
S4
S3
40 mm ±3
(1.6 in. ±0.12)
1
11
9 7 5 3 1
12 10 8 6 4 2
3
4
6
7
9
10
12
13
15
16
17
18
19
20
21
22
11
8
5
14
2

The 22-pin MobileView Connection Cable

The 22-pin connection cable connects a second generation MobileView 2711T terminal to an IP65 junction box. The connection cable is 5, 10, or 15 meters (16.4, 32.8, or 49.2 feet) long. This cable withstands water, cleaning agents, motor oil, drilling oils, grease, lubricants, and condensates that contain hydrochloric acid.
MobileView Te rm in al
PCB Connector
S1, Power and Safety Connection
ETH, Communication Interface
S2, Illuminated Push Button
(1) Shielded.
Connection Cable
Connector No.
Connector Pin No.
S2
S3
S4
S1 Cable Pin No.
Cable Wire Color
Signal Description
1 10 pink 24V DC 2 9 black GND_IN 3 7 brown E-stop, circuit 2 (+) 4 22 white-green E-stop, circuit 2 (-) 5 6 gray E-stop, circuit 1 (+) 6 19 red-blue E-stop, circuit 1 (-)
7 18 green-brown
8 20 yellow
9 8 green
10 21 gray-pink
(1)
1
(1)
2
(1)
3
(1)
6
1 blue TD+ (transmit)
2 orange TD- (transmit)
3 white RD+ (receive)
4 red RD- (receive)
Enabling switch, circuit 1 (+)
Enabling switch, circuit 1 (– )
Enabling switch, circuit 2 (+)
Enabling switch, circuit 2 (–)
2 11 violet E-stop, illuminated (+) 4 12 white-pink E-stop, illuminated (–)
1 5 white Semi-wireless jumper 3 14 blue Semi-wireless jumper 5 13 white-blue Box ID
15 Li1 Bridge 16 Li1 Bridge 17 Not used
24 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
S1 Pins Detail
Adjust the Touch Screen
Chapter 3 Operate the Terminal
WA RN I NG : f the LCD screen darkens or if the backlight is not functioning
properly, the screen may be difficult to read and use of this screen could result in a potentially hazardous outcome. Do not use the LCD touch screen under these circumstances. The design of the system must take into account the possibility of the LCD screen or LCD touch screen losing functionality and unable to be used to maintain or change control of the system. The touch screen shall not be the single point of control of critical functions and is not intended to replace an E-stop.
Design of the system should follow all applicable code and good engineering practice. Factors to consider include:
• The possibility of an unreadable LCD screen
• The possibility of an inoperable touch screen
• Unexpected communication errors or delays
• Operator error in the control of the system
• Proper use of E-stops and other safety practices The user shall provide means to achieve a safe state during anomalies and to verify that the system has adequate redundancy for critical functions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Adjust the Display Brightness and GPU Energy Setting
To achieve 0…50 deg C operating temperature, the display brightness should be set to 50% and the GPU to Maximum Battery Life. All MobileView 2711T terminals have an adjustable display-brightness setting that can be adjusted through the Power Options icon on the terminal desktop. The display­brightness default setting is 70%.
IMPORTANT The MobileView 2711T is UL rated for 0…45 °C (32…113 °F) under full
load.
IMPORTANT
To maintain operating temperature, the power setting for the GPU should be set for Maximum Battery Life.
To adjust the GPU for maximum battery life:
1. From the desktop, select Power Options.
Increasing the brightness from the default setting reduces the life of the LED backlight, particularly at high temperatures.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 25
Chapter 3 Operate the Terminal
2. Select Embedded device power plan and Change plan settings.
3. Make settings for display as appropriate for your location but adjust the plan brightness slider to 50%.
26 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 3 Operate the Terminal
4. Select Change advanced power settings. The Power Options settings screen appears. Make sure Embedded device power plan [Active] is selected from the drop down list at the top of the screen.
5. Select Intel(R) Graphics Settings > Intel(R) Graphics Power Plan. Then select Maximum Battery Life from the drop down list next to settings.
6. Click OK.
Recalibrate the Touch Screen
The touch screen is calibrated before shipment. You can recalibrate the touch screen. For more information, see Touch Calibration
on page 68.
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 27
Chapter 3 Operate the Terminal
Shut Down the MobileView 2711T Terminal
To shut down the MobileView 2711T terminal, perform the following steps.
IMPORTANT
1. Close any open applications and return to the MobileView 2711T terminal desktop.
2. Tap on the desktop task bar to shut down the MobileView 2711T terminal.
3. Tap OK on the shutdown confirmation dialog box.
The terminal shuts down.
If you disabled EWF to make application changes, then you must enable EWF again before your shut down the MobileView 2711T terminal.
Review Enhanced Write Filter (EWF) down the MobileView 2711T terminal.
on page 53 before you shut
Install the Mounting Brackets
Disconnect Power from the MobileView 2711T Terminal
To disconnect power from the terminal, disconnect the tethered cable from the MobileView junction box.
IMPORTANT
There are two mounting brackets available for MobileView terminals. Both brackets are an accessory, which means each one must be ordered separately from the MobileView 2711T terminal.
The MobileView standard mounting bracket (Cat. No. 2711T-BRACKET) is used for stationary operation or storage of the terminal. The mounting bracket ships with a cutout template, publication 2711T-DS001
Do not disconnect the tethered cable from the junction box until you first shut down the MobileView 2711T terminal.
If you disconnect power from the terminal before you first shut it down, then you risk the following:
• You can corrupt the Windows operating system
• You lose application settings that were changed while the terminal was powered up
• You can corrupt any applications that were running, such as FTView ME
, for installation.
Use suitable flat-head screws (not shipped with product) to mount the bracket.
28 Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021
Chapter 3 Operate the Terminal
All dimensions are in mm (in.)
200 (7.9)
100 (3.9)
A
B
100 (3.9)
6 (0.24)
6 (0.24)
Detail A
Detail B
6 (0.24)
6 (0.24)
393 (15.5)
118 (4.6)
The MobileView VESA® mounting bracket (Cat. No. 2711T-VMBRACKET) connects to the back of the MobileView terminal, so the terminal can be mounted, stored, and locked into the bracket. This bracket is when locked storage is preferred.
The mounting bracket ships with a cutout template, publication 2711T-DS003 for installation.
The lock handle turns when lifted for easier movement of its locking pin. When you use the lock handle, verify that it locks flush against the bracket surface. If not, lift and turn the lock handle slightly until it locks fully.
Use suitable flat-head screws (not shipped with product) to mount the bracket.
,
Rockwell Automation Publication 2711T-UM001G-EN-P - March 2021 29
Loading...
+ 65 hidden pages