Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware
of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause
an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and
understanding of the product.
Identifies information about practices or circumstances that can lead
to personal injury or death, property damage, or economic loss.
Attentions help you identify a hazard, avoid a hazard, and recognize
the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or
motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or
motor, to alert people that surfaces may reach dangerous
temperatures.
Allen-Bradley, CompactLogix, DH+, FactoryTalk, FactoryTalk View Machine Edition, FactoryTalk View ME, FactoryTalk Site
Edition, FactoryTalk View Studio, PanelBuilder, PanelView, PanelView e, PanelView Plus, PLC 5, Rockwell Automation, RSLinx,
RSLinx, RSLinx Lite, RSView, SLC, SLC 500, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
We Can Get You From
Here...
Where to Start
PanelView 1400e Terminal
...To Here
SLC 500 Controller
PLC-5 Controller
PanelView Plus Terminal
SLC 500 Controller
3Publication 2711P-QS001A-EN-P - October 20073
L
C
P
o
l
l
e
5
-
r
o
C
n
r
t
Where to Start
Follow this path to migrate your PanelView 1000e or 1400e terminal
and application to the PanelView Plus terminal platform.
Chapter 1
Migration Considerations
Chapter 2
Select a Terminal
Replacement
Chapter 3
Migrate Your Application
Chapter 4
Review the Application
Conversion Log
Chapter 5
Review Object Mapping
Chapter 6
Review Unsupported
Features and Implement
Workarounds for Migration
Issues
Chapter 7
Qualify the Runtime
Application
Chapter 8
Create the Runtime
Application
Chapter 9
Measure and Improve
Application Runtime
Performance
Before updating the migrated application,
review the conversion log details and the
remaining chapters. If you determine that
the conversion operation would not be
feasible, you can use the conversion
services provided by Rockwell
Automation. For more information, see
the Conversion Services, publication
GMSC10-PP016
This document provides guidelines and procedures for migrating a
PanelView 1000e or 1400e terminal application to the PanelView Plus
terminal platform. The procedures and guidelines cover:
• selecting and optionally installing a PanelView Plus terminal
replacement.
• migrating your PanelView 1000e or 1400e application to
FactoryTalk View Machine Edition software.
• updating the migrated application and ladder logic, as
necessary, to verify compatibility with FactoryTalk View
Machine Edition software.
• reviewing and implementing workarounds for unsupported
features.
• verifying the correct operation of the migrated application on
the PanelView Plus terminal.
• measuring and improving performance of the migrated
application.
The procedures and guidelines are designed to make the migration
process as easy as possible.
The beginning of most chapters contains the following information.
Read these sections carefully before beginning work in each chapter.
• Before You Begin - This section lists the steps that must be
completed and decisions that must be made before starting the
chapter. The chapters in this quick start must be completed or
reviewed in the order in which they appear.
• What You Need - This section lists the items that are required to
complete the steps in the current chapter. This includes, but is
not limited, to hardware and software.
• Follow These Steps - This section illustrates the path or steps in
the current chapter.
Also note that the electronic version of this publication contains links
to other publications for easier navigation and reference.
9Publication 2711P-QS001A-EN-P - October 20079
Preface Preface
Audience
This quick start was created to assist a user familiar with Rockwell
Automation HMI products on how to convert an existing application
for the PanelView Plus terminal platform.
Required Software
The table provides the software required to convert a PanelView
1000e or 1400e application to a PanelView Plus application.
SoftwareVersion
FactoryTalk View Studio, which
includes:
• FactoryTalk View Machine Edition
• RSLinx Enterprise
PanelBuilder 1400e SoftwareVersion 5.16
Version 5.0
Migration Services
This migration serviceIncludesFor more information
Step Forward ProgramProvides a credit for returned product.
• PanelView 1400e to PanelView 1000e
• PanelView Enhanced to PanelView Plus
PV1000e Migration Kits PV1000e terminal and adapter plate at a
reduced price
Consult your local distributor for details
Consult your local distributor for details
PanelView Plus Starter KitsPanelView Plus terminal and associated
software at a reduced price to help you get
started with a new product family.
Bundled Migration Services• PanelView Enhanced to PanelView Plus
terminal hardware conversion
• PanelView Enhanced to PanelView Plus
application file conversion
• Turnkey service including any ladder
logic changes required
• Delivered onsite by Rockwell
Automation service engineers
• Project supervision and conversion
engineering services
• Standardized service bundle
• Fixed price proposal
10Publication 2711P-QS001A-EN-P - October 2007
Consult your local distributor for details
For more information on services, go to this
website:
http:\\rockwellautomation.com/services/on
site
Preface Preface
Conventions
This manual uses the following conventions.
ConventionMeaningExample
Courier
font
Check or uncheckClick to activate or deactivate a checkbox.Check the Disable Keying checkbox.
Click
Type or enter text exactly as shown.Type cmd.
Click the left mouse button once while the cursor is positioned
on object or selection.
Click Browse.
Double-click
Expand
Right-click
SelectClick to highlight a menu item or list choice.Select the SBCP ActiveX file.
>Shows nested menu selections as menu name followed by menu
Click the left mouse button twice in quick succession while the
cursor is positioned on object or selection.
Click the + to the left of a given item /folder to show its
contents.
Click the right mouse button once while the cursor is positioned
on object or selection.
Provides details on how to use the cutout adapter kit, catalog number
2711P-RAT12E, to mount a PanelView Plus or PanelView Plus CE 1250 touch
screen terminal into an existing PanelView 1400e touch screen panel cutout.
Provides details on how to use the cutout adapter kit, catalog number
2711P-RAK12E, to mount a PanelView Plus or PanelView Plus CE 1250 keypad
terminal into an existing PanelView 1400e keypad panel cutout.
Adapter Kit for PanelView Standard or PanelView e
Terminal Cutouts Installation Instructions, publication
2711P-IN010
PanelView Plus Terminals and Display Modules
Installation Instructions, publication 2711P-IN001
FactoryTalk View Studio online helpProvides information and procedures for creating and editing a FactoryTalk
Publication 2711P-QS001A-EN-P - October 200711
Provides details on how to use the:
• cutout adapter kit, cat. no. 2711P-RAK10, to mount a PanelView Plus or
PanelView Plus CE 1000 keypad terminal into an existing PanelView 1000e
keypad panel cutout.
• cutout adapter kit, cat. no. 2711P-RAT10, to mount a PanelView Plus or
PanelView Plus CE 1000 touch screen terminal into an existing PanelView
1000e touch screen, panel cutout.
Provides details on how to install the PanelView Plus 1250 or 1500 terminal in
a panel.
Provides catalog numbers for the PanelView Plus terminals.
View Machine Edition application and supported features.
Preface Preface
12Publication 2711P-QS001A-EN-P - October 2007
Migration Considerations
Chapter
1
Introduction
Migration Considerations
Migration ConsiderationExplanationFor More Information
Application reuse?Do you need to reuse your PanelView 1000e or 1400e
Use multiple RIO racks?Does your application require more than one rack of discrete
Require relay or beeper?Does your application use a built-in alarm relay or beeper? The
This chapter covers considerations to address before migrating a
PanelView 1000e or 1400e application to the PanelView Plus platform.
The table provides an explanation of things to consider when
migrating an application.
Reviewing Object Mapping,
application and PLC ladder logic? If so, you can convert your
application for a PanelView Plus terminal using FactoryTalk
View Machine Edition (ME) software. The application and PLC
ladder logic may require updates because some objects or
features may not directly migrate to FactoryTalk View ME
software.
If you do not want to reuse your current application but instead
create a new one with FactoryTalk View ME software, you can
stop here.
Remote I/O? The PanelView Plus terminals support multiple
racks of discrete Remote I/O, depending on the scanner type.
PanelView Plus terminals do not support a built-in alarm relay
or beeper. However, you can use an external alarm relay.
page 35
Reviewing and Modifying
Expressions, page 37
Reviewing Unsupported
Features, page 41
Reviewing Terminal
Comparisons, page 17
13Publication 2711P-QS001A-EN-P - October 200713
Chapter 1 Migration Considerations
Migration ConsiderationExplanationFor More Information
Required enhanced features?Does your application require enhanced features? If so, you
can take advantage of the advanced features offered by the
PanelView Plus terminals.
• Functions: trending, data logging, alarming,
information and local messages, expressions, security,
language switching, recipes, global objects,
multiversion support, face plates, graphic libraries,
parameter files, rich graphics, and animation.
• Communication: Ethernet, ControlNet, DeviceNet,
DHPlus, Remote I/O, and third party PLC connectivity.
• Hardware: Analog resistive touchscreen, x86
processor, up to 128 MB of application memory,
modular display, communication, and logic
components, USB support, high-bright display, and
stainless steel bezel options.
• Remote connectivity: FTP, Web server, VNC, remote
desktop. Applies only to PanelView Plus CE terminals.
• Other: Adobe PDF, PowerPoint, Word, Excel, and MPEG
viewers, Internet Explorer (full-featured), various
ActiveX controls. Applies only to PanelView Plus CE
terminals.
What are the terminal
replacement options?
The terminal replacement options for the PanelView 1000e
and 1400e terminals are the PanelView Plus 1250 or 1500
Selecting a Terminal
Replacement, page 16
terminals.
The rest of this document steps you through the process of selecting a
replacement terminal, migrating, and testing the application.
14Publication 2711P-QS001A-EN-P - October 2007
Select a Terminal Replacement
Chapter
2
Introduction
Before You Begin
What You Need
Follow These Steps
In this chapter, you will select and optionally install a PanelView Plus
terminal replacement for your PanelView 1000e or 1400e terminal.
Review the migration considerations table (chapter 1).
Nothing is required.
Follow these steps to select a PanelView Plus 1250 or 1500 terminal as
a replacement for your PanelView ‘e’ terminal.
Selecting a Terminal
Replacement
Page 16
Reviewing Terminal
Comparisons
Page 16
Installing a PanelView
Plus Terminal
Page 18
15Publication 2711P-QS001A-EN-P - October 200715
Chapter 2 Select a Terminal Replacement
Selecting a Terminal
Replacement options for the PanelView 1000e and 1400e terminals
include the PanelView Plus or PanelView Plus CE 1250 and 1500
Replacement
terminals. Some of the PanelView Plus terminals fit directly into the
existing panel cutout of the PanelView ‘e’ terminals; others will
require an adapter plate.
PanelView Plus Replacement Terminals
For this PanelView ‘e’ terminalSelect one of these replacement terminalsAdapter Plate
Required
PanelView 1000e touch screenPanelView Plus 1250 touch screen
PanelView Plus CE 1250 touch screen
(1)
PanelView 1000e keypad PanelView Plus 1250 keypad or keypad and touch
PanelView Plus CE 1250 keypad or keypad and touch
PanelView 1400e touch screenPanelView Plus 1250 touch screen
PanelView Plus CE 1250 touch screen
(1)
PanelView Plus 1500 touch screen
PanelView Plus CE 1500 touch screen
(1)
PanelView 1400e keypadPanelView Plus 1250 keypad or keypad and touch
PanelView Plus CE 1250 keypad or keypad and touch
PanelView Plus 1500 keypad or keypad and touch
PanelView Plus CE 1500 keypad or keypad and touch
(1)
The PanelView Plus CE terminal is required if your application requires the set bit cursor point function.
(2)
The PanelView Plus or PanelView Plus CE 1500 terminal will fit in the existing PanelView 1400e panel cutout. The adapter plate is required only to cover the stud
mounting holes.
No—
No—
(1)
Yes
(2)
Yes
Yes2711P-RAK12E
(1)
(2)
Yes
(1)
Adapter Plate
Cat. No.
2711P-RAT12E
2711P-RAT15
2711P-RAK15
16Publication 2711P-QS001A-EN-P - October 2007
Select a Terminal Replacement Chapter 2
Reviewing Terminal
Review dimensions and other pertinent information comparing the
PanelView 1000e and 1400e keypad and touch terminals with the
Comparisons
equivalent PanelView Plus or PanelView Plus CE 1250 or 1500
terminals.
The PanelView Plus 1250 and 1500 terminals are available as
preconfigured units or separate modular components. The catalog
numbers of the preconfigured units are specific to operator input,
display size, communication, power, and memory requirements.
For a list of valid catalog numbers for preconfigured units or modular
components of the PanelView Plus terminals, refer to this website:
http://www.ab.com/catalogs/
Touch Screen Terminal Comparisons
AttributePanelView 1000e
Cat. No. 2711e-T10C6
Depth, approx.157 mm (6.18 in.)404 mm (15.9 in.)
Panel cutout, H x W257 x 338 mm
10.11 x 13.29 in.
Alarm relay24V ac, 1 A
24V dc, 1 A
PanelView 1400e
Cat. No. 2711e-T14C6
326 x 391 mm
12.85 x 15.375 in.
250V ac, 18A
30V dc, 8 A
PanelView Plus 1250
Cat. No. 2711P-T12Cxxx
55 mm (2.18 in.)
257 x 338 mm
10.11 x 13.29 in.
Requires external relayRequires external relay
Optional add-on communication modules will increase the overall depth of the product.
Keypad Terminal Comparisons
AttributePanelView 1000e
Cat. No. 2711e-K10C6
Depth, approx.156 mm (6.15 in.)404 mm (15.9 in.)
Panel cutout, H x W257 x 390 mm
10.11 x 15.35 in.
Alarm relay24V ac, 1 A
24V dc, 1 A
Display10.4 in. VGA
TFT flat panel display
Operator inputKeypadKeypadKeypadKeypad
(1)
Optional add-on communication modules will increase the overall depth of the product.
14.0 in. VGA/SVGA
CRT
PanelView 1400e
Cat. No. 2711e-K14C6
326 x 429 mm
12.85 x 16.90 in.
250V ac, 8 A
30V dc, 8 A
14.0 in. VGA/SVGA
CRT
12.1 in. SVGA
TFT flat panel display
PanelView Plus 1250
Cat. No. 2711P-K15Cxxx
55 mm (2.18 in.)
257 x 390 mm
10.11 x 15.35 in.
Requires external relayRequires external relay
12.1 in. SVGA
TFT flat panel display
(1)
15.1 in. SVGA
TFT flat panel display
PanelView Plus 1500
Cat. No. 2711P-K15xxx
65 mm (2.55 in.)
305 x 419 mm
12.0 x 16.5 in.
15.1 in. SVGA
TFT flat panel display
(1)
Publication 2711P-QS001A-EN-P - October 200717
Chapter 2 Select a Terminal Replacement
Installing a PanelView Plus
Terminal
Install the selected PanelView Plus 1250 or 1500 terminal into the
existing PanelView 1000e or 1400e panel cutout. You may need an
adapter plate depending on your terminal selection.
To assist you with the installation, refer to:
• PanelView Plus Terminals and Display Modules Installation
Instructions, publication 2711P-IN001
• Appropriate adapter plate installation instructions, if required.
.
18Publication 2711P-QS001A-EN-P - October 2007
Migrate Your Application
Chapter
3
Introduction
Before You Begin
What You Need
In this chapter, you will import your existing PanelBuilder 1400e
application into FactoryTalk View Machine Edition (ME) software.
Different software is used by each PanelView terminal platform to
develop applications.
• PanelView 1000e and 1400e terminals run applications created
with PanelBuilder 1400e configuration software.
• PanelView Plus terminals run applications created with
FactoryTalk View ME software.
• Review the migration considerations table (Chapter 1).
• Select a PanelView Plus terminal replacement and adapter plate,
if required (Chapter 2).
• Optionally install the PanelView Plus terminal replacement
(Chapter 2). You can install the terminal after migrating and
testing your application.
• FactoryTalk View Studio software
• PanelBuilder 1400e .pvc application file. The application file can
reside on your local hard drive or a CompactFlash card.
19Publication 2711P-QS001A-EN-P - October 200719
Chapter 3 Migrate Your Application
Follow These Steps
Follow these steps to import your PanelBuilder 1400e application into
FactoryTalk View Machine Edition software.
Launch FactoryTalk View
Machine Edition
Software
page 21
Create a New
Application Name
page 21
Select the PanelBuilder
1400e Application to
Migrate
page 22
Configure the Import
Options
page 23
Review Project Status
Dialog
page 24
20Publication 2711P-QS001A-EN-P - October 2007
Migrate Your Application Chapter 3
Import Application
1. Launch FactoryTalk View
Studio software.
2. Click the New tab.
3. Enter an Application name
and click Import.
Follow the steps in this procedure to migrate any PanelView 1000e or
1400e application into FactoryTalk View Machine Edition software.
4. Read the FactoryTalk View
dialogue and click OK.
RSLinx for FactoryTalk does
not need to be installed
prior to importing your
PanelBuilder 1400e
application.
Publication 2711P-QS001A-EN-P - October 200721
Chapter 3 Migrate Your Application
5. Select PanelBuilder 1400e
Application (*.pvc) and click
Next.
6. Click the ... button.
7. Browse to and select your
PanelBuilder 1400e .pvc
application and click Open.
8. Click Next.
22Publication 2711P-QS001A-EN-P - October 2007
9. Configure the import
options based on your
replacement terminal.
Click Help at any time for
clarification of each dialog
option.
a. Check the Convert to
new window size
checkbox.
b. Select the size (in pixels)
of your PanelView Plus
terminal display as
shown in chart.
c. Check the Scale graphic
displays checkbox.
When selected, this
setting rescales all
displays.
d. If your original
PanelView e terminal
used a touch screen or
touch/keypad, check the
box under Touch
property conversion.
e. Click the Help button and
read the differences
between the caption
alignment options and
select an option for your
new application.
f. Click Finish.
Migrate Your Application Chapter 3
The Importing Progress
dialog shows the conversion
status. This process may
take a while, depending on
the size of your application.
When completed, you will
see the Project Status dialog
in the next step.
Publication 2711P-QS001A-EN-P - October 200723
Chapter 3 Migrate Your Application
10. Review the Project Status
dialog and click OK.
11. Repeat steps 1 through 10
for each PanelBuilder 1400e
application you want to
migrate to FactoryTalk View
ME software.
24Publication 2711P-QS001A-EN-P - October 2007
Chapter
Review the Application Conversion Log
4
Introduction
Before You Begin
What You Need
In this chapter, you will review the conversion log generated by
FactoryTalk View Machine Edition (ME) software. The results of this
log will help you to determine what updates are required in your
converted application.
• Review migration considerations (Chapter 1).
• Select a PanelView Plus terminal replacement and adapter plate,
if required (Chapter 2).
• Install the PanelView Plus terminal in the existing PanelView
1000e or 1400e panel cutout (Chapter 2).
• Import your PanelBuilder 1400e .pvc application into
FactoryTalk View ME software (Chapter 3).
• A PanelBuilder 1400e application migrated into FactoryTalk
View ME software. This was done in Chapter 3.
• The new name given the migrated application in FactoryTalk
View ME software. This was done in Chapter 3.
• Conversion log generated by the FactoryTalk View ME import
wizard.
25Publication 2711P-QS001A-EN-P - October 200725
Chapter 4 Review the Application Conversion Log
Follow These Steps
Follow this path to review changes that are required to your
FactoryTalk View ME application.
About the Conversion
Log
page 26
Open the Conversion
Log
page 27
Review the Conversion
Log
page 28
About the Conversion Log
The application conversion log is generated by the Import Wizard
when you import your PanelBuilder 1400e application into
FactoryTalk View ME software. This log provides detailed information
about objects or features that did not convert directly from your
PanelBuilder 1400e application. Use this log as a guide to update your
application accordingly. Modifications to the application are required
to verify that the application will operate correctly in FactoryTalk View
ME software.
IMPORTANT
It is important that you review each object and feature in the
converted application to verify that each will function as
expected. Because objects or features may not map directly
into FactoryTalk View ME software, you may need to update
your ladder logic to achieve the same operational results as
your PanelBuilder 1400e application.
26Publication 2711P-QS001A-EN-P - October 2007
Review the Application Conversion Log Chapter 4
Open the Conversion Log
1. Navigate to this folder
location.
2. Double-click the HMI
project folder that contains
the new application name
you created.
You entered this name in
the import wizard when
importing your PanelBuilder
1400e application into
FactoryTalk View ME
software.
The conversion log is stored with the new application that you
created when importing your PanelBuilder 1400e application into
FactoryTalk View ME software.
Follow these steps to locate the conversion log.
C:\Documents and Settings\All Users\Documents\RSView
Enterprise\ME\HMI projects\
TIP
All of your FactoryTalk View ME applications will be located in
this folder. This includes new or imported applications.
3. Double-click the convert.log
file generated by the import
wizard when you imported
your application.
Your convert.log file will
vary from the example
shown.
Publication 2711P-QS001A-EN-P - October 200727
Chapter 4 Review the Application Conversion Log
Review the Conversion Log
The conversion log contains a list of messages from warnings, errors,
and unsupported features or objects in the converted application. You
can compare these messages to those in the table below for
information on why the message was logged.
Most conversion log messages identify these attributes for a
FactoryTalk View ME object:
• Display name
• Position (x,y) of the object
• New graphic object name
You can use this information to locate the object and make required
modifications. The description for a message may reference a
workaround in this document.
IMPORTANT
Some features or objects are no longer supported in FactoryTalk
View ME software. However, new features or objects are
available providing the same or enhanced functionality.
Match the messages in the conversion log with the messages in the
table. The Display Name, Object Name, and Position Text references
in the messages are unique for each application.
Conversion Log Messages
MessageApplies to this
PanelBuilder 1400e object
Blinking wallpaper objects not
supported.
<Object Name> at <Position> on
<Display Name>.
Screen Select Keypad converted to a
default Display List Selector.
<Object Name> at <Position> on
<Display Name>.
Screen Keypad Enable converted to a
default Display List Selector.
<Object Name> at <Position> on
<Display Name>.
• Image
• Te xt
• Drawing
Screen Select KeypadA PanelBuilder 1400e display contained a Screen Select
Screen Select KeypadA PanelBuilder 1400e display contained a Screen Keypad
Description
A PanelBuilder 1400e object with blink set to true was
converted to wallpaper.
• At runtime, the PanelView ‘e’ object would blink.
• In FactoryTalk View ME software, the object will not blink
at runtime because wallpaper objects are disabled.
Keypad object.
FactoryTalk View ME software does not support a Screen
Select Keypad object so converts it to a default Display List
Selector, which needs to be configured.
Enable object.
FactoryTalk View ME software does not support a Screen
Keypad Enable object so converts it to a default Display List
Selector, which needs to be configured.
28Publication 2711P-QS001A-EN-P - October 2007
Conversion Log Messages
Review the Application Conversion Log Chapter 4
MessageApplies to this
PanelBuilder 1400e object
"Fixed Position" decimal point display
option not supported.
• Numeric Input Cursor Point
• Numeric Data Display
<Object Name> at <Position> on
<Display Name>.
"PLC Controlled" decimal point
display option not supported.
• Numeric Input Cursor Point
• Numeric Data Display
<Object Name> at <Position> on
<Display Name>.
"Fixed Position" decimal point input
option not supported.
<Object Name> at <Position> on
<Display Name>.
• Numeric Input Cursor Point
• Numeric Keypad Enable
• Numeric Keypad object
Description
The object has its Decimal Point Display option set to Fixed
Position.
FactoryTalk View ME software does not support an option to
display a decimal point in a numeric value. You can achieve the
same result using an expression.
For information on a workaround, refer to page 82.
The object has its Decimal Point Display option set to PLC
Controlled.
FactoryTalk View ME software does not support an option to
display a decimal point in a numeric value. You can achieve the
same result using an expression.
For information on a workaround, refer to page 81.
The object has its Decimal Point Input option set to Fixed
Position.
FactoryTalk View ME software does not support an option to
input a decimal point in a numeric value. You can achieve the
same result using an expression.
"PLC Controlled" decimal point input
option not supported.
<Object Name> at <Position> on
<Display Name>.
"Decimal Key Controlled" decimal
point input option not supported.
<Object Name> at <Position> on
<Display Name>.
Numeric Keypad converted to a
Numeric Input Enable.
<Object Name> at <Position> on
<Display Name>.
For information on a workaround, refer to page 82.
• Numeric Input Cursor Point
• Numeric Keypad Enable
• Numeric Keypad
The object has its Decimal Point Input option set to PLC
Controlled.
FactoryTalk View ME software does not support an option to
input a decimal point in a numeric value. You can achieve the
same result using an expression.
For information on a workaround, refer to page 81.
• Numeric Input Cursor Point
• Numeric Keypad Enable
• Numeric Keypad
The object has its Decimal Point Input option set to Decimal
Key Controlled.
FactoryTalk View ME software does not support an option to
input a decimal point in a numeric value. You can achieve the
same result using an expression.
For information on a workaround, refer to page 81.
Numeric KeypadThe display contains a Numeric Keypad object.
FactoryTalk View ME software does not support a Numeric
Keypad object so converts it to a Numeric Input Enable, which
needs to be configured.
Publication 2711P-QS001A-EN-P - October 200729
Chapter 4 Review the Application Conversion Log
Conversion Log Messages
MessageApplies to this
PanelBuilder 1400e object
Date labels not supported on Trend's
TrendA trend has one or more of its minimum, median or maximum
X-Axis.
<Object Name> at <Position> on
<Display Name>.
Blinking pens not supported by Trend.
TrendA trend had one or more of its pens configured to blink.
<Object Name> at <Position> on
<Display Name>.
Background screen plotting of pens
TrendA trend has one of its pens configured to use background
using expressions not supported by
Trend.
<Object Name> at <Position> on
<Display Name>.
Cursor List object at
Cursor ListA display contains a Cursor List object.
<PV ‘e’ Position> on <Display Name>
not supported.
Description
date labels enabled.
The FactoryTalk View ME trend displays the current date in its
title. It does not display the minimum, median or maximum
date as part of its X-axis.
The FactoryTalk View ME trend does not allow any of its pens
to blink.
screen plotting and has an expression assigned to the Pen
Value control.
The FactoryTalk View ME trend supports background screen
plotting by adding the tags assigned to the Pen1 to Pen8
controls to a Data Log Model.
You cannot add expressions to a Data Log Model.
FactoryTalk View ME software does not support a Cursor List
object so does not convert it. See page 68 for a workaround.
Multistate Indicator Object List at
<PV ‘e’ Position> on <Display Name >
not supported.
Local Message Object List at
<PV ‘e’ Position> on <Display Name >
not supported.
Numeric Data Display Object List at
<PV ’e’ Position> on <Display Name >
not supported.
Multi-Line Alarm Window blinking
not supported by [ALARM] display.
Multistate Indicator Object List A display contains a Multistate Indicator Object List.
FactoryTalk View ME software does not support a Multistate
Indicator Object List so does not convert it. See page 56 for a
workaround.
Local Message Object List.A display contained a Local Message Object List.
FactoryTalk View ME software does not support a Local
Message Object List so does not convert it. See page 60 for a
workaround.
Numeric Data Display Object
A display contains a Numeric Data Display Object List.
List
FactoryTalk View ME software does not support a Numeric
Data Display Object List so does not convert it. See page 64 for
a workaround.
Alarm ConfigurationThe Alarm Message Window is enabled with:
• Multi-line set.
• Blink enabled.
The multiline Alarm Window is converted to a FactoryTalk
View ME software [ALARM] display containing an Alarm List
object.
30Publication 2711P-QS001A-EN-P - October 2007
Loading...
+ 130 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.