Rockwell Automation MicroLogix 1200 Installation Instructions Manual

Installation Instructions
MicroLogix™
1200 Thermocouple/mV Input
Module
(Catalog Number 1762-IT4)
Inside…
Module Overview......................................................................................2
Module Installation...................................................................................3
System Assembly......................................................................................5
Mounting...................................................................................................6
Field Wiring Connections..........................................................................8
Cold-Junction Compensation (CJC)........................................................13
I/O Memory Mapping .............................................................................13
Specifications .........................................................................................16
Hazardous Location Considerations .......................................................21
Environnements dangereux ....................................................................22
For More Information..............................................................................23
Publication 1762-IN013A-EN-P - April 2002
2 MicroLogix™ 1200 Thermocouple/mV Input Module
Module Overview
The thermocouple/mV modules receives and stores digitally converted thermocouple and/or millivolt (mV) analog data from any combination of up to four thermocouple or millivolt analog sensors. Each input channel is individually configurable via software for a specific input device and provides open-circuit, over-range and under-range detection and indication. The module receives all of its +5V dc and +24V dc power from the 1762 expansion I/O bus. The module features a terminal block with a cold-junction compensation (CJC) sensor.
Accepted Inputs Range
Thermocouple Type J -210 to +1200°C (-346 to +2192°F) Thermocouple Type K -270 to +1370°C (-454 to +2498°F) Thermocouple Type T -270 to +400°C (-454 to +752°F) Thermocouple Type E -270 to +1000°C (-454 to +1832°F) Thermocouple Type R 0 to +1768°C (+32 to +3214°F) Thermocouple Type S 0 to +1768°C (+32 to +3214°F) Thermocouple Type B +300 to +1820°C (+572 to +3308°F) Thermocouple Type N -210 to +1300°C (-346 to +2372°F) Thermocouple Type C 0 to +2315°C (+32 to + 4199°F) millivolt inputs -50 to +50 mV
-100 to +100 mV
Publication 1762-IN013A-EN-P - April 2002
Description
1a
MicroLogix™ 1200 Thermocouple/mV Input Module 3
9
1a
7
6
1b
4
Item Description Item Description
1a upper panel mounting tab 5 bus connector cover
1b lower panel mounting tab 6 flat ribbon cable with bus connector (female)
2 power diagnostic LED 7 terminal block
3 module door with terminal identification
label
2
3
6
5
8
8 DIN rail latch
2
1b
4 bus connector with male pins 9 pull loop
Module Installation
1762 I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2 Over Voltage Category II
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
(2)
(IEC 60664-1).
(1)
) and to circuits not exceeding
(3)
Publication 1762-IN013A-EN-P - April 2002
4 MicroLogix™ 1200 Thermocouple/mV Input Module
Prevent Electrostatic Discharge
ATTENTION
!
Remove Power
ATTENTION
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
Remove power before removing or installing this module. When you remove or install a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
!
sending an erroneous signal to your system’s field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
causing permanent damage to the module’s circuitry
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
Publication 1762-IN013A-EN-P - April 2002
MicroLogix™ 1200 Thermocouple/mV Input Module 5
System Assembly
The expansion I/O module is attached to the controller or another I/O module by means of a ribbon cable after mounting as shown below.
TIP
WARNING
!
Use the pull loop on the connector to disconnect modules. Do not pull on the ribbon cable.
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must
be fully seated and the bus connector cover must be snapped in place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on page 7. If DIN rail mounting is used, an end stop must be installed ahead of the controller and after the last 1762 I/O module.
Publication 1762-IN013A-EN-P - April 2002
6 MicroLogix™ 1200 Thermocouple/mV Input Module
Mounting
ATTENTION
Do not remove protective debris strip until after the module and all other equipment near the module is mounted and wiring is complete. Once wiring is complete and the module is free of debris, carefully remove protective debris strip. Failure to remove strip before operating can cause overheating.
!
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown:
To p
Side Side
MicroLogix 1200
1762 I/O
Bottom
1762 I/O
1762 I/O
TIP
ATTENTION
!
1762 expansion I/O may be mounted horizontally only.
During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage when power is applied to the module.
Publication 1762-IN013A-EN-P - April 2002
MicroLogix™ 1200 Thermocouple/mV Input Module 7
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN rail mounting area of the module against the DIN rail. The latch will momentarily open and lock into place.
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35) for environments with vibration or shock concerns.
End Anchor
End Anchor
TIP
For environments with extreme vibration and shock concerns, use the panel mounting method described below, instead of DIN rail mounting.
Panel Mounting
Use the dimensional template shown below to mount the module. The preferred mounting method is to use two M4 or #8 panhead screws per module. M3.5 or #6 panhead screws may also be used, but a washer may be needed to ensure a good ground contact. Mounting screws are required on every module.
For more than 2 modules: (number of modules - 1) x 40.4 mm (1.59 in.)
40.4 (1.59)
Expansion I/O
MicroLogix 1200
Expansion I/O
MicroLogix 1200
NOTE:
Expansion I/O
Hole spacing tolerance:
MicroLogix 1200
±0.4 mm (0.016 in.).
100 (3.94)
14.5 (0.57)
90 (3.54)
MicroLogix 1200
40.4 (1.59)
Publication 1762-IN013A-EN-P - April 2002
8 MicroLogix™ 1200 Thermocouple/mV Input Module
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
System Wiring Guidelines
ATTENTION
The possibility exists that grounded or exposed thermocouples can become shorted to a potential greater than that of the thermocouple itself. Due to possible shock hazard, care should be taken when wiring these types of thermocouples.
!
Consider the following when wiring your system:
Do not tamper with or remove the CJC sensor on the terminal block.
Removal of the sensor will reduce accuracy and set the open circuit bit for the CJC sensor.
For thermocouple inputs, always use shielded, twisted-pair thermocouple
extension lead wires specified by the thermocouple manufacturer for the themocouple type you are using. Using an incorrect thermocouple extension wire type or not following correct polarity convention will cause invalid readings.
Keep cable shield connection to ground as short as possible.
To limit noise, keep thermocouple and millivolt signal wires as far away as
possible from power and load lines as well as other sources of electrical noise, such as motors, transformers, contactors, and AC devices.
If the field wiring must cross AC or power cables, ensure that they cross at
right angles.
Publication 1762-IN013A-EN-P - April 2002
MicroLogix™ 1200 Thermocouple/mV Input Module 9
For millivolt inputs, always use Belden™ 8761 (shielded, twisted-pair) or
equivalent wire to ensure proper operation and high immunity to electrical noise.
If multiple power supplies are used with millivolt analog inputs, the power
supply commons must be connected.
Ground the shield drain wire at one end only. The typical location is the
same point as the sensor ground reference.
– For grounded thermocouples or millivolt sensors, this is at the sensor
end.
– For insulated/ungrounded thermocouples, this is at the module end.
Contact your sensor manufacturer for additional details.
If it is necessary to connect the shield drain at the module end, connect it to
earth ground using a panel or DIN rail mounting screw.
Routing the field wiring in a grounded conduit can further reduce electrical
noise.
Terminal Block Layout
CJC CJC
IN2 +
IN2 -
IN3 +
IN3 -
IN 0 + IN 0 ­IN1 + IN1 -
Labeling the Terminals
A write-on label is provided with the module. Mark the identification of each terminal with permanent ink, and slide the label back into the door.
Publication 1762-IN013A-EN-P - April 2002
10 MicroLogix™ 1200 Thermocouple/mV Input Module
Wiring the Finger-Safe Terminal Block
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
!
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use the stripped
end of the wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.904 Nm (8 in-lbs).
3. After wiring is complete, remove the debris shield.
TIP
Publication 1762-IN013A-EN-P - April 2002
If you need to remove the finger-safe cover, insert a screw driver into one of the square wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.
MicroLogix™ 1200 Thermocouple/mV Input Module 11
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire Type Wire Size Terminal Screw Torque
Solid Cu-90°C (194°F) #14 to #22 AWG 0.904 Nm (8 in-lbs) Stranded Cu-90°C (194°F) #16 to #22 AWG 0.904 Nm (8 in-lbs)
Wiring Input Devices to the 1762-IT4
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments.
!
After the thermocouple module is properly installed, follow the wiring procedure below, using the shielded thermocouple extension cable recommended for the type of thermocouple you are using, or Belden 8761 for non-thermocouple applications.
Cut foil shield and drain wire
signal wire
signal wire
signal wire
drain wire
foil shield
cable
signal wire
To wire your sensor to the module, follow these steps:
1. At each end of the cable, strip some casing to expose the individual wires.
2. Trim the signal wires to 2-inch lengths. Strip about 3/16 inch (5 mm) of
insulation away to expose the end of the wire.
3. At one end of the cable, twist the drain wire and foil shield together, bend
them away from the cable, and apply shrink wrap. Then earth ground at the preferred location based on the type of sensor you are using.
4. At the other end of the cable, cut the drain wire and foil shield back to the
cable and apply shrink wrap.
Publication 1762-IN013A-EN-P - April 2002
12 MicroLogix™ 1200 Thermocouple/mV Input Module
5. Connect the signal wires to the module terminal block and input.
6. Repeat steps 1 through 5 for each channel on the module.
Terminal Block with CJC Sensor and Thermocouple Junctions
CJC sensor
+
-
ungrounded thermocouple
TIP
IMPORTANT
CJC+
CJC -
IN 2+
IN 2-
IN 3+
IN 3-
IN 0+ IN 0-
IN 1 + IN 1-
+
grounded thermocouple
-
within 10V dc
+
-
grounded thermocouple
When using an ungrounded thermocouple, the shield must be connected to ground at the module end.
When using grounded and/or exposed thermocouples that are touching electrically conductive material, the ground potential between any two channels cannot exceed ±10V dc, or temperature readings will be inaccurate and the module may be damaged.
Publication 1762-IN013A-EN-P - April 2002
MicroLogix™ 1200 Thermocouple/mV Input Module 13
Cold-Junction Compensation (CJC)
To obtain accurate readings from each of the channels, the temperature at the terminal junction between the thermocouple wire and the input channel must be compensated for. A cold-junction compensating thermistor has been integrated in the terminal block, as shown on page 12.
ATTENTION
!
Do not remove or loosen the cold-junction compensating thermistor assembly on the terminal block. The thermistor assembly is critical to ensure accurate thermocouple input readings at each channel. If the CJC sensor is removed, the open-circuit detection bit (OC4) and the general status bit (S4) are set. The module will continue to operate, but with reduced accuracy.
I/O Memory Mapping
A
ddressing
The addressing scheme for 1762 Expansion I/O is shown below.
(1)
Word
Bit
File Type = Input (I)
Data File 0 or 1
Slot Number
I1:x.0/0
Data File # 0 = Output Data File # 1 = Input
Slot Delimiter
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.
Word Delimiter
Bit Delimiter
Publication 1762-IN013A-EN-P - April 2002
14 MicroLogix™ 1200 Thermocouple/mV Input Module
Input Data File
For each module, slot x, words 0 through 3 contain the analog values of the inputs. The input data file is shown below.
Word/
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3
0
SGN
1
SGN
2
SGN
3
SGN
4 Reserved OC4 OC3 OC2 OC1 OC0 Reserved S4 S3 S2 S1 S0 5U0O0U1O1U2O2U3O3U4O4 Reserved
Analog Input Data Channel 0
Analog Input Data Channel 1
Analog Input Data Channel 2
Analog Input Data Channel 3
210
The bits are defined as follows:
Sx = General status bits for channels 0 through 3 (S0 through S3) and the
CJC sensor (S4). This bit is set (1) when an error (over-range, under-range, open-circuit, or input data not valid) exists for that channel. An input data not valid condition is determined by the user program. Refer to the MicroLogix™ 1200 I/O Thermocouple/mV Input Module User Manual, publication number 1762-UM002 for additional details.
OCx = Open-circuit indication for channels 0 through 3 (OC0 through OC3)
and the CJC sensor (OC4).
Ox = Over-range flag bits for channels 0 through 3 (O0 through O3) and the
CJC sensor (O4). These bits can be used in the control program for error detection.
Ux = Under-range flag bits for channels 0 through 3 (U0 through U3) and the
CJC sensor (U4). These bits can be used in the control program for error detection.
Configuration Data File
The configuration data file consists of 5 words. Words 0 through 3 of the configuration file allow you to change the parameters of each channel independently. For example, word 0 corresponds to channel 0. The functional arrangement of the bits for a single channel are shown in the table on page 15. Word 4 is the Module Configuration Word and is explained on page 16.
Publication 1762-IN013A-EN-P - April 2002
MicroLogix™ 1200 Thermocouple/mV Input Module 15
To Select
10 Hz 60 Hz 50 Hz 250Hz 500 Hz 1 kHz
Filter Frequency
Upscale 00 Downscale 01 Hold Last State 10 Zero 11
Open Circuit
Degrees C 0
Degrees F 1
Temperature
Units
Thermocouple J 0000 Thermocouple K 0001 Thermocouple T 0010 Thermocouple E 0011 Thermocouple R 0100 Thermocouple S 0101 Thermocouple B 0110
Input Type
Thermocouple N 0111 Thermocouple C 1000
-50 to +50 mV 1001
-100 to +100 mV 1010 Raw/Proportional 000 Engineering Units 001 Engineering UnitsX10 100 Scaled-for-PID 010
Data Format
Percent Range 011 Disable 0
1514131211109876543210
Make these bit settings
110 000 001 011 100 101
(1)
Not Used
Enable 1
Enable
Channel
(1) An attempt to write any non-valid (spare) bit configuration into any selection field results in a module configuration error.
TIP
Program defaults are indicated by zero (0) values. For example, type J thermocouple is the default (no user intervention) thermocouple type.
Publication 1762-IN013A-EN-P - April 2002
16 MicroLogix™ 1200 Thermocouple/mV Input Module
Module Configuration Word
Word 4 of the configuration data file contains the Enable/Disable Cyclic Calibration bit as shown in the table below.
To Select Make these bit settings
1514131211109876543210
Cyclic Calibration
(1) When enabled, an autocalibration cycle is performed on all enabled channels every 5 minutes.
Enabled Disabled
(1)
0 1
Specifications
General Specifications
Specification Value
Dimensions 90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width) height including mounting tabs is 4.33 in.
Approximate Shipping Weight (with carton)
Storage Temperature -40°C to +85°C (-40°F to +185°F) Operating Temperature 0°C to +55°C (-32°F to +131°F) Operating Humidity 5% to 95% non-condensing Operating Altitude 2000 meters (6561 feet) Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak Shock Operating: 30G Vendor I.D. Code 1 Product Type Code 10 Product Code 64 Agency Certification C-UL certified (under CSA C22.2 No. 142)
220g (0.53 lbs.)
UL 508 listed CE compliant for all applicable directives C-Tick marked for all applicable acts
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
Noise Immunity NEMA standard ICS 2-230 Radiated and Conducted Emissions EN50081-2 Class A
Publication 1762-IN013A-EN-P - April 2002
C-UL under CSA C22.2 No. 213)
MicroLogix™ 1200 Thermocouple/mV Input Module 17
Specification Value
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (EN61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect Radiated Immunity (EN61000-4-3) 10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz
keyed carrier Fast Transient Burst (EN61000-4-4) 2 kV, 5 kHz Surge Immunity (EN61000-4-5) 1 kV galvanic gun Conducted Immunity (EN61000-4-6)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.
10V, 0.15 to 80 MHz
(1)
Input Specifications
Specification 1762-IT4
Number of Inputs 4 input channels plus a CJC sensor Resolution 15 bits plus sign Bus Current Draw (max.) 40 mA at 5V dc
50 mA at 24V dc
Heat Dissipation 1.5 Total Watts (The Watts per point, plus the minimum Watts, with all
points energized.) Converter Type Delta Sigma Input Filtering Programmable notch filter with 10, 50, 60, 250, 500 and 1k Hz
frequencies. Channel Update Time Input filter and configuration dependent. See page 18.
Rated Working Voltage
(1)
Common Mode Voltage Range Common Mode Rejection 115 dB (minimum) at 50 Hz (with 10 Hz or 50 Hz filter)
Normal Mode Rejection Ratio 85 dB (minimum) at 50 Hz (with 10 Hz or 50 Hz filter)
Cable Impedance (max.) 25 Input Impedance >10M Open-circuit Detection Time (max.)
Calibration The module performs autocalibration upon power-up and whenever a
30V ac/30V dc
(2)
±10V dc maximum per channel
115 dB (minimum) at 60 Hz (with 10 Hz or 60 Hz filter)
85 dB (minimum) at 60 Hz (with 10 Hz or 60 Hz filter)
7 ms to 1.515 seconds
(3)
channel is enabled. You can also program the module to calibrate every
five minutes using the Enable/Disable Cyclic Calibration bit.
(1) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input
signal and the value that floats above ground potential (for example, 30V dc input signal and 20V dc potential above
ground). (2) For proper operation, both the plus and minus input terminals must be within ±10V dc of analog common. (3) Open-circuit detection time is equal to channel update time, which is based on filter frequency, number of channels
enabled, and whether cyclic calibration in enabled.
Publication 1762-IN013A-EN-P - April 2002
18 MicroLogix™ 1200 Thermocouple/mV Input Module
Input Specifications Continued
Specification 1762-IT4
Repeatability Maximum Overload at Input
Terminals Module Error over Full Temperature
Range (0 to +55°C [+32°F to +131°F])
CJC Accuracy ±1.3°C (±2.34°F) Power Supply Distance Rating 6 (The module may not be more than 6 modules away from the system
Input Group to Bus Isolation 720V dc for 1 minute (qualification)
Input Channel Configuration via configuration software screen or the user program (by writing a
Module OK LED On: module has power, has passed internal diagnostics, and is
Channel Diagnostics Over- or under-range and open-circuit by bit reporting
(1) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.
(2) Maximum current input is limited due to input impedance.
(1)
See “Repeatability” on page 20.
±35V dc continuous
See “Input Accuracy” on page 19.
power supply.)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
unique bit pattern into the module’s configuration file).
communicating over the bus. Off: Any of the above is not true.
(2)
Channel Update Time
Filter Frequency Selection Channel Update Time
10 Hz 303 ms 50 Hz 63 ms 60 Hz 53 ms 250 Hz 15 ms 500 Hz 9 ms 1 kHz 7 ms
Publication 1762-IN013A-EN-P - April 2002
Input Accuracy
MicroLogix™ 1200 Thermocouple/mV Input Module 19
Input Type
(1)
Accuracy for 10 Hz, 50 Hz and 60 Hz
(2)
Filters
(max.)
at 25°C [77°F]
Themocouples J (-210 to 1200°C [-346 to 2192°F]) ±0.6°C [± 1.1°F] Themocouple N (-200 to +1300°C [-328 to 2372°F]) ±1°C [± 1.8°F] Themocouple N (-210 to -200°C [-346 to -328°F]) ±1.2°C [±2.2°F] Themocouple T (-230 to +400°C [-382 to +752°F]) ±1°C [± 1.8°F] Themocouple T (-270 to -230°C [-454 to -382°F]) ±5.4°C [± 9.7°F] Themocouple K (-230 to +1370°C [-382 to +2498°F]) ±1°C [± 1.8°F] Themocouple K (-270 to -230°C [-454 to -382°F]) ±7.5°C [± 13.5°F] Themocouple E (-210 to +1000°C [-346 to +1832°F]) ±0.5°C [± 0.9°F] Themocouple E (-270 to -210°C [-454 to -346°F]) ±4.2°C [± 7.6°F] Themocouples S and R ±1.7°C [± 3.1°F] Thermocouple C ±1.8°C [±3.2°F] Thermocouple B ±3.0°C [±5.4°F] ±50 mV ±15 µV ±100 mV ±20 µV
(1) The module uses the National Institute of Standards and Technology (NIST) ITS-90 standard for thermocouple linearization. (2) Accuracy is dependent upont the analog/digital converter output rate selection, data format, and input noise. Refer to the
MicroLogix 1200 Thermocouple/mV Input Module User’s Manual
information.
, publication number 1762-UM002A, for additional
Publication 1762-IN013A-EN-P - April 2002
20 MicroLogix™ 1200 Thermocouple/mV Input Module
Repeatability
Input Type Repeatability for 10 Hz Filter at
25°C [77°F]
Themocouple J ±0.1°C [±0.18°F] Themocouple N (-110°C to +1300°C [-166°F to +2372°F]) ±0.1°C [±0.18°F] Themocouple N (-210 to -110°C [-346°F to -166°F]) ±0.25°C [±0.45°F] Themocouple T (-170°C to +400°C [-274°F to +752°F]) ±0 .1°C [±0.18°F] Themocouple T (-270°C to -170°C [-454°F to -274°F]) ±1.5°C [±2.7°F] Themocouple K (-270 to +1370°C [-454°F to +2498°F]) ±0.1°C [±0.18°F] Themocouple K (-270°C to -170°C [-454°F to -274°F]) ±2.0°C [±3.6°F] Themocouple E (-220 to +1000°C [-364°F to +1832°F]) ±0.1°C [±0.18°F] Themocouple E (-270 to -220°C [-454°F to -364°F]) ±1.0°C [±1.8°F] Themocouples S and R ±0.4°C [±0.72°F] Themocouple C ±0.2°C [±0.36°F] Themocouple B ±0.7°C [±1.26°F] ±50 mV ±6 µV ±100 mV ±6 µV
Publication 1762-IN013A-EN-P - April 2002
MicroLogix™ 1200 Thermocouple/mV Input Module 21
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING
!
EXPLOSION HAZARD
Substitution of components may impair suitability for
Class I, Division 2.
Do not replace components or disconnect equipment
unless power has been switched off.
Do not connect or disconnect components unless power
has been switched off.
This product must be installed in an enclosure.
In Class I, Division 2 applications, the bus connector must
be fully seated and the bus connector cover must be snapped in place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on page 7. If DIN rail mounting is used, an end stop must be installed ahead of the controller and after the last 1762 I/O module.
All wiring must comply with N.E.C. article 501-4(b).
Publication 1762-IN013A-EN-P - April 2002
22 MicroLogix™ 1200 Thermocouple/mV Input Module
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT
!
DANGER D’EXPLOSION
La substitution de composants peut rendre cet
équipement impropre à une utilisation en environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est coupée.
Ne pas connecter ou déconnecter des composants sans
s'être assuré que l'alimentation est coupée.
Ce produit doit être installé dans une armoire.
Pour les applications de Classe I, Division 2, le
connecteur de bus doit être correctement installé et son couvercle enclenché.
Pour les applications de Classe 1, Division 2, tous les
modules doivent être installés en contact direct les uns avec les autres, comme indiqué page 7. Si on utilise le montage sur rail DIN, une butée doit être placée à l'avant de l'automate et après la dernière unité d'E/S 1762.
Publication 1762-IN013A-EN-P - April 2002
MicroLogix™ 1200 Thermocouple/mV Input Module 23
For More Information
For Refer to this Document Pub. No.
Information on installing, wiring, and operating a MicroLogix 1200 Programmable Controller
Installation guide for the MicroLogix 1200 Programmable Controller
Installation guide for the MicroLogix 1200 Memory Module and Real Time Clock
Installation guide for the 1762-IA8 Discrete Input Module
Installation guide for the 1762-OW8 Discrete Output Module
Installation guide for the 1762-IQ8 Discrete Input Module
Installation guide for the 1762-IF2OF2 Analog Input/Output Module
More information on proper wiring and grounding techniques.
MicroLogix 1200 Programmable Controllers User Manual
MicroLogix 1200 Programmable Controllers Installation Instructions
MicroLogix 1200 Memory Module and/or Real Time Clock Installation Instructions
1762-IA8 120V ac Input Module Installation Instructions
1762-OW8 Relay Output Module Installation Instructions
1762-IQ8 DC Input Module Installation Instructions
1762-IF2OF2 Analog Input/Output Module Installation Instructions
Industrial Automation Wiring and Grounding Guidelines
1762-UM001
1762-IN006
1762-IN001
1762-IN002
1762-IN003
1762-IN004
1762-IN005
1770-4.1
If you would like a manual, you can:
download a free electronic version from the internet:
www.ab.com/micrologix or www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representative
visiting www.theautomationbookstore.com and placing your order
calling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
Publication 1762-IN013A-EN-P - April 2002
MicroLogix is a trademark of Rockwell Automation. Belden is a trademark of Belden, Inc.
Publication 1762-IN013A-EN-P - April 2002 PN 40071-145-01(1)
Copyright © 2 002 Rockwell Automation. All rights reserved . Printed in the U.S.A.
´H'+M!¶1b¨
Loading...