Solid state equipment has operational characteristics differing from those of electromechanical equipment. Saf ety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
Rockwell Automation sales office or online at http://literature.rockwellautomation.com
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability
for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local
) describes some important differences
WARNING
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, Kinetix, Ultra3000, LDL-Series Ironless Linear Servo Motors, RSLogix 5000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
This manual provides detailed installation instructions for mounting,
wiring, and maintaining your LDL-Series Ironless Linear Servo Motors.
Who Should Use This
This manual is intended for engineers or technicians directly involved
in the installation, wiring, and maintenance of LDL-Series ironless
Manual
linear motors.
If you do not have a basic understanding of linear motors, contact
your local Rockwell Automation sales representative for information
on available training courses before using this product.
Additional Resources
The following documents contain additional information conce rning
related Rockwell Automation products.
ResourceDescription
Kinetix 2000 Multi-axis Servo Drive User Manual, publication
2093-UM001
Kinetix 6000 Multi-axis Servo Drive User Manual, publication
2094-UM001
Ultra3000 Digital Servo Drives Installation Manual, publication
2098-IN003
How to install, setup, and troubleshoot a Kinetix 2000 drive
How to install, setup, and troubleshoot a Kinetix 6000 drive
How to install, setup, and troubleshoot an Ultra3000 drive
Ultra3000 Digital Servo Drives Integration Manual, publication
2098-IN005
Ultra3000 Digital Servo Drives User Manual, publication
2098-UM001
Motion Analyzer CD, download at http://ab.com/e-tools.Drive and motor sizing with application analysis software
Motion Modules in Logix5000 Control Systems User Manual,
publication
System Design for Control of Electrical Noise Reference Manual,
publication
Kinetix Motion Control Selection Guide, publication GMC-SG001Information about Kinetix products
Safety Guidelines for the Application, Installation, and
Maintenance of Solid State Controls, publication
Allen-Bradley Industrial Automation Glossary, publication AG-7.1 A glossary of industrial automation terms and abbreviations
Rockwell Automation Product Certification Website, publication
available at
National Electrical Code. Published by the National Fire
Protection Association of Boston, MA.
LOGIX-UM002
GMC-RM001
SGI-IN001
http://www.ab.com
Instruction on configuring Ultra3000 and Ultra500 drives, creating and
configuring project, source, and header files and creating and running
programs.
Information on configuring and troubleshooting your ControlLogix and
CompactLogix SERCOS interface modules, and using the home to
torque-level sequence
Information, examples, and techniques designed to minimize system
failures caused by electrical noise
Characteristics, application, installation, and maintenance of solid
state controls
For declarations of conformity (DoC) currently available from Rockwell
Automation
An article on wire sizes and types for grounding electrical equipment
You can view or download publications at
http://literature.rockwellautomation.com. To order paper copies of
technical documentation, contact your local Rockwell Automation
distributor or sales representative.
7Publication LDL-UM001A-EN-P - March 20097
Preface
Notes:
8Publication LDL-UM001A-EN-P - March 2009
Safety Considerations
Chapter
1
Introduction
Labels
TitleLocation LabelDetails
This chapter describes the safety issues encountered while using a
linear motor and the precautions you can take to minimize risk.
Potential hazards discussed here are identif ied by label s affixed to the
device.
TopicPage
Labels9
High Energy Magnets10
Vertical or Incline Installation12
Operational Guidelines13
Here you will find the safety and identification labels affixed to your
linear motor components. To prevent injury and damage to the linear
motor, review the safety label and its de tails and locati on before using
the linear motor.
Safety Label
Magnetic Field
Danger
9Publication LDL-UM001A-EN-P - March 20099
AThe Magnetic Fields label identifies non-ionizing radiation
DANGER
MAGNETIC FIELDS
LOCATED IN THIS AREA.
Can be harmfull to
pacemakers and other
sensitive equipment.
found in the magnet channels. Magnetic channels are
constructed with strong magnets. Strong magnets can
disrupt the functionality of automatic implantable
cardioverter defibrillators (AICD); people with a pacemaker
should not work near the magnet channels. Maintenance
personnel working near the magnet channels should avoid
the use of metallic tools and secure items such as badge clip
and other personal effects that could be attracted by the
strong magnets. Strong magnets can erase magnetic media.
Never let credit cards or electronic media contact or come
near the magnet channels.
Chapter 1 Safety Considerations
TitleLocation LabelDetails
Coil Name PlateBThis name plate shows the coil catalog number, serial
Identification Labels
www.ab.com
CAT. NO. LDL-XXXXXXX-XHTXX
SERIAL NO. XXXX-X-XXXX
CLASS B, 230 VAC, 0-167 Hz, 3Ø
E230241 MADE IN USA
number operating voltage and frequency.
Magnet Channel
Name Plate
RoHS CompliantDLDL-Series linear motor components are RoHS compliant.
CThis name plate shows the magnet channel catalog number,
CAT. NO. LDL-XXXXXXXXX
SERIAL NO. XXXX-X-XXXX
www.ab.com
RoHS COMPLIANT
Directive 2002/95/EC
MADE IN USA
serial number.
Label Locations for LDL-Series Linear Motor
The coil shown here is upside down
relative to the magnet channel so the
MAGNETIC FIELDS
LOCATED IN THIS AREA.
Can be harmfull to
pacemakers and other
sensitive equipment.
D
DANGER
A
labels are seen.
B
CAT. NO. LDL-C050200-DHT11
SERIAL NO. XXXXX-X-XXXX
m
o
.c
b
w.a
w
w
IANT
L
P
OM
Directive 2002/95/EC
oHS C
R
z, 3Ø
H
A
-167
US
, 0
C
IN
E
VA
D
30
A
, 2
B
S
M
S
41
LA
02
C
23
E
MADE IN USA
CAT. NO. LDL-NM075600
SERIAL NO. XXXX-X-XXXX
SERIES A
w.ab.com
w
w
C
High Energy Magnets
Linear motor magnet channels contain high energy magnets that
attract ferrous metals from a considerable distance. Precautions must
be taken while unpacking, handling, and shipping by air.
Unpacking and Handling
Unpack magnet channels one at a time. Repack magnet channels after
inspection and before it is stocked or staged for installation. Leave
10Publication LDL-UM001A-EN-P - March 2009
Safety Considerations Chapter 1
protective wrapping, cardboard and flux containment plates in place
until magnet channel is installed. Clear the inspection and repacking
area of any ferrous metals that will attracted to or attract the magnetic
assembly. If magnet channels must be unpacked at the same time
maintain a distance of 1.5 m (5 ft) between assemblies.
Air Freight Restrictions
When air freighting linear motor special preparations and precautions
must be taken. The following information outlines the basic
requirements at the publication d at e of th is document. However,
regulations are subject to change and additional area or carrier
restrictions may be imposed. Always check with your carrier or
logistics specialist regarding current local, regional, and national
transportation requirements when ship ping this product.
Linear motor magnet channels contain magnetized material, as
classified by International Air Transport Association (IATA) Dangerous
Goods Regulations. An IATA trained individual must be involved
when shipping this product via domestic or international air freight.
Packing Instruction 902 provides information regarding the
preparation of this product for air transportation. Follow these
regulations for general marking and labeling requirements, the
application of specific Magnetized Material Handling Labels, and
instructions for preparing the Shipper's Declaration for Dangerous
Goods.
As a minimum, refer to the following IATA Dangerous Goods
Regulations:
• Subsection 1.5: Training
• Subsection 3.9.2.2: Classification as Magnetized Material
• Subsection 4.2: Identification as UN 2807, Magnetized Material,
Class 9, Packing Instruction 902
• Subsection 7.1.5: Marking
• Subsection 7.2: Labeling
• Subsection 7.4.1: Magnetized Material Label
• Section 8: Shipper's Declaration for Dangerous Goods
When shipped via ground in the United States, these products are not
considered a U.S. D.O.T. Hazardous Material and standard shipping
procedures apply.
Publication LDL-UM001A-EN-P - March 200911
Chapter 1 Safety Considerations
Vertical or Incline
Installation
A linear motor driven system mounted vertically or on an incline will
not maintain position when the power is removed. Under the
influence of gravity the motion platform and its payload will fall to the
low end of travel. Design engineers should allow for this by designing
in controlled power down circuits or mechanical controls to prevent
the linear motor driven system and its payload from being damaged
when the power fails.
ATTENTION
Linear motors are capable of high accelerations, sudden and
fast motion. Rockwell Automation is not responsible for
misuse, or improper implementation of this equipment.
ATTENTION
Linear motor driven systems must have end of travel bumpers.
They must be designed to take a large impact from uncontrolled
motion. The payload must be secured to the system such that it
will not sheer off in the event of an impact in excess of the
bumper ratings.
ATTENTION
The Hall effect module contains an electrostatic discharge
(ESD) sensitive devise. You are required to follow static-control
precautions when you install, test, service, or repair this
assembly. If you do not follow ESD control precautions,
components can be damaged. If you are not familiar with static
control precautions, refer to Guarding Against Electrostatic
Damage, publication 8000-4.5.2
, or any other applicable ESD
awareness handbook.
BURN HAZARD
When the linear motors are running at their maximum rating the
temperature of attached heat sink can reach 100 ºC (212 ºF).
SHOCK HAZARD
An assembled linear motor will generate power if the coil or
magnet channel is moved. Un-terminated power cables present
an electrical shock hazard. Never handle flying leads or touch
power pins while moving the motor.
12Publication LDL-UM001A-EN-P - March 2009
Safety Considerations Chapter 1
Operational Guidelines
Please read and follow the guidelines shown here to safely operate
the linear motor created from the these linear motor component s .
ATTENTION
Observe maximum safe speed. Linear motors are capable of
very high forces, accelerations, and speeds. The maximum
obtainable acceleration and speed is based on the drive output
(bus voltage and current settings). The allowable maximum
speed is application specific and partly based on the linear
motion mechanics supplied by others.
ATTENTION
Moving parts can cause injury. Before operating the linear
motor, make sure all components are secure and magnet
mounting hardware is below magnet surface. Remove all
unused parts from the motor travel assembly to prevent them
from jamming in the motor air gap and damaging the coil or
flying off and causing bodily injury.
IMPORTANT
You are responsible for making sure the servo control system
safely controls the linear motor with regards to maximum safe
force, acceleration, and speed, including runaway conditions.
ATTENTION
ATTENTION
A runaway condition can be caused by incorrect motor, hall
effect, and position feedback wiring resulting in violent
uncontrolled motion.
Keep away from the line of motor travel at all times. Always
have bumpers in place and securely fastened before applying
power to your linear motor.
High Voltage can kill. Do not operate with exposed wires. Do
not go near electrically live parts.
Publication LDL-UM001A-EN-P - March 200913
Chapter 1 Safety Considerations
WARNING
Large Position Error Tolerances, such as those calculated
by the Auto Tune function in RSLogix 5000 programming
software, or when configuring a new axis with RSLogix
5000 software, can lead to undetected and repetitive
high energy impacts against axis end stops if proper
precautions are not in place. These tolerances can also
lead to undetected and repetitive high energy impacts
against unexpected obstructions. Such impacts can lead
to equipment damage and/or serious injury.
To identify the safety concerns that you have with
default Position Error Tolerance or after an Auto-Tune
Function go to the Rockwell Automation Knowlegebase
Click on Find Technical Support Answers and search for
Answer Id 55937.
.
14Publication LDL-UM001A-EN-P - March 2009
Start
Chapter
2
Introduction
Use this chapter to become familiar with the linear motor
components, their maintenance needs, and their configuration.
TopicPage
Catalog Number Explanation16
Linear Motor Components17
Design Consideration18
Maintenance19
Motor Storage19
15Publication LDL-UM001A-EN-P - March 200915
Chapter 2 Start
Catalog Number
Explanation
An ironless linear motor is comprised of a coil and a magnet channel.
The following keys show the catalog definition for the linear motors.
LDL - x xxx xxx - x x x x x
Cable Termination
0 = Flying leads
1 = Circular DIN-Type connector
Cable Length
0 = 300 mm (12.45 in.)
1 = 600 mm (23.62 in.)
2 = 1000 mm (39.37 in.)
Thermal Protection
T = PTC Thermal Sensor
Feedback
N = No Feedback
H = Hall Effect (Trapezoidal)
Winding Code
D = D winding
E = E winding
Coil Length
120 = 120 mm (4.72 in.)
240 = 240 mm (9.45 in.)
360 = 360 mm (14.17 in.)
480 = 480 mm (18.90 in.)
Frame Size
030
050
075
Coil Designation
N = Standard Coil
T = Thick Coil
Bulletin Number
LDL - xx xxx xxx
Magnet Channel Length
120 = 120 mm (4.72 in.)
480 = 480 mm (18.90 in.)
Frame Size
030
050
075
Coil Designation
NM = Standard Coil
TM = Thick Coil
Bulletin Number
16Publication LDL-UM001A-EN-P - March 2009
Start Chapter 2
Linear Motor Components
6
5
4
3
Use the diagrams and descriptions to identify the uniq ue compo nents
of the linear motor .
Components of Ironless Linear Motor Coil and Magnet Channel
1
LDL-N075120-xHT11
7
CAT. NO. LDL-NM075600
SERIAL NO. XXXX-X-XXXX
SERIES A
.com
w.ab
w
w
Motor Coil Shown
MADE IN USA
MAGNETIC FIELDS
LOCATED IN THIS AREA.
Can be harmfull to
pacemakers and other
sensitive equipment.
DANGER
LDL- NM075480
2
Magnet Channel Shown
Component
Number
ComponentDescription
1Ironless motor coilCopper coils contained in an epoxy form. When powered,
the coil interacts with the magnet channel.
2Magnet channelHigh powered static magnets create the flux field the
powered coil interacts with.
3Encoder connectorConnect your encoder here using connector kit, catalog
number LDC-ENC-CNCT.
4Feedback connectorConnect to your drive feedback using either catalog number
2090-CFBM4DF-CDAFxx (for moving coil) or
2090-XXNFMF-Sxx (for moving magnet).
5Power connectorConnect to your drive power using either catalog number
2090-CPWM4DF-xxAFxx (for moving coil) or
2090-XXNPMF-xxSxx (for moving magnet).
6Thermistor connectorConnects the PTC thermistor signal to the feedback
connector.
7Hall effect moduleThis module provides input signals for commutation
start-up. Replacement catalog numbers for the Hall effect
module are LDL-HALL-C for LDL-xxxxxxx-xHT11 and
LDL-HALL-F for LDL-xxxxxxx-xHT20.
Publication LDL-UM001A-EN-P - March 200917
Chapter 2 Start
Design Consideration
The information provided here is critical to using linear motor
components. Design your system to comply with the following points
to run safe and successfully.
Motor Air Gap
Maintaining the air gap is critical to proper installation and operation
of the linear motor components. Use the coil, and magnet drawings in
Appendix A
maintaining installation envelope dimension in your design the
vertical air gap requirement will be met. The following diagram show s
the critical dimensions.
to calculate the installation envelope dimension. By
Coil
Overall dimension
Magnet Channel
Bumpers, Shock Absorbers, or End Stops
Always include in your design a mechanical stop at the ends of travel.
Designed them such that they can prevent the moving mass from
leaving its travel limits. Take into consideration the maximum speed
and inertia of your moving mass when designing your mechanical
18Publication LDL-UM001A-EN-P - March 2009
Start Chapter 2
stops. The following diagram shows a minimal system with
mechanical stops.
Carriage/Heat Sink
Mechanical Stops
Mechanical Stops
Encoder strip
Encoder readhead
Linear Encoder
Your linear motor components needs to be integrated with a linear
encoder purchased from a third party.
Carriage/Heat Sink
The linear motor coil requires a heat sink to maintain performance.
The heat sink requires a minimal mass and surface area as shown on
page 62
designed into the base in moving magnet system.
. It can as so serve as the carriage in moving coil system or be
Maintenance
Motor Storage
Publication LDL-UM001A-EN-P - March 200919
Linear motors require no maintenance when operated in a relatively
clean environments. For operation in harsh and dirty environments,
minimal cleaning is recommended every 6 months.
Clean the metallic debris and other contaminants from the air gap. Use
a strip of masking tape to effectively remove the metal debris. Apply a
strip of tape in the magnet channel and then remove it.
Motor storage area should be clean, dry, vibration free, and have a
relatively constant temperature. If a motor is stored on equipment, it
should be protected from the weather. All motor surfaces subject to
corrosion should be protected by applying a corrosion resistant
coating.
Chapter 2 Start
Notes:
20Publication LDL-UM001A-EN-P - March 2009
Chapter
Installing the LDL-Series Linear Motor
3
Introduction
Unpacking and Inspection
The following section shows you how to safely unpack and install
your linear motor components.
Topic Page
Unpacking and Inspection21
Installing the Linear Motor Components22
Mount the Magnet Channel22
Mount the Motor Coil25
Inspect motor assemblies for damage that may have occurred in
shipment. Any damage or suspected damage should be immediately
documented. Claims for damage due to shipment are usually made
against the transportation company. Contact Rockwell Automation
immediately for further advise.
ATTENTION
Linear motors contain powerful permanent magnets which
require extreme caution during handling. When handing
multiple magnet channels do not allow the channels to come in
contact with each other. Do not disassemble the magnet
channels. The forces between channels are very powerful and
can cause bodily injury. Persons with pacemakers or Automatic
Implantable Cardioverter Defibrillator (AICD) should maintain a
minimum distance of 0.33 m (1 ft) from magnet assemblies.
Additionally, unless absolutely unavoidable, a minimum
distance of 1.5 m (5 ft) feet must be maintained between
magnet assemblies and other magnetic or ferrous composite
materials. Use only non-metallic instrumentation when
verifying assembly dimension prior to installation
• Compare the purchase order with the packing slip.
• Check the quantity of magnet channels received matches your
job requirements.
• Identify the options that came with your linear motor.
• Inspect the assemblies and confirm the presence of specified
options.
21Publication LDL-UM001A-EN-P - March 200921
Chapter 3 Installing the LDL-Series Linear Motor
Installing the Linear Motor
Components
Use the following procedures to install the magnet channel and the
motor coil.
Required Tools:
• Aluminum straight edge
• Non-magnetic M4 or M5 hex wrench
• Magnet channel alignment tool
IMPORTANT
TIP
The alignment tool is shipped attached to the cables next to the
Hall effect module. Remove before operating the linear motor.
Non-magnetic tools and hardware made of beryllium copper,
300 series stainless steel, and others should be used. If not
available, proceed carefully since magnetic and ferrous items
will be attracted to the magnet channel.
Mount the Magnet Channel
1. Select screw size and quantity.
The size of the Socket Head Cap Screw (SHCS) depends on
mounting configuration. The diagram shows three ways you can
mount your linear motor components. Mounting configuration B
de-rates the motor continuous force by 10%. See Appendix A
starting on page 66
Mounting
Configuration
AM616.0 (11.8)10.8 (8.0)
B and CM59.5 (7.0)6.36 (4.7)
for SHCS quantity.
Require
SHCS
SHCS Torque
Black Oxide Steel
N•m (lb•ft)
Stainless Steel
N•m (lb•ft)
22Publication LDL-UM001A-EN-P - March 2009
Installing the LDL-Series Linear Motor Chapter 3
2. Verify installation envelope dimensions.
See table on page 23.
Mounting Configuration AMounting Configuration BMounting Configuration C
J
Coil Cat. No.Dimension H
mm (in.)
LDL-x 030xxx-xxxxx80.0 (3.15)
LDL-x 050xxx-xxxxx100.0 (3.94)
LDL-x 075xxx-xxxxx130.0 (5.12)
W1
0.83 ±0.30 mm (0.003 ±0.011 in.)
Magnet Channel
Cat. No.
LDL-NM030xxx
LDL-NM050xxx
LDL-TM030xxx
LDL-TM050xxx
LDL-NM075xxx38.05 (1.50)
LDL-TM075xxx39.35 (1.55)
0.10 mm (0.003 in.)
Dimension W
mm (in.)
36.4 (1.43)
37.7 (1.48)
3. Install the first magnet channel.
Tighten but do not torque screws.
Publication LDL-UM001A-EN-P - March 200923
Chapter 3 Installing the LDL-Series Linear Motor
4
4. Install additional magnet channels.
Place a magnet channel on the mounting surface at a distance
from the previously installed magnet channel and slide it into
position.
2
3
5. Align the magnet channels with an aluminum straight edge and
the alignment tool and tighten the screws.
a. Place the alignment tool in the alignment hole at the butting
end of the first two magnet channels.
b. Align the edges of the magnet channel with the aluminum
straight edge and tighten the screws.
c. Repeat alignment between the fixed magnet channel and the
next magnet channels needing alignment until all the magnet
channels are tightened.
Alignment tool
Aluminum straight edge
6. Torque all the screws to values listed in the table on page 22
.
7. Remove the alignment tool.
24Publication LDL-UM001A-EN-P - March 2009
Installing the LDL-Series Linear Motor Chapter 3
Mount the Motor Coil
Use M4 x 0.7 screws with a length that extends through the carriage
mounting surface by minimum of 5 mm (0.197 in.), but not more than
7 mm (0.276 in.).
Follow these steps to mount the motor coil.
1. Clean and remove burrs from the coil mounting surface.
2. Attach the motor coil to the carriage using M4 x 0.7 screw
Lightly tighten the screws.
.
3. Slide the assembly on to the bearings.
Publication LDL-UM001A-EN-P - March 200925
Chapter 3 Installing the LDL-Series Linear Motor
Shim
4. Verify the gap between the motor and the magnet channel is
0.83
±0.30 mm (0.033 ±0.011 in.).
Use plastic shim stock and adjust as necessary.
5. Torque the M4 SCHS to 4.6 N•m (3.4 lb•ft) for black oxide steel
screw or 3.10 N•m (2.3 lb•ft) for stainless steel screws.
6. Install the bearing fasterners.
7. Secure the assembly using all the mounting holes.
26Publication LDL-UM001A-EN-P - March 2009
Chapter
A
CB
D
E
H
L
F
G
4
LDL-Series Linear Motor Connector Data
Introduction
Linear Motor Coil
Connectors
This chapter provides power, thermistor, and Hall effect cable
connector information for the linear motor coil and Hall effect
module.
TopicPage
Linear Motor Coil Connectors27
Hall Effect Module Connectors28
There are two connectors on the linear motor coil, catalog number
LDL-xxxxxxxx-xxT11, the power and the Positive Temperature
Coefficient (PTC) thermistor.
Power Connector
The following tables identify the power signals for DIN style circular
connector.
1 A Quad B TTL (1 V p-p), + A DifferentialAM+ (SIN+)
2 A Quad B TTL (1 V p-p), - A DifferentialAM- (SIN-)
3 A Quad B TTL (1 V p-p), + B DifferentialBM+ (COS+)
4 A Quad B TTL (1 V p-p), - B DifferentialBM- (COS+)
5 TTL + Index Mark Differential IM+
1Positive Temperature Coefficient (PTC)
TS+
thermistor +
3Positive Temperature Coefficient (PTC)
thermistor -
4–Reserved
TS-
Mates with PTC thermistor
connector on Hall effect module.
The following tables show the pinouts the Hall effect module.
Feedback Connector
6 TTL - Index Mark DifferentialIM7 Reserved–
8
9 Encoder and Hall Sensor Power +5V DC
10 Common Common
11 Reserved–
12 Common Common
14 PTC Thermistor PTC Temp15 TTL - Trapezoidal Hall Commutation S1
16 TTL - Trapezoidal Hall Commutation S2
17 TTL - Trapezoidal Hall Commutation S3
Case Shield –
28Publication LDL-UM001A-EN-P - March 2009
PTC Thermistor Connector
4
31
4
1
3
6
9
7
LDL-Series Linear Motor Connector Data Chapter 4
PinDescriptionSignal
1Positive Temperature Coefficient (PTC)
TS+
thermistor +
4Reserved–
3Positive Temperature Coefficient (PTC)
TS-
thermistor -
Encoder Connector
PinDescriptionSignal
1A Quad B TTL, + A Differential AM+
2A Quad B TTL, + B Differential BM+
3TTL + Index Mark Differential IM+
4A Quad B TTL, - A DifferentialAM5A Quad B TTL, - B DifferentialBM6TTL - Index Mark Differential IM75V DC ReturnCommon
8Encoder and Hall Sensor
Power
+5V DC
Mates with PTC thermistor
connector on linear motor coil.
Mating connector available a
part of encoder connector kit
catalog number LDC-ENC-CNCT.
Publication LDL-UM001A-EN-P - March 200929
9Shield Drain–
Chapter 4 LDL-Series Linear Motor Connector Data
Notes:
30Publication LDL-UM001A-EN-P - March 2009
Chapter
Wiring the LDL-Series Linear Motor
5
Introduction
Connect the Linear Motor
Coil
This section shows you how to wire your LDL-Series linear motor.
TopicPage
Connect the Linear Motor Coil31
Signal and Wire Definitions for Flying Lead Components33
Making Your Own Extension Cables34
Mounting and Wiring Two Identical Coils in Tandem35
Use the following procedure to connect your linear motor, catalog
number LDL-xxxxxxx-xHT11.
1. Using the Encoder Connector Kit, catalog number
LDC-ENC-CNCT, and the connector data on page 29
encoder to the connector.
ATTENTION
Be sure that cables are installed and restrained to prevent
uneven tension or flexing at the cable connectors. Use Bulk
Head Connector Kit, catalog number LDC-BULK-HD, for
mounting these connectors.
, wire your
Excessive and uneven lateral force at the cable connectors may
result in the connector’s environmental seal opening and
closing as the cable flexes.
Failure to observe these safety precautions could result in
damage to the motor and its components.
2. Connect your encoder to the encoder connector on the Hall
effect module.
3. Attach the feedback and the power cables.
ATTENTION
d. Align flats on each connector.
31Publication LDL-UM001A-EN-P - March 200931
Do not connect or disconnect the motor feedback cable or the
power cable while power. It may result in unexpected motion or
cause damage to the components.
Chapter 5 Wiring the LDL-Series Linear Motor
e. Do not apply excessive force when mating the cab le and
motor connectors. If the connectors do not go together with
light hand force, realign and try again.
Feedback
Power
Connector
Power Extension Cable
2090-CPWM4DF-xxAFxx or 2090-XXNPMF-xxSxx
Feedback Extension Cable
2090-CFBM4DF-CDAFxx or 2090-XXNFMF-Sxx
ATTENTION
Be sure that cables are installed and restrained to prevent
Connector
uneven tension or flexing at the cable connectors. Excessive
and uneven lateral force at the cable connectors may result in
the connector’s environmental seal opening and closing as the
cable flexes. Failure to observe these safety precautions could
result in damage to the motor or encoder.
Encoder
Connector
Connect your encoder using
Encoder Connector Kit, catalog
number LDC-ENC-CNCT.
To User Supplied Encoder
To Drive
f. Hand tighten the knurled collar with five to six turns to fully
seat the connector.
ATTENTION
Keyed connectors must be properly aligned and hand-tightened
the recommended number of turns.
Improper alignment is indicated by the need for excessive force,
such as the use of tools, to fully seat connectors.
Connectors must be fully tightened for connector seals to be
effective.
Failure to observe these safety precautions could result in
damage to the motor, cables, and connector components.
32Publication LDL-UM001A-EN-P - March 2009
Wiring the LDL-Series Linear Motor Chapter 5
Signal and Wire Definitions
For linear motors, catalog numbers LDL-xxxxxxx-xHT20, wire using
wiring diagram on page 70
for Flying Lead Components
here, for wire gauge information see page 65
Linear Motor Coil
The following shows the wire color and signals for the linear motor
coil power and PTC thermistor cables, catalog
number LDL-xxxxxxx-xxT20.
Power Signals
. Wire colors and signal types are shown
.
Color SignalComments
RedMotor Phase U (A)• Observe maximum applied voltage
WhiteMotor Phase V (B)
BlackMotor Phase W (C)
GreenMotor Ground• Terminate per drive manual instructions.
Shield Cable Shield
specification.
• Consult drive manual or supplier for specific
wiring instructions to the drive. Wiring is
phase/commutation sensitive.
• Shield is not connected to the motor frame.
ATTENTION
Disconnect input power supply before installing or servicing
motor.
Motor lead connections can short and cause damage or injury if
not well secured and insulated.
Insulate the connections, equal to or better than the insulation
on the supply conductors.
Properly ground the motor per selected drive manual.
PTC Thermistor Signals
ColorDescription Signal
BlackPositive Temperature Coefficient (PTC)
thermistor +
BlackPositive Temperature Coefficient (PTC)
thermistor -
TS+
TS-
Publication LDL-UM001A-EN-P - March 200933
Chapter 5 Wiring the LDL-Series Linear Motor
Hall Effect Module
This table shows the signal and wire colors for Hall effect module
with flying leads, catalog number LDL-HALL-F.
Color Signal Signal Spec
Red+V5…24V DC Hall supply, 20 mA.
BlackVRTNHall effect signal common.
Making Your Own
Extension Cables
WhiteS1
BlueS2
OrangeS3
Silver braidCable shieldTerminate at drive end per drive
–
manual instructions.
Flying lead coil and Hall effect modules require circular DIN style
connectors to interface with Allen-Bradley extension cables. The
following connectors kits are available for terminating flying lead coils
and Hall effect modules.
The cable length from the coil to drive should be limited to 10 m
(32.8 ft). If longer cables are necessary a 1321-3Rx-x series line reactor
is required. Refer to 1321 Power Conditioning Products Technical
Data, publication 1321-TD001
, to choose a line reactor for
applications requiring cable longer than 10 m (32.8 f t).
34Publication LDL-UM001A-EN-P - March 2009
Wiring the LDL-Series Linear Motor Chapter 5
Mounting and Wiring Two
Identical Coils in Tandem
This type of installation requires custom motor database file which is
available upon request. Contact Application Engineering at
631.344.6600 to request this file.
The following tables and diagrams show the wiring and spacing for
(1)
two identical coils mechanically top mounted
to the same plate and
driven by one amplifier. There are three configurations shown here
for mounting motors in tandem: power and encoder cables exiting on
the right, the center, and on opposite ends.
ATTENTION
Coils must have identical part numbers. Using mis-matched
coils will cause a hazardous condition resulting in damage to
the equipment and a possible fire.
Cables Exit to the Right
If mounting coils in tandem, such that the power cables exit both of
the coils on right side as shown, use the following table to find
mounting distance and phase wiring.
L1
Coil #2
Phase Wiring for Right Exit Power Cables
L1
mm (in.)
80 (3.15)RedWhiteU
120 (4.72)RedBlackU
Coil # 1
(1)
Master
WhiteBlackV
BlackRedW
WhiteRedV
BlackWhiteW
Coil # 2
(2)
Slave
Coil #1 is the master
Coil #1
Hall Effect
Amplifier
Phase
(1) Contact Application Engineering (631.344.6600) for side mounting of the coils.
Publication LDL-UM001A-EN-P - March 200935
Chapter 5 Wiring the LDL-Series Linear Motor
Phase Wiring for Right Exit Power Cables
L1
mm (in.)
Coil # 1
Master
(1)
Slave
(2)
Coil # 2
Amplifier
Phase
160 (6.30)RedRedU
WhiteWhiteV
BlackBlackW
(1) Master has Hall effect module.
(2) Slave has no Hall effect module.
Cables Exit in the Center
If mounting coils in tandem, such that the power cables exit in the
center, as shown, use the following table to find mounting distance
and phase wiring.
Coil #1 is the master
Coil #1
L1
Coil #2
Hall Effect
Phase Wiring for Center Exit Power Cables
L1
mm (in.)
90 (3.54)
or
150 (5.91)
Coil # 1
Master
(1)
Coil # 2
Slave
(2)
RedWhiteU
WhiteRedV
BlackBlackW
(1) Master has Hall effect module.
(2) Slave has no Hall effect module.
Amplifier
Phase
36Publication LDL-UM001A-EN-P - March 2009
Wiring the LDL-Series Linear Motor Chapter 5
Cables Exit on Opposite Ends
If mounting coils in tandem, such that the power cables exit opposite
to each other, as shown, use the following table to find mounting
distance and phase wiring.
Coil #1 is the master
Coil #2
Phase Wiring for Opposite End Exit Power Cables
L1
mm (in.)
90 (3.54)
or
150 (5.91)
Coil # 1
Master
(1)
Coil # 2
Slave
(2)
RedRedU
WhiteBlackV
BlackWhiteW
(1) Master has Hall effect module.
(2) Slave has no Hall effect module.
Coil #1
Hall Effect
Amplifier
Phase
Publication LDL-UM001A-EN-P - March 200937
Chapter 5 Wiring the LDL-Series Linear Motor
Notes:
38Publication LDL-UM001A-EN-P - March 2009
Chapter
6
Configure and Start Up the LDL-Series Linear
Motor
Introduction
Before You Begin
This section covers the setup and connection verification of a linear
motor with either Kinetix 6000, Kinetix 2000, or an Ultra3000 drive.
TopicPages
Before You Begin39
What You Need40
Required Files40
Follow These Steps41
Update Linear Motor Database41
Set Up the Connection to Kinetix 6000 or Kinetix 2000 Drive42
Set Up the Connection to an Ultra3000 Drive47
Verify Motor Encoder Direction49
Verify Motor Encoder Resolution50
Verify Linear Motor Wiring and Function50
This chapter assumes you have wired your linear motor and
Allen-Bradley drive as shown on wiring diagrams in Appendix
starting on page 67
.
B
IMPORTANT
It is important that the motor be wired correctly to get positive
motion when commutated.
Please read and understand Motor Direction Defined
.
Motor Direction Defined
Positive motion is dependent on encoder o rient ation, encoder wiring,
and coil or magnet channel motion.
Most linear encoders are installed with the encoder cable facing the
same direction as the coil cable.
39Publication LDL-UM001A-EN-P - March 200939
Chapter 6 Configure and Start Up the LDL-Series Linear Motor
Wire the linear encoder such that the position feedback is positive
(phase A+ leads phase B+) when the motor is moving in the positive
direction.
When the motor power and Hall sensor wiring is connected as sh own
in wiring diagrams in Appendix
defined as the motor coil moving toward its power cable. This
diagram shows positive motion for both a moving coil and a moving
magnet channel.
Motor Direction
B, the positive direction of motion is
Coil Motion
What You Need
Required Files
Stationary Magnet
Stationary Coil
Magnet Motion
You need a computer with RSLogix 5000 software installed and
internet access.
Firmware revisions and software versions required to support the
linear motors include the following:
• RSLogix 5000 software, version 16.00 or later
• Kinetix 2000 or Kinetix 6000 multi-axis drives
– Firmware revision 1.96 or later
– For RSLogix 5000 software, version 16.xx
use Motion Database file, version 4_17_0 or later
40Publication LDL-UM001A-EN-P - March 2009
Configure and Start Up the LDL-Series Linear Motor Chapter 6
– For RSLogix 5000 software, version 17.xx or later
use Motion Database file, version 5_8_0 or later
• Ultra3000 drives
– Firmware revision 1.52 or later
– Motor Database, motor_03_18_09.mdb or later
• Motion Analyzer software, version 4.7 or later
Follow These Steps
Download these files from http://support.rockwellautomation.com
.
Contact Rockwell Automation Technical Support at 440.646.5800 for
assistance.
The following flow chart illustrates the required steps.
Update Linear
Motor Database
Kinetix 6000 Drive or
Kinetix 2000 Drive
Set-up Connection to
Kinetix 6000 or
Kinetix 2000 Drive
Drive Model?
Verify Motor
Encoder Direction
Ultra3000 Drive
Set up the
Connection to an
Ultra3000 Drive
Verify Motor
Encoder Resolution
Verify Linear
Motor Wiring
and Function
Update Linear Motor
Install the current Motion Database, as required, before
commissioning your linear motor. See the Required Files
on page 40.
Database
Publication LDL-UM001A-EN-P - March 200941
Chapter 6 Configure and Start Up the LDL-Series Linear Motor
Set Up the Connection to
Kinetix 6000 or Kinetix 2000
Drive
This procedure configures the Kinetix 6000 or Kinetix 2000 drive for
your linear motor and encoder combination.
For help using RSLogix 5000 software as it applies to setting up your
linear motor, refer to Additional Resources
on page 7. This procedure
assumes you are familiar with RSLogix 5000 software.
1. Click the Driver/Motor tab.
2. Click Change Catalog and select the appropriateMotor
(1) Requires custom database file contact Application Engineering at 631.444.6600.
20 µm pitch Sin/Cos encoder
13. Click OK.
(1)
46Publication LDL-UM001A-EN-P - March 2009
Configure and Start Up the LDL-Series Linear Motor Chapter 6
Set Up the Connection to an
This procedure configures the Ultra3000 drive for your linear motor
and encoder combination.
Ultra3000 Drive
For help using Ultraware software as it applies to setting up your
linear motor, refer to Additional Resource s
assumes you are familiar with Ultraware software.
on page 7. This procedure
1. Open your Motor Configurator Utility.
2. Select the linear motor catalog number.
3. From the Edit menu choose Duplicate.
4. Rename Model.
5. Click Encoder Type and select either Incremental or Sin/Cos .
6. Click Lines Per Meter and the enter value.
The following tables list typical values for lines per meter.
Configure and Start Up the LDL-Series Linear Motor Chapter 6
Verify Motor Encoder
Direction
In this section you select controller tag, and use the
motor_ActualPostion tag to evaluate the encoder installation.
1. Disable the drive.
2. Note the ActualPostion tag value.
3. Move the axis in the positive direction.
See page 39
for definition for positive direction.
4. Verify that the ActualPostion tag value increases as the axis
moves.
If the positive direction of travel does not match what has been
defined by the motor power and Hall Sensing wiring, then
change the direction by re-wiring the encoder using the
following table.
Move To
Encoder PhaseDrive CN2, pinEncoder PhaseDrive CN2, pin
A+1B+ 3
A-2B- 4
B+3A+1
B-4A- 2
Publication LDL-UM001A-EN-P - March 200949
Chapter 6 Configure and Start Up the LDL-Series Linear Motor
Verify Motor Encoder
Resolution
This test compares the physically measured distance to the distance
calculated by the software. It also verifies the encoder setting in the
RSLogix 5000 software.
1. Measure and mark a fixed distance of travel on the axis.
2. Record the ActualPosition tag value with carriage at the starting
position.
3. Move the carriage to the end position.
4. Record the ActualPosition tag value.
5. Calculate the distance moved using the record values.
6. Compare the actual distance and the calculated distance.
If the values do not match, verify resolution of installed encoder
and the values used in the Motor Feedback, Co nversion, and
Units tabs.
Verify Linear Motor Wiring
and Function
The Homing and Hookup tabs in RSlogix 5000 software check the
motor power (U, V, W), Hall sensing signals (S1, S2, S3) and the
encoder wiring are correct.
IMPORTANT
Follow this steps to verify your motor wiring and function.
1. Click the Hookup tab.
2. Configure the parameters.
The following table shows the Suggested Settings.
ParameterSuggested Setting
The following components must be wired correctly for your
drive and linear motor to operate properly:
• Hall Effect Module
• Coil Power Wires
• Thermistor
• Encoder
Test increment60.00 mm
Drive PolarityPositive
50Publication LDL-UM001A-EN-P - March 2009
Configure and Start Up the LDL-Series Linear Motor Chapter 6
3. Click OK.
4. Click Test Marker… to run the Test Marker test.
See your encoder user documentation for location and
frequency of markers.
5. Position the coil so that it can move 60 mm (2.36 in.) in the
forward or reverse direction.
6. Click Test Feedback… to run the Test Feedback test.
Move the axis by hand at least 60 mm (2.36 in.) when prompted.
When using Allen-Bradley servo drives match the counting
direction of your position feedback encoder to the directi on th e
motor moves when positive current is applied.
7. Click Test Command & Feedback… to run the Test Command &
Feedback test.
Follow the on-screen instructions.
IMPORTANT
IMPORTANT
Be sure all the tests on the Hookup tab have passed
before proceeding.
When using Kinetix 6000 and Kinetix 2000 drives, the
Test Command Feedback test may pass even though the
Hall Effect module is not wired correctly.
Publication LDL-UM001A-EN-P - March 200951
Chapter 6 Configure and Start Up the LDL-Series Linear Motor
8. Click the Tune tab.
WARNING
Large Position Error Tolerances, such as those calculated
by the Auto Tune function in RSLogix 5000 programming
software, or when configuring a new axis with RSLogix
5000 software, can lead to undetected and repetitive
high energy impacts against axis end stops if proper
precautions are not in place. These tolerances can also
lead to undetected and repetitive high energy impacts
against unexpected obstructions. Such impacts can lead
to equipment damage and/or serious injury.
To identify the safety concerns that you have with
default Position Error Tolerance or after an Auto-Tune
Function, go to the Rockwell Automation Knowlegebase
Click Find Technical Support Answers and search for
Answer Id 55937.
9. Configure the parameters in the Tune tab as suggested in the
Initial Setting column. Leave all other tune options off for your
first pass. If necessary, reduce the Velocity Loop Proportional
Gain to maintain stability.
Configure and Start Up the LDL-Series Linear Motor Chapter 6
10. Click the Homing tab.
11. Choose Sequence to Switch-Marker, or Torque Level-Marker
when a repeatable power-up position is desired.
Typical linear TTL and Sin/Cos encoders will home repeatability
to within one count of resolution when their inde x mark is used.
Publication LDL-UM001A-EN-P - March 200953
Chapter 6 Configure and Start Up the LDL-Series Linear Motor
Notes:
54Publication LDL-UM001A-EN-P - March 2009
Specifications and Dimensions
Appendix
A
Introduction
This appendix provides product specifications and mounting
dimensions for your LDL-Series ironless linear motor components.
TopicPage
Performance Specifications56
General Specifications61
Product Dimensions63
55Publication LDL-UM001A-EN-P - March 200955
Appendix A Specifications and Dimensions
Performance
Specifications
AttributeValue
Motor type
Operating speed, max10 m/s (32.8 ft/s)
Operating voltage, (not for direct connection to AC line)230V AC rms
Dielectric rating of motor power connections (U,V,W), to ground for 1.0 s
Cogging torque Zero
Applied bus voltage, max
Electrical cycle length60 mm (2.36 in.)
Coil temperature, max130 °C (266 °F)
Insulation class130 °C (266 °F) Class B
Thermal time constant, Ref, winding to ambient35 min
These tables provide performance specifications for the LDL-Series
ironless linear servo motors.
Common Performance Specifications
These performance specifications apply to all LDL-Series ironless
linear servo motors.
3 phase, wye winding, synchronous permanent magnet stator,
non-ventilated linear motor
(1)
1500V AC rms, 50/60 Hz
(2)
325V DC
Paint colorBlack
(1) Tested during manufacturing process, Do not re-apply test voltage. Contact Application Engineering (631.344.6600) for advice on testing coils post production.
(2) Maximum cable length is 10 m (32.8 ft). Contact Application Engineering (631.344.6600) for applications requiring longer cables.
56Publication LDL-UM001A-EN-P- March 2009
Specifications and Dimensions Appendix A
LDL-Series Ironless Linear Motor Performance Specifications
LDL-Series Ironless Linear Motor (Standard 30 mm frame size)
(1) Coils at maximum temperature, 130 °C (266 °F), mounted to an aluminium heat sink whose area is noted in table on page 62, and at 40 °C (104 °F) ambient.
(2) Continuous force and current based on coil moving with all phases sharing the same load in sinusoidal commutation.
(3) For standstill conditions, multiply continuous force and continuous current by 0.9.
(4) Coil mountings on either of the two narrow sides reduces continuous force by 10%.
(5) Calculated at 11% duty cycle for 1.0 second max. Some applications may produce significantly higher peak forces. Call Applications Engineering (631.344.6600) for details.
(6) Winding parameters listed are measured line-to-line (phase-to-phase).
(7) Currents and voltages listed are measured 0-peak of the sine wave unless noted as rms.
(8) Specifications are ±10%. Phase-to-phase inductance is ±30%.
F
a
0 (0)
Publication LDL-UM001A-EN-P - March 200957
Appendix A Specifications and Dimensions
LDL-Series Ironless Linear Motor (Standard 50 mm frame size)
(1) Coils at maximum temperature, 130 °C (266 °F), mounted to an aluminium heat sink whose area is noted in table on page 62, and at 40 °C (104 °F) ambient.
(2) Continuous force and current based on coil moving with all phases sharing the same load in sinusoidal commutation.
(3) For standstill conditions, multiply continuous force and continuous current by 0.9.
(4) Coil mountings on either of the two narrow sides reduces continuous force by 10%.
(5) Calculated at 11% duty cycle for 1.0 second max. Some applications may produce significantly higher peak forces. Call Applications Engineering (631.344.6600) for details.
(6) Winding parameters listed are measured line-to-line (phase-to-phase).
(7) Currents and voltages listed are measured 0-peak of the sine wave unless noted as rms.
(8) Specifications are ±10%. Phase-to-phase inductance is ±30%.
41.3
(1.1)
124.0
(3.2)
41.3
(1.1)
82.7
(2.1)
27.2 (19.2)9.1 (6.4)36.3 (25.6)18.1 (12.8)
8.2 (5.8)2.7 (1.9)10.9 (7.7)5.5 (3.9)
2.3721.331.787.11
0 (0)
58Publication LDL-UM001A-EN-P- March 2009
Specifications and Dimensions Appendix A
LDL-Series Ironless Linear Motor (Thick 50 mm frame size)
(1) Coils at maximum temperature, 130 °C (266 °F), mounted to an aluminium heat sink whose area is noted in table on page 62, and at 40 °C (104 °F) ambient.
(2) Continuous force and current based on coil moving with all phases sharing the same load in sinusoidal commutation.
(3) For standstill conditions, multiply continuous force and continuous current by 0.9.
(4) Coil mountings on either of the two narrow sides reduces continuous force by 10%.
(5) Calculated at 11% duty cycle for 1.0 second max. Some applications may produce significantly higher peak forces. Call Applications Engineering (631.344.6600) for details.
(6) Winding parameters listed are measured line-to-line (phase-to-phase).
(7) Currents and voltages listed are measured 0-peak of the sine wave unless noted as rms.
(8) Specifications are ±10%. Phase-to-phase inductance is ±30%.
47.4
(1.2)
142.3
(3.6)
47.4
(1.2)
94.9
(2.4)
27.2 (19.2)9.1 (6.4)36.3 (25.6)18.1 (12.8)
8.2 (5.8)2.7 (1.9)10.9 (7.7)5.5 (3.9)
3.1428.252.359.42
0 (0)
Publication LDL-UM001A-EN-P - March 200959
Appendix A Specifications and Dimensions
LDL-Series Ironless Linear Motor (Standard 75 mm frame size)
(1) Coils at maximum temperature, 130 °C (266 °F), mounted to an aluminium heat sink whose area is noted in table on page 62, and at 40 °C (104 °F) ambient.
(2) Continuous force and current based on coil moving with all phases sharing the same load in sinusoidal commutation.
(3) For standstill conditions, multiply continuous force and continuous current by 0.9.
(4) Coil mountings on either of the two narrow sides reduces continuous force by 10%.
(5) Calculated at 11% duty cycle for 1.0 second max. Some applications may produce significantly higher peak forces. Call Applications Engineering (631.344.6600) for details.
(6) Winding parameters listed are measured line-to-line (phase-to-phase).
(7) Currents and voltages listed are measured 0-peak of the sine wave unless noted as rms.
(8) Specifications are ±10%. Phase-to-phase inductance is ±30%.
60Publication LDL-UM001A-EN-P- March 2009
Specifications and Dimensions Appendix A
General Specifications
These tables provide weight, heat sink, environmental for LDL-Series
ironless linear motors.
Weight Specifications
Weight Specifications - Motor Coil with Flying Leads
Cat. No.
LDL-N030120-DHT20
LDL-T030120-DHT20
LDL-N030240-xHT20
LDL-T030240-xHT20
LDL-N050120-DHT20
LDL-T050120-DHT20
LDL-N050240-xHT20
Weight, Approx.
kg (lb)
0.63 (1.38)
0.74 (1.64)
1.14 (2.51)
1.37 (3.02)
0.75 (1.66)
0.91 (2.01)
1.39 (3.07)
Cat. No.
LDL-T050240-xHT20
LDL-N050360-xHT20
LDL-T050360-xHT20
LDL-N050480-xHT20
LDL-T050480-xHT20
LDL-N075480-xHT20
LDL-T075480-xHT20
Weight Specifications - Motor Coil with Connectors
Temperature, operating ambient0…40 °C (32…104 °F)
Temperature, storage ambient -30…70 °C (-22…158 °F)
Humidity, relative non-condensing5…95%
Liquid/dust protectionIP 65
Shock, max.20 g peak, 6 ms duration
Vibration, max30…2000 Hz, 2.5 g peak
Certifications
Certification
(when product is marked)
c-UL-usUL recognized to U.S. and Canadian safety standards (UL 1004-1 and 840 File E230241).
CE
(1) Refer to http://www.ab.com for Declarations of Conformity Certificates.
(1)
Standards
European Union 2004/108/EC EMC Directive compliant with EN 61800-3:2004: Adjustable Speed
Electrical Power Drive Systems - Part 3; EMC Product Standard including specific test methods.
European Union 2006/95/EC Low Voltage Directive compliant with:
• EN 60034-1:2004 Rotating Electrical Machines, Part I: Rating and Performance.
• EN 60204-1:2006 Safety of Machinery – Electrical Equipment of Machines, Part 1: General
Requirements.
62Publication LDL-UM001A-EN-P- March 2009
Specifications and Dimensions Appendix A
Product Dimensions
LDL-Series ironless linear motor components are designed to metric
dimensions. Inch dimensions are conversions from millimeters.
Untoleranced dimensions are for reference.
Publication LDL-UM001A-EN-P - March 200963
Appendix A Specifications and Dimensions
Motor Coil Dimensions
Magnet channel
shown for reference.
J
0.83±0.30
T
Air Gap
(0.033±.011)
Feedback
Power
Connector
Connector
Dimensions are in mm (in.)
C
D
E
F
Thermistor Cable
Flying Leads
1000 mm (39.37 in.)
28.00
(1.102)
80.00
(3.150)
A
B
Power Cable
Flying Leads
1000 mm (39.37 in.)
8.5 (0.33),
Mounting holes
M4 x 0.7
22.00
38.00
60.00
quantity A1.
G
(0.866)
(1.496)
Typical
(2.362)
I
Hall Effect Module
Flying Leads
1000 mm (39.37 in.)
32.00
H
0.260 (0.010)
Coil Face Runout (T.I.R.)
(1.260)
350
(13.9)
(24)
600
Encoder
Connector
28.00
(1.102)
80.00
(3.150)
A
B
C
D
E
F
8.5 (0.33),
quantity A1.
M4 x 0.7
Mounting holes
26.00
35.00
(1.024)
(1.378)
L
4.50
(0.177)
LDL-Series Ironless Linear Motor Coil Dimension (LDL-xxxxxxx-xHT20) with Flying Leads
26.00
35.00
(1.024)
(1.378)
L
4.50
(0.177)
Refer to table on page 65 for coil mounting surface flatness requirement.
7 (0.28)
quantity A2.
Mounting holes
typical both sides,
M4 x 0.7
Dimensions for side view of linear motor coil with connectors is identical to this view with flying leads.
LDL-Series Ironless Linear Motor Coil Dimension (LDL-xxxxxxx-xHT11) with Connectors
64Publication LDL-UM001A-EN-P- March 2009
Specifications and Dimensions Appendix A
Flatness
mm/300 x 300 (in./12 x 12)
(AWG)
2
Power Cable Gauge
mm
A2
Qty
0.25 (0.010)
0.50 (20)
0.75 (18)
0.64 (0.025)
0.75 (18)
0.75 (18)
(9.685)
(7.087)
8.30 (0.33)
100.00
(3.937)
90.50
(3.563)
366.00
300.00
320.00
1260.38 (0.015)
8.30 (0.33)
(14.409)
(11.811)
––
(12.598)
168
486.00
(19.134)
420.00
(16.535)
440.00
(17.323)
360.00
(14.173)
320.00
(12.598)
8.30 (0.33)
130.00
(5.118)
115.50
(4.547)
10.80 (0.43)
Static Bend Radius
mm (in.)
Cable Dia.
mm (in.)
A1
Qty
42
T
mm (in.)
8.30 (0.33)
(1)
mm (in.)
J
I
mm (in.)
126.00
H
mm (in.)
60.00
G
mm (in.)
F
mm (in.)
E
mm (in.)
D
mm (in.)
(4.961)
(2.362)
80.00
(3.149)
70.50
(2.776)
8.30 (0.33)
84
8.30 (0.33)
246.00
(9.685)
180.00
(7.087)
42
126.00
(4.961)
60.00
(2.362)
84
8.30 (0.33)
246.00
180.00
240.00
LDL-T050480-xHTxx10.80 (0.43)0.50 (20)
200
120.00
496.0
(9.449)
(7.874)
(4.724)
(19.53)
LDL-N075480-DHTxx
LDL-N075480-EHTxx0.50 (20)
LDL-T075480-DHTxx
LDL-T075480-EHTxx0.50 (20)
(1) Tolerance for J dimension is ±0.26 mm (0.010 in.).
Cable Specifications
Shield Type
(AWG)
2
Gauge
mm
Conductors
(1)
Cable
40.52 (20)Braid6.4 (0.25)17.0 (0.67)
40.82 (18)Braid7.0 (0.28)18.0 (0.70)
(2)
(2)
Thermistor20.20 (26)None4.0 (0.16)10.0 (0.40)
Power
Power
Hall Module60.13 (24)Foil5.0 (0.20)15.0 (0.59)
(1) All cables are non-flex.
(2) Power cable specification is dependent on coil used. See Power Cable Gauge column in the table on the top of this page.
C
mm (in.)
LDL-Series Ironless Linear Motor Coil Dimensions (LDL-xxxx-xHTxx)
B
mm (in.)
A
L
Cat. No.
––––––
mm (in.)
136.0
mm (in.)
LDL-N030120-DHTxx
––––
200.00
120.00
(5.35)
256.0
LDL-T030120-DHTxx10.80 (0.43)
LDL-N030240-xHTxx
(7.874)
(4.724)
(10.08)
LDL-T030240-xHTxx10.80 (0.43)
––––––
136.0
(5.35)
LDL-N050120-DHTxx
––––
200
(7.874)
120.0
(4.724)
256.0
(10.08)
LDL-T050120-DHTxx10.80 (0.43)
LDL-T050240-xHTxx
240.00
(9.449)
200
(7.874)
120.00
(4.724)
376.0
(14.80)
LDL-N050480-DHTxx
LDL-N050360-xHTxx10.80 (0.43)
LDL-T050360-xHTxx
LDL-N050240-xHTxx10.80 (0.43)
LDL-N050480-EHTxx0.50 (20)
Publication LDL-UM001A-EN-P - March 200965
Appendix A Specifications and Dimensions
LDL
S
i
I
l
Li
M
t
M
t
Ch
l
Di
i
Magnet Channel Dimensions
Dimensions are in mm (in.)
G
25.00
Setup Dimension
(0.984)
H
T
W
- 0.00 (-0.000)
T DP Both Sides
Ø 4.00 (0.157) +0.06 (+0.002)
60.00
(2.362)
Mounting Hole Dimensions
60.00
(2.362)
Mounting Hole Dimensions
Flatness
(3)
Y
Hole
N
M
(2)
L
mm/300 x 300 (in./12 x 12)
mm (in.)
Qty
1295.00 (3.740)0.13 (0.005)
mm (in.)
mm (in.)
119.00 (4.685)
14.00 (0.551)
119.00 (4.685)1295.00 (3.740)0.13 (0.005)
1295.00 (3.74)0.13 (0.005)
119.00 (4.685)
14.00 (0.551)
119.00 (4.685)1294.00 (3.740)0.13 (0.005)
1295.00 3.740)0.13 (0.005)
119.00 (4.685)
19.00 (0.748)
119.00 (4.685)1295.00 (3.740)0.13 (0.005)
D
mm (in.)
Gap will result from setting the
plates to setup dimension shown.
Ø10.00 (0.394)
See table for hole quantity.
(1)
G
mm (in.)
9.86 (0.388)18.90 (0.744)
M6 x 1.0-6H thru
See table for hole quantity.
T
Refer to table for magnet channel mounting surface flatness requirement.
) Tolerance for G dimension is +0.35 mm (+0.012 in.), -0.12 mm (-0.004 in.).
) Tolerance for L dimension is ±0.25 mm (±0.010 in.).
) Tolerance for Y dimension is ±0.05 mm (±0 in.002 in.).
Interconnect Diagrams
Appendix
B
Introduction
Wiring Examples
This appendix provides wring examples to assist you in wring an
LDL-Series linear motors to an Allen-Bradley drive.
TopicPage
Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT11 Linear Motor with
a TTL Encoder
Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT11 Linear Motor with
a Sin/Cos Encoder
Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT20 Linear Motor with
a TTL Encoder
Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT20 Linear Motor with
a Sin/Cos Encoder
Ultra3000 Drives and LDL-xxxxxxx-xHT11 Linear Motor with a TTL Encoder72
Ultra3000 Drives and LDL-xxxxxxx-xHT11 Linear Motor with a Sin/Cos Encoder 73
Ultra3000 Drives and LDL-xxxxxxx-xHT20 Linear Motor with a TTL Encoder73
Ultra3000 Drives and LDL-xxxxxxx-xHT20 Linear Motor with a Sin/Cos Encoder 75
These notes apply to the wiring examples on the pages that follow.
68
69
70
71
Note Information
1
Use cable shield clamp in order to meet CE requirements. No external connection
to ground is required.
2
For motor cable specifications, refer to the Kinetix Motion Control Selection
Guide, publication GMC-SG001.
3
When using Sin/Cos encoder with Kinetix 6000 drives refer to Appendix C on
page 77
.
67Publication LDL-UM001A-EN-P- March 200967
Appendix B Interconnect Diagrams
Wiring Example for Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT11
Linear Motor with a TTL Encoder
Kinetix 2000 or Kinetix 6000
IAM (inverter) or AM
Module
Motor Power
(MP) Connector
Cable Shield
Clamp
Note 1
Motor Feedback
(MF) Connector
(IAM/AM) Module
Refer to low profile connector
illustration (lower left) for proper
grounding and shield termination
techniques.
Low Profile Connector
(Use 2090-K6CK-D15M for Kinetix 6000 Drives
and 2090-K2CK-D15M for Kinetix 2000 Drives.)
LDL-Series Linear Motor Coil
1
U
2
V
3
W
4
Brown
Black
Blue
Green/Yellow
2090-CPWM4DF-xxAFxx,
2090-XXNPMF-xxSxx
A
B
C
Three-phase
Motor Power
GND
Motor Power Cable
Note 2
N/C
2090-XXNFMF-Sxx or
2900-CFBM4DF-CDAFxx
N/C
WHT/Orange
Blue
WHT/Blue
Yellow
WHT/Yellow
WHT/Gray
Gray
White/Green
Green
WHT/Red
Red
WHT/Black
Black
11
12
13
8
6
14
10
5
4
3
2
1
TS+
TS-
S1
S2
S3
ECOM
+5V DC
IMIM+
BM-
BM+
AM-
AM+
13
14
15
16
17
10
9
6
5
4
3
2
1
Thermal
Switch
Feedback Cable
Note 2
AM+
AM-
BM+
BM-
IM+
IM+5VDC
ECOM
1
4
2
5
3
6
8
7
TTL Encoder
Ground techniques for
feedback cable shield.
Clamp
Exposed shield secured
under clamp.
Clamp screw (2)
Turn clamp over to hold
small cables secure.
68Publication LDL-UM001A-EN-P- March 2009
Interconnect Diagrams Appendix B
Wiring Example for Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT11
Linear Motor with a Sin/Cos Encoder
Kinetix 2000 or Kinetix
6000 IAM (inverter) or
AM Module
Motor Power
(MP) Connector
U
V
W
Cable Shield
Clamp
Note 1
11
12
13
Motor Feedback
(MF) Connector
(IAM/AM) Module
8
6
14
10
5
4
3
2
1
Refer to low profile connector
illustration (lower left) for proper
grounding and shield termination
techniques.
Low Profile Connector
(Use 2090-K6CK-D15M for Kinetix 6000 Drives
and 2090-K2CK-D15M for Kinetix 2000 Drives.)
LDL-Series Linear Motor Coil
1
2
3
4
Brown
Black
Blue
Green/Yellow
2090-CPWM4DF-xxAFxx,
2090-XXNPMF-xxSxx
A
B
Three-phase
Motor Power
C
GND
Motor Power Cable
Note 2
TS+
TS-
S1
S2
S3
ECOM
+5V DC
IM-
IM+
COS-
COS+
SIN-
SIN+
13
14
15
16
17
10
9
6
5
4
3
2
1
Thermal
Switch
N/C
WHT/Orange
Blue
WHT/Blue
Yellow
WHT/Yellow
WHT/Gray
Gray
White/Green
Green
WHT/Red
Red
WHT/Black
Black
N/C
2090-XXNFMF-Sxx or
2900-CFBM4DF-CDAFxx
Feedback Cable
Note 2
SIN+
SINCOS+
COS-
IM+
IM-
+5VDC
ECOM
1
4
2
5
3
6
8
7
Sin/Cos Encoder
Note 3
Ground techniques for
feedback cable shield.
Clamp
Exposed shield secured
under clamp.
Clamp screw (2)
Turn clamp over to hold
small cables secure.
Publication LDL-UM001A-EN-P- March 200969
Appendix B Interconnect Diagrams
Wiring Example for Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT20
Linear Motor with a TTL Encoder
Kinetix 2000 or Kinetix 6000
IAM (inverter) or AM
Module
Note 3
Cable Shield
Clamp
Note 1
Motor Power
(MP) Connector
Motor Feedback
(MF) Connector
(IAM/AM) Module
W
V
U
11
12
13
8
1
2
3
4
5
10
14
6
Refer to low profile connector
illustration (lower left) for proper
grounding techniques.
LDL-Series Linear Motor Coil
4
3
2
1
Green/Yellow
W
V
U
TS+
TS -
Black
White
Red
Black
Black
W
V
U
GND
Three-phase
Motor Power
Thermal
Switch
Power
Red
White
S1
Blue
S2
Orange
S3
Black
COM
Hall Effect
Module
AM+
AM-
BM+
BM-
IM+
IM-
POWER
COM
Wire as shown here using
cable type appropriate for
Linear Encoder
TTL Encoder
your application.
Low Profile Connector
Ground techniques for
feedback cable shield.
(Use 2090-K6CK-D15M for Kinetix 6000 Drives
and 2090-K2CK-D15M for Kinetix 2000 Drives.)
Clamp
Exposed shield secured
under clamp.
Clamp screw (2)
Turn clamp over to hold
small cables secure.
70Publication LDL-UM001A-EN-P- March 2009
Interconnect Diagrams Appendix B
Wiring Example for Kinetix 6000 or Kinetix 2000 Drives and LDL-xxxxxxx-xHT20
Linear Motor with a Sin/Cos Encoder
Kinetix 2000 or Kinetix 6000
IAM (inverter) or AM
Module
Cable Shield
Clamp
Note 1
Motor Power
(MP) Connector
W
V
U
11
12
13
8
Motor Feedback
(MF) Connector
(IAM/AM) Module
3
4
5
10
14
6
Refer to low profile connector
illustration (lower left) for proper
grounding techniques.
LDL-Series Linear Motor Coil
4
3
2
1
Green/Yellow
W
V
U
TS+
TS -
Black
White
Red
Black
Black
W
V
U
Three-phase
GND
Motor Power
Thermal
Switch
Power
Red
White
S1
Blue
S2
Orange
S3
Black
COM
Hall Effect
Module
1
2
Wire as shown here using
cable type appropriate for
your application.
COS+
COS-
SIN+
SIN-
IM+
IM-
POWER
COM
Linear Encoder
Sin/Cos Encoder
Note 3
Low Profile Connector
Ground techniques for
feedback cable shield.
(Use 2090-K6CK-D15M for Kinetix 6000 Drives
and 2090-K2CK-D15M for Kinetix 2000 Drives.)
Clamp
Exposed shield secured
under clamp.
Clamp screw (2)
Turn clamp over to hold
small cables secure.
Publication LDL-UM001A-EN-P- March 200971
Appendix B Interconnect Diagrams
Ultra3000 Drive
Wiring Example for Ultra Drive and LDL-xxxxxxx-xHT11 Linear Motor with a TTL
Encoder
LDL-Series Linear Motor Coil
LDL-Series Linear MotorCoil
Motor Power
(TB1) Connector
Cable ShieldClampNote 1
Motor Feedback
(CN2) Connector
Refer to low profile connector
illustration (lower left) for proper
grounding and shield termination
techniques.
1
U
2
V
3
W
4
11
12
13
8
6
14
10
5
4
3
2
1
WHT/Orange
N/C
WHT/Yellow
White/Green
WHT/Black
Refer to low profile connectorillustration (lower left) for proper grounding and shieldterminationtechniques.
Blue
WHT/Blue
Yellow
WHT/Gray
Gray
Green
WHT/Red
Red
Black
Brown
Black
Blue
Green/Yellow
2090-CPWM4DF-xxAFxx,
2090-XXNPMF-xxSxx
Motor Power Cable
Note 2
Motor PowerCable
Note 2
2090-XXNFMF-Sxx or
2900-CFBM4DF-CDAFxx
Feedback Cable
Feedback Cable
Note 2
Note 2
N/C
TS+
TS-
ECOM
+5V DC
IM-
IM+
COS-
COS+
SIN-
SIN+
SIN+
SINCOS+
COS-
IM+
IM+5VDC
ECOM
A
B
Three-phase
Three-phase
Motor Power
C
Motor Power
GND
13
S1
S2
S3
14
15
16
17
10
9
6
5
4
3
2
1
1
4
2
5
3
6
8
7
Thermal
Thermal
Switch
Switch
TTL Encoder
TTL EncoderWirecolor shown for Renishaw
RGH22 linear incremental encoder
Ground techniques for
feedback cable shield.
withits reference mark actuatorinstalled.
Exposed shield secured
under clamp.
2090-UXBB-DM15
Cable Tie
Motor Feed Breakout Board
72Publication LDL-UM001A-EN-P- March 2009
Interconnect Diagrams Appendix B
Wiring Example for Ultra3000 Drive and LDL-xxxxxxx-xHT11 Linear Motor with a
Sin/Cos Encoder
Ultra3000 Drive
Motor Power
(TB1) Connector
Cable Shield
Clamp
Note 1
Motor Feedback
(CN2) Connector
1
U
2
V
3
W
4
N/C
WHT/Orange
WHT/Blue
WHT/Yellow
WHT/Gray
White/Green
WHT/Black
11
12
13
8
6
14
10
5
4
3
2
1
Refer to low profile connector
illustration (lower left) for proper
grounding and shield termination
techniques.
Blue
Yellow
Gray
Green
WHT/Red
Red
Black
Brown
Black
Blue
Green/Yellow
2090-CPWM4DF-xxAFxx,
2090-XXNPMF-xxSxx
Motor Power Cable
Note 2
2090-XXNFMF-Sxx or
2900-CFBM4DF-CDAFxx
Feedback Cable
Note 2
N/C
ECOM
+5V DC
COS-
COS+
SIN-
SIN+
SIN+
SINCOS+
COS-
IM+
IM-
+5VDC
ECOM
TS+
TS-
S1
S2
S3
IM-
IM+
LDL-Series Linear Motor Coil
A
B
Three-phase
Motor Power
C
GND
13
14
15
16
17
10
9
6
5
4
3
2
1
1
4
2
5
3
6
8
7
Thermal
Switch
Sin/Cos Encoder
Ground techniques for
feedback cable shield.
Exposed shield secured
under clamp.
2090-UXBB-DM15
Cable Tie
Motor Feed Breakout Board
Wiring Example for Ultra3000 Drive and LDL-xxxxxxx-xHT20 Linear Motor with a
TTL Encoder
Publication LDL-UM001A-EN-P- March 200973
Appendix B Interconnect Diagrams
Ultra3000 Drive
Cable Shield
Clamp
Note 1
Motor Power
(TB1) Connector
Motor Feedback
(CN2) Connector
W
V
U
11
12
13
8
1
2
3
4
5
10
14
6
Refer to low profile connector
illustration (lower left) for proper
grounding techniques.
LDL-Series Linear Motor Coil
4
3
2
1
Green/Yellow
W
V
U
TS+
TS -
Black
White
Red
Black
Black
W
V
U
GND
Three-phase
Motor Power
Thermal
Switch
Power
Red
White
S1
Blue
S2
Orange
S3
Black
COM
Hall Effect
Module
AM+
AM-
BM+
BM-
IM+
IM-
Linear Encoder
Wire as shown here using
cable type appropriate for
POWER
COM
TTL Encoder
your application.
Ground techniques for
feedback cable shield.
Exposed shield secured
under clamp.
2090-UXBB-DM15
Cable Tie
Motor Feed Breakout Board
74Publication LDL-UM001A-EN-P- March 2009
Interconnect Diagrams Appendix B
Wiring Example for Ultra3000 Drive and LDL-xxxxxxx-xHT20 Linear Motor with a
Sin/Cos Encoder
Ultra3000 Drive
Cable Shield
Clamp
Note 1
Motor Power
(TB1) Connector
Motor Feedback
(CN2) Connector
W
V
U
11
12
13
8
1
2
3
4
5
10
14
6
Refer to low profile connector
illustration (lower left) for proper
grounding techniques.
LDL-Series Linear Motor Coil
4
3
2
1
Green/Yellow
W
V
U
TS+
TS -
Black
White
Red
Black
Black
W
V
U
GND
Three-phase
Motor Power
Thermal
Switch
Power
Red
White
S1
Blue
S2
Orange
S3
Black
COM
Hall Effect
Module
COS+
COS-
SIN+
SIN-
IM+
IM-
Linear Encoder
Wire as shown here using
cable type appropriate for
POWER
COM
Sin/Cos Encoder
your application.
Ground techniques for
feedback cable shield.
Exposed shield secured
under clamp.
2090-UXBB-DM15
Cable Tie
Motor Feed Breakout Board
Publication LDL-UM001A-EN-P- March 200975
Appendix B Interconnect Diagrams
Notes:
76Publication LDL-UM001A-EN-P- March 2009
Appendix
C
Sin/Cos Linear Encoder and Kinetix 6000
Drives
Introduction
Kinetix 6000 Drive
Feedback Connection
This appendix guides you through commissioning a linear motor with
a Sin/Cos 1V peak-to-peak output linear encoder.
TopicPage
Kinetix 6000 Drive Feedback Connection77
Encoder Counting Direction78
Set Up the Axis Properties78
For robust operation when interfacing your Sin/Cos 1V peak-to-peak
differential output linear encoder to a Kinetix 6000 drive, you should
terminate the sine and cosine signals as follows.
SIN+
SIN-
COS+
COS-
150 7
Resistor
1/4 W, 5%
150 7
Resistor
1/4 W, 5%
AM+
AM-
BM+
BM-
1
2
3
Feedback Connector
2090-K6CK-D15M
4
Low Profile Connector
1N5819,
(~5.1V DC)
Add a Shottky diode for cable
lengths less then 10 m (32.8 ft).
or equivalent
(5.4V DC)+5V DC
14
For systems where the cable length is less than 10 m (32.8 ft), the
encoder power supply from the Kinetix 6000 drive feedback
connector should be dropped from its nominal 5.4…5.1V DC volts
with the addition of a Shottky Diode, see schematic.
77Publication LDL-UM001A-EN-P - March 200977
Appendix C Sin/Cos Linear Encoder and Kinetix 6000 Drives
Encoder Counting Direction
Set Up the Axis Properties
Normally, the encoder signals will output sine-leads-cosine (AM leads
BM) when the linear encoder head is moving towards its cable,
relative to the encoder scale. SERCOS drives count this in a negative
direction.
When installing a Sin/Cos linear encoder, setup the Axis Property tabs
by doing the following.
1. Click the Motor Feedback tab.
2. Enter the following parameter s.
ParameterValueComment
Feedback TypeSin/Cos–
Cycles25 per Millimeter For 40 µ pitch encoder scale.
50 per Millimeter For 20 µ pitch encoder scale.
Interpolation Factor1024 –
78Publication LDL-UM001A-EN-P - March 2009
Sin/Cos Linear Encoder and Kinetix 6000 Drives Appendix C
air gap
bumper
carriage design, heat sink
end of travel bumper
linear encoder
dielectric rating
22
17
18
18
19
12
19
56
dimensions
coil
64
magnet channel
direction
49
66
E
encoder 31
resolution
encoder connector
encoder connector kit
encoder sin/cos
end of travel bumpers
end of travel impact
end stop
envelope dimensions
environmental specifications
ESD components
Hall effect ESD
50
29
31
77
12
12
18
23
12
F
feedback connector 28
ferrous material
final alignment
firmware revision
flying leads
22
24
40
31
H
Hall effect module 17
hardware requirements
magnet channel
heat sink
19, 62
max temperature
22
12
I
inspection 21
installation
firmware
motor
motor coil
software
insulation class
interconnect diagrams
wiring example notes
21
40
22
25
40
56
67
L
label
identification
large impacts
10
12
62
Publication LDL-UM001A-EN-P - March 200981
Index
length 16
linear encoder
19
M
magnet channel 16, 17, 22
alignment
alignment tool
maintenance
max. speed
max. temp
coil
motion analyzer version
motor
database
direction
storage
type
mounting
configuration
hardware
motor coil
multiple motors
power cable
screw length
24
24
19
13
56
40
49
19
56
23
25
coil
magnet channel
25
35
27
25
22
N
non-magnetic 22
O
operating
speed
56
56
voltage
P
perfomance 19
phase alignment
two motors
pinout
coil power
encoder
feedback
power connector
PTC thermistor
power connector
procedure
cleaning magent channel
connections
35
27
29
28
2728, 2917, 27
31
40
19
install magnet channel
install motor coil
power connection
verify encoder resolution
verify motor wiring
air freight restriction
dangerous goods declaration
form 902 instructions
shock absorber
software
required version
spacing
two motors
specifications
common
environment
standard 30 mm frame
standard 50 mm frame
standard 75 mm frame
56
9
9
12
22
77
4242
47
11
11
18
40
35
62
22
50
28
7
11
575860
82Publication LDL-UM001A-EN-P - March 2009
Index
thick 30 mm frame57
thick 50 mm frame
thick 75 mm frame
storage
19
T
tandem motors 35
temperature
max heat sink
Thermal
thermal time constant
time constant
tools
torque
56
22
magnet channel
12
56
22
U
unpacking 21
V
5960
56
verify
direction
motor wiring
resolution
49
50
50
W
warning
air freight restrictions
automatic implantable cardioverter
defibrillator (AICD)
powerful forces
weight
coil flying lead
magnet channel
31
wiring
wiring diagram
connectorized
Sin/Cos encoder
TTL encoder
flying lead
Sin/Cos encoder
TTL encoder
68, 72
11
9
61
61
69, 73
68, 72
71, 74, 75
70
9
Publication LDL-UM001A-EN-P - March 200983
Rockwell Automation
Support
Rockwell Automation provides technical information on the Web to assist
you in using its products. At
find technical manuals, a knowledge base of Faqs, technical and application
notes, sample code and links to software service packs, and a MySupport
feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation,
configuration, and troubleshooting, we offer TechConnect support programs.
For more information, contact your local di st ri buto r or Rockwe l l Aut oma ti on
representative, or visit
http://support.rockwellautomation.com, you can
http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please
review the information that's contained in this manual. Y ou can also contact a
special Customer Support number for initial help in getting your product up
and running.
United States1.440.646.3434
Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United
States
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully
operational when shipped from the manufacturing facility. However, if your
product is not functioning and needs to be returned, follow these
procedures.
United StatesContact your distributor. You must provide a Customer Support case
number (call the phone number above to obtain one) to your distributor
in order to complete the return process.
Outside United
States
Please contact your local Rockwell Automation representative for the
return procedure.
Publication LDL-UM001A-EN-P - March 2009 85PN 814062