FLEX 5000 Analog Isolated Current/Voltage/HART Input and Output Modules User Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WA RN I NG : Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
2Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Rockwell Automation Publication 5094-UM007B-EN-P - October 20207
Table of Contents
Notes:
8Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Preface
About This PublicationThis manual describes how to use FLEX 5000™ analog I/O modules in
Logix 5000™ control systems.
Make sure that you are familiar with the following:
•Use of a controller in a Logix 5000 control system
•Use of an EtherNet/IP™ network, if the analog I/O modules are installed
in a remote location from the controller that is accessible via the
EtherNet/IP network
•Studio 5000 Logix Designer® environment
Download Firmware, AOP,
EDS, and Other Files
IMPORTANT
Download firmware, associated files (such as AOP, EDS, and DTM), and access
product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc
Remember the following when you use FLEX 5000 Analog HART
I/O Modules:
• You cannot use FLEX 5000 I/O modules with all Logix 5000 controllers.
For example, you can use FLEX 5000 I/O modules with
CompactLogix™ 5380 and ControlLogix® 5580 controllers but not with
CompactLogix 5370 and ControlLogix 5570 controllers.
For the most current information on the Logix 5000 controllers with
which you can use FLEX 5000 I/O modules, see the product
description at rok.auto/flex5000IO
• You must use the Studio 5000 Logix Designer application, version
32.02 or later, to configure the FLEX 5000 analog HART I/O modules.
• You must use the Studio 5000 Logix Designer application, version
33.00 or later, to support ControlLogix 5580 High Availability
controllers.
.
.
Summary of ChangesThis publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Top ic Pa ge
Updated software version requirements9
Added software and firmware compatibility11
Reorganized common features29
Updated firmware revision requirements32
Added dedicated digital input point description39
Added digital input point features chapter49
Added points category description78
Corrected Output Ch0x category descriptions83
Added diagnostic assemblies chapter133
Added PlantPAx HART instruction compatible device connectionthroughout
Rockwell Automation Publication 5094-UM007B-EN-P - October 20209
Preface
Additional ResourcesThese documents contain additional information concerning related products
FLEX 5000 Terminal Base Assembly Modules Installation Instructions,
publication 5094-IN010
FLEX 5000 Modules Specifications Technical Data, publication 5094-TD001
CompactLogix 5380 Controllers User Manual, publication 5069-UM001Describes how to configure, operate, and troubleshoot CompactLogix 5380 controllers.
ControlLogix 5580 and GuardLogix 5580 Controllers User Manual, publication
1756-UM543.
FLEX 5000 Digital I/O Modules User Manual, publication 5094-UM001
FLEX 5000 Analog I/O Modules User Manual, publication 5094-UM002Describes how to configure, operate, and troubleshoot FLEX 5000 analog I/O modules.
FLEX 5000 EtherNet/IP Adapter User Manual, publication 5094-UM005
FLEX 5000 High-speed Counter I/O Modules User Manual, publication 5094-
UM003
EtherNet/IP Communication Modules in 5000 Series Control Systems User
Manual, publication ENET-UM004
Electronic Keying in Logix 5000 Control Systems Application Technique,
publication LOGIX-AT001
EtherNet/IP Network Devices User Manual, ENET-UM006
Ethernet Reference Manual, ENET-RM002
System Security Design Guidelines Reference Manual, SECURE-RM001
Safety Guidelines for the Application, Installation, and Maintenance of
Solid-state Control, publication SGI-1.1
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications
Describes how to configure, operate, and troubleshoot FLEX 5000 digital I/O modules.
.Provides declarations of conformity, certificates, and other certification details.
Describes how to install and wire the 5094-IF8IH and 5094-IF8IHXT analog input modules.
Describes how to install and wire the 5094-OF8IH and 5094-OF8IHXT analog output modules.
Describes how to install and wire the terminal base assemblies for the FLEX 5000 system.
Provides specifications for FLEX 5000 EtherNet/IP adapters and FLEX 5000 modules.
Describes how to configure, operate, and troubleshoot ControlLogix 5580 and GuardLogix®
5580 controllers.
Describes how to configure, operate, and troubleshoot FLEX 5000 EtherNet/IP adapters
Describes how to configure, operate, and troubleshoot FLEX 5000 high-speed counter
modules.
Describes how to configure, operate, and troubleshoot the FLEX 5000 EtherNet/IP adapters.
Describes how to use electronic keying in Logix 5000 control system applications.
Describes how to configure and use EtherNet/IP devices to communicate on the EtherNet/IP
network.
Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Provides guidance on how to conduct security assessments, implement Rockwell
Automation products in a secure system, harden the control system, manage user access,
and dispose of equipment.
Provides a quick reference tool for Allen-Bradley® industrial automation controls and
assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
general guidelines for the application, installation, and maintenance of solid-state control in
the form of individual devices or packaged assemblies incorporating solid-state
components.
You can view or download publications at rok.auto/literature
10Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Logix 5000 controllers use FLEX 5000 analog HART I/O modules to control
devices in a control system. The controllers access the modules over an
EtherNet/IP network. FLEX 5000 analog HART I/O modules use terminal base
(TB) assemblies to connect field-side wiring.
FLEX 5000 analog HART I/O modules connect a Logix controller to your
process. HART input modules (5094-IF8IH, 5094-IF8IHXT) receive signals
from process value transmitters and convert them to corresponding
measurement values for use in the Logix controller (for example, temperature,
flow, pressure, or pH). HART output modules (5094-OF8IH, 5094-OF8IHXT)
provide current or voltage output signals that adjust the settings of valves and
other devices in accord with desired process behavior.
Module and Software
Compatibility
Instruments that support the HART protocol allow several process parameters
to be measured with one field device, provide status and diagnostics
information, and allow remote configuration and troubleshooting.
FLEX 5000 analog HART I/O modules implement the Producer/Consumer
network communication model for both the module itself and the HART
devices that are attached to it. This communication is an intelligent data
exchange between modules / HART devices and other system devices in which
each module / HART device produces data without first being polled. You use
the Studio 5000 Logix Designer application, version 32.02 or later, to configure
the modules and HART devices.
Controller and programming software compatibility requirements apply when
you use FLEX 5000 standard and safety I/O modules. A module type and how it
is used affect which requirements apply.
You must also consider Logix Designer application version requirements when
you design your system. For example, you can use High Availability with only
version 33 or greater of the Logix Designer application.
Rockwell Automation Publication 5094-UM007B-EN-P - October 202011
Chapter 1 FLEX 5000 HART I/O Modules
Firmware and Software Compatibility
•You must use the Studio 5000 Logix Designer application, version 32.02
or later, to configure the FLEX 5000 analog HART I/O modules.
•You must use the Studio 5000 Logix Designer application, version 33.00
or later, to support ControlLogix 5580 High Availability controllers.
•You must use module firmware 3.011 or later to support ControlLogix
5580 High Availability controller redundancy, and PlantPAx® HART
instruction compatible device connection.
FLEX 5000 HART Module Feature Comparison
Table 1 describes the module firmware revision comparison for input modules.
Table 1 - FLEX 5000 HART Input Module Supported Features
FLEX 5000 HART
Firmware Revision
2.0
3.0
Table 2
describes the module firmware revision comparison for output
Module
5094-IF8IH,
5094-IF8IHXT
5094-IF8IH,
5094-IF8IHXT
Supported features
Analog input
HART device connection
Analog input
HART device connection
PlantPAx HART instruction compatible device connection
Digital input (type 3 / type-3d support)
ControlLogix 5580 High Availability controller
modules.
Table 2 - FLEX 5000 HART Output Module Supported Features
FLEX 5000 HART
Firmware Revision
2.0
3.0
Module
5094-OF8IH,
5094-OF8IHXT
5094-OF8IH,
5094-OF8IHXT
Supported features
Analog output
HART device connection
Analog output
HART device connection
PlantPAx HART instruction compatible device connection
ControlLogix 5580 High Availability controller
IMPORTANTAfter upgrading your FLEX 5000 HART module firmware to the latest
firmware revision, you need to wait 2 to 3 minutes before the channels
reflect the upgrade and are ready to use.
12Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 1 FLEX 5000 HART I/O Modules
STATUS
POWER
ANALOG 8 INPUT HART ISOLATED
5094-IF8IH
5
3
TB3I
FLEX 5000TM I/O
0 1 2 3 4 5 6 7
2
1
3
534
Module OverviewFigure 1 shows the parts of an example FLEX 5000 analog HART I/O module.
Figure 1 - Example FLEX 5000 Analog HART I/O Module
ItemDescription
1
2
3
4Ter min al b ase - Indicates the type of terminal base assembly to use with the module.
5Latching hooks - Securely installs FLEX 5000 modules on the terminal base assembly.
Status indicators - Displays the status of communication, module health, and input/output
devices. Indicators help with troubleshooting anomalies.
Release lever - Disengages the latching hooks to allow removal of the module from the
terminal base assembly.
Module keying - Indicates the keying position the terminal base assembly must be configured
to before installing the module.
HART CommunicationThe HART field communication protocol is widely accepted in industry as a
standard for digitally enhanced 4…20 mA communication with smart
(microprocessor-based) field devices. A digital signal is superimposed on the
4…20 mA current loop to provide two means of communication from the
device. The 4…20 mA analog channel lets the primary process variable be
communicated at the fastest possible rate while the digital channel
communicates multiple process variables, data quality, and device status. The
HART protocol lets these simultaneous communication channels be used in a
complementary fashion.
(1)
shows information about the HART protocol.
Figure 2
(1) This figure is from the HART Communication Protocol Specifications, April 2001, Revision
Rockwell Automation Publication 5094-UM007B-EN-P - October 202013
6.0, HART Communication Foundation. All Rights Reserved.
Chapter 1 FLEX 5000 HART I/O Modules
The Highway Addressable Remote Transducer (HART)
protocol supports two-way digital communication,
complements traditional 4…20 mA analog signals, and
includes the following features:
• Predefined commands
– Universal command
–Common practice
– Device specific
• Large installed base
• Worldwide support
Figure 2 - HART Protocol
20 mA
Analog
Signal
4 mA
c
+0.5 mA
0.5 mA
R
Analog
Signal
0
2200
1200
Hz
Hz
“0”
“1”
R
c
HART Signal
c
R
= Command
c
= Response
R
c
R
01 2
Time (seconds)
FLEX 5000 analog HART I/O modules support the HART protocol and perform
these operations:
•Conversion of 4…20 mA analog signals to digital numeric values in
engineering units (such as kg, m, or percent) that are used in the Logix
controller.
•Conversion of digital numeric values in engineering units to 4…20 mA
analog signals to control process devices.
•Producer/Consumer network communication model directly to each
HART device.
•Automatic collection of dynamic process data from the connected HART
device. For example, temperature, pressure, flow, or valve position.
•Automatic collection of device-specific variables from the connected
HART device.
•Execution of commands through Studio 5000 Logix Designer using
input and output tags.
•Facilitation of configuration and troubleshooting of the HART field
device from your control room using FDT/DTM supported software.
With the FLEX 5000 analog HART I/O modules, both the controller and
software for device maintenance and management can access field device
data.
14Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
The FLEX 5000 analog HART I/O modules support command-response
communication protocol in a point-to-point wiring architecture.
The FLEX 5000 analog HART I/O module is the primary master device and
continuously obtains information from the connected HART devices. The
secondary master can be used for device maintenance, for example a handheld
communicator, as shown here.
Chapter 1 FLEX 5000 HART I/O Modules
Primary master
Secondary master
(handheld communicator
as secondary master)
Slave
Most 4…20 mA transmitters are available with a HART protocol interface. The
type of data available depends on the type of instrument.
An example application is a HART enabled mass flowmeter. The standard mA
signal from the flowmeter provides one primary measurement - flow. The mA
signal with HART provides more process information. The mA signal that
represents flow is still available. The HART configuration of the flowmeter can
be set to communicate primary variable (PV), secondary variable (SV), tertiary
variable (TV), and quaternary variable (QV). These values can represent mass
flow, static pressure, temperature, total flow, and other conditions.
Dynamic variables, device-specific variables, device status, and command
execution are all available through input and output controller tags in Studio
5000 Logix Designer.
Device status information is also provided through HART.
HART connectivity provides all this information with no changes to the
existing 4…20 mA wiring.
FDT/DTM technology through HART connectivity is supported and also
provides remote configuration and troubleshooting of HART devices through
software.
HART-enabled I/O Modules
The FLEX 5000 analog HART I/O modules have built-in HART modems, so
there is no need to install external HART multiplexers or clip-on HART
modems. The 5094-IF8IH, 5094-OF8IHXT, 5094-OF8IH, and 5094-OF8IHXT
modules have separate HART modems for each channel.
HART implementation in 5094 provides a connection between the controller
and each HART device.
A HART device that is configured in a 5094 I/O module supports a configurable
connection that can include up to four Dynamic Variables, eight Device
Variables, and four HART Commands.
Rockwell Automation Publication 5094-UM007B-EN-P - October 202015
Chapter 1 FLEX 5000 HART I/O Modules
Notes:
16Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 2
Analog HART I/O Module Operation in a Logix
5000 Control System
Top icPa ge
Remote I/O Modules17
Before You Begin18
Types of Analog I/O Modules18
Power the Modules18
Ownership19
Configure Analog HART I/O Modules20
Input Module Operation23
Output Module Operation23
HART Device Operation26
Listen Only Mode25
Protected Operations26
IMPORTANT
Remember the following when you use FLEX 5000 Analog HART
I/O Modules:
• You cannot use FLEX 5000 I/O modules with all Logix 5000 controllers.
For example, you can use FLEX 5000 I/O modules with
CompactLogix 5380 and ControlLogix 5580 controllers but not with
CompactLogix 5370 and ControlLogix 5570 controllers.
For the most current information on the Logix 5000 controllers with
which you can use FLEX 5000 I/O modules, see the product
description at rok.auto/flex5000IO
• You must use the Studio 5000 Logix Designer application, version
32.02 or later, to configure the FLEX 5000 analog HART I/O modules.
• You must use the Studio 5000 Logix Designer application, version
33.00 or later, to support ControlLogix 5580 High Availability
controllers.
.
Remote I/O ModulesYou use FLEX 5000 analog HART I/O modules as remote I/O modules that are
accessible via an EtherNet/IP network. The modules are installed to the right
of a FLEX 5000 EtherNet/IP adapter.
Logix 5000 controllers can exchange data with the modules over the network.
Rockwell Automation Publication 5094-UM007B-EN-P - October 202017
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
5069-L340ERM
EtherNet/IP Network
5094 I/O with shield bar
5094-AENTR
Figure 3 - FLEX 5000 I/O Modules in a Logix 5000 Control System
IP ADDRESS
POWER
X100
FLEX 5000TM I/O
EtherNet/IP™ Adapter
X10
STATUS
NET
LINK 1
X1
LINK 2
5094-AENTR
PRP
DLR
FLEX 5000TM I/O
ANALOG 8 OUTPUT HART ISOLATED
5094-OF8IH
0 1 2 3 4 5 6 7
STATUS
POWER
2
3
TB3I
FLEX 5000TM I/O
ANALOG 8 INPUT HART ISOLATED
5094-IF8IH
0 1 2 3 4 5 6 7
STATUS
POWER
3
5
TB3I
FLEX 5000TM I/O
ANALOG 8 OUTPUT HART ISOLATED
5094-OF8IHXT
0 1 2 3 4 5 6 7
Before You BeginBefore you use your analog HART I/O module, you must complete the
following:
a. Install a FLEX 5000 EtherNet/IP adapter.
b. Install the FLEX 5000 I/O modules to the right of adapter.
c. Install an EtherNet/IP network.
d. Install the Logix 5000 controller that accesses the FLEX 5000 I/O
modules via an EtherNet/IP network.
Make sure that you have enough FLEX 5000 terminal base (TB) assemblies to
satisfy your application needs. For more information, see the FLEX 5000
Terminal Base Assembly Modules Installation Instructions,
publication 5094-IN010
.
STATUS
POWER
2
3
TB3I
IMPORTANT
TBs are not included with your module and are not available for
purchase. TBs consist of a mounting base (MB) and removable terminal
block (RTB). You must purchase MBs and RTBs separately and assemble
them together.
Types of Analog I/O
Modules
Ta b l e 3 describes the types of FLEX 5000 analog HART I/O modules.
Power the ModulesFLEX 5000 analog HART I/O modules receive the following power types:
•System-side power that powers the system and lets modules transfer
data and execute logic. System-side power is also known as Backplane
power.
•Field-side power that powers field-side devices that are connected to
some FLEX 5000 I/O modules. Field-side power is also known as
SA power.
18Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
System-side power begins at the FLEX 5000 EtherNet/IP adapter and passes
across the FLEX 5000 module internal circuitry via terminal base power bus,
that is, Backplane power.
Field-side power, that is, SA power begins at the first terminal base assembly
and can be daisy chained to the next terminal base assembly on the right. You
can also install a separate field-side power source to each terminal base
assembly.
For more information on how to power FLEX 5000 analog HART I/O modules,
see the FLEX 5000 EtherNet/IP Adapter User Manual, publication 5094-
UM005.
SA Power Requirements
Take note of the following when supplying SA power to your system:
•You must limit the SA field-side power source to 10 A, max, at
18...32V DC.
•Confirm that the external module power supply is adequately sized for
the total module power bus current draw in the system.
•For example, if the total module power current draw, including current
inrush requirements, is 5 A, you can use a module power supply that is
limited to 5 A.
•You must use SELV-listed power supplies for module power if there are
functional safety modules that are connected to the FLEX 5000 I/O
family.
•Not all power supplies are certified for use in all applications, for
example, nonhazardous and hazardous environments.
•Isolated source power of up to 25 mA available from the module to
simplify the channel to channel isolation wiring for current sensors.
IMPORTANT
We recommend that you use separate external power supplies for the
adapter and the adjacent terminal base. This practice can prevent
unintended consequences that can result if you use one supply.
OwnershipEvery I/O module in a Logix 5000 control system must be owned by a
controller, also known as the owner-controller. When the FLEX 5000 Analog
HART I/O modules are used in a Logix 5000 control system, the ownercontroller performs the following:
•Stores configuration data for every module that it owns.
•Can reside in a location that differs from the FLEX 5000 I/O modules.
•Sends the I/O module configuration data to define module behavior and
begin operation in the control system.
Each FLEX 5000 Analog HART I/O module must continuously maintain
communication with its owner-controller during normal operation.
FLEX 5000 Analog HART I/O modules are limited to one owner-controller.
Rockwell Automation Publication 5094-UM007B-EN-P - October 202019
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
Configure Analog HART I/O
Modules
You must create a Studio 5000 Logix Designer application project for the
Logix 5000 controller that owns the FLEX 5000 analog HART I/O modules and
attached HART devices. The project includes module configuration data for
the FLEX 5000 Analog HART I/O modules.
The Studio 5000 Logix Designer application transfers the project to the ownercontroller during the program download. Data is then transferred to the
FLEX 5000 analog HART I/O modules over the EtherNet/IP network.
The FLEX 5000 analog HART I/O modules can operate immediately after
receiving the configuration data.
Connections
During module configuration, you must define the module. Among the
Module Definition parameters, you must choose a connection type for the
module. A connection is a real-time data transfer link between the ownercontroller and the module that occupies the slot that the configuration
references.
During HART device configuration, you must define the input and output tags
for any connected HART device.
When you download module configuration to a controller, the controller
attempts to establish a connection to each module in the configuration.
Because part of module configuration includes a slot in the FLEX 5000 I/O
system, the owner-controller checks for the presence of a module or connected
HART device there. If a module or HART device is detected, the ownercontroller sends the configuration. One of the following occurs:
•If the configuration is appropriate to the module or HART device that is
detected, a connection is made and operation begins.
•If the configuration is not appropriate to the module or HART device that
is detected, the data is rejected and the Studio 5000 Logix Designer
application indicates that an error occurred.
The configuration can be inappropriate for many reasons. For example, a
mismatch in electronic keying that helps prevents normal operation.
The owner-controller monitors its connection with a module and HART
devices. Any break in the connection, for example, the loss of power to the
FLEX 5000 I/O system, causes a fault. The Studio 5000 Logix Designer
application monitors the fault status tags to indicate when a fault occurs on a
module or HART device.
Connection Types Available with FLEX 5000 Analog HART I/O Modules
When configuring an analog HART input or output module, you must define
the module. Connection is a required parameter in the Module Definition. The
choice determines what data is exchanged between the owner-controller and
the module.
20Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
For more information on configuring the I/O modules, see Configure the
Module on page 71.
Table 4
describes the connection types that you can use with FLEX 5000 analog
HART I/O modules.
Table 4 - Connections - HART I/O Modules
Description
Connection Type
Data
Listen Only
HART Input ModulesHART Output Modules
The module returns the following to the
owner-controller:
General fault data
Input data
When a Listen Only data connection is used, another controller owns the module.
A controller that makes a Listen Only connection to the module does not write
configuration for the module. It merely listens to the data exchanged with the ownercontroller.
IMPORTANT: If a controller uses a Listen Only connection, the connection must use the
Multicast option.
For more information on Listen Only connections, see Listen Only Mode
this case, all other connections to the module, for example, the connection to the
owner-controller must also use the Multicast option.
The module returns the following to the
owner-controller:
General fault data
Output data
on page 25. In
Data Types Available with FLEX 5000 Analog HART I/O Modules
The Module Definition includes a Data parameter that matches the module
type. Input modules use Input Data, and output modules use Output Data.
The available Data parameter choices are as follows:
•5094-IF8IH and 5094-IF8IHXT – The Input Data choice is either Analog,
Analog and Discrete, or Discrete.
•5094-OF8IH and 5094-OF8IHXT – The Output Data choice is always
Analog.
For more information on the Connection and Data parameter choices
available with FLEX 5000 I/O modules, see the Studio 5000 Logix Designer
application.
Requested Packet Interval
The Requested Packet Interval (RPI) is a configurable parameter that defines a
specific rate at which data is exchanged between the owner-controller and the
module.
You set the RPI value during initial module configuration and can adjust it as
necessary after module operation has begun. Valid RPI values for analog HART
I/O modules are 0.2…750 ms. Valid RPI values for HART devices are
500…9999.9 ms.
Rockwell Automation Publication 5094-UM007B-EN-P - October 202021
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
IMPORTANT
If you change the RPI while the project is online, the connection to the
module is closed and reopened in one of the following ways:
• You inhibit the connection to the module, change the RPI value, and
uninhibit the connection.
• You change the RPI value. In this case, the connection is closed and
reopened immediately after you apply the change to the module
configuration.
For more information on guidelines for specifying RPI rates, see the
Logix 5000 Controllers Design Considerations Reference Manual, publication
1756-RM094
.
Connection Over an EtherNet/IP Network
During module and connected HART device configuration, you must
configure the Connection over EtherNet/IP parameter. The configuration
choice dictates how input data is broadcast over the network.
The FLEX 5000 analog HART I/O modules use one of the following methods to
broadcast data:
•Multicast - Multicast connections deliver information from one sender
to multiple receivers simultaneously.
Copies of one transmission are passed to a selected subset of possible
destinations.
•Unicast - Unicast connections are point-to-point transmissions between
a source node and destination node on the network.
A transmission is sent to one destination controller depending on the
module configuration.
Unicast is the default setting. We recommend that you use Unicast because it
reduces network bandwidth usage. However, if you are using a ControlLogix
5580 High Availability controller, you must use multicast.
Multicast is more efficient than sending multiple unicast streams to multiple
notes. Use multicast in the following situations:
•FLEX 5000 I/O is used in a Redundancy application
•Communication is with multiple destinations
IMPORTANTWhen using a ControlLogix 5580 High Availability controller, a HART
modules occupies 1 multicast connection and HART devices occupy up
to 4 multicast connections. These connections total a maximum of 5
connections per HART module and limits the adapter to a maximum of 6
HART modules.
22Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
You can verify how many multicast connections are on your network by looking at
your adapter Diagnostic Overview web page.
Input Module OperationLogix 5000 controllers do not poll the FLEX 5000 analog input modules for
input data. Instead, the input modules send their input data, that is channel
and status data, at the RPI.
At the RPI, not only does the module send input data to the controller, but also
the controller sends data to the module inputs. For example, the controller
sends data to command the module to unlatch alarms or enable alarms.
FLEX 5000 analog input modules reside in a FLEX 5000 I/O system that is
accessible to a Logix 5000 controller over an EtherNet/IP network. A
FLEX 5000 EtherNet/IP adapter is the first component in a FLEX 5000 I/O
system and connects the system to the EtherNet/IP network.
FLEX 5000 analog input modules communicate input data to the FLEX 5000
EtherNet/IP adapter at the defined RPI. The input data consists of channel and
status data.
At the RPI, the following events occur.
1. The remote analog input module scans its channels for input data.
2. The module sends the data to the FLEX 5000 EtherNet/IP adapter.
3. The FLEX 5000 EtherNet/IP adapter in the FLEX 5000 I/O system sends
the data over the EtherNet/IP network.
4. One of the following:
• If the controller is directly connected to the EtherNet/IP network, it
receives the input data immediately.
• If the controller is connected to the EtherNet/IP network through
another communication module, the module sends the data to its
backplane and the controller receives it.
Output Module OperationThe controller sends data to an output module at the RPI or after an
Immediate Output (IOT) instruction is executed.
Rockwell Automation Publication 5094-UM007B-EN-P - October 202023
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
The RPI defines when the controller sends data to the FLEX 5000 analog
output module and when the output module reads back data. The controller
sends data to an output module only at the RPI.
At the RPI, not only does the controller send data to the output module, but
also the output module sends data to the controller. For example, the output
module sends an indication of the channel data quality.
FLEX 5000 analog input modules reside in a FLEX 5000 I/O system that is
accessible to a Logix 5000 controller over an EtherNet/IP network. A
FLEX 5000 EtherNet/IP adapter is the first component in a FLEX 5000 I/O
system and connects the system to the EtherNet/IP network.
FLEX 5000 analog output modules receive output data from a controller. The
output module also sends data to the controller.
Controller to Remote Analog Output Module Data Transmission
The controller broadcasts data to its local backplane at one of the following:
•RPI
•An IOT instruction is executed.
IMPORTANT
An IOT instruction sends data to all output modules in the system
immediately, and resets the RPI timer.
Based on the RPI rate and the length of the controller program scan, the output
module can receive and readback data multiple times during one program
scan.
When the RPI is less than the program scan length, the output channels can
change values multiple times during a program scan. The owner-controller
does not depend on the program scan to complete to send data.
These events occur when the controller sends data to a FLEX 5000 output
module.
1. Data is sent in one of the following ways:
• If the controller is directly connected to the EtherNet/IP network, it
broadcasts data to the network.
In this case, skip to step 3
.
• If the controller is connected to the EtherNet/IP network via a
communication module, the controller transmits the data to the
backplane.
In this case, proceed to step 2.
2. The EtherNet/IP communication module transmits the data to the
EtherNet/IP network.
3. The FLEX 5000 EtherNet/IP adapter in the FLEX 5000 I/O system
receives the data from the network and transmits it to the backplane.
4. The remote analog output module receives the data from the backplane
and behaves as dictated by its configuration.
24Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
Remote Analog Output Module to Controller Data Transmission
When a FLEX 5000 analog output module receives new data and the requested
data value is present on the RTB, the output module sends, or reads back a data
value back to the controller and to the rest of the control system. The data value
corresponds to the signal present at its terminals. This feature is called Output
Readback.
In addition to the Output Readback, the output module sends other data to the
controller at the RPI. For example, the module alerts the controller if a short
circuit condition exists on the module.
The following events occur when a remote FLEX 5000 analog output module
sends data to the controller at the RPI.
1. The module sends the data to the backplane.
2. The FLEX 5000 EtherNet/IP adapter in the FLEX 5000 I/O system sends
the data over the EtherNet/IP network.
3. One of the following:
• If the controller is directly connected to the EtherNet/IP network, it
receives the input data from the network without need for a
communication module.
• If the controller is connected to the EtherNet/IP network through
another communication module, the module transmits the data to its
backplane and the controller receives it.
Listen Only ModeAny controller in the system can listen to the data from an I/O module. An
owner-controller, as described in Ownership
analog I/O modules.
Other controllers can use a Listen Only connection with the analog I/O
module. In this case, the ‘listening’ controller can only listen to input data or
output readback data. The listening controller does not own the module
configuration or exchange other data with the module.
During the I/O configuration process, you can specify a Listen Only
connection. For more information on Connection options, see Input Module
Definition on page 76.
IMPORTANT
Remember the following:
• If a controller uses a Listen Only connection, the connection must use
the Multicast option. In this case, all other connections to the module,
for example, the connection of the owner-controller, must also use the
Multicast option.
• If a controller attempts to use a Listen Only connection to a module but
the owner-controller connection uses the Unicast option, the attempt at
a Listen Only connection fails.
The ‘Listen Only’ controller receives data from the module as long as a
connection between an owner-controller and module is maintained.
• If the connection between an owner-controller and the module is
broken, the module stops sending data and connections to all ‘listening
controllers’ are also broken.
• Connected HART devices cannot be added to Listen Only connections.
on page 19, exchanges data with
Rockwell Automation Publication 5094-UM007B-EN-P - October 202025
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
Protected OperationsTo maintain the secure operation of your FLEX 5000 analog HART I/O module,
operations that can disrupt module operation are restricted based on the
module operating mode. Table 5
Table 5 - Protected Operations on FLEX 5000 Analog HART I/O Modules
Current Module Operation
Connection not runningAccepted
Connection running
Firmware update is in processRejected
Calibration is in process
(1) A module calibration request is accepted when the module is connected and the owner-controller is in Program mode.
(2) The module accepts the requests and changes listed. Keep in mind, when the request or change is made, the calibration process is automatically aborted. We recommend that you wait for
the module calibration to finish before attempting any of the requests or changes.
(3) When the request is made through the Module Properties dialog box.
(4) Only requests for Listen Only connections are accepted.
(5) Configuration change is accepted in the following scenarios:
- Changes are made in the Module Properties dialog box and you click Apply.
- Changes are made in the Configuration tags and you send a Reconfigure Module MSG to the module.
(6) The difference between Rejected and Not allowed is that rejected activities can be attempted in the Studio 5000 Logix Designer application but do not take effect. The activities that are not
allowed, that is, attempts to change the Connection or Data Format used, do not occur in the Studio 5000 Logix Designer application.
For example, if you attempt to reset a module that is connected to the owner-controller, the Studio 5000 Logix Designer application executes the request and alerts you that it was rejected.
If you attempt to change the data format on a module that is connected to an owner-controller, the Studio 5000 Logix Designer application does not execute the attempted change. The
application only alerts you that the change is not allowed. In the case, if the change is attempted online, the Module Definition dialog box field that changes the data format is disabled.
(7) The change occurs after the connection is closed and reopened. You can close and reopen the connection in the following ways:
- Change the project while it is offline and download the updated project before going online again.
- Change the project while it is online and click Apply or OK in the Module Properties dialog box. In this case, before the change is made, a dialog box alerts you of the ramifications before
the change is made.
Firmware
Update
Request
Rejected
Accepted
Module Reset
Request
(1)
(2)
Module
Calibration
(3)
Request
Connection
Request
Accepted
describes the restrictions.
Activity
Configuration
Change
(4)
Accepted
(5)
Connection or
Data Format
Change
Not allowed
(6)
Electronic
Keying
Change
Accepted
RPI Change
(7)
HART Device OperationBefore using the HART capabilities, be sure that:
•the I/O module and the associated field device are working properly in
the analog 4…20 mA mode.
•the channel is configured as 4…20 mA range with HART enabled.
•the field device is HART capable.
•no more than one HART field device is connected to each channel.
•Notch Filter of input channel or Ramping Rate of output channel is set to
a valid value.
Input data of HART device, that is device status, dynamic, or device variable
values and status, are sent to Logix Controller at the RPI.
At the RPI, not only does the module send input data of the HART devices to
the controller, but also the controller sends data for the HART devices to the
module. For example, the controller sends data to reset Configuration
Changed status or initiate an execution of a pre-configured HART command.
IMPORTANTIf you switch the controller to Program mode or inhibit an output
module, it may cause the output channels to de-energize and the HART
device to not power up.
To power up the HART device, switch the controller to Run mode and
uninhibit the output module.
26Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
Protected Operations for
HART Devices
To maintain the secure operation of your HART device, operations that can
disrupt module operation are restricted based on the module operating mode.
Table 6
describes the restrictions.
Table 6 - Protected Operations on HART Devices
Activity
Current Module Operation
Connection not runningAccepted
Connection runningRejected
(1) Device Configuration change is accepted if changes are made using FTD/DTM, handheld device, and HART commands.
(2) The difference between Rejected and Not allowed is that rejected activities can be attempted in the Studio 5000 Logix Designer application but do not take effect. The activities that are not
allowed, that is, attempts to change the Connection or Data Format used, do not occur in the Studio 5000 Logix Designer application.
For example, if you attempt to reset a module that is connected to the owner-controller, the Studio 5000 Logix Designer application executes the request and alerts you that it was rejected.
If you attempt to change the data format on a module that is connected to an owner-controller, the Studio 5000 Logix Designer application does not execute the attempted change. The
application only alerts you that the change is not allowed. In the case, if the change is attempted online, the Module Definition dialog box field that changes the data format is disabled.
(3) The change occurs after the connection is closed and reopened. You can close and reopen the connection in the following ways:
- Change the project while it is offline and download the updated project before going online again.
- Change the project while it is online and click Apply or OK in the Module Properties dialog box. In this case, before the change is made, a dialog box alerts you of the ramifications before the
change is made.
- RPI changes applied to one channel applies the same change to all channels in the configuration section.
Device Reset
Request
Connection
Request
Device Configuration
Change
(1)
Accepted
Device Connection or
Data Format Change
Not allowed
(2)
Electronic Keying
Change
(3)
Accepted
RPI Change
Rockwell Automation Publication 5094-UM007B-EN-P - October 202027
Chapter 2 Analog HART I/O Module Operation in a Logix 5000 Control System
Notes:
28Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
Chapter 3
Common I/O Module Features
Top icPa ge
Software Configurable29
Fault and Status Reporting30
Module Inhibiting30
Electronic Keying31
Producer/Consumer Communication31
Status Indicators32
Use CIP Sync Time with I/O Modules32
Module Firmware32
Common Analog Channel Features33
This chapter describes module features that are available on both FLEX 5000
HART input and output modules.
FLEX 5000 analog HART input modules convert an analog signal to a digital
value. For example, the modules can convert the following:
•Volts
•Milliamps
You can configure FLEX 5000 HART input modules to support digital input
signals when your application requires channel to channel isolation. The
following types of discrete device types are supported:
•Digital Input
•IEC 61131-2 Type 3-d Digital Input
For information on digital input points, see Chapter 5
FLEX 5000 analog HART output modules convert a digital value to an analog
signal. For example, the modules can convert the following:
•Volts
•Milliamps
FLEX 5000 analog HART enabled modules decodes HART information from
signal embedded within the channel.
Software ConfigurableYou use the Studio 5000 Logix Designer application to configure the module,
monitor system operation, and troubleshoot issues. You can also use the
Studio 5000 Logix Designer application to retrieve the following information
from any module in the system:
•Serial number
Rockwell Automation Publication 5094-UM007B-EN-P - October 202029
Chapter 3 Common I/O Module Features
•Firmware revision information
•Product code
•Vendor
•Error and fault information
•Diagnostic information
By minimizing the need for tasks, such as setting hardware switches and
jumpers, the software makes module configuration easier and more reliable.
Fault and Status ReportingThe FLEX 5000 analog HART I/O modules report fault and status data along
with channel data. Fault and status data is reported in the following ways:
•Studio 5000 Logix Designer application
•Module status indicators
For more information on fault reporting, see the individual module feature
chapters and Appendix A, Troubleshoot Your Module
on page 107.
Module InhibitingModule inhibiting lets you indefinitely suspend a connection, including Listen
Only connections, between an owner-controller and an analog I/O module
without removing the module from the configuration. This process lets you
temporarily disable a module, such as to perform maintenance.
IMPORTANT
You can use module inhibiting in the following ways:
•You write a configuration for an I/O module but inhibit the module to
help prevent it from communicating with the owner-controller. The
owner does not establish a connection and the configuration is not sent
to the module until the connection is uninhibited.
•In your application, a controller already owns a module, has downloaded
the configuration to the module, and is exchanging data over the
connection between the devices.
You can use module inhibiting in these instances:
•You want to update an analog I/O module, for example, update the
module firmware revision. Use the following procedure.
a. Inhibit the module.
b. Perform the update.
c. Uninhibit the module.
•You use a program that includes a module that you do not physically
possess yet. You do not want the controller to look for a module that does
not yet exist. In this case, you can inhibit the module in your program
until it physically resides in the proper slot.
Once a module is inhibited, the connections to the module and attached
HART devices are also closed and the CIP messaging to the HART
devices is disabled.
To see where to inhibit a FLEX 5000 analog HART I/O module, see page 77
30Rockwell Automation Publication 5094-UM007B-EN-P - October 2020
.
Loading...
+ 124 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.