External Dynamic Brake Kit
Installation Instructions
1
30.0
(1.18)
17.0
(0.67)
13.0
(0.51)
L1 L2 L3
316.0
(12.44)
60.0
(2.36)
335.0
(13.19)
AK-R2-091P500
AK-R2-047P500
AK-R2-360P500
I
61.0
(2.40)
31.0
mm
(in.)
(1.22)
386.0
(15.20)
59.0
(2.32)
405.0
(15.94)
AK-R2-030P1K2
AK-R2-120P1K2
2
0V
DC+
O
DC–
3
AC Drive
50.8 mm
(2.0 in.)
M5 x 0.8
(#10-24)
0V

Three-Phase
4
5
AC Input
AC Drive
AC Drive
(Input Contactor) M
R (L1)
S (L2)
Power O
T (L3)
Power On
BR1
BR+
BR2
BR-
Thermostat
Connectors
M
M
Power Source DB Resistor Thermostat
ATT ENT ION :
Resistor temperature may exceed 200
!
degrees C.
!
ATT ENT ION : AC drives do not offer protection for externally mounted brake resistors,
especially in the case of brake IGBT failure. A risk of fire exists if external braking
resistors are not protected. External resistor packages must be protected from over
temperature or the protective circuit shown, or equivalent, must be supplied.
Thermostat Contact Rating: 125 VAC, 15 A, Opens at 227 °C (440 °F) Closes at 182 °C (359 °F)
Application Cross-Reference
Drive and Motor
Size
kW (HP) Part Nu mber
100…120 Volt AC Input Drives
0.75 (1) AK-R2-091P500 91 0.08617218% 100% 23% 150% 31%
1.1 (1.5) AK-R2-091P500 91 0.086 17 164% 100% 16% 148% 11%
200…240 Volt AC Input Drives
0.37 (0.5) AK-R2-091P500 91 0.086 17 293% 100% 46% 150% 31%
0.75 (1) AK-R2-091P500 91 0.08617218% 100% 23% 150% 15%
1.5 (2) AK-R2-091P500 91 0.086 17 109% 100% 11% 109% 11%
2.2 (3) AK-R2-047P500 47 0.166 33 144% 100% 15% 144% 11%
4 (5) AK-R2-047P500 47 0.166 33 79% 79% 11% N/A N/A
5.5 (7.5) AK-R2-030P1K2 30 0.26 52 90% 90% 10% N/A N/A
7.5 (10) AK-R2-030P1K2 30 0.26 52 66% 66% 10% N/A N/A
11 (15) See Note 3 15 0.52 104 90% 90% 10% N/A N/A
15 (20) See Note 3 15 0.52 104 66% 66% 10% N/A N/A
400…480 Volt AC Input Drives
0.37 (0.5) AK-R2-360P500 360 0.086 17 305% 100% 47% 150% 31%
0.75 (1) AK-R2-360P500 360 0.086 17 220% 100% 23% 150% 15%
1.5 (2) AK-R2-360P500 360 0.086 17 110% 100% 12% 110% 11%
2.2 (3) AK-R2-120P1K2 120 0.26 52 197% 100% 24% 150% 16%
4 (5) AK-R2-120P1K2 120 0.26 52 124% 100% 13% 124% 10%
5.5 (7.5) AK-R2-120P1K2 120 0.26 52 90% 90% 10% N/A N/A
7.5 (10) AK-R2-120P1K2 120 0.26 52 66% 66% 10% N/A N/A
11 (15) See Note 3 60 0.52 104 90% 90% 10% N/A N/A
15 (20) See Note 3 60 0.52 104 66% 66% 10% N/A N/A
600 Volt AC Input Drives
0.37 (0.5) AK-R2-360P500 360 0.086 17 274% 100% 46% 150% 31%
0.75 (1) AK-R2-360P500 360 0.086 17 251% 100% 23% 150% 15%
1.5 (2) AK-R2-360P500 360 0.086 17 172% 100% 11% 150% 8%
2.2 (3) AK-R2-120P1K2 120 0.26 52 193% 100% 24% 150% 16%
4 (5) AK-R2-120P1K2 120 0.26 52 185% 100% 13% 150% 9%
5.5 (7.5) AK-R2-120P1K2 120 0.26 52 141% 100% 9% 141% 7%
7.5 (10) AK-R2-120P1K2 120 0.26 52 103% 100% 7% 103% 7%
11 (15) See Note 3 60 0.52 104 141% 100% 9% 141% 7%
15 (20) See Note 3 60 0.52 104 103% 100% 7% 103% 7%
Note 1: Always check resistor ohms against minimum resistance for drive being used.
Note 2: Duty cycle listed is based o n full speed to zero speed deceleration.
For constant regen at full speed, duty c ycle capability is half of what is listed.
Application Type 1 represents maximum capability up to 100% braking torque where possible.
Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
Resistance
Ohms ±5%
Continuous PowerkWMax Energy
kJ
Max Braking
Torq ue
% of Motor
Application Type 1 Application Type 2
Braking Torque
% of Motor
Note 3: For 11 and 15 kW (15 and 20 HP) normal duty external resistor applications, use two
7.5 kW (10 HP) size resistors wired in parallel.
Duty Cycle%Braking Torque
% of Motor
www.rockwellautomation.com
Duty Cycle
%
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street,
/
Middle East/Africa: Rockwell Automati
Europe
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
on,
Pegasus Park, De Kleetlaan 12a,
Publication RA-IN004B-EN-P – April 2011
Supersedes RA-IN004A-EN-P – Januar y 2003 Copyright © 2011 Rockwell Automation, Inc. All rights reserved.
Milwaukee, WI 53204-2496 USA,
1831 Diegem, Belgium,
Tel:
(1) 414.382.2000, Fax: (1) 414.382.4444
Tel: (32) 2 663 0600, Fax: (32) 2 663 0640