Plug-In Jumper
Querverbindung
Connexion transvrsale
Plug-In Jumper, 2-pole, red 1492-CJLJ6-2-R 60
Plug-In Jumper, 3-pole, red 1492-CJLJ6-3-R 60
Plug-In Jumper, 10-pole, red 1492-CJLJ6-10-R 20
Plug-In Jumper, 41-pole, red 1492-CJLJ6-41-R 10
Plug-In Jumper, 2-pole, blue 1492-CJLJ6-2-B 60
Plug-In Jumper, 3-pole, blue 1492-CJLJ6-3-B 60
Plug-In Jumper, 10-pole, blue 1492-CJLJ6-10-B 20
Markers
Verbindermarkierer
Repérage de blocs de jonction 1492-M6X10 200
Power Supply
24 V DC Output
15 W 1606-XLP15E
30 W 1606-XLP30E
50 W 1606-XLP50E
100 W 1606-XLP100E
120 W (5 A) 1606-XLE120E
Accessories / Zubehör / Accessoires
Thermocouple, Type K
931H-T2C1D-DC
Installation Instructions
Beipackinformation
Notice d’utilisation
DIR 10000043421
(Version 00)
1. General instructions
• Disconnect power prior to installation
• Installation only by Qualified personnel
• Follow all applicable local and national electrical codes
During range selection, appropriate safety
measures against electrostatic discharge (ESD)
are to be considered.
2. Application
The Type K Thermocouple conditioner is designed to
galvanically isolate and convert thermoelectric voltages into
standard signals 0(4) ...20 mA and 0 ... (5)10 V.
(see enclosure).
3. Configuration
Set the DIP switches according to the table printed on
the enclosure (factory setting 0 ... 20 mA).
4. Mounting, electrical connection
The signal conditioners are mounted on standard TS35
rails and fixed in position by a suitable end bracket.
For terminal assignments see enclosure.
Wire cross-section max. 2.5 mm
2
.
ATEX - Approval Rockwell Automation
UL DEMKO 09 ATEX 147279X 1201South Second Street
T II 3G Ex nAnL IIC T4 Milwaukee, Wi 53204
U.S.A.
UL Class 1, Division 2 Markings
for selected Signal Conditioners
A. “This equipment is suitable for use in Class I, Division 2,
Groups A, B, C and D hazardous locations or nonhazardous locations only or the equivalent.”
B. “WARNING: EXPLOSION HAZARD - Substitution of
components may impair suitability for use in Class I,
Division 2 environments.”
C. “WARNING: EXPLOSION HAZARD - The area must be
known to be nonhazardous before servicing/replacing
the unit and before installing or removing I/O wiring.”
D. “WARNING: EXPLOSION HAZARD - Do Not disconnect
equipment unless power has been disconnected and
the area is known to be nonhazardous.”
FOR INSTALLATION IN CLASS I, ZONE 2 LOCATIONS:
E. This equipment is to be installed into suitable enclosure,
providing a degree of protection not less than IP 54 in
accordance with IEC 60529 unless the apparatus is
intended to be afforded an equivalent degree of protection by location.
Do not disconnect while circuit is live unless area is known
to be non hazardous. The enclosure for the installation of
English
Input data
Input (fixed)
Output data
Output
(selectable)
Load resistance
Output current
Output voltage
Accuracy
(incl. linearization and cold junction compensation)
Thermo Type
Typ K, 0...1000 °C
Temperature coefficent
Response time
General data
Supply voltage
Current carrying capacity
of the connection between
connections 3 and 5:
Power consumption
Operating temperature
Storage temperature
Dimensions L/W/H mm
Coordination of insulation acc. to DIN EN50178, 04/98
Rated voltage
Rated surge voltage
Overvoltage category
Contamination class
* Tu 20 °C
Thermocouple as in EN 60584-1
Type K, 0...1000 °C
0...10V / 4...20mA
/ 0…5V
0...20mA (factory setting)
< 400 Ohm @ power supply ≥ 24 Vdc
> 10 kOhm
< 0.6 % of selected range
< 250 ppm/K of selected range
< 0.7 sek
24 Vdc (±10%)
100 mA
approx. 0.6 W
0...+55 °C
-25 °C...+85 °C
88 / 98 / 6.1
100 V
500 V
III
2
6. Technical data*