Rockwell Automation 900-TC8 User Manual

Disconect power to device before installing or servicing. Do not touch the terminals of controller when voltage is applied. Do not allow metal fragments or lead wire scraps to fall inside this product. This may cause electric shock, fire or malfunction.
Temperature/ Process Controller
Model 900-TC8
(Series B)
English
10000022590 (Version 00) Printed In China
For detailed operating instructions, please refer to the 900-TC8 User's Manual (900-UM007_-EN-E). It can be found online at http://www.ab.com/manuals/.
Significance of CAUTIONS
Indicates information that, if not heeded, could result in injury,
ATTENTION
damage to the product, or faulty operation.
RE1
3091739-6A
Do not use this product where subject to flammable or explosive gas. This product is UL listed as Open Type, Listed Process Control Equipment and must be mounted in an enclosure. More than one disconnect switch may be required to de-energize the equipment before servicing. Signal inputs are SELV, limited energy. Caution - To reduce risk of fire or Electrical shock, Do not interconnect the outputs of different Class 2 circuits. Never disassemble, repair or modify the product. The life expectancy of the output relays varies greatly with the switching capacity and other switching conditions. Always use the output relays within their rated load and electrical life expectancy. If an output relay is used beyond its life expectancy, its contacts may become fused or burned. Use copper wire only 24-14 AWG stranded or solid. Torque screws to 0.74 to 0.90 Nm or 6.5 to 8 lb-in. Only two wires of same type and size per terminal. Correctly set the temperature controller settings to match the control target. If the settings are not compatible with the control target, the product may operate in an unexpected manner, resulting in damage to the product or an accident. To maintain safety in the event of malfunction of the temperature controller, we recommend taking safety measures, for example, installing an excessive temperature rise prevention alarm on a separate line. If malfunction prevents control, they may result in an accident. To reduce the risk of electrical shock or fire, install in a Pollution Degree 2 environment (controlled environment relatively free of contaminants). If the semiconductor (Triac) output is used and an excessive electrical surge or noise spike is impressed on the output terminals, a short circuit failure of the triac output is likely to occur. This could result in excessive current draw and possible fire. Use surge suppression to prevent excessive surges and fusing to help prevent an over current condition.
When the product is used under the circumstances or environment below, ensure adherence to limitations of the ratings and functions. Also, take countermeasures for safety precautions such as fail-safe installations.
* Use under circumstances or environment which are not described in the instruction manual.
* Use for applications where death or serious property damage is possible and extensive safety
precautions are required.
Installation
Dimensions
Dimensions (mm)
48
96
Watertight
* The internal components (e.g. circuit boards) of the controller can be removed from the case without removing the terminal wiring.
* Do not remove the terminal block. Doing so may result in failure or malfunction.
packing
79.2
6
78
2
44
112
Terminal
Adapter
cover
In the pack:
• Main unit
• Watertight packing
• Adapter
• Instruction manual
• Terminal cover
91
Solderless terminal size: M3.5
Names of parts on front panel
• Mode key Press this key to change the contents of the display. Press this button for 1 s or longer for reverse scroll.
• Group key Use this key to change groups:
• Press the key and the key together for at least 3 seconds to switch to protect group .
Function key/Auto/Manual key
Press this function key to operate the function set with the PF Setting.
Operation menu
Input type
Input type
Platinum resistance thermometer
Thermocouple
Temperature input type
Infrared
Thermosensor
Analog input
Thermocouple
• The default is “5” (shaded). will be display when a platinum resistance thermometer is mistakenly connected while input
type is not set for it. To clear the display, correct the wiring and cycle the power supply.
Input type
Current input
Voltage input
Analog
input type
• The default is “0” (shaded).
Alarms
Setting
0
No alarm function
1
1
*
1
*
1
*
Deviation upper/lower limit
Deviation upper limit
2
3
Deviation lower limit
4
Deviation upper/lower range
Deviation upper/lower limit
5
standby sequence ON
Deviation upper limit
6
standby sequence ON
Deviation lower limit
7
standby sequence ON
8
Absolute value upper limit
9
Absolute value lower limit
Absolute value upper limit
10
standby sequence ON
Absolute value lower limit
11
standby sequence ON
LBA (only for alarm 1)
12
13 PV Change Rate Alarm
1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
*
different types of alarm. These are indicated by the letter "L" and "H".
• Default = "2" (shaded)
JPt100
10 - 70°C
60 - 120°C 115 - 165°C 140 - 260°C
0 - 50mV
4 - 20mA 0 - 20mA
1 - 5V 0 - 5V
0 - 10V
Alarm type
Input
Pt100
K
J
T
E L
U
N R S B
W
PLII
Input
Setting
–200 to 850 (°C)
0
–199.9 to 500.0 (°C)
1
0.0 to 100.0 (°C)
2
–199.9 to 500.0 (°C)
3
0.0 to 100.0 (°C)
4
–200 to 1300 (°C)
5
–20.0 to 500.0 (°C)
6
–100 to 850 (°C)
7
–20.0 to 400.0 (°C)
8
–200 to 400 (°C)
9
–199.9 to 400.0 (°C)
10
-200 to 600 (°C)
11
–100 to 850 (°C)
12
–200 to 400 (°C)
13
–199.9 to 400.0 (°C)
14
–200 to 1300 (°C)
15
0 to 1700 (°C)
16
0 to 1700 (°C)
17
100 to 1800 (°C)
18
0 to 90 (°C)
19
0 to 120 (°C)
20
0 to 165 (°C)
21
0 to 260 (°C)
22
Use the following ranges for scaling: –1999 to 9999,
23
–199.9 to 999.9, Vary Depending on "L", "H" value
24
0 to 2300 (°C) 0 to 1300 (°C)
25
Setting
0
Use the following ranges for scaling: –1999
1
to 9999, –199.9 to 999.9, –19.99 to 99.99,
2
–1.999 to 9.999
3 4
Positive alarm value (X)
Error display (trouble shooting)
When an error has occurred, the No.1 display shows the error code. Take necessary action according to the error code, referring the table below.
No.1 display
If the input value exceeds the display limit (–1999 to 9999), though it is within the control range, [[[[ will be displayed under –1999 and above 9999. Under these conditions, control output and alarm output will operate normally. Refer to "900-TC User's Manual" for details of control range.
2: Error shown only for"Process value / Set point". Not shown for other status.
*
(S. Err)
(E333)
(E111 )
Meaning
Input error
*2
A/D converter error
*2
Memory error
Check the wiring of inputs, disconnections, shorts and input type.
After the correction of A/D converter error, turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise.
Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise.
Alarm output function
LH
ON OFF
SP
ON OFF
SP
X
ON OFF
SP
LH
ON OFF
SP
LH
ON OFF
SP
ON OFF
SP
X
ON OFF
SP
ON OFF
0
ON OFF
0
ON OFF
0
ON OFF
0
Action
Setting range
/ -300 to 1500 (°F) / -199.9 to 900.0 (°F) / 0.0 to 210.0 (°F) / -199.9 to 900.0 (°F) / 0.0 to 210.0 (°F) / -300 to 2300 (°F) / 0.0 to 900.0 (°F) / -100 to 1500 (°F) / 0.0 to 750.0 (°F) / -300 to 700 (°F) / -199.9 to 700.0 (°F) / -300 to 1100 (°F) / -100 to 1500 (°F) / -300 to 700 (°F) / -199.9 to 700.0 (°F) / -300 to 2300 (°F) / 0 to 3000 (°F) / 0 to 3000 (°F) / 300 to 3200 (°F) / 0 to 190 (°F) / 0 to 240 (°F) / 0 to 320 (°F) / 0 to 500 (°F)
/ 0 to 3200 (°F) / 0 to 2300 (°F)
Setting range
Negative alarm value (X)
Output off
Vary with "L", "H" values
X
Vary with "L", "H" values
Vary with "L", "H" values
X
X
X
X
X
X
ON OFF
SP
X
ON OFF
SP
X
ON OFF
SP
X
ON OFF
SP
X
ON OFF
0
X
ON OFF
0
X
ON OFF
0
X
ON OFF
0
Status at error
Control
Alarm
output
Operates
OFF
as above the
upper limit.
OFF
OFF
OFF
OFF
ATTENTION
Mounting
Individual mounting (mm) Side-by-side mounting (mm)
Waterproofing is impossible with side-by-side installation. When waterproofing is required, fit watertight packing on the backside
+0.6
of front panel.
45
0
120 min
This is a class A product.
In residential environment areas it may cause radio interference, in which case the user may be required to
• No.1 display Process value or set data symbol
• No.2 display Set point, set data read-out value or changed input value
• No. 3 display
MV, Soak Time Remain, and Multi-SP.
• Up and Down keys Use the keys to change the values displayed on the No.2 display. Each press of key increments or advances the values displayed on the No.2 display. Each press of key decrements or returns the values displayed on the No.2 display.
Initial setting group
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
3: Refer to the adjoining tables for details of input types and alarm types.
*
4: Applicable only to models with alarm functions.
*
5: Operation is stopped when moved to the initial setting group.
*
(control/alarm are both stopped.)
*6
: The grayed-out parameters may not be displayed according to the model and
parameter.
7: This function is supported by models with heater burnout / short detection.
*
(control/alarm are both stopped.)
Other functions
In addition to the aforementioned, there are alarm hysteresis, automatic return of display mode and others in the advanced setting group. Refer to "900-TC8 User's Manual" for details. For communications details, please refer to "900-TC communications User's Manual".
take adequate measures to reduce interference.
Operation stopped.(control/alarm are both stopped.)
3
Input Type *
Scaling Upper Limit (only when setting analog input)
Scaling Lower Limit (only when setting analog input)
Decimal Point (only when setting analog input)
Temperature Unit (C stands for Celsius, F for Fahrenheit)
SP Upper Limit
SP Lower Limit
PID ON/OFF In ON/OFF control = In 2-PID control =
Standard or Heating/Cooling Standard control = Heating and cooling control = (Select standard control or heating and cooling control as required)
ST (Self-tuning) ST ON =
ST OFF =
Program Pattern
Control Period (Heating) (Unit: Seconds)
Control Period (Cooling) (Unit: Seconds)
Direct/Reverse Operation
In Reverse operation (Heating) = In Direct operation (Cooling) =
Alarm 1 Type: Specified models only
Alarm 1 Hysteresis
Alarm 2 Type: Specified models only
Alarm 2 Hysteresis
Alarm 3 Type: Specified models only
Alarm 3 Hysteresis
Transfer Output Type
Transfer Output Upper Limit
Transfer Output Lower Limit
Linear Current Output
Extraction of Square Root Enable (Only when analog input is set)
Initial setting group enables users to specify their preferred operating conditions (input type, alarm type, control method, etc.)
°C= °F=
• Insert the main unit through the mounting hole in the panel (1-8 mm thickness). Insert the mounting brackets (supplied) into the fixing slots located on the top and bottom of the rear case.
0
+0.8
Alternately tighten the top and bottom screws on the mounting fixtures applying
92
equal pressure a little at a time until the rachet rotates freely.
• When more than one machine is installed, make sure that the ambient temperature does not exceed the specified limit.
Operation indicators
• SUB1: Auxiliary output 1 indicator Lit when the function assigned to auxiliary output 1 is
ON.
• SUB2: Auxiliary output 2 indicator Lit when the function assigned to auxiliary output 2 is
ON.
• SUB3: Auxiliary output 3 indicator Lit when the function assigned to auxiliary output 3 is
ON.
• HA: Heater burnout alarm/Heater short alarm/Heater overcurrent alarm indicator
Lit when a heater burnout alarm, heater short alarm, or heater overcurrent alarm has occurred.
• OUT1: Control output 1 indicator
Lit when control output 1 is ON and not lit when it's OFF. For a current output, lit except for a 0% ou
Hold down
for at least 3 seconds
(No. 1 display flushes
then the control stops)
Hold down
for at least
1 second
*3 *4
*3 *4
*3 *4
Hold and keys
down for at least 1 second
(1) This product is designed for indoor use only. Do not use this product in the following:
* Places directly subject to heat radiated from heating equipment. * Places subject to splashing liquid or oil atmosphere (exceeds NEMA 4X). * Places subject to direct sunlight, could discolor or cause excessive heat. * Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas). * Places where intense temperature changes exceed the published ratings. * Places subject to icing and condensation. * Places subject to vibration and large shocks.
(2) Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product. Do not block the ventilation holes on the product. (4) Be sure to wire properly with correct polarity of terminals. (5) Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. (6) Do not wire the terminals which are not used. (7) Allow as much space as possible between the controller and devices that generate a powerful
high-frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or
common wiring with the power lines when you are wiring to the terminals. (8) Use this product within the rated load and power supply. (9) Make sure that the rated voltage is attained within two seconds of turning the power ON. (10)
Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power
before starting actual control operations to ensure the correct temperature display.
(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON
before you turn the controller ON.
(12) Always turn power off. A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator, and must be marked as
a disconnecting means for this unit. (13) If you remove the controller from its case, or put the controller into its case, never touch nor
apply shock to the terminals and the electronic parts inside. Make sure the electronic components and the case are not contacted when inserting the internal mechanism. Always ensure power is OFF when doing any maintenance on the controller or associated circuits.
(14) Cleaning: Do not use paint thinner or the equivalent. Use standard grade alcohol to clean the
outside of the product.
(15) Consider the 2 second delay required for the controller outputs to respond when you design your
control system. (16) If an option unit is used in the system refer to its Installation Manual before operating. (17)
The output may turn OFF when shifting to certain levels. Take this into consideration when performing
control.
(18) The number of EEPROM write operations is limited. Therefore, use RAM write mode when frequently
overwriting data during communications or other operations.
Memory protection--EEPROM (non-volatile memory) (Number of write operations: 1,000,000)
Connections (The applicability of the electric terminals varies with the type of machine.)
NOTICE
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
(48 x number of units-2.5)
+1
0
0
+0.8
92
• OUT2: Control output 2 indicator Lit when control output 2 is ON and not lit when it's OFF.
• STOP: control stop indicator Lights when event input or “Run/Stop” is stopped during operation. During control stop, functions other than control output are valid.
• CMW: communications writing enable/ disable indicator Lights when communications writing is “enabled” and is out when it is “disabled”.
Control output 1
Relay output
250 VAC, 5A (resistive load)
Voltage output (for driving SSR)
12 VDC, 40 mA
Current output
0 to 20 mA DC 4 to 20 mA DC Load: 600 Ωmax.
Control output 2
Voltage output (for driving SSR)
12 VDC, 21 mA
Triac relay output 250 VAC, 3 A (resistive load)
Auxiliary output
Relay outputs
250 VAC, 3 A (resistive load)
• Since the voltage output (control output 1) is not electrically insulated from the internal wiring, one or other of the control output terminals must be left unearthed when using an earthed (grounded) type thermocouple thermometer. (Connection makes measurements unreliable due to ground loop currents.) Basic insulation is provided between the voltage outputs (control output 2) and internal circuits.
1, 2, 3
Input power supply
Control output 1
Auxiliary output 3
Auxiliary output 2
Auxiliary output 1
tput.
The setting data for the 900-TC-8 is shown here as an example.
*5
POWER ON
Operation group
PV/SP
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
Protect group
Set point during SP ramp
Heater Current 1 Value Monitor (Unit: A) *7
Leakage Current 1 Value Monitor (Unit: A) *7
Program start
Soak time remain
Run/Stop When control start =
When control stop =
Alarm value 1 *4
Alarm value upper limit 1
Alarm value lower limit 1
Alarm value 2 *4
Alarm value upper limit 2
Alarm value lower limit 2
Alarm value 3 *4
Alarm value upper limit 3
Alarm value lower limit 3
Operation group should normally be used during operations.
Operation / Adjustment Protect
Initial Setting /
Communication Protect
Setting Change Protect
PF Key Protect
Move to Protect Group
Restricts which parameters can be displayed or changed, and restricts change by key operation.
*4
*4
*4
*4
*4
*4
Hold and keys
down for at least
Press
(less than 1 second)
3 seconds
Protection function
Protection function is to prevent unwanted settings. It restricts the parameter to be used
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------------------
Operation / Adjustment protection
The following table shows the relationship between settings and protect limits related to Operation group and Adjustment group.
Operation group
Adjustment group
Initial setting/Communications protection
This protect level restricts movement to the initial setting group, communications setting group and advanced function setting group.
Set value
Parameter change protection
Parameter changes by key operation are restricted.
PF Key operation can be enabled or disabled.
AT (auto-tuning)
• AT in Adjustment group
Designate " : 100% AT execute" or " : 40% AT execute" to execute AT and " : AT cancel" to.
“100%AT Execute”
Also when AT execution ends, the display automatically returns to “ ”.
“AT cancel”
“ ” flashes
U
D
Specifications
Power supply voltage 100-240VAC type 24V AC/DC type Operating frequency 50-60Hz Operating voltage range 85 to 110% of the rated voltage Power consumption Approx. 10VA (AC100-240V) Approx. 5.5VA (AC24V) Approx. 4W (DC24V) Indication accuracy (Ambient temperature: 23°C) (±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max. Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2 % FS ±1 digit max. Event input Contact input No-contact input ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max. Control output 1 Relay output: SPST-NO, 250 VAC, 5A(resistive load) Voltage output: 12 VDC, 40 mA Current output: 4 to 20 mA DC, and 0 to 20 mA DC load: 600 ohms max. Electrical life of relay: 100,000 operations Control output 2 Voltage output: 12 VDC, 21 mA Triac output: SPST-NO, 250 VAC, 3A(resistive load) Electrical life of relay: 1 million operations Control method ON/OFF or 2-PID control Auxiliary output Relay output: SPST-NO, 250 VAC, 3 A(resistive load), electrical life: 100,000 operations Ambient temperature –10 to 55 C (Avoid freezing or condensation) Ambient humidity RH 25 to 85% Storage temperature –25 to 65 C (Avoid freezing or condensation) Altitude Max. 2,000m Recommended fuse T2A, 250V AC, time-lag, low-breaking capacity Weight Approx. 260g (main unit only) Degree of protection Front panel: Type 4X (UL50)
IP66 (IEC 61010-1)
The temperature controller is mounted on the flat surface of an enclosure that is rated and marked “Type 4X for Indoor Use Only Installation environment Installation category II, pollution degree 2 (as per IEC61010-1) Transfer output 4 to 20 mA DC Load 600 ohms max.
1
11
12
2
+
3
13
4
-
14
5
15
6
16
7
17
8
18
9
19
10
20
Adjustment group
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
Group
Initial setting
group
Event Inputs
EV2
EV1
CT1
CT2
DO NOT USE
DO NOT USE
­+
TC/Pt multi-input
Process value Set point Others
Communications
RS-232C
RS-485
SD11 RD12 SG13
+
Control Output 2
-
DO NOT USE
A
DO NOT
+
USE
B B
Only the value set to the “ : Temperature Input Shift” parameter is applied to the entire temperature input range. When the process value is 200 °C, the process value is treated as 201.2 °C after input shift if the input shift value is set to 1.2 °C. The process value is treated as 198.8 °C after input shift if the input shift value is set to –1.2 °C.
Adjustment Group
AT Execute/Cancel
100%AT Execute 40%AT Execute
Heater Current 1 Value Monitor (Unit: A) *7
Heater Burnout Detection 1 (Unit: A) *7
Heater Overcurrent Detection 1 (Unit: A)
Leakage Current 1 Value Monitor (Unit: A) *7
HS Alarm 1 (Unit: A) *7
Temperature Input Shift (Unit:゜C or ゜F )
Upper Limit Temperature Input Shift Value when 2 point input shift is selected
Lower Limit Temperature Input Shift Value when 2 point input shift is selected
Proportional Band
Integral Time (Unit: secs)
Derivative Time (Unit: secs)
mA
-
-
V
DO NOT USE
+
Analog input
Set value
123
0
○ ◎ ◎ ◎
Communications
setting group
0 1 2
OFF “ ”: Parameter can be changed by key operation ON “ ” : Parameter cannot be changed by key operation (“ ” will light.) (Protect group parameters can all be changed.)
PF key protection
OFF “ ”: PF Key enabled. ON “ ” : PF Key disabled.
Thermocouple:
output current: approx. 7 mA per contact. ON:1 k ohms max., OFF: 100 k ohms min.
Rear case: IP20. Terminal section: IP00
B (+)11 A (-)12
DO NOT USE13
• °C / °F : temperature unit The temperature unit is displayed
when the configured display value is a temperature.
When this parameter is set to “ °C”,
C
” is displayed, and when set to
“ “ °F”, “
F
” is displayed.
This flashes while ST(Self-Tuning) is activated.
• : Protection indicator Lit when Setting Change Protect is
ON (disables the Up and Down Keys).
• MANU: Manual output indicator Lit when the Auto/Manual Mode is set
to Manual Mode.
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
*6
Adjustment group is for entering set values and shift values for control.
Cooling Coefficient
Dead Band
Manual Reset Value (Unit: %)
Hysteresis (Heating)
Hysteresis (Cooling)
Soak Time
Wait Band
SP Ramp Set Value
MV Upper Limit
MV Lower Limit
MV Change Rate Limit
Extraction of Square Root Low-cut Point
: Can be displayed and changed : Can be displayed : Can not be displayed and change to other groups not possible
Default setting : 0 (shaded)
Advanced function
setting group
Default setting : 1 (shaded)
: Change to other groups possible : Change to other groups not possible
Loading...