Contents of the Ultra5000 Connector Kit

Wiring the CN1A and CN1B I/O Connectors

These instructions describe how to wire the I/O connectors for an Allen-Bradley the I/O connectors on the Ultra5000 drives are provided.
The Ultra5000 Connector Kit includes the following items:
Item Description Quantity
1 CN1A - 28 pin I/O connector plug (Weidmueller 174828) 1
2 CN1B - 14 pin I/O connector plug (Weidmueller 174821) 1
3 1/16 inch flat blade screwdriver 1
CN1A (28-pin) and CN1B (14-pin) are plugable, double-row, spring clamp I/O connectors with 3.5mm spacing. To wire I/O connections:
ATTENTION
!
Ultra5000™ Intelligent Positioning Drive. Pinouts for
The Ultra5000 drive contains stored energy devices. To avoid the hazard of electrical shock, verify that all voltages on the system bus network have been discharged before attempting to service, repair or remove this unit. Only qualified personnel familiar with solid state control equipment and safety procedures in publication NFPA 70E, Standard for Electrical Safety Requirements for Employee Workplaces, or applicable local codes should attempt this procedure.
1. Strip approximately 6 mm (0.25 in.) of insulation from the end of your I/O wires. Exercise caution not to damage wire strands as you remove the insulation. Maximum wire gauge for these connectors is 0.75 mm
2. With the flat blade screwdriver, depress the spring clamp next to the I/O pin you are preparing and insert the wire, as shown. Note: The connector is keyed by an offset bar on the drive. Verify proper orientation of the plug by temporarily attaching it to the I/O connector on the drive. Always remove the plug before inserting signal wires.
3. After removing the screwdriver, gently pull on each wire to ensure fastness. Re-insert any loose wires.
1 Publication 2090-IN005A-EN-P August 2002
2
(18 AWG).

Ultra5000 I/O Pinouts

The tables are arranged to match the drive’s I/O pin arrangement. Refer to the Ultra5000 Hardware Installation Manual (2098-IN001x-EN-P) for more information on these signals.
CN1A Connector CN1B Connector
Pin Signal Pin Signal Pin Signal Pin Signal
2
15 INPUT9 1 INPUT1
16 INPUT10 2 INPUT2
17 INPUT11 3 INPUT3 10 AIN2 3 AX-
18 INPUT12 4 INPUT4 11 +5VCOM 4 BX+
19 INPUT13 5 INPUT5 12 AOUT1 5 BX-
20 INPUT14 6 INPUT6 13 AOUT2 6 IX+
21 INPUT15 7 INPUT7 14 SHIELD 7 IX-
22 INPUT16 8 INPUT8
23 OUTPUT5 9 OUTPUT1
24 OUTPUT6 10 OUTPUT2
25 OUTPUT7 11 OUTPUT3
26 OUTPUT8+ 12 OUTPUT4
27 OUTPUT8- 13 SHIELD
28 IOCOM
1
The Ultra5000 0.5, 1.0, and 2.0 kW, and all 460V drives (2098-IPD-005-xx, 2098-IPD-010-xx, 2098-IPD-020-xx, and
2098-IPD-HVxxx-xx models) require a user supplied I/O power source.
2
High speed inputs.
1
14 IOPWR
8 +5VCOM 1 +5V
2
9 AIN1 2 AX+
1

Related Documentation

Documents cited contain additional information concerning related Allen-Bradley products or general information that may be helpful. To obtain a copy, contact your local Rockwell Automation office or distributor, or access the documents on-line at
www.theautomationbookstore.com www.ab.com/manuals/gmc
Allen-Bradley is a registered trademark of Rockwell Automation, Inc. Ultra5000 is a trademark of Rockwell Automation, Inc.
Publication 2090-IN005A-EN-P August 2002 PN 0013-2059-001-01
.
or
© 2002 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...