Rockwell Automation 2090-SRxxx User Manual

Installation Instructions
External Shunt Modules
Catalog Numbers 1394-SR9A, 1394-SR9AF, 1394-SR36A, 1394-SR36AF, 2090-SR120-09, 2090-SR040-09, 2090-SR040-18
Topic Page
About the External Shunt Modules 1 Important User Information 2 Catalog Number Explanation 3 Before You Begin 3 Install the External Shunt Module 13 Replace the Shunt Module Fuse 20 External Shunt Module Specifications 21 Additional Resources 22

About the External Shunt Modules

These externally-mounted passive shunt modules provide a means for servo drives to dissipate excess regenerative energy from the DC bus. This is needed when system loads require power dissipation beyond the capability of the shunt resistor internal to the servo drive. These are passive shunt resistors and require transistor activation by the servo drive.
A properly-sized shunt module regulates excessive bus voltage by passing current through a resistor, which dissipates the current as heat and minimizes drive faults caused by excess bus voltage.
Shunt Module Compatibility
Shunt Cat. No. Drive Cat. No.
2090-SR120-09 2098-xxx-HV030 and 2098-xxx-HV050 2090-SR040-09 2098-xxx-HV100 2090-SR040-18 2098-xxx-HV100 1394-SR9A 1394-SR9AF 1394-SR36A 1394-SR36AF
(1)
The 2094-BSP2 shunt module is mounted on the Bulletin 2094 power rail and provides connections to an external shunt module.
2094-BSP2 1394x-SJT22-x
(1)
and
2 External Shunt Modules
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 Automation sales office or online at http://literature.rockwellautomation.com some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell
) describes
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you to identify a hazard, avoid a hazard, and recognize the consequences.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Publication 2090-IN004B-EN-P — June 2008
External Shunt Modules 3
1394 - SR xxxx
Bulletin Number
SR = Shunt Resistor
kW Rating
9A = 300 W continuous, 4 Ω , no fan 9AF = 900 W continuous, 4 Ω , no fan 36A = 1800 W continuous, 4 Ω , no fan 36AF = 3600 W continuous, 4 Ω , fan-cooled, thermal switch
2090 - SR
xxx - xx
Bulletin Number
Resistance Rating
120 = 120 Ω 040 = 40 Ω
SR = Shunt Resistor
Continuous Power Rating
09 = 900 W continuous, no fan 18 = 1800 W continuous, no fan

Catalog Number Explanation

Catalog numbers consist of various characters, each of which identifies a specific version or option for that component. Use the catalog numbering charts below to understand the configuration of your shunt module.
Bulletin 1394 External Shunt Modules
Bulletin 2090 External Shunt Modules

Before You Begin

Before you begin mounting your shunt module, make sure you:
have the required tools and materials.
understand the mounting requirements.
understand high-frequency bonding.
know how to establish noise zones.

Required Tools and Materials

These tools and materials are required to complete the installation of an external shunt module:
Screwdrivers
User-supplied power wiring
Mounting fasteners
Publication 2090-IN004B-EN-P — June 2008
4 External Shunt Modules
ATTENTION

Mounting Requirements

Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry, which can result in damage to components.
These requirements apply when preparing to mount your shunt module:
Mo
unt the shunt in an enclosure providing protection against dust and splashing water (IP54), or dust free and protected against water jets (IP65).
Many NEMA (National Electrical Manufacturers Association)
ype 4 cabinets provide this level of protection.
T
Install
the panel for mounting your system components inside the enclosure on a flat, rigid, vertical surface that won’t be subjected to shock, vibration, moisture, oil mist, dust, or corrosive vapors.
Refer to
Environmental Specifications on page 21 for specific
recommendations.
Maintain minimum clearances for proper airflow, easy module
access, and proper bend radius for the cables as shown in the figures beginning on page 5
.
Use high-frequency (HF) bonding techniques to connect the
module, enclosure, machine frame, and motor housing, and to provide a low-impedance return path for high-frequency (HF) energy and reduce electrical noise.
Refer to HF Bonding Your Shunt Module, on page 6, for more information.
Publication 2090-IN004B-EN-P — June 2008
Se
gregate DC-bus wiring from control wiring and motor feedback cables. Do not run shunt wiring in wireways. Use twisted pair cable from the drive to external shunt module.
Refer to
Establishing Noise Zones, beginning on page 6, for
specific recommendations.
IMPORTANT
Mount the shunt module in an upright position. Do not mount the
150 mm (6.0 in.) clearance
for airflow and installation.
150 mm (6.0 in.) clearance
for airflow and installation.
150 mm (6.0 in.) clearance for airflow and installation.
150 mm (6.0 in.) clearance
for airflow and installation.
Enclosure
Bulletin 1394 and 2090 External Shunt Modules (1394-SR9Ax module is shown in this example.)
BURN HAZARD
ATTENTION
shunt module on its side.
Minimum Clearance Requirements (within an enclosure)
Shunt Module
ALLEN-BRADLEY
R
BULLETIN 1394 300W SHUNT MODULE CAT. PART SER. INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
External Shunt Modules 5
The shunt resistors can reach temperatures in excess of 350 °C (662 °F). Do not handle a shunt module that has been operational until it has cooled sufficiently.
Combustible materials above the shunt module or its enclosure may need the protection of a metal plate to shield them from the heat.
Failure to observe these precautions could result in damage to surrounding materials, possibly leading to a fire or personal injury.
The shunt resistors release large amounts of heat. When mounted inside an enclosure, you must provide adequate ventilation so the maximum ambient temperature of 50 °C (122 °F) is not exceeded. Failure to observe this precaution could result in damage to the module.
Publication 2090-IN004B-EN-P — June 2008
6 External Shunt Modules
1394 Digital Servo Controller
3600W Shunt Module
BULLETIN 1394 3600W SHUNT MODULE
ALLEN-BRADLEY
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
CAT. PART SER. INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
R
150 mm (6.0 in.) clearance for airflow and installation.
150 mm (6.0 in.) clearance
for airflow and installation.
150 mm (6.0 in.) clearance
for airflow and installation.
254 mm (10.0 in.) clearance for airflow and installation.
Bulletin 1394 and 2090 External Shunt Modules (1394-SR36Ax module is shown in this example.)
IMPORTANT
Minimum Clearance Requirements (outside the enclosure)

HF Bonding Your Shunt Module

Bonding is the practice of connecting metal chassis, assemblies, frames, shields, and enclosures to reduce the effects of electromagnetic interference (EMI). For more information on the concept of high-frequency (HF) bonding, the ground plane principle, and electrical noise reduction, refer to System Design for Control of Electrical Noise Reference Manual, publication
To improve the bond between the drive system and subpanel, construct your subpanel out of zinc plated (paint-free) steel.
GMC-RM001.

Establishing Noise Zones

This table provides the zoning requirements of cables connecting to the external shunt module.
Zone Method
Wire/Cable
COL, DC+ (shielded option) X X COL, DC+ (unshielded option) X Thermal switch X X Fan (if present) X
Very Dirty
Dirty Clean
Ferrite Sleeve
Shielded
Cable
Publication 2090-IN004B-EN-P — June 2008
External Shunt Modules 7
C
D
D
D
D
D
VD
C
VD
D
1394 Digital Servo Controller
300W Shunt Module
BULLETIN 1394 300W SHUNT MODULE
ALLEN-BRADLEY
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
CAT. PART SER.
INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
R
(1)
Line Interface Module
Kinetix 6000 Drive System
Dirty Wireway
Clean Wireway
Motor Power Cables
Very Dirty Connections Segregated
(not in wireway)
Customer-supplied
Metal Enclosure
150 mm (6.0 in.)
clearance, min on all four
sides of the shunt module.
Enclosure
2094-BSP2 Shunt Module
Shunt DC-bus Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, two twists per foot, min (3rd choice).
Metal Conduit (where required by local code)
I/O and Feedback Cables
Shunt Thermal Switch and Fan Wires (when present)
No sensitive
equipment within
150 mm (6.0 in.).
Route 24V DC I/O shielded cable.
Route encoder/analog/registration
shielded cables.

Noise Zones for Kinetix 6000 Drives

Observe these guidelines when mounting your external shunt module outside the enclosure:
Mount circuit components and wiring in the very dirty zone or
in an externally shielded enclosure. Run shunt DC-bus and fan wiring inside metal conduit to minimize the effects of EMI and RFI.
Mount resistors (other than metal-clad) in a shielded and
ventilated enclosure outside the cabinet.
Keep unshielded wiring as short as possible. Keep shunt DC-bus
wiring as flat to the cabinet as possible.
Route thermal switch and fan wires separate from shunt DC-bus.
External Shunt Module Mounted Outside the Enclosure
Publication 2090-IN004B-EN-P — June 2008
8 External Shunt Modules
C
D
D
D
D
D
VD
C
VD
1394 Digital Servo Controller
300W Shunt Module
BULLETIN 1394 300W SHUNT MODULE
ALLEN-BRADLEY
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
CAT. PART SER. INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
R
D
Line Interface Module
Kinetix 6000 Drive System
Dirty Wireway
Clean Wireway
Motor Power Cables
Enclosure
2094-BSP2 Shunt Module
I/O and Feedback Cables
150 mm (6.0 in.)
clearance, min on all four
sides of the shunt module.
Shunt Thermal Switch and Fan Wires (when present)
Very Dirty Connections Segregated
(not in wireway)
Shunt DC-bus Wiring Methods:
Twisted pair in conduit (1st choice). Shielded twisted pair (2nd choice). Twisted pair, two twists per foot, min (3rd choice).
No sensitive
equipment within
150 mm (6.0 in.).
Route 24V DC I/O shielded cable.
Route encoder/analog/registration
shielded cables.
When mounting your shunt module inside the enclosure, follow these additional guidelines:
Metal-clad modules can be mounted anywhere in the dirty zone,
but as close to the Kinetix 6000 system as possible.
Shunt DC-bus wires can be run with motor power cables.
Keep unshielded wiring as short as possible. Keep shunt wiring
as flat to the cabinet as possible.
Separate shunt DC-bus cables from other sensitive, low voltage
signal cables.
External Shunt Module Mounted Inside the Enclosure
Publication 2090-IN004B-EN-P — June 2008
Loading...
+ 16 hidden pages