Rockwell Automation 193-592-EC1, 193-592-EC3, 193-592-EC5 User Manual

E3 and E3 Plus Solid-State
A
Overload Relay
Quick Start Guide
(Bulletins 193 and 592)
2
ATTENTION
!
This guide does not replace the User Manual, publication 193-UM002_-EN-P, and is intended for qualified service personnel responsible for setting up and servicing these devices. You must have previous experience with and a basic understanding of electrical terminology, configuration procedures, required equipment, and safety precautions. The user manual can be downloaded from http://
literature.rockwellautomation.com.
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes, and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Rockwell Automation publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley distributor), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
3
IMPORTANT
IMPORTANT
IMPORTANT
IMPORTANT
General Precautions
In addition to the specific precautions listed throughout this manual, the following general statements must be observed.
The purpose of this publication is to serve as a guide for proper installation. The National Electrical Code and any other governing regional or local code overrules the information in this publication.A hazard of personal injury/equipment damage exists if codes are ignored during installation. Rockwell Automation cannot assume responsibility for the compliance or proper installation of the E3 Overload Relay or associated equipment.
Only personnel familiar with the E3 Overload Relay and associated machinery should plan to install, start up, and maintain the system. Failure to comply may result in personal injury/equipment damage.
An incorrectly applied or installed E3 Overload Relay can result in damage to the components or reduction in product life. Wiring or application errors, such as incorrectly configuring the FLA Setting, supplying incorrect or inadequate DeviceNet supply voltage, connecting an external supply voltage to the input or thermistor terminals, or operating/storing in excessive ambient temperatures may result in malfunction of the E3 Overload Relay.
The E3 Overload Relay contains ESD (electrostatic discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to Allen-Bradley publication 8200-4.5.2, Guarding Against Electrostatic Damage, or any other applicable ESD protection handbook.
Publication 193-QR003B-EN-P - October 2009
4
Introduction
Follow these steps to successfully commission the E3 Overload Relay:
Table 1: Commissioning Procedure
Step Description
1 Hardware Installation
2 Wiring Installation
3 DeviceNet Commissioning
4 Setup Requirements
– Typical Motor Connections – External Current Transformer Applications (193-EC_ZZ or 592-EC_ZZ) – External Ground Fault Sensor Applications (193-EC3_ _ , 592-EC3_ _ and 193-EC5_ _ , 592-EC5_ _)
Setup for Bulletin 193 or 592-EC1/EC2/EC3/EC5 Overload Relay
– Protective Trip and Warning Summaries – Parameter Group Listing
Setup for Cat. No. 193-EC4 Current Monitor Relay
– Trip and Warning Summaries – Parameter Group Listing
Hardware Installation
1
2
CLICK
3
The following figures illustrate the starter assembly instructions.
Starter Assembly Instructions
Figure 1: 100-C09…C43 Starter Assembly Instructions (for use with Cat. Nos.
193-EC_ _B and -EC_ _D)
/tN
22 lb-in.
5
Publication 193-QR003B-EN-P - October 2009
6
1
2
/tN
35 lb-in.
Figure 2: 100-C60…C85 Starter Assembly Instructions (for use with Cat. No.
193-EC_ _E).
Figure 3: 100-D95...D860 Starter Assembly Instructions (for use with Cat. Nos.
193-EC_ _F, 193-EC_ _G, and 193-EC_ _H).
7
Publication 193-QR003B-EN-P - October 2009
8
E3 PLUS
LED Status Indicators
DeviceNet Port
Input Terminals
Test/Reset Button
Node Address Switches (Series B and later)
Output and PTC Terminals
Ground Fault Sensor Input
Voltage Input Module Connection (193/592 EC5 only)
Wiring Installation
Typical Motor Connections
Refer to the product nameplate or user manual for power lug termination information including:
Terminal wire size and torque specifications
Maximum wire lengths
Lug kit catalog numbers (108…1250 A)
For reliable input signal processing, input wiring should be routed in raceways separate from power cabling.
Terminal Designations
Figure 4: E3 and E3 Plus Feature Overview
Control Terminals
The following table defines the E3 Overload Relay control terminal designations.
Table 2: Control Terminal Designation
9
Ter mi na l
Designation
1 IN 1 General-purpose sinking input number 1 2 IN 2 General-purpose sinking input number 2 3 IN 3 General-purpose sinking input number 3 ➊➋ 4 IN 4 General-purpose sinking input number 4 ➊➋ 5V+ 6V+ 7 IN 5 General-purpose sinking input number 5 8 IN 6 General-purpose sinking input number 6
13/14 OUT A Output A 23/24 OUT B Output B ➊➋ 95/96 Trip Relay Trip Relay
IT1/IT2 PTC Thermistor (PTC) input ➊➍
S1/S2 External ground fault sensor input ➋➎
Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2and 193/592-EC3). Available only on cat. nos. 193/592-EC5_ _.An earth ground connection to this terminal will assist in obtaining compliance with electromagnetic
compatibility requirements.
The use of shielded cable is recommended for the positive PTC thermistor circuit to assist in obtaining
compliance with electromagnetic compatibility requirements.
Available only on cat. nos. 193/592-EC3_ _ and 193/592-EC4_ _.
Reference Description
+24V DC supply for inputs
End Earth Ground
DeviceNet Terminals
The following table defines the DeviceNet connector terminal designations.
Table 3: DeviceNet Terminal Designation
Terminal Signal Function Color
1 V- Common Black 2 CAN_L Signal Low Blue 3 Drain Shield Non-insulated 4 CAN_H Signal High White 5 V+ Power Supply Red
Publication 193-QR003B-EN-P - October 2009
10
ATTENTION
!
Grounding
The following grounding recommendations are provided to ensure electromagnetic compatibility compliance during installation:
The earth ground terminal of the E3 Overload Relay shall be connected to a solid
earth ground via a low-impedance connection
Installations employing an external ground fault sensor shall ground the cable shield
at the sensor with no connection made at the E3 Plus Overload Relay
The PTC thermistor cable shield shall be grounded at the E3 Plus Overload Relay
with no connection made at the opposite end
Wiring Diagrams
When working on energized circuits, do not rely on the voltage and current information provided by the E3 and E3 Plus for personal safety. Always use a portable voltage or current measurement device and measure the signal locally.
Figure 5: Three-Phase D.O.L & Single-Phase Wiring Diagrams
L1 L2 L3
Voltage Input Module
(For 193/592-EC5 only)
Three-Phase Direct-On-Line
Wiring Diagram
L2 L3
L1
E3/E3Plus
2/T1 4/T2 6/T3
T1T2T3
M
S.C.P.D.
Single-Phase Full-Voltage
Wiring Diagram
L1
L1 L2 L3
L1 L2 L3
E3/E3Plus
E3/E3Plus
E3/E3Plus
2/T1 4/T2 6/T3
2/T1 4/T2 6/T32/T1 4/T2 6/T3
2/T1 4/T2 6/T3
2/T1 4/T2 6/T3
T1
T2
M
L2
L1 L2
Voltage Input Module
(For 193/592-EC5 only)
11
IMPORTANT
IMPORTANT
IMPORTANT
Parameter 27, Single/Three Ph, should be set to single-phase for single-phase devices and three-phase for three-phase devices.
In single-phase devices, traditional single-phase wiring (connecting T2 to L3) will result in a vector imbalance of current flowing through the E3 Plus Overload Relay. This will result in inaccurate ground fault reporting and protection.
External Current Transformer Application (Cat. No. 193-EC_ZZ)
E3 and E3 Plus Overload Relays (Cat. No. 193-EC_ZZ) are designed for use with separately mounted, customer-supplied current transformers (CTs) as required in higher-current applications. The FLA setting range is 9…5000 A for these units, with a legal setting range per the user’s manual. Parameter 78, CT Ratio, is provided for setting the current transformer ratio to be installed.
Current Transformer Specifications
The 193-EC_ZZ Overload Relays are intended for use with a CT having a secondary current rating of 5 A. The installer shall provide one CT for each motor phase and shall connect the CT secondary leads to the appropriate E3 Overload Relay power terminals as shown in Figure 7: on page 13. The CT shall have an appropriate ratio rating as detailed in the user’s manual. Additionally, the CT shall be selected to be capable of providing the required VA to the secondary load, which includes the E3 Overload Relay burden of 0.1 VA at the rated secondary current and the wiring burden.
Finally, the CT shall be rated for protective relaying to accommodate the high inrush currents associated with motor startup and shall have an accuracy of range.
±2% over its normal operating
ANSI (USA) Class C5 B0.1 CSA (Canada) Class 10L5 IEC (Europe) 5 VA Class 5P10
The improper selection of a current transformer can result in the E3 Overload Relay reporting inaccurate motor operational data and possible motor damage. The selected current transformer must be rated for protective relaying applications.
Publication 193-QR003B-EN-P - October 2009
12
IMPORTANT
6x
6x
OR
y
C
t
s
d
y
Installation Instructions
Cat. No. 193-EC_ZZ Overload Relays are designed to be installed in cat. no. 193-ECPM2 panel mount adapters and connected to separately mounted current transformers. For a panel mount adapter assembly, refer to the instructions included with the panel mount adapter. The E3 Overload Relay must be mounted a distance equal to, or greater than, six times the cable diameter (including insulation) from the nearest current-carrying conductor or current transformer. For applications employing multiple conductors per phase, the diameter of each cable should be added and multiplied by six to determine the proper placement distance for the E3 Overload Relay.
Figure 6: Cat. No. 193-EC_ZZ Overload Relay Mounting Placement
Primar
urren
Transformer
E3 Overloa Rela
Placement of the E3 Overload Relay closer than the recommended distance of six times the cable diameter may compromise its current reporting and protection capabilities.
13
C
3
3
3E3
/2
3
/4
T
/1
/3
L
3/6
/1
3/5
y
C
t
s
y
C
t
s
Figure 7: External CT Connection Diagrams
IE
Primar
urren
Transformer
L
L2
L1
E
T1
T2
Primar
urren
Transformer
L
L2/3L
L1
T1/2T2/4T
T
External Potential (Voltage) Transformer Application (Cat. No. 193/592-EC5_ _)
The E3 Plus Overload Relay Catalog Number 193/592-EC5_ _ can be used with external step-down potential transformers (PTs). The PT ratio is programmed into the E3 Plus by entering the primary winding rating into Parameter 289, PT Pri, and the secondary winding rating into Parameter 290, PT Sec. The voltage mode is also programmed into the E3 Plus by selecting the appropriate mode in Parameter 156, Vol t Mode. The E3 Plus will support Wye, Delta, and Open Delta voltage modes with potential transformers.
Publication 193-QR003B-EN-P - October 2009
14
Load
L1 L2 L3
Line
N/GND
L1 L2 L3
Wye Connection with PTs
Load
L1 L2 L3
Line
L1 L2 L3
Open Delta Connection with PTs
Figure 8: External PT Connection Diagrams
Line
L1 L2 L3
L1 L2 L3
Delta Connection with PTs
Load
15
External Ground Fault Sensor Application (Cat. Nos. 193/592-EC3_ _, 193/592-EC4_ _, and 193/592-EC5_ _)
Cat. Nos. 193/592-EC3_ _, 193/592-EC4_ _, and 193/592-EC5_ _ E3 Plus Overload Relays are intended to provide ground fault protection when used with the cat. no. 193-CBCT external ground fault (core balance) sensor. The ground fault sensor mounts separately from the E3 Plus Overload Relay and must be placed within three meters of the relay. The customer-supplied cable for wiring the ground fault sensor to the E3 Plus Overload Relay should meet the specifications outlined in Table 1.9 on page 15.
_
Table 1.9 Ground Fault Sensor Terminals (S1 and S2)
Wire type Shielded, twisted pair Cross section
Tor q ue
0.2…4.0 mm
0.55 N
2
(#24…12 AWG)
m (5 lb-in.)
Power Cable Installation Instructions
1. All power cables (including the neutral when used) must pass through the sensor window. The equipment ground conductor (the conductor used to carry the non-current-carrying metal parts of equipment, as defined by Article 100 of the NEC), must not pass through the sensor window.
2. The power cables through the sensor window should be straight, tightly bundled, centered in the window, and perpendicular to the sensor for a length equal to, or greater than, six times the cable diameter (including insulation) from the sensor.
3. All other conductors with available currents in excess of 1,000 A should be placed a distance equal to, or greater than, six times the cable diameter (including insulation) from the sensor.
4. The power cables of the branch circuit to be protected by the E3 Plus Overload Relay must not be grounded on the load side of the ground fault sensor.
5. If the power cables are enclosed in a conducting jacket, the jacket must be grounded on the line side of the sensor. The jacket must not pass through the sensor window, but must be cut at the window and joined with a conductor that passes outside the sensor window.
6. The power system may be solidly grounded or grounded through an impedance at its source as long as the impedance allows a magnitude of fault current to flow that is within the 1…5 A operational range of the E3 Plus Overload Relay (193/592-EC2_ _) or the 20 mA…5 A operational range of the E3 Plus Overload Relay (193/ 592-EC3
_ _, 193/592-EC4_ _, and 193/592-EC5_ _).
Publication 193-QR003B-EN-P - October 2009
16
IMPORTANT
MOTOR
L1 L2
L3
S1
S2
S1 S2
193-CBCT_
Ground
Fault
Sensor
E3 Plus
Overload Relay
Figure 10: Ground Fault Sensor Mounting Placement
GF Sensor
90˚
Power Cables
6x
6x
Figure 11: Power Cable Configuration — Two Cables per Phase
1
L3 L1
1
L2 L2
L1
L3
The spacer is a short (approximately 10 times the cable diameter in length) piece of cable with no connections to any terminal.
Figure 12: Ground Fault Sensor Wiring to the E3 Plus Overload Relay
The shield of the twisted pair cable must be connected to earth ground at the sensor, with no connection made at the E3 Plus Overload Relay.
17
IMPORTANT
DeviceNet Node Commissioning
Overview
E3 Overload Relays are shipped with a default software node address (MAC ID) setting of 63 and the data rate set to Autobaud. Each device on a DeviceNet network must have a unique node address which can be set to a value from 0…63.
Keep in mind, most DeviceNet systems use address 0 for the master device (scanner) and node address 63 should be left vacant for introduction of new slave devices. The node address and data rate for series B or later, E3 Overload Relays can be changed using software or by setting the hardware switches that reside on the front of each unit. While both methods yield the same result, it is good practice to choose one method and deploy it throughout the system.
The following recommendations are intended to ensure a trouble-free startup and operation:
1. Use the node commissioning tool in RSNetWorx or the DeviceNet configuration terminal (cat. no. 193-DNCT) when modifying the E3 node address. Do not use the General tab found in the product window in RSNetWorx. The node commissioning tool ensures the device goes through a hard reset and requires the user to upload the most current parameter information from the device prior to making configuration changes.
2. Ensure you have the most current configuration information prior to saving an RSNetWorx configuration file.
3. If you intend to employ the ADR function of the DeviceNet scanner, ensure the device configuration is as you intend it BEFORE saving it to memory.
4. Be aware the Restore Device Defaults button in RSNetWorx will reset the E3 Overload Relay node address setting to 63. For Series B or later devices, the hardware node address switches take precedence over the software node address setting.
Publication 193-QR003B-EN-P - October 2009
18
Figure 13: Node Address Switches
Table 2: Node Address Setting
Switch Settings Description
0…63 The node address setting is determined by the switch values when set in this range. 64…99 For switch settings in this range, the node address setting is determined by the software
99 Factory default setting.
Note: For node address switch values in the range of 0…63, cycle power to the E3 Overload Relay to initialize the new setting.
setting using the RSNetWorx for DeviceNet configuration tool.
Setup Requirements
Setup for Cat. Nos. 193/592-EC1/EC2/EC3/EC5 Overload Relays
After the E3 Overload Relay is installed according to the guidelines specified in this manual, apply power to the overload relay’s DeviceNet connector. After applying power, the following sequence should occur:
1. The Trip relay should close 2.35 seconds later and the TRIP/WARN LED will not flash (unless a Non-Volatile Fault previously existed or a fault condition is present).
2. At the same time, the NETWORK STATUS LED should flash green for approximately two seconds, then red for a 1/4 second. If autobaud is enabled and the E3 Overload Relay is connected to an active network, the green LED will continue to flash once the baud rate has been determined. If the E3 Overload Relay is not connected to an active network, the LED will not continue to flash.
3. Once the E3 Overload Relay has been allocated by a master, the NETWORK STATUS LED will turn solid green.
After being powered up, use the DeviceNet Configuration Terminal (Cat. No. 193-DNCT) in order to set up the parameters. There are five basic parameters that need to be established before using the protective functions. These parameters are listed under the OVERLOAD SETUP menu and include: Single/Three Phase, Full Load Current (FLA) Setting, Trip Class, Overload/PTC Reset mode, and Overload Reset Level. (Note: You will need to program additional parameters when customer-supplied CTs are used.)
Once these parameters are set, the E3 Overload Relay is functional. Use the ADVANCED SETUP menu to set other parameters per the specific application requirements.
Protective Trip/Warning Summaries & Parameter Group Listing (Cat. Nos. 193/592-EC1/EC2/EC3/EC5)
Table 3: Trip Summary
19
Tri p
Function
Overload Enabled ➋➋Trip Class
Phase Loss Enabled ➌➌0.1…25.0 s 1.0 s 0…250 s 0 s Ground Fault
(193/592-EC2) Ground Fault
(193/592-EC3) Stall Disabled 100…600% 600% 0…250 s➎10 s ——
Jam Disabled 50…600% 250% 0.1…25.0 s 5.0 s 0…250 s 10 s Underload Disabled 10…100% FLA ➏50% 0.1…25.0 s 5.0 s 0…250 s 10 s
PTC Disabled — Current
Imbalance Comm Fault Enabled — Comm Idle Disabled — Remote Trip Disabled — Voltage Input
Module Hardware Fault
Undervoltage L-L
Overvoltage L-L ➐ Disabled 0...65535 500 0.1…25.0 s 1.0 s 0…250 s 10 s
Tri p Enable Factory Default
Disabled Internal 1…5 A 2.5 A 0.0…25.0 s 0.5 s 0…250 s 10 s
Disabled External
Disabled 10…100% 35% 0.1…25.0 s 5.0 s 0…250 s 10 s
Disabled —
Disabled 0...65535 1 00 0.1…25.0 s 1.0 s 0…250 s 10 s
Trip Level Settings Trip Delay Settings Inhibit Time
Range Default Range Default Range Default
Tri p Cl ass10——
0.02…5 A
5…30
2.5 A 0.0…25.0 s 0.5 s 0…250 s 10 s
Settings
Voltage Unbalance
Phase Rotation ➐ Disabled 1…2 1 0…250 s 10 s
Under Frequency
Over Frequency ➐ Disabled 0…250 63 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Real Power
Over Real Power
Disabled 0…100 75 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…250 57 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Publication 193-QR003B-EN-P - October 2009
20
Table 3: Trip Summary
Tri p
Function
Under Consumed kVAR
Over Consumed kVAR
Under Generated kVAR
Over Generated kVAR
Under Power kVA
Over Power kVA ➐ Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Under Power Factor Lagging
Over Power Factor Lagging
Under Power Factor Leading
Over Power Factor Leading
The inhibit time setting parameters are applicable to both the trip and warning functions. FLA Setting range and default values are dependent upon the current rating of the product. See the user
manual for more information.
Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not
user-adjustable.
Must use Ground Fault Sensors (Cat. No. 193-CBCT_).Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the
programmed Stall Trip Level, stall protection is disabled.
50…100% for devices with FRN 1.003 and earlier.Available on 193/592-EC5 only.
Tri p
Enable Factory Default
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -32767…0 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -32767…0 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…32767 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -100…0 -90 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -100…0 -95 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0...100 90 0.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0...100 95 0.1…25.0 s 1.0 s 0…250 s 10 s
Trip Level Settings Trip Delay Settings Inhibit Time
Range Default Range Default Range Default
Settings
Table 4: Warning Summary
21
Warning Function
Overload Disabled 0…100% 85% — Phase Loss — Ground Fault (193/592-EC2) Disabled Internal 1…5 A2.0 A 0…250 s 10 s
Ground Fault (193/592-EC3) Disabled External
Stall — Jam Disabled 50…600% 150% 0…250 s 10 s Underload Disabled 10…100% 70% 0…250 s 10 s Thermistor (PTC) Disabled — Current Imbalance Disabled 10…100% 20% 0…250 s 10 s Comm Fault Disabled — Comm Idle Disabled — Voltage Input Module
Hardware Fault r
Under Voltage L-L r Disabled 0...65535 400 0…250 s 10 s Over Voltage L-L Disabled 0...65535 490 0…250 s 10 s Voltage Unbalance Disabled 0…100 85 0…250 s 10 s Phase Rotation Disabled 1…2 1 0…250 s 10 s Under Frequency Disabled 0…250 58 0…250 s 10 s Over Frequency Disabled 0…250 62 0…250 s 10 s Under Real Power Disabled 0…32767 0…250 s 10 s Over Real Power Disabled 0…32767 0…250 s 10 s Under Consumed kVAR Disabled 0…32767 0…250 s 10 s Over Consumed kVAR Disabled 0…32767 0…250 s 10 s Under Generated kVAR Disabled -32767…0 0…250 s 10 s Over Generated kVAR Disabled -32767…0 0…250 s 10 s Under Power kVA Disabled 0…32767 0…250 s 10 s Over Power kVA Disabled 0…32767 0…250 s 10 s Under Power Factor Lagging Disabled -100…0 -95 0…250 s 10 s Over Power Factor Lagging Disabled -100…0 -90 0…250 s 10 s Under Power Factor Leading Disabled 0...100 95 0…250 s 10 s Over Power Factor Leading Disabled 0...100 90 0…250 s 10 s
Warning
Enable Factory Default
Enabled
Warning Level Settings Inhibit Time Settings
Range Default Range Default
0.02…5 A
2.0 A 0…250 s 10 s
The inhibit time setting parameters are applicable to both the trip and warning functions.Overload warning setting is entered as a percentage of the thermal capacity utilized.Must use Ground Fault Sensors (Cat. No. 193-CBCT_).50…100% for devices with FRN 1.003 and earlier.Available on 193/592-EC5 only.
Publication 193-QR003B-EN-P - October 2009
22
Table 5: Parameter Group Listing
Monitor Params
1 L1 Current
2 L2 Current 28 FLA Setting 53 Program Lock 25 Warning Enable 56 NonVol Baud Rate
3 L3 Current 29 Trip Class 54 Set to Defaults 27 Single/Three Ph 58 COS Mask
4 Average Current
5 L1 % FLA
6 L2 % FLA 78 CT Ratio 30 OL/PTC ResetMode 61 Assy Word0 Param 7 L3 % FLA 31 OL Reset Level 62 Assy Word1 Param 71 OutB Pr FltState 8 Average % FLA 32 OL Warning Level 63 Assy Word2 Param 72 OutB Pr FltValue
9 % Therm Utilized 33 PL Inhibit Time 64 Assy Word3 Param
10 GF Current 34 PL Trip Delay
11 Current Imbal 35 GF Inhibit Time
12 OL Time To Trip 36 GF Trip Delay 13 OL Time To
Reset 37 GF Trip Level 14 Trip Status 38 GF Warn Level 15 Warning Status 39 Stall Enbld Time 16 Trip Log 0 40 Stall Trip Level 17 Trip Log 1 41 Jam Inhibit Time 18 Trip Log 2 42 Jam Trip Delay 19 Trip Log 3 43 Jam Trip Level 20 Trip Log 4 44 Jam Warn Level 21 Device Status 45 UL Inhibit Time 22 Firmware 46 UL Trip Delay 23 Dev Config 47 UL Trip Level 90 Warn Log 0 48 UL Warn Level 91 Warn Log 1 49 CI Inhibit Time 92 Warn Log 2 50 CI Trip Delay 93 Warn Log 3 51 CI Trip Level 94 Warn Log 4 95 Elapsed Time 78 CT Ratio 96 Starts
Counter 83 IN 1 Assignment 97 Starts
Available 84 IN 2 Assignment 98 Time To Start 85 IN 3 Assignment
Series C (FRN 4.00 and higher)
Overload
Setup Reset/Lock Advanced Setup
27 Single/
Three Ph 26 Trip Reset 24 Trip Enable 55 AutoBaudEnable 65 OutA Pr FltState 79 Comm Override
30 OL/PTC
ResetMode 103 Test Enable* 28 FLA Setting 59 Output Assembly
31 OL Reset
Level 104 Clear Queue* 29 Trip Class 60 Input Assembly
52 CI Warn Level
86 IN 4 Assignment 87 2-Spd Net Enable 88 2-Speed FLA Set 89 GF Trip Inhibit 99 Starts/Hour 100 Starts Interval 101 PM - # Starts
102 PM - Oper. Hours
105 GF Warn Delay
106 GF Sensing Range
DeviceNet
Setup
Output
Setup DeviceLogix
66 OutA Pr
FltValue 67 OutA DN
FltState 81 Net outputs 68 OutA DN
FltValue
69 OutA DN
IdlState
70 OutA DN
IdlValue
73 OutB DN
FltState
74 OutB DN
FltValue
75 OutB DN
IdlState
76 OutB DN
IdlValue
80 Network
Override
82 Net Out COS
Mask
23
Table 6: Parameter Group Listing, Continued
Trip Snapshot
Device
Logix
79 Comm
Override 132 Trip History 0 144 SS L1 Current 160 V Trip Status 156 Volt Mode 173 L1 Real Power 157 Power Scale
80 Network
Override 133 Trip History 1 145 SS L2 Current 161 V Warn Status 158 V Trip Enable 174 L2 Real Power 225 PW Trip Enable 81 Net outputs 134 Trip History 2 146 SS L3 Cu rrent 162 L1-L2 Voltage 159 V Warn Enable 175 L3 Real Power 226 PW Warn Enable 82 Net Out COS
Mask 135 Trip History 3 147 SS %TCU 163 L2-L3 Voltage 215 UV Inhibit Time 176 Total Real Power 241 UW Inhibit Time
o Series C (FRN 5.00 and Higher)
193/592-EC5 Only
Tri pWa rn History
136 Trip History 4 148 SS GF Current 164 L3-L1 Voltage 216 UV Trip Delay 177 L1 Reactive Power 242 UW Trip Delay 137 Warn History 0 149 SS L1-L2 Voltage 165 Ave Voltage L-L 217 UV Trip Level 178 L2 Reactive Power 243 UW Trip Level 138 Warn History 1 150 SS L2-L3 Voltage 166 L1-N Voltage 218 UV Warn Level 179 L3 Reactive Power 244 UW Warn Level 139 Warn History 2 151 SS L3-L1 Voltage 167 L2-N Voltage 219 OV Inhibit Time 180 Tot Reactive Power 245 OW Inhibit Time 140 Warn History 3 152 SS Tot Real Pwr 168 L3-N Voltage 220 OV Trip Delay 181 L1 Apparent Power 246 OW Trip Delay 141 Warn History 4 153 SS Tot kVAR 169 Ave Voltage L-N 221 OV Triip Level 182 L2 Apparent Power 247 OW Trip Level 142 TripHistory Mask 15 4 SS Tot kVA 170 Volt Unbalance 222 OV Warn Level 183 L3 Apparent Power 248 OW Warn Level 143 WarnHistory Mask 155 SS Total PF 171 Volt Frequency 223 Ph Rot Inhib Time 184 Tot Apparent Power 249 UVARC Inhibit Time 299 V TripHist Mask 172 V Phase Rot 224 Ph Rot Trip 185 L1 PF 250 UVARC Trip Delay 300 V WarnHist Mask 229 V UnhalInhib Time 186 L2 PF 251 UVARC Trip Level 301 PW TripHist Mask 230 V UnbalTripDelay 187 L3 PF 252 UVARC Warn Level 302 PW WarnHist Mask 231 V UnbalTrip Level 188 Total PF 253 OVARC Inhibit Time
Voltage
Voltage Setup
Monitor
Power Monitor
Power Setup
232 V UnbalWarnLevel 189 kWh 10E6 254 OVARC Trip Delay 233 UF Inhibit Time 190 kWh 10E3 255 OVARC Trip Level 234 UF Trip Delay 191 kWh 10E0 256 OVARC Warn Level 235 UF Trip Level 192 kWh 10E-3 257 UVARG Inhibit Time 236 UF Warn Level 193 kVARh Con 10E6 258 UVARG Trip Delay 237 OF Inhibit Time 194 kVARh Con 10E3 259 UVARG Trip Level 238 OF Trip Delay 195 kVARh Con 10E0 260 UVARG Warn Level 239 OF Trip Level 196 kVARh Con 10E-3 261 OVARG Inhibit Time 240 OF Warn Level 197 kVARh Gen 10E6 262 OVARG Trip Delay 289 PT Pri 198 kVARh Gen 10E3 263 OVARG Trip Level 290 PT Sec 199 kVARh Gen 10E0 264 OVARG Warn Level
200 kVARh Gen 10E-3 265 UVA Inhibit Time 201 kVARh Net 10E6 266 UVA Trip Delay 202 kVARh Net 10E3 267 UVA Trip Level 203 kVARh Net 10E0 268 UVA Warn Level 204 kVARh Net 10E-3 269 OVA Inhibit Time 205 kVAh 10E6 270 OVA Trip Delay 206 kVAh 10E3 271 OVA Trip Level 207 kVAh 10E0 272 OVA Warn Level 208 kVAh 10E-3 273 UPFLG Inhibit Time 209 kW Demand 274 UPFLG Trip Delay 210 Max kW Demand 275 UPFLG Trip Level 211 VAR De mand 276 UPFLG Warn Level 212 Max VAR Demand 277 OPFLG Inhibit Time 213 VA Demand 278 OPFLG Trip Delay 214 Max VA Demand 279 OPFLG Trip Level 227 PW Trip Status 280 OPFLG Warn Level 228 PW Warnn Status 281 UPFLD Inhibit Time
282 UPFLD Trip Delay 283 UPFLD Trip Level 284 UPFLD Warn Level 285 OPFLD Inhibit Time 286 OPFLD Trip Delay 287 OPFLD Trip Level 288 OPFLD Warn Level 291 Demand Period 292 Num of Periods
Publication 193-QR003B-EN-P - October 2009
24
Setup for Cat. No. 193-EC4 Current Monitor Relay
After the E3 Plus Current Monitor Relay is installed according to the guidelines specified in this manual, apply power to the relay’s DeviceNet connector. After applying power, the following sequence should occur:
1. The Trip relay should close 2.35 seconds later and the TRIP/WARN LED will not flash (unless a Non-Volatile Fault previously existed or a fault condition is present).
2. At the same time, the NETWORK STATUS LED should flash green for approximately two seconds, then red for a 1/4 second. If autobaud is enabled and the E3 Plus Current Monitor Relay is connected to an active network, the green LED will continue to flash once the baud rate has been determined. If the E3 Plus Current Monitor Relay is not connected to an active network, the LED will not continue to flash.
3. Once the E3 Plus Current Monitor Relay has been allocated by a master, the NETWORK STATUS LED will turn solid green.
After being powered up, use the DeviceNet Configuration Terminal (Cat. No. 193-DNCT) in order to set up the parameters. There are six basic parameters that need to be established before using the trip functions. These parameters are listed under the ADVANCED SETUP menu and include: L1 UC Trip Level, L2 UC Trip Level, L3 UC Trip Level, L1 OC Trip Level, L2 OC Trip Level, and L3 OC Trip Level. After the parameters have been configured, enable the specific trip bit as described in Table 7: for Parameter 24 (Trip Enable) to energize the relay when conditions are met.
Once these parameters are set, the E3 Plus Current Monitor Relay is functional. Use the ADVANCED SETUP menu to set other parameters per the specific application requirements.
Protective Trip/Warning Summaries & Parameter Group Listing (Cat. No. 193-EC4)
Table 7: Trip Summary
25
Tri p
Function
Ground Fault Disabled 0.02…5 A 2.5 A 0.0…25 s 0.5 s 0…250 s 10 s L1
Undercurrent L2
Undercurrent L3
Undercurrent L1
Overcurrent L2
Overcurrent L3
Overcurrent L1 Loss Disabled 0.5…25 s 0.5 s 0…250 s 1.0 s L2 Loss Disabled 0.5…25 s 0.5 s 0…250 s 1.0 s L3 Loss Disabled 0.5…25 s 0.5 s 0…250 s 1.0 s Comm Fault Disabled — Comm Idle Disabled — Remote Trip Disabled
Trip Enable
Factory Default
Disabled 0.2…45 A 0.1…25 s 1.0 s 0…250 s 1.0 s
Disabled 0.2…45 A 0.1…25 s 1.0 s 0…250 s 1.0 s
Disabled 0.2…45 A 0.1…25 s 1.0 s 0…250 s 1.0 s
Disabled 0.4…270 A 0.1…25 s 1.0 s 0…250 s 1.0 s
Disabled 0.4…270 A 0.1…25 s 1.0 s 0…250 s 1.0 s
Disabled 0.4…270 A 0.1…25 s 1.0 s 0…250 s 1.0 s
Trip Level Settings Trip Delay Settings Inhibit Time
Range Default Range Default Range Default
Settings
Publication 193-QR003B-EN-P - October 2009
26
Table 8: Warning Summary
Warning Function
Ground Fault Disabled 0.02…5 A 2.0 A 0.0…25 s 0.0 s 0…250 s 10 s L1
Undercurrent L2
Undercurrent L3
Undercurrent L1
Overcurrent L2
Overcurrent L3
Overcurrent L1 Loss Disabled 0…250 s 1.0 s L2 Loss Disabled 0…250 s 1.0 s L3 Loss Disabled 0…250 s 1.0 s Comm Fault Disabled — Comm Idle Disabled — Remote Trip Disabled
Warning
Enable Factory Default
Disabled 0.2…45 A 0…250 s 1.0 s
Disabled 0.2…45 A 0…250 s 1.0 s
Disabled 0.2…45 A 0…250 s 1.0 s
Disabled 0.4…270 A 0…250 s 1.0 s
Disabled 0.4…270 A 0…250 s 1.0 s
Disabled 0.4…270 A 0…250 s 1.0 s
Warning Level
Settings
Range Default Range Default Range Default
Warning Delay Settings Inhibit Time
Settings
Table 9: Parameter Group Listing (Cat. No. 193-EC4)
27
Monitor
Params
1 L1 Current 26 Trip Reset 24 Trip Enable 55 AutoBaudEnable 65 OutA Pr FltState 79 Comm Override 2 L2 Current 53 Program Lock 25 Warning Enable 56 NonVol Baud Rate 66 OutA Pr FltValue 80 Network Override 3 L3 Current 54 Set to Defaults 35 GF Inhibit Time 58 COS Mask 67 OutA DN FltState 81 Net Outputs
10 GF Current 103 Test Enable 36 GF Trip Delay 59 Output Assembly 68 OutA DN FltValue
14 Trip Status 104 Clear Queue 37 GF Trip Level 60 Input Assembly 69 OutA DN IdlState 15 Warning Status 38 GF Warn Level 61 Assy Word0 Param 70 OutA DN IdlValue 16 Trip Log 0 83 IN 1 Assignment 62 Assy Word1 Param 71 OutB Pr FltState 17 Trip Log 1 84 IN 2 Assignment 63 Assy Word2 Param 72 OutB Pr FltValue 18 Trip Log 2 85 IN 3 Assignment 64 Assy Word3 Param 73 OutB DN FltState 19 Trip Log 3 86 IN 4 Assignment 74 OutB DN FltValue 20 Trip Log 4 89 GF Trip Inhibit 75 OutB DN IdlState 21 Device Status 101 # of Starts 76 OutB DN IdlValue 22 Firmware 102 Operating Hours 23 Dev Config 105 GF Warn Delay 90 Warn Log 0 106 GF Sensing Range 91 Warn Log 1 107 UC Inhibit Time 92 Warn Log 2 108 L1 UC Trip Level 93 Warn Log 3 109 L1 UC Trip Delay 94 Warn Log 4 110 L1 UC Warn Level 95 Elapsed Time 111 L2 UC Trip Level 96 Starts Counter 112 L2 UC Trip Delay
Reset / Lock Advanced Setupt DeviceNet Setup Output Setup
113 L2 UC Warn Level 114 L3 UC Trip Level 115 L3 UC Trip Delay 116 L3 UC Warn Level 117 OC Inhibit Time 118 L1 OC Trip Level 119 L1 OC Trip Delay 120 L1 OC Warn Level 121 L2 OC Trip Level 122 L2 OC Trip Delay 123 L2 OC Warn Level 124 L3 OC Trip Level 125 L3 OC Trip Delay 126 L3 OC Warn Level 127 LL Inhibit Time 128 L1 Loss Trip Delay 129 L2 Loss Trip Delay 130 L3 Loss Trip Delay
DeviceLogix
82 Net Out COS
Mask
Publication 193-QR003B-EN-P - October 2009
28
ATTENTION
!
ATTENTION
!
Table 10: Parameter Group Listing (Cat. No. 193-EC4), Continued
132 Trip History 0 144 SS L1 Current 133 Trip History 1 145 SS L2 Current 134 Trip History 2 146 SS L3 Current 135 Trip History 3 148 SS GF Current 136 Trip History 4 137 Warn History 0 138 Warn History 1 139 Warn History 2 140 Warn History 3 141 Warn History 4 142 TripHistory Mask 143 WarnHistory Mask
Series C (FRN 5.00 and Higher)
TripWarn History Tri p Snap shot
Short-Circuit Ratings
To prevent electrical shock, disconnect from power source before installing or servicing
Select the motor branch circuit protection that complies with the National Electrical Code and any othergoverning regional and local codes
The Bulletin 193/592 E3 Overload relay is suitable for use on circuits capable of delivering not more than the RMS symmetrical amperes listed in the followign tables:
29
Table 11: Standard Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14
Cat. No. Max. Available Fault
Current [A]
193-EC_B, 592EC_T 5000 193-EC_D, 592EC_C 5000 193-EC_E, 592EC_D 10000 193-EC_F 10000 193-EC_G 18000 193-EC_H 42000 193-EC_Z 5000
Max. Voltage [V]
600
Publication 193-QR003B-EN-P - October 2009
30
Table 12: High Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14 with Bulletin 100-C and 100-D contactors
Cat. No. Contactor Max.
100-C09 9 100-C12 12 20 100-C16 16 30 100-C23 23 30 100-C30 30 50 100-C37 37 50 100-C43 43 70 100-C60 60 80 100-C72 72 100 100-C85 85 150
100-D210 210 400 100-D250 250 400 100-D300 300 500 100-D210 210 400 100-D250 250 400 100-D300 300 500 100-D300 300 500 100-D420 420 600
193-EC1 193-EC2 193-EC3 193-EC4 193-EC5
_B
_D
_E
FF, ZZ 100-D95 95 200 FF, ZZ 100-D110 110 200 FF, ZZ 100-D140 140 250 GF, ZZ 100-D180 180 300
GG, ZZ
HG, ZZ
JG, ZZ
Starter FLC [A]
Max. Available Fault Current [A]
100000 600
Max. Voltage [V]
Max. Class J or CC Fuse [A]
20
31
Table 13: High Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14 with NEMA contactors
Cat. No. Contactor
592-EC1 592-EC2 592-EC3 592-EC5
Size
_T 00 100000 600 20 — _C
_C 1 100000
_C 2 100000
_D 3 100000
Max. Available Fault Current [A]
0 100000
Max. Voltage [V]
Max. UL Fuse [A] Circuit Breaker/
240
480
600 30 30
240
480
600 30 50
240
480 60 100 — 600 60 100
240 200 350
480 100 200
600 100 200
Table 14: IFC Short-Circuit Ratings per EN60947-4-1
RJ
30
30
60
30
100
30
30
100
50
200
Limiter
FDB 3025/ LFB3070R
FDB 3025/ LFB3070R
FDB 3050/ LFB3035R
FDB 3050/ LFB3035R
FDB 3100/ LFB3150R
FDB 3150/ LFB3150R
FDB 3125/ LFB3150R
FDB 3100/ LFB3150R
Cat. No. Prospective
Short-Circuit Current I
[A]
r
193-EC_B, 592EC_T 1000 193-EC_D, 592EC_C 3000 193-EC_E, 592EC_D 5000 193-EC_F 10000 193-EC_G 18000 193-EC_H 30000 193-EC_Z 1000
Conditional
Max. Voltage [V] Short-Circuit Current Iq [A]
100000 690
Publication 193-QR003B-EN-P - October 2009
32
Fuse Coordination
Table 15: IEC Type 1 and Type II Fuse Coordination with Bulletin 100-C and 100-D Contactors per EN60947-4-1
Cat. No. Contactor Max.
100-C09 9 100-C12 12 20 20
_B
100-C16 16 30 30 100-C23 23 40 40 100-C30 30
_D
100-C37 37 50 50 100-C43 43 70 70 100-C60 60 80 80
_E
100-C72 72 100 100
193-EC1 193-EC2 193-EC3 193-EC4 193-EC5
100-C85 85 5000 150 150 FF, ZZ 100-D95 95 FF, ZZ 100-D110 110 200 200 FF, ZZ 100-D140 140 250 250 GF, ZZ 100-D180 180 300 300
100-D210 210 400 400
GG, ZZ
100-D250 250 400 400 100-D300 300 500 500 100-D210 210 400 400
HG, ZZ
100-D250 250 400 400 100-D300 300 500 500 100-D300 300 500 500
JG, ZZ
100-D420 420 600 600
Starter FLC [A]
Prospective Short-Circuit Current I
1000
3000
10000
r
[A]
Conditional Short-Circuit Current I
[A]
q
100000 600
Max. Voltage [V]
Type I with Class J Fuse [A]
20 15
50 50
200 200
Type II with Class J Fuse [A]
Table 16: Type 1 and Type II Fuse Coordination with NEMA Contactors
33
Cat. No. Contactor
592-EC_T 00 9 1000 592-EC_C 0, 1 18, 27 3000 30 30 592-EC_C 2 45 3000 60 60 592-EC_D 3 90 5000 200 200
Size
Max. Starter FLC [A]
Prospective Short-Circuit Current Ir [A]
Conditional Short-Circuit Current Iq [A]
100000 600
Max. Voltage [V]
Type I with Class J Fuse [A]
20 20
Type II with Class J Fuse [A]
Publication 193-QR003B-EN-P - October 2009
Publication 193-QR003B-EN-P - October 2009 PN-37176 Supercedes publication 193-QR003A-EN-P - January 2008 Copyright ©2009 Rockwell Automation, Inc. All Rights Reserved. Printed in USA
Loading...