This guide does not replace the User Manual, publication
193-UM002_-EN-P, and is intended for qualified service personnel
responsible for setting up and servicing these devices. You must have
previous experience with and a basic understanding of electrical
terminology, configuration procedures, required equipment, and safety
precautions. The user manual can be downloaded from http://
literature.rockwellautomation.com.
Important User Information
Because of the variety of uses for the products described in this publication, those responsible
for the application and use of this control equipment must satisfy themselves that all
necessary steps have been taken to assure that each application and use meets all performance
and safety requirements, including any applicable laws, regulations, codes, and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are
intended solely for purposes of example. Since there are many variables and requirements
associated with any particular installation, Rockwell Automation does not assume
responsibility or liability (to include intellectual property liability) for actual use based upon
the examples shown in this publication.
Rockwell Automation publication SGI-1.1, Safety Guidelines for the Application, Installation
and Maintenance of Solid-State Control (available from your local Allen-Bradley distributor),
describes some important differences between solid-state equipment and electromechanical
devices that should be taken into consideration when applying products such as those
described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without
written permission of Rockwell Automation, is prohibited.
Publication 193-QR003B-EN-P - October 2009
3
IMPORTANT
IMPORTANT
IMPORTANT
IMPORTANT
General Precautions
In addition to the specific precautions listed throughout this manual, the following general
statements must be observed.
The purpose of this publication is to serve as a guide for proper
installation. The National Electrical Code and any other governing
regional or local code overrules the information in this publication.A
hazard of personal injury/equipment damage exists if codes are
ignored during installation. Rockwell Automation cannot assume
responsibility for the compliance or proper installation of the E3
Overload Relay or associated equipment.
Only personnel familiar with the E3 Overload Relay and associated
machinery should plan to install, start up, and maintain the system.
Failure to comply may result in personal injury/equipment damage.
An incorrectly applied or installed E3 Overload Relay can result in
damage to the components or reduction in product life. Wiring or
application errors, such as incorrectly configuring the FLA Setting,
supplying incorrect or inadequate DeviceNet supply voltage,
connecting an external supply voltage to the input or thermistor
terminals, or operating/storing in excessive ambient temperatures may
result in malfunction of the E3 Overload Relay.
The E3 Overload Relay contains ESD (electrostatic discharge)
sensitive parts and assemblies. Static control precautions are required
when installing, testing, servicing, or repairing this assembly.
Component damage may result if ESD control procedures are not
followed. If you are not familiar with static control procedures, refer
to Allen-Bradley publication 8200-4.5.2, Guarding Against Electrostatic Damage, or any other applicable ESD protection handbook.
Publication 193-QR003B-EN-P - October 2009
4
Introduction
Follow these steps to successfully commission the E3 Overload Relay:
Table 1: Commissioning Procedure
StepDescription
1Hardware Installation
2Wiring Installation
3DeviceNet Commissioning
4Setup Requirements
– Typical Motor Connections
– External Current Transformer Applications (193-EC_ZZ or 592-EC_ZZ)
– External Ground Fault Sensor Applications (193-EC3_ _ , 592-EC3_ _ and
193-EC5_ _ , 592-EC5_ _)
Setup for Bulletin 193 or 592-EC1/EC2/EC3/EC5 Overload Relay
– Protective Trip and Warning Summaries
– Parameter Group Listing
Setup for Cat. No. 193-EC4 Current Monitor Relay
– Trip and Warning Summaries
– Parameter Group Listing
Publication 193-QR003B-EN-P - October 2009
Hardware Installation
1
2
CLICK
3
The following figures illustrate the starter assembly instructions.
Starter Assembly Instructions
Figure 1: 100-C09…C43 Starter Assembly Instructions (for use with Cat. Nos.
193-EC_ _B and -EC_ _D)
/tN
22 lb-in.
5
Publication 193-QR003B-EN-P - October 2009
6
1
2
/tN
35 lb-in.
Figure 2: 100-C60…C85 Starter Assembly Instructions (for use with Cat. No.
193-EC_ _E).
Publication 193-QR003B-EN-P - October 2009
Figure 3: 100-D95...D860 Starter Assembly Instructions (for use with Cat. Nos.
193-EC_ _F, 193-EC_ _G, and 193-EC_ _H).
7
Publication 193-QR003B-EN-P - October 2009
8
E3 PLUS
LED Status Indicators
DeviceNet Port
Input Terminals
Test/Reset Button
Node Address Switches
(Series B and later)
Output and PTC Terminals
Ground Fault Sensor Input
Voltage Input Module
Connection
(193/592 EC5 only)
Wiring Installation
Typical Motor Connections
Refer to the product nameplate or user manual for power lug termination information
including:
• Terminal wire size and torque specifications
• Maximum wire lengths
• Lug kit catalog numbers (108…1250 A)
For reliable input signal processing, input wiring should be routed in raceways separate from
power cabling.
Terminal Designations
Figure 4: E3 and E3 Plus Feature Overview
Publication 193-QR003B-EN-P - October 2009
Control Terminals
The following table defines the E3 Overload Relay control terminal designations.
Table 2: Control Terminal Designation
9
Ter mi na l
Designation
1IN 1General-purpose sinking input number 1
2IN 2General-purpose sinking input number 2
3IN 3General-purpose sinking input number 3 ➊➋
4IN 4General-purpose sinking input number 4 ➊➋
5V+
6V+
7IN 5General-purpose sinking input number 5 ➋
8IN 6General-purpose sinking input number 6 ➋
13/14OUT AOutput A
23/24OUT BOutput B ➊➋
95/96Trip RelayTrip Relay
IT1/IT2PTCThermistor (PTC) input ➊➍
S1/S2—External ground fault sensor input ➋➎
➊ Features are available only with the E3 Plus Overload Relay (cat. nos. 193/592-EC2and 193/592-EC3).
➋ Available only on cat. nos. 193/592-EC5_ _.
➌ An earth ground connection to this terminal will assist in obtaining compliance with electromagnetic
compatibility requirements.
➍ The use of shielded cable is recommended for the positive PTC thermistor circuit to assist in obtaining
compliance with electromagnetic compatibility requirements.
➎ Available only on cat. nos. 193/592-EC3_ _ and 193/592-EC4_ _.
ReferenceDescription
+24V DC supply for inputs
EndEarth Ground ➌
DeviceNet Terminals
The following table defines the DeviceNet connector terminal designations.
The following grounding recommendations are provided to ensure electromagnetic
compatibility compliance during installation:
• The earth ground terminal of the E3 Overload Relay shall be connected to a solid
earth ground via a low-impedance connection
• Installations employing an external ground fault sensor shall ground the cable shield
at the sensor with no connection made at the E3 Plus Overload Relay
• The PTC thermistor cable shield shall be grounded at the E3 Plus Overload Relay
with no connection made at the opposite end
Wiring Diagrams
When working on energized circuits, do not rely on the voltage and
current information provided by the E3 and E3 Plus for personal
safety. Always use a portable voltage or current measurement device
and measure the signal locally.
Parameter 27, Single/Three Ph, should be set to single-phase for
single-phase devices and three-phase for three-phase devices.
In single-phase devices, traditional single-phase wiring (connecting
T2 to L3) will result in a vector imbalance of current flowing through
the E3 Plus Overload Relay. This will result in inaccurate ground fault
reporting and protection.
External Current Transformer Application (Cat. No. 193-EC_ZZ)
E3 and E3 Plus Overload Relays (Cat. No. 193-EC_ZZ) are designed for use with separately
mounted, customer-supplied current transformers (CTs) as required in higher-current
applications. The FLA setting range is 9…5000 A for these units, with a legal setting range
per the user’s manual. Parameter 78, CT Ratio, is provided for setting the current transformer
ratio to be installed.
Current Transformer Specifications
The 193-EC_ZZ Overload Relays are intended for use with a CT having a secondary current
rating of 5 A. The installer shall provide one CT for each motor phase and shall connect the
CT secondary leads to the appropriate E3 Overload Relay power terminals as shown in Figure
7: on page 13. The CT shall have an appropriate ratio rating as detailed in the user’s manual.
Additionally, the CT shall be selected to be capable of providing the required VA to the
secondary load, which includes the E3 Overload Relay burden of 0.1 VA at the rated
secondary current and the wiring burden.
Finally, the CT shall be rated for protective relaying to accommodate the high inrush currents
associated with motor startup and shall have an accuracy of
range.
≤±2% over its normal operating
ANSI (USA)Class C5 B0.1
CSA (Canada)Class 10L5
IEC (Europe)5 VA Class 5P10
The improper selection of a current transformer can result in the E3
Overload Relay reporting inaccurate motor operational data and
possible motor damage. The selected current transformer must be
rated for protective relaying applications.
Publication 193-QR003B-EN-P - October 2009
12
IMPORTANT
6x
6x
OR
y
C
t
s
d
y
Installation Instructions
Cat. No. 193-EC_ZZ Overload Relays are designed to be installed in cat. no. 193-ECPM2
panel mount adapters and connected to separately mounted current transformers. For a panel
mount adapter assembly, refer to the instructions included with the panel mount adapter. The
E3 Overload Relay must be mounted a distance equal to, or greater than, six times the cable
diameter (including insulation) from the nearest current-carrying conductor or current
transformer. For applications employing multiple conductors per phase, the diameter of each
cable should be added and multiplied by six to determine the proper placement distance for
the E3 Overload Relay.
Placement of the E3 Overload Relay closer than the recommended
distance of six times the cable diameter may compromise its current
reporting and protection capabilities.
The E3 Plus Overload Relay Catalog Number 193/592-EC5_ _ can be used with external
step-down potential transformers (PTs). The PT ratio is programmed into the E3 Plus by
entering the primary winding rating into Parameter 289, PT Pri, and the secondary winding
rating into Parameter 290, PT Sec. The voltage mode is also programmed into the E3 Plus by
selecting the appropriate mode in Parameter 156, Vol t Mode. The E3 Plus will support Wye,
Delta, and Open Delta voltage modes with potential transformers.
Cat. Nos. 193/592-EC3_ _, 193/592-EC4_ _, and 193/592-EC5_ _ E3 Plus Overload Relays
are intended to provide ground fault protection when used with the cat. no. 193-CBCT
external ground fault (core balance) sensor. The ground fault sensor mounts separately from
the E3 Plus Overload Relay and must be placed within three meters of the relay. The
customer-supplied cable for wiring the ground fault sensor to the E3 Plus Overload Relay
should meet the specifications outlined in Table 1.9 on page 15.
_
Table 1.9 Ground Fault Sensor Terminals (S1 and S2)
Wire typeShielded, twisted pair
Cross section
Tor q ue
0.2…4.0 mm
0.55 N
2
(#24…12 AWG)
•m (5 lb-in.)
Power Cable Installation Instructions
1. All power cables (including the neutral when used) must pass through the sensor
window. The equipment ground conductor (the conductor used to carry the
non-current-carrying metal parts of equipment, as defined by Article 100 of the
NEC), must not pass through the sensor window.
2. The power cables through the sensor window should be straight, tightly bundled,
centered in the window, and perpendicular to the sensor for a length equal to, or
greater than, six times the cable diameter (including insulation) from the sensor.
3. All other conductors with available currents in excess of 1,000 A should be placed a
distance equal to, or greater than, six times the cable diameter (including insulation)
from the sensor.
4. The power cables of the branch circuit to be protected by the E3 Plus Overload Relay
must not be grounded on the load side of the ground fault sensor.
5. If the power cables are enclosed in a conducting jacket, the jacket must be grounded
on the line side of the sensor. The jacket must not pass through the sensor window,
but must be cut at the window and joined with a conductor that passes outside the
sensor window.
6. The power system may be solidly grounded or grounded through an impedance at its
source as long as the impedance allows a magnitude of fault current to flow that is
within the 1…5 A operational range of the E3 Plus Overload Relay (193/592-EC2_
_) or the 20 mA…5 A operational range of the E3 Plus Overload Relay (193/
592-EC3
_ _, 193/592-EC4_ _, and 193/592-EC5_ _).
Publication 193-QR003B-EN-P - October 2009
16
IMPORTANT
MOTOR
L1 L2
L3
S1
S2
S1
S2
193-CBCT_
Ground
Fault
Sensor
E3 Plus
Overload Relay
Figure 10: Ground Fault Sensor Mounting Placement
GF Sensor
90˚
Power
Cables
6x
6x
Figure 11: Power Cable Configuration — Two Cables per Phase
1
L3L1
1
L2L2
L1
L3
The spacer is a short (approximately 10 times
the cable diameter in length) piece of cable
with no connections to any terminal.
Figure 12: Ground Fault Sensor Wiring to the E3 Plus Overload Relay
Publication 193-QR003B-EN-P - October 2009
The shield of the twisted pair cable must be connected to earth
ground at the sensor, with no connection made at the E3 Plus
Overload Relay.
17
IMPORTANT
DeviceNet Node Commissioning
Overview
E3 Overload Relays are shipped with a default software node address (MAC ID) setting of 63
and the data rate set to Autobaud. Each device on a DeviceNet network must have a unique
node address which can be set to a value from 0…63.
Keep in mind, most DeviceNet systems use address 0 for the master device (scanner) and
node address 63 should be left vacant for introduction of new slave devices. The node
address and data rate for series B or later, E3 Overload Relays can be changed using software
or by setting the hardware switches that reside on the front of each unit. While both methods
yield the same result, it is good practice to choose one method and deploy it throughout the
system.
The following recommendations are intended to ensure a trouble-free
startup and operation:
1. Use the node commissioning tool in RSNetWorx or the
DeviceNet configuration terminal (cat. no. 193-DNCT) when
modifying the E3 node address. Do not use the General tab found
in the product window in RSNetWorx. The node commissioning
tool ensures the device goes through a hard reset and requires
the user to upload the most current parameter information from
the device prior to making configuration changes.
2. Ensure you have the most current configuration information
prior to saving an RSNetWorx configuration file.
3. If you intend to employ the ADR function of the DeviceNet
scanner, ensure the device configuration is as you intend it
BEFORE saving it to memory.
4. Be aware the Restore Device Defaults button in RSNetWorx will
reset the E3 Overload Relay node address setting to 63. For
Series B or later devices, the hardware node address switches take
precedence over the software node address setting.
Publication 193-QR003B-EN-P - October 2009
18
Figure 13: Node Address Switches
Table 2: Node Address Setting
Switch SettingsDescription
0…63The node address setting is determined by the switch values when set in this range.
64…99For switch settings in this range, the node address setting is determined by the software
99Factory default setting.
Note: For node address switch values in the range of 0…63, cycle power to the E3 Overload Relay to
initialize the new setting.
setting using the RSNetWorx for DeviceNet configuration tool.
Setup Requirements
Setup for Cat. Nos. 193/592-EC1/EC2/EC3/EC5 Overload Relays
After the E3 Overload Relay is installed according to the guidelines specified in this manual,
apply power to the overload relay’s DeviceNet connector. After applying power, the following
sequence should occur:
1. The Trip relay should close 2.35 seconds later and the TRIP/WARN LED will not
flash (unless a Non-Volatile Fault previously existed or a fault condition is present).
2. At the same time, the NETWORK STATUS LED should flash green for
approximately two seconds, then red for a 1/4 second. If autobaud is enabled and the
E3 Overload Relay is connected to an active network, the green LED will continue to
flash once the baud rate has been determined. If the E3 Overload Relay is not
connected to an active network, the LED will not continue to flash.
3. Once the E3 Overload Relay has been allocated by a master, the NETWORK
STATUS LED will turn solid green.
After being powered up, use the DeviceNet Configuration Terminal (Cat. No. 193-DNCT) in
order to set up the parameters. There are five basic parameters that need to be established
before using the protective functions. These parameters are listed under the OVERLOAD
SETUP menu and include: Single/Three Phase, Full Load Current (FLA) Setting, Trip Class,
Overload/PTC Reset mode, and Overload Reset Level. (Note: You will need to program
additional parameters when customer-supplied CTs are used.)
Once these parameters are set, the E3 Overload Relay is functional. Use the ADVANCED
SETUP menu to set other parameters per the specific application requirements.
Publication 193-QR003B-EN-P - October 2009
Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. Nos. 193/592-EC1/EC2/EC3/EC5)
Table 3: Trip Summary
19
Tri p
Function
OverloadEnabled➋➋Trip Class
Phase LossEnabled➌➌0.1…25.0 s1.0 s0…250 s0 s
Ground Fault
JamDisabled50…600%250%0.1…25.0 s5.0 s0…250 s10 s
UnderloadDisabled10…100% FLA ➏50%0.1…25.0 s5.0 s0…250 s10 s
PTCDisabled——————
Current
Imbalance
Comm FaultEnabled——————
Comm IdleDisabled——————
Remote TripDisabled——————
Voltage Input
Module
Hardware Fault
➐
Undervoltage
L-L ➐
Overvoltage L-L ➐ Disabled 0...655355000.1…25.0 s 1.0 s 0…250 s 10 s
Tri p
Enable
Factory
Default
Disabled Internal 1…5 A2.5 A0.0…25.0 s0.5 s0…250 s10 s
DisabledExternal
Disabled10…100%35%0.1…25.0 s5.0 s0…250 s10 s
Disabled — — — — — —
Disabled 0...655351 000.1…25.0 s 1.0 s 0…250 s 10 s
Trip Level SettingsTrip Delay SettingsInhibit Time
Range DefaultRangeDefaultRangeDefault
Tri p Cl ass10——
0.02…5 A ➍
5…30
2.5 A0.0…25.0 s0.5 s0…250 s10 s
Settings ➊
Voltage
Unbalance ➐
Phase Rotation ➐ Disabled 1…21 — — 0…250 s 10 s
Under
Frequency ➐
Over Frequency ➐ Disabled 0…250630.1…25.0 s 1.0 s 0…250 s 10 s
Under Real
Power ➐
Over Real
Power ➐
Disabled 0…100750.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…250570.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…327670.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…327670.1…25.0 s 1.0 s 0…250 s 10 s
Publication 193-QR003B-EN-P - October 2009
20
Table 3: Trip Summary
Tri p
Function
Under
Consumed
kVAR ➐
Over Consumed
kVAR ➐
Under
Generated
kVAR ➐
Over Generated
kVAR ➐
Under Power
kVA ➐
Over Power kVA ➐ Disabled 0…327670.1…25.0 s 1.0 s 0…250 s 10 s
Under Power
Factor Lagging
➐
Over Power
Factor Lagging
➐
Under Power
Factor Leading
➐
Over Power
Factor Leading
➐
➊ The inhibit time setting parameters are applicable to both the trip and warning functions.
➋ FLA Setting range and default values are dependent upon the current rating of the product. See the user
manual for more information.
➌ Phase loss trip level is factory-set at a current imbalance greater than or equal to 100% and is not
user-adjustable.
➍ Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
➎ Stall protection is only applicable during the motor starting sequence. If any phase of current falls below the
programmed Stall Trip Level, stall protection is disabled.
➏ 50…100% for devices with FRN 1.003 and earlier.
➐ Available on 193/592-EC5 only.
Tri p
Enable
Factory
Default
Disabled 0…327670.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…327670.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -32767…00.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -32767…00.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0…327670.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -100…0-900.1…25.0 s 1.0 s 0…250 s 10 s
Disabled -100…0-950.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0...100900.1…25.0 s 1.0 s 0…250 s 10 s
Disabled 0...100950.1…25.0 s 1.0 s 0…250 s 10 s
Trip Level SettingsTrip Delay SettingsInhibit Time
Stall—————
JamDisabled50…600%150%0…250 s10 s
UnderloadDisabled10…100%➍70%0…250 s10 s
Thermistor (PTC)Disabled————
Current ImbalanceDisabled10…100%20%0…250 s10 s
Comm FaultDisabled————
Comm IdleDisabled————
Voltage Input Module
Hardware Fault r
Under Voltage L-L rDisabled0...655354000…250 s10 s
Over Voltage L-L ➎Disabled0...655354900…250 s10 s
Voltage Unbalance ➎Disabled0…100850…250 s10 s
Phase Rotation ➎Disabled1…210…250 s10 s
Under Frequency ➎Disabled0…250580…250 s10 s
Over Frequency ➎Disabled0…250620…250 s10 s
Under Real Power ➎Disabled0…327670…250 s10 s
Over Real Power ➎Disabled0…327670…250 s10 s
Under Consumed kVAR ➎Disabled0…327670…250 s10 s
Over Consumed kVAR ➎Disabled0…327670…250 s10 s
Under Generated kVAR ➎Disabled-32767…00…250 s10 s
Over Generated kVAR ➎Disabled-32767…00…250 s10 s
Under Power kVA ➎Disabled0…327670…250 s10 s
Over Power kVA ➎Disabled0…327670…250 s10 s
Under Power Factor Lagging ➎Disabled-100…0-950…250 s10 s
Over Power Factor Lagging ➎Disabled-100…0-900…250 s10 s
Under Power Factor Leading ➎Disabled0...100950…250 s10 s
Over Power Factor Leading ➎Disabled0...100900…250 s10 s
Warning
Enable
Factory
Default
Enabled — — — —
Warning Level SettingsInhibit Time Settings ➊
Range DefaultRangeDefault
0.02…5 A ➌
2.0 A0…250 s10 s
➊ The inhibit time setting parameters are applicable to both the trip and warning functions.
➋ Overload warning setting is entered as a percentage of the thermal capacity utilized.
➌ Must use Ground Fault Sensors (Cat. No. 193-CBCT_).
➍ 50…100% for devices with FRN 1.003 and earlier.
➎ Available on 193/592-EC5 only.
86 IN 4 Assignment
87 2-Spd Net Enable
88 2-Speed FLA Set
89 GF Trip Inhibit
99 Starts/Hour➊
100 Starts Interval➊
101 PM - # Starts➊
102 PM - Oper. Hours➊
105 GF Warn Delay➊
106 GF Sensing Range➊
DeviceNet
Setup
Output
SetupDeviceLogix
66 OutA Pr
FltValue
67 OutA DN
FltState81 Net outputs
68 OutA DN
FltValue
69 OutA DN
IdlState
70 OutA DN
IdlValue
73 OutB DN
FltState
74 OutB DN
FltValue
75 OutB DN
IdlState
76 OutB DN
IdlValue
80 Network
Override
82 Net Out COS
Mask
Publication 193-QR003B-EN-P - October 2009
23
Table 6: Parameter Group Listing, Continued
➋
Trip Snapshot
➋
Device
Logix
79 Comm
Override 132 Trip History 0144 SS L1 Current160 V Trip Status156 Volt Mode173 L1 Real Power157 Power Scale
80 Network
Override133 Trip History 1145 SS L2 Current161 V Warn Status158 V Trip Enable174 L2 Real Power225 PW Trip Enable
81 Net outputs 134 Trip History 2146 SS L3 Cu rrent162 L1-L2 Voltage159 V Warn Enable175 L3 Real Power226 PW Warn Enable
82 Net Out COS
Mask135 Trip History 3147 SS %TCU163 L2-L3 Voltage215 UV Inhibit Time176 Total Real Power241 UW Inhibit Time
o Series C (FRN 5.00 and Higher)
➌ 193/592-EC5 Only
Tri pWa rn
History
136 Trip History 4148 SS GF Current164 L3-L1 Voltage216 UV Trip Delay177 L1 Reactive Power 242 UW Trip Delay
137 Warn History 0149 SS L1-L2 Voltage 165 Ave Voltage L-L 217 UV Trip Level178 L2 Reactive Power 243 UW Trip Level
138 Warn History 1150 SS L2-L3 Voltage 166 L1-N Voltage218 UV Warn Level179 L3 Reactive Power 244 UW Warn Level
139 Warn History 2151 SS L3-L1 Voltage 167 L2-N Voltage219 OV Inhibit Time180 Tot Reactive Power 245 OW Inhibit Time
140 Warn History 3152 SS Tot Real Pwr168 L3-N Voltage220 OV Trip Delay181 L1 Apparent Power 246 OW Trip Delay
141 Warn History 4153 SS Tot kVAR169 Ave Voltage L-N 221 OV Triip Level182 L2 Apparent Power 247 OW Trip Level
142 TripHistory Mask15 4 SS Tot kVA170 Volt Unbalance 222 OV Warn Level183 L3 Apparent Power 248 OW Warn Level
143 WarnHistory Mask 155 SS Total PF171 Volt Frequency 223 Ph Rot Inhib Time184 Tot Apparent Power 249 UVARC Inhibit Time
299 V TripHist Mask172 V Phase Rot224 Ph Rot Trip185 L1 PF250 UVARC Trip Delay
300 V WarnHist Mask229 V UnhalInhib Time 186 L2 PF251 UVARC Trip Level
301 PW TripHist Mask230 V UnbalTripDelay187 L3 PF252 UVARC Warn Level
302 PW WarnHist Mask231 V UnbalTrip Level188 Total PF253 OVARC Inhibit Time
Voltage
➌ Voltage Setup ➌
Monitor
Power Monitor
➌ Power Setup ➌
232 V UnbalWarnLevel 189 kWh 10E6254 OVARC Trip Delay
233 UF Inhibit Time190 kWh 10E3255 OVARC Trip Level
234 UF Trip Delay191 kWh 10E0256 OVARC Warn Level
235 UF Trip Level192 kWh 10E-3257 UVARG Inhibit Time
236 UF Warn Level193 kVARh Con 10E6258 UVARG Trip Delay
237 OF Inhibit Time194 kVARh Con 10E3259 UVARG Trip Level
238 OF Trip Delay195 kVARh Con 10E0260 UVARG Warn Level
239 OF Trip Level196 kVARh Con 10E-3261 OVARG Inhibit Time
240 OF Warn Level197 kVARh Gen 10E6262 OVARG Trip Delay
289 PT Pri198 kVARh Gen 10E3263 OVARG Trip Level
290 PT Sec199 kVARh Gen 10E0264 OVARG Warn Level
200 kVARh Gen 10E-3265 UVA Inhibit Time
201 kVARh Net 10E6266 UVA Trip Delay
202 kVARh Net 10E3267 UVA Trip Level
203 kVARh Net 10E0268 UVA Warn Level
204 kVARh Net 10E-3269 OVA Inhibit Time
205 kVAh 10E6270 OVA Trip Delay
206 kVAh 10E3271 OVA Trip Level
207 kVAh 10E0272 OVA Warn Level
208 kVAh 10E-3273 UPFLG Inhibit Time
209 kW Demand274 UPFLG Trip Delay
210 Max kW Demand275 UPFLG Trip Level
211 VAR De mand276 UPFLG Warn Level
212 Max VAR Demand 277 OPFLG Inhibit Time
213 VA Demand278 OPFLG Trip Delay
214 Max VA Demand279 OPFLG Trip Level
227 PW Trip Status280 OPFLG Warn Level
228 PW Warnn Status 281 UPFLD Inhibit Time
282 UPFLD Trip Delay
283 UPFLD Trip Level
284 UPFLD Warn Level
285 OPFLD Inhibit Time
286 OPFLD Trip Delay
287 OPFLD Trip Level
288 OPFLD Warn Level
291 Demand Period
292 Num of Periods
Publication 193-QR003B-EN-P - October 2009
24
Setup for Cat. No. 193-EC4 Current Monitor Relay
After the E3 Plus Current Monitor Relay is installed according to the guidelines specified in
this manual, apply power to the relay’s DeviceNet connector. After applying power, the
following sequence should occur:
1. The Trip relay should close 2.35 seconds later and the TRIP/WARN LED will not
flash (unless a Non-Volatile Fault previously existed or a fault condition is present).
2. At the same time, the NETWORK STATUS LED should flash green for
approximately two seconds, then red for a 1/4 second. If autobaud is enabled and the
E3 Plus Current Monitor Relay is connected to an active network, the green LED will
continue to flash once the baud rate has been determined. If the E3 Plus Current
Monitor Relay is not connected to an active network, the LED will not continue to
flash.
3. Once the E3 Plus Current Monitor Relay has been allocated by a master, the
NETWORK STATUS LED will turn solid green.
After being powered up, use the DeviceNet Configuration Terminal (Cat. No. 193-DNCT) in
order to set up the parameters. There are six basic parameters that need to be established
before using the trip functions. These parameters are listed under the ADVANCED SETUP
menu and include: L1 UC Trip Level, L2 UC Trip Level, L3 UC Trip Level, L1 OC Trip Level,
L2 OC Trip Level, and L3 OC Trip Level. After the parameters have been configured, enable
the specific trip bit as described in Table 7: for Parameter 24 (Trip Enable) to energize the relay
when conditions are met.
Once these parameters are set, the E3 Plus Current Monitor Relay is functional. Use the
ADVANCED SETUP menu to set other parameters per the specific application
requirements.
Publication 193-QR003B-EN-P - October 2009
Protective Trip/Warning Summaries & Parameter Group Listing
(Cat. No. 193-EC4)
Table 7: Trip Summary
25
Tri p
Function
Ground FaultDisabled0.02…5 A2.5 A0.0…25 s0.5 s0…250 s10 s
L1
Undercurrent
L2
Undercurrent
L3
Undercurrent
L1
Overcurrent
L2
Overcurrent
L3
Overcurrent
L1 LossDisabled——0.5…25 s0.5 s0…250 s1.0 s
L2 LossDisabled——0.5…25 s0.5 s0…250 s1.0 s
L3 LossDisabled——0.5…25 s0.5 s0…250 s1.0 s
Comm FaultDisabled——————
Comm IdleDisabled——————
Remote TripDisabled——————
Trip Enable
Factory
Default
Disabled0.2…45 A—0.1…25 s1.0 s0…250 s1.0 s
Disabled0.2…45 A—0.1…25 s1.0 s0…250 s1.0 s
Disabled0.2…45 A—0.1…25 s1.0 s0…250 s1.0 s
Disabled0.4…270 A—0.1…25 s1.0 s0…250 s1.0 s
Disabled0.4…270 A—0.1…25 s1.0 s0…250 s1.0 s
Disabled0.4…270 A—0.1…25 s1.0 s0…250 s1.0 s
Trip Level SettingsTrip Delay SettingsInhibit Time
RangeDefaultRangeDefaultRangeDefault
Settings
Publication 193-QR003B-EN-P - October 2009
26
Table 8: Warning Summary
Warning
Function
Ground FaultDisabled0.02…5 A2.0 A0.0…25 s0.0 s0…250 s10 s
L1
Undercurrent
L2
Undercurrent
L3
Undercurrent
L1
Overcurrent
L2
Overcurrent
L3
Overcurrent
L1 LossDisabled————0…250 s1.0 s
L2 LossDisabled————0…250 s1.0 s
L3 LossDisabled————0…250 s1.0 s
Comm FaultDisabled——————
Comm IdleDisabled——————
Remote TripDisabled——————
Warning
Enable
Factory
Default
Disabled0.2…45 A———0…250 s1.0 s
Disabled0.2…45 A———0…250 s1.0 s
Disabled0.2…45 A———0…250 s1.0 s
Disabled0.4…270 A———0…250 s1.0 s
Disabled0.4…270 A———0…250 s1.0 s
Disabled0.4…270 A———0…250 s1.0 s
Warning Level
Settings
RangeDefaultRangeDefaultRangeDefault
Warning Delay SettingsInhibit Time
Settings
Publication 193-QR003B-EN-P - October 2009
Table 9: Parameter Group Listing (Cat. No. 193-EC4)
27
Monitor
Params
1 L1 Current26 Trip Reset24 Trip Enable55 AutoBaudEnable65 OutA Pr FltState79 Comm Override
2 L2 Current53 Program Lock25 Warning Enable56 NonVol Baud Rate66 OutA Pr FltValue80 Network Override
3 L3 Current54 Set to Defaults35 GF Inhibit Time58 COS Mask67 OutA DN FltState81 Net Outputs
Table 10: Parameter Group Listing (Cat. No. 193-EC4), Continued
132 Trip History 0144 SS L1 Current
133 Trip History 1145 SS L2 Current
134 Trip History 2146 SS L3 Current
135 Trip History 3148 SS GF Current
136 Trip History 4
137 Warn History 0
138 Warn History 1
139 Warn History 2
140 Warn History 3
141 Warn History 4
142 TripHistory Mask
143 WarnHistory Mask
➊ Series C (FRN 5.00 and Higher)
TripWarn History ➊ Tri p Snap shot ➊
Short-Circuit Ratings
To prevent electrical shock, disconnect from power source before
installing or servicing
Select the motor branch circuit protection that complies with the
National Electrical Code and any othergoverning regional and local
codes
The Bulletin 193/592 E3 Overload relay is suitable for use on circuits capable of delivering
not more than the RMS symmetrical amperes listed in the followign tables:
Publication 193-QR003B-EN-P - October 2009
29
Table 11: Standard Fault Short-Circuit Ratings per UL 508 and CSA 22.2, No. 14