the ArmorBlock Module
Connect the Wiring to the ArmorBlock Module
Communicate with Y
Configure Y
Manager Configuration T
Configure Y
Manager Configuration T
Reset Faults25
Configure Y
For this reference information
Default Configuration
Status indicators
Troubleshooting34
Specifications35
our ArmorBlock Module
our ArmorBlock Module Of
ool
our ArmorBlock Module Online Using the DeviceNet
ool
our ArmorBlock Module with EDS Files
fline Using the DeviceNet
3
8
10
11
17
28
See page:
14
34
This 1792 ArmorBlock I/O block module (Cat. No. 1792-IB8)
contains I/O circuits, a built-in power supply, and a built-in DeviceNet
I/O adapter. Because of its sealed housing, this 1792 I/O block requires
no enclosure. It is compatible with PLC or SLC programmable
controllers using DeviceNet scanners. The I/O values are accessible
from the PLC or SLC programmable controller data table.
This ArmorBlock module has no switches to set. You set module
parameters using the DeviceNet Manager Software (cat. no.
1787-MGR) or similar configuration tool.
ArmorBlock is a trademark of Allen-Bradley Co. Inc.
Publication 1792-5.2 – October 1996
ArmorBlock 8 Input Module2
European Union Directive Compliance
If this product is installed within the European Union or EEA regions
and has the CE mark, the following regulations apply.
EMC Directive
This apparatus is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) using a technical construction
file and the following standards, in whole or in part:
• EN 50081-2EMC – Generic Emission Standard, Part 2 –
Industrial Environment
• EN 50082-2EMC – Generic Immunity Standard, Part 2 –
Industrial Environment
The product described in this manual is intended for use in an industrial
environment.
Low Voltage Directive
This apparatus is also designed to meet Council Directive 73/23/EEC
Low Voltage, by applying the safety requirements of EN 61131–2
Programmable Controllers, Part 2 – Equipment Requirements and
Tests.
For specific information that the above norm requires, see the
appropriate sections in this manual, as well as the following
Allen-Bradley publications:
• Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
• Automation Systems Catalog, publication B111
Publication 1792-5.2 – October 1996
ArmorBlock 8 Input Module
Install Your ArmorBlock Module
Installation of the ArmorBlock module consists of:
• setting the node address in the ArmorBlock module
• mounting the ArmorBlock module
• connecting the wiring
• communicating with your module
• configuring the parameters
Set the Node Address
Each ArmorBlock comes with its internal program set for node address
63. To set the node address, you need the following:
• host computer with DeviceNet Manager Software (or similar
configuration software tool)
• 1770-KFD RS-232 module (or similar interface)
• suitable cables to connect the 1770-KFD to your module and to
connect the 1770-KFD to your host computer
3
Set the node address to meet your system requirements as follows:
1. Set up a system (as shown below) to communicate with your
ArmorBlock module.
Power
from 9V DC Power-Supply Adapter
1770-KFD
RS-232 module
open style connector to
sealed mini-female cable
host computer with the
DeviceNet Manager software
power supply
Publication 1792-5.2 – October 1996
ArmorBlock 8 Input Module4
2. Using DeviceNet Manager Software, go online using the “Setup
Online Connection” selection on the utility pulldown menu.
3. The DeviceNet Driver selection screen appears.
Select the driver for your application and click on .
4. The Driver configuration screen lets you:
• set the data rate
• set the interface adapter node address
• select the interface adapter serial port
• set interface adapter baud rate
Click on to go online.
Publication 1792-5.2 – October 1996
ArmorBlock 8 Input Module
5
5. The bar at the bottom of the screen will tell you when you go online.
6. At the utility pulldown, select “Node Commissioning.”
7. You can set the node address on the “Device Configuration – Node
Commissioning” screen. Note that the node address “out of the box”
setting is 63. Set the desired node address per your system
requirements.
Set new node
address here.
You can also set the data rate on this screen, if required. However,
your module is shipped with the “autobaud” parameter enabled.
This assures that the module will be at the correct data rate for any
network to which it is connected. To change the data rate, you must
first disable autobaud on the parameter screen, then return to the
“Device Configuration – Node Commissioning” screen and enter
the new data rate.
8. Click on
to apply the new node settings.
9. Repeat the above procedure to set the node addresses of any
additional ArmorBlock modules you want to install.
Publication 1792-5.2 – October 1996
ArmorBlock 8 Input Module6
Mount the ArmorBlock Module
Mount the block module directly to the machine or device. Complete
mounting dimensions are shown below. Note that the block dimensions
allow direct connection of a T-port tap (cat. no. 1485P-P1N5-j) to the
DeviceNet connector. (Refer to publication 1485-6.7.1 for cabling
details.)
The ArmorBlock module has a sloping top and a gap at the rear to
allow water or other liquids to run off during washdowns. The flow
through the gap prevents buildup of debris under the block.
Preferred mounting position is with the microconnectors pointing
down. However, the block can be mounted in any orientation.
Publication 1792-5.2 – October 1996
Mounting Dimensions
.
1.90
(48.3)
3.055
(77.6)
Inches
(Millimeters)
2.63
(66.7)
2.5
(63.5)
ADDRESS
NODE
ArmorBlock 8 Input Module
25
7
7
(184.2)
ARMORBLOCK
MOD/NET
INPUT
STATUS
FAULT
TE
RA
DATA
1792-IB8
I/O
4
mounting holes
for #10 screws
6.24
(158.5)
Block dimensions allow T
-port tap
connection directly onto connector
For washdown installations,
or excessively moist areas,
mount block with micro
connectors down.
7.74
(196.6)
Direction
of liquid flow
Publication 1792-5.2 – October 1996
ArmorBlock 8 Input Module8
DeviceNet mini connector
Connect the Wiring to the ArmorBlock Module
The block module uses quick disconnect, screw-on style connectors
for:
• I/O input wiring
• the DeviceNet connector
0
2
1
8 micro connectors for signal wiring
4
3
5
6
7
Micro plugs are included with your module. Use these plugs to cover
and seal unused ports.
Pinout diagrams for these connectors are shown below.
ATTENTION: All connectors must be securely
tightened to properly seal the connections against leaks
!
and maintain NEMA 4X and 6P requirements.
Publication 1792-5.2 – October 1996
ArmorBlock 8 Input Module
Connecting the Input Wiring
Connect input wiring to the micro connectors which screw into mating
connectors on the side of the block.
Make connections as shown below.
I/O Input Micro Connector
9
4
1
3
2
(View into socket)
Pin 1 = Sensor Source Voltage Positive
Pin 2 = Not used
Pin 3 = Negative/Return
Pin 4 = Signal
Connecting the DeviceNet Wiring
Connect DeviceNet wiring to the 5-pin mini connector on the end of
the block. Connections are shown below.
This ArmorBlock module acts as a slave in a master/slave environment.
It is both a “polled device” and a “change of state device.”
When configured as a polled device, a master initiates communication
by sending its polled I/O message to the ArmorBlock module. The 8
input module scans the inputs and fault bit producing a response that
reflects their status.
When configured as a “change of state” device, productions occur
when an input changes or an input source voltage fault occurs. If
neither has occurred within the “expected packet rate,” a heartbeat
production occurs. This heartbeat production tells the scanner module
that the ArmorBlock module is alive and ready to communicate.
Bit0706050403020100
ProducesI7I6I5I4I3I2I1I0
ProducesSReserved
Where: I = Input
S = Sensor source voltage fault
WordBitDescription
Produces100–07Input bits – bit 00 corresponds to input 0, bit 01 to input 1, and
Produces
Publication 1792-5.2 – October 1996
00–06Reserved
2
07Sensor source voltage fault bit – this bit is set (1) when the sensor
so on.
0 = input off; 1 = the input is on.
source voltage is faulted.
ArmorBlock 8 Input Module
Configure Your Armor Module Offline Using the
DeviceNet Manager Configuration Tool
To configure your ArmorBlock module offline:
• add the device to the network
• set the parameters for the device
• save the parameters to a file
Note: You cannot actually configure your device offline. You can set
and save the parameters to a file for downloading to the device when
you go online.
11
Publication 1792-5.2 – October 1996
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.