This ArmorBlock LP2 I/O module (Cat. No. 1792D-4BT4L P) is a standalone 24V dc I/O product which communicates via a DeviceNet network.
The sealed housing of this module requires no enclosure.
This module has 4 sinkin g inputs and 4 sourcing outputs accessed through
Y splitter cables. Four self-protected 24V dc outputs can provide up to
300mA each.
Package Contents
Your package contains:
• 1 ArmorBlock LP2 Module
• Installation Instructions
Publication 1792D-5.26 - January 1999
24 Sinking Input / 4 Output Module
European Union Directive Compliance
If this product has the CE mark it is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet
the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the followin g stand ards, in
whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial
Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage,
by applying the safety requirements of EN 61131-2 Programmable
Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines For Noise
Immunity, publication 1770-4.1
• Automation Syst em s Cata lo g, pu blication B1 11
Install Your ArmorBlock LP2 I/O Module
T o install the mo du le:
• Set the node address and baud rate.
• Mount the module .
• Connect the unit to the DeviceNet trunk and the auxilary power source.
• Connect the cord sets.
Set the Node Address
Set the node address using RSNetworx for DeviceNet software,
DeviceNetManager software, or another software configuration tool. The
module is equipped with AutoBaud detect. AutoBaud lets the module read
the settings already in use on your DeviceNet network and automatically
adjusts to follow those settings.
Publication 1792D-5.26 - January 1999
4 Sinking Input / 4 Output Module3
Install the Module
1. Attach the module using the dimensions shown below.
I0
I3
I2
Module Status
4.21 in
107mm
1.95 in
49.5mm
I1
Network Status
12in
305mm
0.25 in
6.25mm
1.02 in
26.0mm
2. Connect the grey DeviceNet cabl e to the DeviceNet trunk. Use the
1485P-P1R5-MN5 R1 T-Part tap to connect to round media. Use the
1485P-P1E4-R5 to connect to the Kwik Link flat media system.
Connect the Input / Output Cord Sets to the LP2 Module
This module uses 5 pin micro (12mm) style PCB mounted connectors.
Four micro caps cover the connectors on your module. Remove the caps
and connect your cord sets to the appropriate ports. This product has two
inputs or outputs per I/O connector. Use a “Y” splitter cable for access to
all I/O connections. For more informa tion on these cables, see the Product
Data guide publica ti on 1792-2.1.
Use the micro caps to cover and seal unused ports. Pinout diagrams for the
connectors are shown next.
Input Micro-Connector
2
1
5
3
4
2
1
5
3
4
1
Logic Ground is approximately 0.4V above De vic eNet V-measured at the modul e.
(View into Sockets)
Pin 1 Sensor Source Voltage
Pin 2 Input B
Pin 3 Return Logic Ground
Pin 4 Input A
Pin 5 Not Used
Output Micro-Connector
(View into Sockets)
Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxilary Power Ground
Pin 4 Output A
Pin 5 Not Used
1
41452
Publication 1792D-5.26 - January 1999
44 Sinking Input / 4 Output Module
ATTENTION:
• Make sure to connect the pro pe r color coded cables togeth er.
!
DeviceNet cab le sh ould connect to Device Net cables and
auxillary outputs should match auxillary outputs.
• Make sure all connectors and caps are securely tightened
to properly seal the connections against leaks and
maintain IP67 requirements
• For maximum noise immunity, input and output cable
return wires must be properly terminated. When inputs
and outputs are connected in l oopback, return wires
should be connected together.
• I/O cable length should be less than 30 meters.
I/O connectors for this module are shown below.
I0
Connector A
O0
I1
O1
Input 1
I2
Connector B
Input 2
Input 3
Network Status
O2
I3
O3
Auxiliary Power
Module Status
Connector C
Output 0Input 0
Output 1
Connector D
Output 2
Output 3
30706-M
Output Power and DeviceNet Cables
Refer to the DeviceNet Cable Planning and Installation Manual for more
information on output power and DeviceNet cables for your application.
Publication 1792D-5.26 - January 1999
4 Sinking Input / 4 Output Module5
Communicate With Your ArmorBlock LP2 I/O Module
This ArmorBlock module’s I/O is exchanged with the master through a
polled, change of state, or cy clic connection.
The module consumes and produces I/O data as follows:
Cyclic - allows configuration of the bl ock as an I/O client. The bl ock will
produce and consume its I/O cyclicall y at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 4 input / 4 output module consumes the
message, update s outputs, an d produ ces a resp onse. The respon se has inp ut
data, and the status of the Auxiliary power.
Change of state - productions occur when an input changes. If no input
change occurs within th e expected packet rate, a hear tbeat production
occurs. This heartbeat production tells the scanner module that the I/O
module is alive and ready to communicate. Consumption occurs when data
changes and the master produces new output data to the I/O module.
Refer to the table below for the word/bit definitions.
Input status bits: When the bit is set (1), the input is on. Bit
00 corresponds to input 0, bit 01 corre sponds to i nput 1, bit
02 corresponds to input 2, bit 03 corresponds to input 3.
04
Reserved
Produces 0
Consumes 0
05
Reserved
06
Output Powr Fault (OPWR): When the b it is set (1) auxilary
power is not present.
07
Reserved
00-03
Output bits: When the bit is set (1 ), the output will be turned
on. Bit 00 corresponds to output 0, bit 01 corresponds to
output 1, bit 02 to output 2, bit 03 to output 3.
04-07
Reserved
The DeviceNet Network uses advanced network technology, producer/
consumer communication, to increase network functionality and
throughput. Visit our web s ite at h ttp://w ww.ab. co m/netw or ks fo r producer/
consumer technology information and updates.
Publication 1792D-5.26 - January 1999
4 Sinking Input / 4 Output Module7
Troubleshoot with the Indicators
This module has the following indicators:
• Network status indicator
• Module status indicator
• Auxiliary Power indicator
• Individual point stat us indicators for inputs 0, 1, 2, and 3 and outputs 0,
1, 2, and 3.
Point indicators
for inputs 0
and 1
Connector A
Point indicators
for inputs 2 and
3
Connector B
DeviceNet Indicators
Module Status Indicator
IndicationStatus
NoneNo Power
Green
Blinking
Solid
Red
Blinking
Solid
Needs Commissioning
Operating Normal
Recoverable Fault
Unrecoverable Fault
Auxiliary Power
Network Status
I0
I1
I2
I3
O0
O1
O2
O3
Module Status
Point indicators
for outputs 0
and 1
Connector C
Point indicators
for outputs 2
and 3
Connector D
30706-M
Publication 1792D-5.26 - January 1999
84 Sinking Input / 4 Output Module
Network Status Indicator
IndicationStatus
NoneNot On-line
Green
Blinking
Solid
Red
Blink
Solid
Auxiliary Power
IndicationStatus
NoneNo Auxiliary Power
Green
SolidAuxiliary Power Present
I/O Status Indicators
On-line/No Connections
On-line/Connected
Connection Timed Out
Failed Communication: A duplicate
node address exists or module is at the
wrong baud rate.
Function Module Status Indicator
OutputsGreen
InputsGreen
Green
Green
Point Indicator
None
Yellow
None
Yellow
Condition
Output not energized
Output energized
No valid input
Valid input
For more information on indications see the Product Data publication
1792-2.1.
Inputs per block 4 - 3 wire or dry contact PNP devices or 2 - 4 wire
Sensor Source Current (per input)50mAOn-state Voltage 25V dc10V dc
On-state Current10mA2mA
Off-state Voltage5V dc
Off-state Current1.5mA
Sourcing Output Specifications MaxMin
Outputs per block 4 sourcing outputs labeled O0, O1, O2, and O3
Output Auxiliary Voltage30V10V
On-state Voltage Drop1VOn-state Current0.3AOff-state Leakage1.5mAModule Current (all outputs)1.2ASurge Current - for 10ms,
repeatable every 2s
No Load Sense Current (On-state)0.18A-
General Specifications
IndicatorsNetwork Status - red/green
Communication Rate• 125Kbps @ 500 meters(1600 feet) for thick
DeviceNet Power Voltage
Current
Auxiliary Power Voltage
Current
Dimensions (assembled to base)
inches - (Millimeters)
PNP devices
0.6A-
Module Status - red/green
Auxiliary Power - green
Point LED - yellow
cable, flat media length 375 meters
• 250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
• 500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
o
-25 to 60
-25 to 80
(-13 to 140oF)
o
C (-13 to 176OF)
Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11(+1)ms pulse width
Tested 10g @ 10-500Hz per IEC 68-2-6
ConductorsPublication DN-6.7.2
EnclosureMeets or exceeds IP67
Agency Certification
(when product is marked)
• CE marked for all applicable directives
This product has been tested at an Open DeviceNet Vendor Association,
Inc. (ODVA) authorized independent test laboratory and found to comply
with ODVA Conformance Test Software Composite Test Version 11.
ArmorBlock, ArmorBlock LP2 and DeviceNetManager are trademarks of Rockwell Automation.
Publication 1792D-5.26 - January 1999
4 Sinking Input / 4 Output Module11
Publication 1792D-5.26 - January 1999
124 Sinking Input / 4 Output Module
Publication 1792D-5.26 - January 1999PN 955134-80
1999 Rockwell International. All Rights Reserved. Printed in USA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.