This ArmorBlock LP2 I/O module (Cat. No. 1792D-2B 2LP) is a standalone 24V dc I/O product which communicates via a DeviceNet network.
The sealed housing of this module requires no enclosure.
This model has 2 sinking inputs and 2 sourcing outputs. Two self-protected
24V dc outputs can provide up to 300mA each.
Package Contents
Your package contains:
• 1 ArmorBlock LP2 Module
• Installation Instructions
Publication 1792D-5.25- January 1999
22 Sinking Input / 2 Output Module
European Union Directive Compliance
If this product has the CE mark it is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet
the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the followin g stand ards, in
whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial
Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage,
by applying the safety requirements of EN 61131-2 Programmable
Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines For Noise
Immunity, publication 1770-4.1
• Automation Syst em s Cata lo g, pu blication B1 11
Install Your ArmorBlock LP2 I/O Module
T o install the mo du le:
• Set the node address and baud rate.
• Mount the module .
• Connect the unit to the DeviceNet trunk and the auxilary power source.
• Connect the cord sets.
Set the Node Address and Baud Rate
Set the node address using RSNetworx for DeviceNet software,
DeviceNetManager software, or anoth e r configuration t ool. The module
is equipped with AutoBaud detect. AutoBaud lets the module read the
settings already in use on your DeviceNet network and automatically
adjusts to follow those settings.
Publication 1792D-5.25- January 1999
2 Sinking Input / 2 Output Module3
Install the Module
1. Attach the module using the dimensions shown below.
I0
I3
I2
Module Status
4.21 in
107mm
1.95 in
49.5mm
I1
Network Status
12in
305mm
0.25 in
6.25mm
1.02 in
26.0mm
2. Connect the grey DeviceNet cabl e to the DeviceNet trunk. Use the
1485P-P1R5-MN5R1 T-Part tap to make the connection to round
media. Use the 1485P-P1E4-R5 to connect to the Kwik Link flat media
system.
Connect the Input / Output Cord Sets to the LP2 Module
This module uses 5 pin micro (12mm) style PCB mounted connectors.
Four micro caps cover the connectors on your module. Remove the caps
and connect your cord sets to the appropriate ports.
Use the micro caps to cover and seal unused ports. Pinout diagrams for the
connectors are shown next.
Input Micro-Connector
2
1
5
3
4
2
1
5
3
4
1
Logic Ground is approximately 0.4V above De vic eNet V-measured at the modul e.
(View into Sockets)
Pin 1 Sensor Source Voltage
Pin 2 Not Used
Pin 3 Return Logic Ground
Pin 4 Input A
Pin 5 Not Used
Output Micro-Connector
(View into Sockets)
Pin 1 Not Used
Pin 2 Not Used
Pin 3 Auxilary Power Ground
Pin 4 Output A
Pin 5 Not Used
1
41452
Publication 1792D-5.25- January 1999
42 Sinking Input / 2 Output Module
ATTENTION:
• Make sure to connect the pr oper color coded cables
!
together . DeviceNet cable shou ld connect with Dev iceNet
cables and auxillary ouput should match auxillary output.
• Make sure all connectors and caps are securely tightened
to properly seal the connections against leaks and
maintain IP67 requirements
• For maximum noise immunity, input and output cable
return wires must be properly terminated. When inputs
and outputs are connected in l oopback, return wires
should be connected together.
• I/O cable length should be less than 30 meters.
I/O connectors for this module are shown below.
I0
O0
Connector A
Input 0
I1
Connector B
O1
Input 1
Auxiliary Power
Network Status
Module Status
Connector C
Output 0
Connector D
Output 1
41454
Connect Output Power and DeviceNet Cables
Output power and DeviceNet cables are described in the installation
publication for the cable base assembly of yo ur choice. Refer to the
DeviceNet Cable Planning and Installati on Manual (DN-6.7.2) .
Communicate With Your ArmorBlock LP2 I/O Module
This ArmorBlock module’s I/O is exchanged with the master through a
poll, change of state, or cyclic connection.
The module consumes and produces I/O data as follows:
Type of I/O ConnectionsConsumesProduces
Cyclic1 Byte1 Byte
Publication 1792D-5.25- January 1999
2 Sinking Input / 2 Output Module5
Polled1 Byte1 Byte
Change of State1 Byte1 Byte
Cyclic - allows configuration of the bl ock as an I/O client. The bl ock will
produce and consume its I/O cyclica l ly at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the ArmorBlock module. This 2 input / 2 output module
consumes the message, updates output s, and produces a response. The
response has input data and the status of the Auxiliary power.
Change of state - productions occur when an input changes. If no input
change occurs within th e expected packet rate, a hear tbeat production
occurs. This heartbeat production tell s the scanne r modul e that the
ArmorBlock LP2 module is alive and ready to communicate. Consumption
occurs when data changes and the master produces new output data to the I/
O block.
Refer to the table below for the word/bit definitions.
Bit0706050403020100
Produces 0
Consumes 0
Where: I = InputO = OutputRSVD = Reserved OPWR = Output Power (Auxiliary Power)
Input status bits: When the bit is set (1), the input is on. Bit
00 corresponds to input 0, bit 01 to input 1.
02-03
Reserved
04
Reserved
05
Reserved
06
Output power fault (OPWR): When the bit is set (1) auxilary
power is not present.
07
Input Short Circuit (ISC)
00-01
Output bits: When the bit is set (1), the output will be turned
on. Bit 00 corresponds to output 0, bit 01 corresponds to
output 1.
02-07
Reserved
The DeviceNet Network us es advanced network technology, producer/
consumer comm unication, to incr ease network functionality and
throughput. Visit our web site at http:// www.ab.com/n etworks for producer/
consumer technology informatio n and updates.
Publication 1792D-5.25- January 1999
62 Sinking Input / 2 Output Module
Troubleshoot with the Indicators
This module has the following indicators:
• Network status indicator
• Module status indicator
• Auxiliary Power indicator
• Individual point stat us indicators for inputs 0, 1 an d ou tpu t s 0, 1
Point indicator for input I0
Connector A
Point indicator for input I1
Connector B
DeviceNet Indicators
Module Status Indicator
IndicationStatus
NoneNo Power
Green
Blinking
Solid
Needs Commissioning
Operating Normal
Red
Blinking
Solid
Recoverable Fault
Unrecoverable Fault
Network Status Indicator
IndicationStatus
NoneNot On-line
Green
Blinking
Solid
Red
Blink
Solid
On-line/No Connections
On-line/Connected
Connection Timed Out
Failed Communication: A duplicate node addr ess exi sts or
module is at the wrong baud rate.
Auxiliary Power
Network Status
I0
I1
O0
O1
Module Status
Point indicator for output O0
Connector C
Point indicator for output O1
Connector D
41454
Publication 1792D-5.25- January 1999
72 Sinking Input / 2 Output Module
Auxiliary Power
IndicationStatus
NoneNo Auxiliary Power
Green
SolidAuxiliary Power Present
I/O Status Indicators
Function Module Status IndicatorPoint Indicator Condition
Inputs per block 2 - 3 wire or dry contact PNP
Sensor Source Current (per input)100mAOn-state Voltage25V dc10V dc
Off-state Voltage5V dc
On-state Current10mA2mA
Off-state Current1.5mA
Sourcing Output Specifications MaxMin
Outputs per block 2 labeled O0 and O1
Output Auxiliary Voltage30V10V
On-state Voltage Drop1VOn-state Current0.3AOff-state Leakage1.5mAModule Current (all outputs)0.6ASurge Current - for 10ms,
repeatable every 2s
No Load Sense Current (On-state)0.18A-
General Specifications
IndicatorsNetwork Status - red/green
Module Status - red/green
Auxiliary Power - green
Point LED - yellow
0.6A-
Publication 1792D-5.25- January 1999
82 Sinking Input / 2 Output Module
Communication Rate• 125Kbps @ 500 meters(1600 feet) for thick
DeviceNet Power Voltage
Current
cable, flat media length 375 meters
• 250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
• 500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters
25V dc
11V dc min
125mA (no sensors)
300mA (full load)
Auxiliary Power Voltage
Current
Dimensions (assembled to base)
Inches (Millimeters)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
1.023H x 2.7w x4.72D
(26)H x (68.5)W x (120)D
-25 to 60
-25 to 80
Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11(+1)ms pulse width
Tested 10g @ 10-500Hz per IEC 68-2-6
30V dc
0.6A max
o
(-13 to 140oF)
o
C (-13 to 176OF)
10V dc
0.6A max
ConductorsPublication DN-6.7.2
EnclosureMeets or exceeds IP67
Agency Certific ation
• CE marked for all applicable directives
(when product is marked)
This product has been tested at an Open DeviceNet Vendor Association,
Inc. (ODVA) authorized independent test laboratory and found to comply
with ODVA Conformance Test Software Composite Test Version 11.
ArmorBlock, ArmorBlock LP2 and DeviceNetManager are trademarks of Rockwell Automation.
Publication 1792D-5.25- January 1999PN 955134-81
1999 Rockwell International. All Rights Reserved. Printed in USA