Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
available from
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation Publication 150-UM009D-EN-P - February 20113
Table of Contents
4Rockwell Automation Publication 150-UM009D-EN-P - February 2011
Chapter
Base
Controller
Fault
Contactor
1
Introduction
This manual provides and overview of the installation, set-up, and typical
operation of the Allen-Bradley hydraulic elevator and escalator starter. This solidstate starter solution is designed to operate 3-phase standard squirrel cage
induction motors and can be connected to a 6 or 12 lead Wye-Delta or standard 3
or 9 lead motors. Through the use of LINE or INSIDE-THE-DELTA control,
the solid-state solution can provide ultimate control of the motor. The advantages
of a solid-state solution include the following:
• Provides smooth motor starting.
• Reduces current surges on weak electrical systems.
• Reduces starting torque of the motor, wich helps to reduce mechanical
stress on system components.
• Helps meet both local and regional electrical codes when reduced voltage
starting is a requirement.
• Eliminates voltage and current spikes associated with traditional WyeDelta starters.
• Maximizes the life of the motor with reduced electrical strain.
• Reduces general system maintenance requirements for improved uptime.
Component Overview
The starter is made up of two components, the base controller and a fault
contactor.
Figure 1 - Bulletin 150-E Components
Rockwell Automation Publication 150-UM009D-EN-P - February 20115
Chapter 1 Introduction
Base Controller
The base controller is a standard product that uses a number of intelligent
features to provide advanced motor control and simple diagnostics. The base
controller consists of the elements necessary to control the motor. These elements
include:
• a main micro-processor
• current sensing
• built-in adjustable overload
• solid-state power modules, and
• electro-mechanical bypass contacts.
Through the use of simple DIP switch configuration, the product can be
configured for a variety of modes. The default configuration uses the built-in
current sensing to limit current to the motor during starting. Once up to speed,
the base controller transitions to the run mode by transitioning to internal bypass
contactors and changing the state of the auxillary contact. The internal bypass
contactor provides decreased heating during run and removes the SCRs from the
circuit.
Fault Contactor
The fault contactor is controlled through the fault contact of the controller.
When control power is applied to the controller, the normally open fault contact
closes and applies control power to the coil of the contactor. The fault contact
will open, removing power from the fault contactor, and thus disabling the motor
during any one of the following events:
• The power is removed from the controller.
• The motor has developed a problem including overloading due to one of
the following:
– Mechanical or electrical reasons
– Ground faults or
– Motor short circuits.
• The starter has detected an internal problem such as a shorted SCR or
overtemperature condition.
6Rockwell Automation Publication 150-UM009D-EN-P - February 2011
Introduction Chapter 1
Function Overview
The Bulletin 150-E elevator panel provides solution to both advanced motor
control and simple diagnostics. The following information provides a brief
overview of the basic product features.
Motor Control
Current Limit Through the use of internal current sensors, the SMC™ will regulate the current
Soft StartThe voltage is ramped from an initial set point to full voltage over the programmed
Soft StopThe voltage is ramped down from full voltage and applied to the motor over a
level applied to the motor over the programmed period of time. This type of motor
control produces a slow start and insures that the current does not exceed the
programmed level. This is the standard configuration of the device and aligns well
with traditional applications.
period of time. This type of motor control produces a smooth start in less time
than the current limit setting. However, the current is not restricted.
programmed period of time. The result is a smooth stop.
Diagnostics
OverloadProvides protection of the motor for over current conditions. This feature offers a
OverTemperature
Phase
Reversal
Phase Loss/
Open Load
Phase
Imbalance
Shorted SCREach time the SMC initiates a start, it checks to see if the SCRs are operating
user-selectable setting called the trip class, which can be used to accommodate
different applications and motor types. When the motor draws more than the
nominal value of current for a period of time, the device will fault on a motor
overload fault.
A built-in self-monitoring method for detecting a SCR over-temperature condition. If
the internal temperature exceeds a design threshold, the device will fault on a SCR
Overtemp fault.
The user can select the phase relationship of the incoming power. If this phase
relationship changes, the device will fault indicating a problem.
When any one of the incoming 3 phases are lost, the controller will fault indicating
a phase loss condition has occurred.
When enabled, will detect if a phase imbalance condition exists and fault the unit.
A phase imbalance is defined as a 65% differential between the highest and
lowest phase for more than 3 seconds.
correctly. If the controller is unable to properly turn on and off any one of the SCRs,
the device will fault on a Shorted SCR fault.
Rockwell Automation Publication 150-UM009D-EN-P - February 20117
Chapter 1 Introduction
Starter Selection
For 6 or 12 Lead Wye-Delta Wound Motors
The following table lists the catalog numbers that can be used with 6 or 12 lead
Wye-Delta motors. For proper operation, the connection should be verified
during installation. Sample connection diagrams for INSIDE-THE-DELTA
connected motors are included in the Installation and Wiring section found later
in this manual.
Table 1 - Cat. Nos. For Use with 6- or 12-Lead Wye-Delta Motors
Motor FLA must fall within the specified range to operate correctly.
➊
Overload Range ➊
Control Voltage Cat. Nos.
150-E32NCE-FC150-E32NCA-FC
150-E74NCE-FC150-E74NCA-FC
150-E234NCE-FC150-E234NCA-FC
For 3- or 9-Lead Closed Delta-Type Motors
The following table lists the catalog numbers that can be used with 3- or 9-lead
closed delta type motors. For proper operation, the connection should be verified
during installation. Sample connection diagrams for LINE connected motors are
included in the Installation and Wiring section found later in this manual.
Table 2 - Cat. Nos. For Use with 6 or 12 Lead Closed Delta-Type Motors
8Rockwell Automation Publication 150-UM009D-EN-P - February 2011
Installation & Wiring
4.56
(115.7)
5.67
(144.0)
7.01
(178.0)
6.50
(165.1)
5.00
(127.0)
4X Ø 0.220 thru
(5.6)
CAT. XXXXXXXX SER. B
T6 T4 T5
1
Chapter
2
Unpacking
Mounting
Dimensions
Prior to installation, unpack the starter panel from its packaging and perform a
complete visual inspection of the panel. Inspect all components including the
controller, wiring, and fault contactor for damage related to shipping and
handling. Claims for damage must be made to the carrier as soon as possible after
receipt of the shipment.
The small footprint of the starter panel makes it ideal for mounting in the same
space previously occupied by legacy solid state starters and traditional Full
Voltage starters. The starter panel does not require mounting requirements
beyond the basic footprint of the panel.
The product may incorporate a small cooling fan. There are no additional cooling
requirements for the product. However, it is good practice to leave at least 6
inches (15.24 cm) of free space above and below the unit for ideal air flow.
Figure 2 - Panel Dimensions for 32, 51, & 64 A Elevator Panels
This screw is intended to secure a prepared bonding conductor (e.g., a bonding conductor with a crimped-
➊
Rockwell Automation Publication 150-UM009D-EN-P - February 20119
on lug) or a suitable terminal for connection of an unprepared bonding conductor (e.g., a bonding
conductor with a stripped wire end). This screw is not intended for a direct field wiring connection of an
unprepared bonding conductor or equipment grounding conductor.
Chapter 2 Installation & Wiring
8.86
(225.0)
5.82
(147.9)
9.45
(240.0)
8.46
(215.0)
8.07
(205.0)
4X Ø 0.260 Thru
(6.6)
CAT. XXXXXXXX SER. B
1
T6 T4 T5
20.28
(515.0)
8.52
(216.4)
1
4X Ø 0.343 thru
(8.7)
CAT. XXXXXXXX SER. B
14.25
(362.0)
13.00
(330.2)
19.27
(489.5)
T6 T4 T5
Figure 3 - Panel Dimensions for 74, 104, & 147 A Elevator Panels
➊
This screw is intended to secure a prepared bonding conductor (e.g., a bonding conductor with a crimped-
on lug) or a suitable terminal for connection of an unprepared bonding conductor (e.g., a bonding
conductor with a stripped wire end). This screw is not intended for a direct field wiring connection of an
unprepared bonding conductor or equipment grounding conductor.
Figure 4 - Panel Dimensions for 234 A Elevator Panels
➊
This screw is intended to secure a prepared bonding conductor (e.g., a bonding conductor with a crimped-
on lug) or a suitable terminal for connection of an unprepared bonding conductor (e.g., a bonding conductor
with a stripped wire end). This screw is not intended for a direct field wiring connection of an unprepared
bonding conductor or equipment grounding conductor.
10Rockwell Automation Publication 150-UM009D-EN-P- February 2011
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.