REMKO SuperTec-Monitor User Manual

Page 1
SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Operation · Fault codes · Troubleshooting
Edition GB – W12
Page 2
Page 3
Contents
Safety notes
Environmental protection and recycling
Warranty
Transport and packaging
System description
Decommissioning
Operation
Settings of the system components
Troubleshooting/Fault codes
4
4
4
5
5
6
6
7-19
20-31
Made by REMKO
Read this installation manual carefully before commissioning / using the device!
These instructions are an integral part of the system and must always be kept in the vicinity of the installation location or on the unit itself. This operating manual is a translation of the German original.
Subject to modifications; no liability accepted for errors or misprints!
3
Page 4
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Safety notes
Carefully read the operating manu­al before placing the unit in service for the first time. It contains useful tips and notes such as ha�-ha�­ard warnings to prevent injury and material damage. Failure to follow the directions in this manual can result in endangerment to persons, the environment and the equip­ment itself and will void any claims for liability.
Keep this manual and the re-
frigerant data sheet near to the units.
The units and components
should be set up and installed only by qualified personnel.
The set-up, connection, and
operation of the units and their components must be in accord­ance with the operating condi­tions stipulated in this manual and comply with all applicable local regulations.
Mobile units must be set up
securely on suitable surfaces and in an upright position. Station­ary units must be permanently installed before operation.
Modification of units and com-
ponents supplied by REMKO is not permitted and can cause malfunctions.
Units and components may
not be operated in areas where there is an increased risk of damage. Observe the minimum clearances.
The electrical supply is to be
adapted to the requirements of the units.
The operational safety of the
units and components is only as­sured if they are fully assembled and used as intended. Safety devices may not be modified or bypassed.
Do not operate units or compo-
nents with obvious defects or signs of damage.
All housing parts and openings
in the unit, e.g. air intakes and outlets, must be free of foreign objects, fluids, or gases.
The units and components must
be kept an adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
Touching some parts of the unit
can result in burns or other inju­ries.
Installation, repair and mainte-
nance work may be carried out only by authorised specialists. Visual inspections and cleaning can be performed by the opera­tor as long as power is discon­nected from the equipment.
To preclude any danger from the
unit, take appropriate ha�ard­prevention measures when performing installation, repair or maintenance work or cleaning the units.
The units or components
are not to be exposed to any mechanical stresses, extreme levels of humidity or direct sunlight.
Environmental protection and recycling
Disposing of packaging
All products are packed for trans­port in environmentally friendly materials. You can make a valuable contribution to reducing waste and sustaining raw materials by only disposing of packaging at ap­proved collection points.
Disposing of the units and their components
Only recyclable materials
are used in the manufac­ture of the units and components. Help protect the environment by ensuring that the units or com­ponents (for example batteries) are not disposed of in household waste, but only in accordance with local regulations and in an environ­mentally safe manner, e.g. using authorised disposal and recycling specialists or council collection points.
Warranty
The precondition for possible warranty claims is that the ordering party or their representa­tive fully complete the warranty reg­istration card and commissioning report included with the unit, at the time when the equipment is purchased and commissioned, and return it to REMKO GmbH & Co. KG.
The warranty conditions are listed in the "General terms and condi­tions". Furthermore, only the par­ties to a contract can strike special agreements beyond these condi­tions. For this reason, please contact your contract partner in the first instance.
4
Page 5
Transport and packaging
The equipment is delivered in sturdy transport packaging. Immediately check the equipment on delivery and make note of any damage or missing parts on the delivery note and inform the for­warding agent and your contractual partner. No warranty can be assumed for later claims.
Description
With the REMKO SYSTEM MONITOR, REMKO is offering an external display unit for CMF/ CMT outdoor units, which makes it both simple and convenient to query operating data from all system components. The REMKO SYSTEM MONITOR is equipped with a DIP switch (SW2) and a two-digit, seven-segment LED display. During fault-free normal operation this shows the operating status, and in the event of a fault shows details on which faults have occurred on the various system components. Using DIP switch SW2 on the REMKO SYSTEM MONITOR, is it possible to per­form targeted diagnostics. To do so, it is necessary to connect the supplied cable to the CNM con­nector on the control board of the CMF/CMT outdoor unit. In the following pages, you will find the settings for SW2 and the associ­ated normal value ranges of the system monitor.
SYSTEM MONITOR for REMKO SuperTec Inverter
The REMKO SYSTEM MONITOR offers you the option to monitor your system components electroni­cally on the outdoor unit. You can query the operating data of all sys­tem components, enabling you to perform targeted troubleshooting, and quickly and easily resolve the cause of the fault. In the following text, this function is identified as the System Monitor, which offers targeted querying of temperatures, pressures, voltages, etc.
NOTE
NOTE
DIP switch SW2 is located on the circuit board of the REMKO SYSTEM MONITOR
The REMKO SYSTEM MONI­TOR is not included in the scope of delivery of the inverter heat pump, and must be or­dered separately. The REMKO SYSTEM MONITOR can be used with all outdoor units in the CMF/CMT range. You can find a detailed list of all the fault codes from page 18 onwards
5
Page 6
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Decommissioning Operation
Shut down the system using the heat pump manager.
Switch off the power supply of the outdoor unit.
Remove tor for the SYSTEM MONITOR from the CMN socket on the control board of the outdoor unit.
Switch the power supply of the outdoor unit back on.
Place the system back into service using the heat pump manager.
the supplied connec-
SYSTEM MONITOR for REMKO SuperTec Inverter
Shut down the system using the heat pump manager.
Switch off the power supply of the outdoor unit.
Remove the right side panel.
This is achieved by undoing three screws on the panel and then pulling off the panel in a downwards direction.
Connect the SYSTEM MONI-
TOR using the supplied connec­tor to the CMN socket on the control board of the outdoor unit.
Switch the power supply of the outdoor unit back on.
Place the system back into service using the heat pump manager.
DIP switch SW2 allows targeted
diagnostics to be performed
From page 7 onwards, you can
find a precise description of the associated normal value ranges of the System Monitor.
In the event of a fault, you can
find a precise fault description with cause and remedy under the "Fault codes" section.
6
Page 7
DIP switch SW 2 during normal operation
Switch off the power supply of the outdoor unit.
To do so, set switches 1-6 of SW2 to their initial setting. All switches in the OFF position
Seven-segment LED display
LEDs flash during normal opera­tion
Remove
the supplied connec­tor for the SYSTEM MONITOR from the CMN socket on the control board of the outdoor unit.
Switch the power supply of the outdoor unit back on.
Place the system back into serv-
ice using the heat pump manager.
The initial setting of DIP switch SW2 in normal operation looks like this:
ON
1 2 3 4 5 6
When the power supply is switched on , the LEDs flash while the air conditioning system is car­rying out an internal system check. This lasts max. 4 minutes.
LED display lights up during normal operation
1. During fault-free normal operation, and with DIP switch SW2 1-6 set to OFF, the first digit of the LED shows the operating mode (Off, Cooling, Heating, Defrost)
First digit: operating mode
Display Operating mode
O OFF/Fan
C Cooling/Drying
H Heating
d Defrost
Interval:
1 second
and the second digit shows the status of the condenser and solenoid valves. You can find detailed descrip tions in the following tables.
2. If a fault occurs (the condenser is switched off by the protective device) the fault code for the particular fault appears on the LED display. This fault code will remain on the display until the condenser is restarted.
Second digit: switching position of the control relay, relay output
Display
Preheating
mode
Condenser
Four-way
valve
Solenoid
valve
0 - - - ­1 - - - ON 2 - - ON ­3 - - ON ON 4 - ON - ­5 - ON - ON 6 - ON ON ­7 - ON ON ON
7
Page 8
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
LED display flashes when a fault has occurred
If the condenser is switched off by a protective device after a fault has occurred, the LED display al­ternates between showing the unit address of the air conditioner in question and the fault code.
Display Description (during operation)
U1 Fault on the high pressure switch, 63H was triggered U2 Hot gas temperature too high, lack of refrigerant U3 Hot gas temperature sensor TH 4 detected open circuit /short-circuit U4 Temperature sensor TH3, TH6, TH7, TH8 in outdoor unit detected open circuit/short-circuit U5 Cooling fin temperature sensor detected open circuit/short-circuit U6 Fault in the power module (inverter) U7 Overheating fault; hot gas temperature too low UF Condenser stopped due to overcurrent (condenser disabled)
UH Fault on the current sensor
UL Fault on the low pressure switch, 62L was triggered UP Condenser stopped by overcurrent
A0-A7 Data transmission fault: priority signal on the M-net
Address of the
malfunctioning
air conditioner
Interval:
1 second
Fault code
Display Description (during operation)
F3 Connector 63L (red) is disconnected F5 Connector 63H (yellow) is disconnected F9 Both connector 63L and 63H are disconnected E8 Data transmission fault: outdoor unit is not receiving any signals from the indoor unit E9 Data transmission fault: outdoor unit is not transmitting any signals to the indoor unit
EA Wiring fault in the interior/exterior control cables: too many indoor units (max. 4)
Eb Wiring fault in the interior/exterior control cables: polarity reversed, cable detached Ec Timeout on system startup
E0-E7 Data transmission fault: other without outdoor unit
8
Page 9
Switch assignment of DIP switch SW2
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Line temperature TH3
-40 – 90
Hot gas temperature TH4 3 – 217
-40 – +90 If the temperature sensor measures values below 0°C, the display switches between the sign, the value, and 2 spaces.
Example: TH3 = -10°C:
0.5 s 0.5 s 2 s „- “ „10“ „ “
3 – 217 If the temperature sensor measures values above 99°C, the display switches between the 100s digit, 10s and 1s dig­its, and 2 spaces.
Example: TH4 = 105°C:
0.5 s 0.5 s 2 s „ 1“ „05“ „ “
°C
°C
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Fan speed (outdoor unit) 0 – 10
Number of switch on/off pro­cedures of the condenser 0 – 9999
0 – 10
0 – 9999 If the number is above 99, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces. Ex­ample: 42500 switching proc.: 425 × 100
0.5 s 0.5 s 2 s „ 4“ „25“ „ “
Levels / Steps
X 100
9
Page 10
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Condenser operating time 0 – 9999
Operating current of the con­denser 0 – 50
0 – 9999 If the number is above 99, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Example: 245:
0.5 s 0.5 s 2 s „ 2“ „45“ „ “
0 – 50 (without decimal places) A
10 hrs
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Condenser operating frequency 0 – 225
Opening width of the LEV-A 0 – 480
0 – 225 If the condenser operating frequency is over 99, the display switches between the 100s digit, 10s and 1s dig­its, and 2 spaces.
Example: 125 H�:
0.5 s 0.5 s 2 s „ 1“ „25“ „ “
0 – 480 If the opening width of the LEV-A is over 99 impulses, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces. Ex­ample: 150 impulses:
0.5 s 0.5 s 2 s „ 1“ „00“ „ “
H�
Impulses
10
Page 11
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
New fault message on the outdoor unit (1) The last message in the fault list is deleted, and the remain­ing messages are moved down one.
Operating mode before fault stop
Fault message "00" is not moved „00“ Flashing: fault message will be moved Constant: movement cancelled
Code for operating mode be­fore fault stop Fault code is displayed if all switches on DIP switch SW2 are in the OFF position.
ON
1 2 3 4 5 6
Fault code
ON
112233445
ON
Line temperature TH3 before fault
-40 – 90
6
Condenser or hot gas tempera­ture TH4 before fault
5
6
3 – 217
-40 – +90 If the temperature sensor measures values below 0°C, the display switches between the sign, the value, and 2 spaces. Ex­ample: TH3 = -15°C:
0.5 s 0.5 s 2 s „- “ „15“ „ “
3 – 217 If the temperature sensor measures values above 99°C, the display switches between the 100s digit, 10s and 1s dig­its, and 2 spaces.
Example: TH4 = 130°C:
0.5 s 0.5 s 2 s „ 1“ „30“ „ “
°C
°C
11
Page 12
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1
2
3
4
5
Operating current of the con­denser before fault 0 – 20
List of the latest faults (1) Alternating display of unit ad­dress and fault code
0 – 20 A
If there are no fault messages, the display switches between "00" and "– –"
Fault code
6
ON
1
ON
1
List of older faults (2) Alternating display of unit ad­dress and fault code
2
3
4
5
6
Duration of test operation 0 – 120
2
3
4
5
6
If there are no fault messages, the display switches between "00" and "– –"
0 – 120 If the duration is over 99 min., the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Example: 105 min.:
0.5 s 0.5 s 2 s „ 1“ „05“ „ “
Fault code
Minutes
12
Page 13
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1
2
3
4
5
Unit output Display takes the form of a
capacity code
Unit output: capacity code CMF80/90: 14 CMF 140/150: 25 CMT100: 14 CMT150: 25
Settings on the outdoor unit
1s digit: (Defrosting mode) 0 = Standard 1 = For high humidity
Capacity code
6
10s digit (Operating mode) 0 = Heat pump 1 = Cooling unit
(Single/three-phased) 0 = Single-phased 2 = Three-phased
ON
1
ON
1
Temperature sensor TH2
-39 – 88
2
3
4
5
6
Vaporiser/condenser tempera­ture sensor of the indoor unit TH5
2
3
4
5
6
-39 – 88
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign and the value.
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign and the value.
°C
°C
13
Page 14
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Heat exchanger temperature sensor on the outdoor unit (two-phase mixture) TH6
-39 – 88
Outdoor temperature TH7
-39 – 88
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign and the value.
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign and the value.
°C
°C
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Cooling fin temperature sensor TH8
-40 – 200
Hot gas overheating tempera­ture SHd 0 – 255 Cooling: TH4 - TH6 Heating: TH4 - TH5
-40 – +200 If the temperature sensor measures values below 0°C, the display switches between the sign and the value. If the temperature is over 99°C, the display switches between the 100s digit and the 10s and 1s digits.
0 – 255 If the temperature difference is over 99 K, the display switches between the 100s digit and the 10s and 1s digits.
°C
K
14
Page 15
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1
2
3
4
5
Subcooler temperature SC 0 – 130 Cooling: TH6 - TH3 Heating: TH5 - TH4
Operating current of the in­door unit 0 – 500
6
0 – 130 If the temperature difference is over 99 K, the display switches between the 100s digit and the 10s and 1s digits.
0 – 500 If the number is above 99, the display switches between the 100s digit and the 10s and 1s digits.
K
0.1A
ON
1
ON
1
Opening width of the LEV B 0 – 480
2
3
4
5
6
Target operating frequency 0 – 255
2
3
4
5
6
0 – 480 If the opening width is over 99 impulses, the display switches between the 100s digit and the 10s and 1s digits.
0 – 255 If the operating frequency is over 99 H�, the display switches between the 100s digit and the 10s and 1s digits.
Impulses
H�
15
Page 16
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
DC bus voltage CMF 80/90/140/150 CMT 100/150
180 - 370
Fault on the temperature sen­sor If no temperature sensor fault has occurred, "—" appears on the LED display.
180 – 370 If the voltage is over 99 V, the display switches between the 100s digit1 and the 10s and 1s digits.
3 = Liquid line on the outdoor unit TH3, TH32
6 = two-phase line (condenser/vaporiser) on the outdoor unit TH6
7 = Outdoor air temperature TH7
8 = Cooling fin temperature sensor TH8
°C
Code
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Condenser operating frequency before fault 0 – 255
Fan speed before fault 0 – 10
0 – 255 If the operating frequency is over 99 H�, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Example: 125 H�:
0.5 s 0.5 s 2 s „ 1“ „25“ „ “
0 – 10 Levels /
H�
Steps
16
Page 17
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1
2
3
4
5
Opening width of the LEV A before fault 0 – 480
Line temperature of the outdoor unit TH33 before fault
-39 – 88
6
0 – 480 If the opening width is over 99 impulses, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Example: 130 impulses:
0.5 s 0.5 s 2 s „ 1“ „30“ „ “
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign and the value.
Impulses
°C
ON
1
ON
1
Vaporiser/condenser tempera­ture sensor of the indoor unit TH5 before fault
2
3
4
5
6
2
3
4
5
6
-39 – 88
Heat exchanger temperature sensor of the outdoor unit TH6 (two-phase mixture) before fault
-39 – 88
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign, the value, and 2 spaces.
Example: -15 °C:
0.5 s 0.5 s 2 s „- “ „15“ „ “
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign, the value, and 2 spaces. Ex­ample: -15 °C:
0.5 s 0.5 s 2 s „- “ „15“ „ “
°C
°C
17
Page 18
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1
2
3
4
5
Outdoor temperature TH7 before fault
-39 – 88
Cooling fin temperature sensor TH8 before fault
-40 – 200
6
-39 – +88 If the temperature sensor measures values below 0°C, the display switches between the sign, the value, and 2 spaces. Ex­ample: -15 °C:
0.5 s 0.5 s 2 s „- “ „15“ „ “
-40 – +200 If the temperature sensor measures values below 0°C, the display switches between the sign, the value, and 2 spaces. If the temperature sen­sor measures values over 99°C, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Impulses
°C
ON
1
ON
1
Hot gas overheating tempera­ture SHd before fault 0 – 255
2
3
4
5
6
Cooling: TH4 - TH6 Heating: TH4 - TH5
Subcooler temperature SC before fault 0 – 130
2
3
4
5
6
Cooling: TH6 - TH3 Heating: TH5 - TH2
0 – 255 If the temperature difference is over 99 K, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Example: 150 K:
0.5 s 0.5 s 2 s „ 1 “ „50“ „ “
0 – 130 If the temperature difference is over 99 K, the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Example: 115 K:
0.5 s 0.5 s 2 s „1 “ „15“ „ “
K
K
18
Page 19
Setting on SW2 System component Measuring range and description Unit
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Switch-on duration until fault 0 – 999
U9: Fault status during the fault
0 – 999 If the duration is over 99 min., the display switches between the 100s digit, the 10s and 1s digits, and 2 spaces.
Example: 415 min.:
0.5 s 0.5 s 2 s „ 4“ „15“ „ “
00 No fault
01 Voltage too high (voltage board)
02 Voltage too low (control board)
04 L-phase fault (control board)
08 Operating signal fault (voltage board)
Minutes
Code
10 PFC fault
-Overvoltage
-Undervoltage
-Overcurrent (voltage board)
20 PFC/ACTM fault
-Undervoltage (check wiring from CNAF, ACTM defective
Examples of multiple faults: 03 Overvoltage (01) and und­ervoltage (02)
0A Under voltage (02) and operating signal fault (08)
14 L-phase fault (04) and PFC fault (10)
19
Page 20
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Fault codes
Please note the following when a fault message is issued:
In the event of a communication error, the information from the LED indicators of the outdoor unit and that on the display of the REMKO SYSTEM MONITOR may differ, or the outdoor unit may not show a fault at all. If a fault occurs, you can determine its cause from the following tables.
Fault code display
LED 1 (green) LED 2 (red) Display
F1
Flashes once
F2
F3
Phase fault detected
Phase fault, wiring fault between indoor/outdoor unit
Phase fault detected
Open L3-phase detected
Connector 63L open
No contact detected from 63L for 3 min.
Description
! CAUTION
When a fault occurs, the fault code is issued on the outdoor unit using flashing codes on two LEDs
Flashes once
Flashes twice
Flashes twice
Flashes 3 times
Flashes once
Flashes twice
F4
F5
F9
FA
F7
F8
EA Wiring fault between indoor and outdoor unit
Eb
E8
E9
Connector 49C open
No contact detected from 49C for 3 min.
Connector 63H open
No contact detected from 63H for 3 min.
Two or more connectors open
At least two open connector contacts detected
L2-phase or connector 51CM open
No L2-phase or no contact detected from 51CM for 3 min.
Fault on the phase fault detection circuit (control board)
No signal detected on control board
Fault with the system circuitry
No feedback signal received from the indoor unit 0.5 sec. after applying the supply voltage
Wiring fault between indoor and outdoor unit
(cable break, loose connection)
Data transfer between indoor and outdoor unit
20
Flashes 4 times
Fb Fault on the control board in the indoor unit
Page 21
Fault code display
LED 1 (green) LED 2 (red) Display
Flashes once
Flashes twice
U2
U7 Hot gas overheating too low
U1
UE
UL Low pressure switch 63L was triggered
Description
Hot gas temperature sensor
Internal thermostat of compressor motor 49C was triggered. Refrigerant level
High pressure switch 63H was triggered
Flashes 3 times
Flashes 3 times
Flashes 4 times
Ud Overheating protection function
Circuit breaker on the condenser (overload)
U6
Fault in the power module
Circuit breaker on the condenser (thermal overload relay)
UA
UC Condenser switched off by internal protection function
UF Condenser blocked, overcurrent protection device was triggered
UP Overload protection device was triggered
UH Fault on the current sensor
U3 Fault on the hot gas temperature sensor TH4
Thermal overload relay is triggered Only for models with a three-phase power supply
Fault on the line temperature sensor of the outdoor unit TH3
Flashes 5 times
Flashes 6 times
Flashes 7 times
Fault on the heat exchanger temperature sensor of the outdoor unit TH6
U4
Fault on the outdoor air temperature sensor of the outdoor unit TH7
Fault on the inverter cooling block temperature sensor TH8
U5 Temperature fault on inverter cooling block
U6 Fault in power supply
21
Page 22
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Fault code Meaning Cause Remedial measures
No supply voltage is present at terminal block TB1.
The main switch connected upstream is turned off. Poor or detached contacts at the terminals. Open phase (L, L1 or N)
There is no voltage at the input of the power supply on the voltage board.
Poor or detached contacts at the terminals. Open phase on the voltage board. Connector unplugged: CMF80/90/-CMT100: R or S CMF140/150-CMT150: TABT or TABS
Check main switch. Check connection, wiring, phases and contacts at TB1 and correct
Check connection, wiring, phases and contacts at TB1 and correct. Check connection, wiring, phases and contacts at the connectors on the voltage board and correct.
No display
and no function
No voltage is supplied to the control board. Poor or detached contacts on the CNDC connector or connector unplugged.
_
Poor or detached contacts on the DCL or ACL transformer.
Poor or detached contacts on the interference board or components of the interference board defective.
Voltage board defective. Replace defective voltage board.
Check contacts on the CNDC connector on the control board and repair. Contacts on connectors LD1, LD2 CNDC on the voltage board Check interference filter and repair.
Check contacts on the DCL transformer and repair. wwLO and LO on the interference board R and S on the voltage board Check contacts of L1 and L2 on the active filter module ACTM and repair.
Check contacts on the interference board and repair. Replace defective interference board.
22
Control board on the outdoor unit
a) 6.3 A fuse blown.
b) Defective components
Control board on the outdoor unit defective.
Replace 6.3 A fuse
Replace defective control board if the above points have not proved to be of assistance.
Replace defective control board if the above points have not proved to be of assistance.
Page 23
Fault code Meaning Cause Remedial measures
Phases reversed, power supply, polarity reversed on connection
F1
F2
and control cables to the indoor unit
1. Three seconds after switching on the power supply, a phase fault is detected.
2. Four minutes after switching on the power supply, reverse polarities are detected on the supply and control cables.
L3-phase open
If a phase fault is detected on L3 two seconds after switching on the power supply, fault message "F2" is issued
Control cables to S1, S2, S3 reversed (TB4), note polarity. Phases L1, L2, L3 reversed (TB1), note polarity. Cables reversed at the terminals for supply voltage TB1 and control cables TB4.
Open phase on L3. Check wiring and correct.
Check connection and polarity at the terminals. Swap phases L1 and L2 at TB1. Check wiring and correct.
F3
F5
F7
Low pressure switch 63L
If the circuit of low pressure switch 63L does not report a contact for over 3 mins after applying the supply voltage, fault message "F3" is issued
High pressure switch 63H
If the circuit of high pressure switch 63H reports a contact for over 3 mins after applying the supply voltage, fault message "F5" is issued.
Phase fault on the control board.
If no signal is being generated by the phase measuring circuit three seconds after switching on the power supply, fault message "F7" is issued.
Poor or detached contacts on the 63L connector on the control board of the outdoor unit, or connector unplugged. Poor or detached contacts on 63L. 63L was triggered due to a lack of refrigerant or by defective components. Control board defective.
Poor or detached contacts on the 63H connector on the control board of the outdoor unit, or connector unplugged. Poor or detached contacts on 63H. 63L was triggered due to defective components. Control board defective.
Control board defective. Replace defective control board.
Check contacts on the 63L connector on the control board and repair. Check contacts and cable on 63L and repair. Check refrigerant level. Test electrical components. Replace defective components. Replace defective control board.
Check contacts on the 63H connector on the control board and repair. Check contacts and cable on 63H and repair. Test electrical components. Replace defective components. Replace defective control board.
23
Page 24
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Fault code Meaning Cause
Poor or detached contacts on the connectors on the control board of the outdoor unit, or connectors unplugged. Poor or detached contacts on other components. Components were triggered by defective components. Control board defective.
Poor or detached contacts on connector 51CM on the control board of the outdoor unit, or connector unplugged. Poor or detached contacts on thermal relay 51CM. Thermal relay 51CM was triggered due to defective components. Control board defective.
Poor or detached contacts on the connections of the control cables, or wiring fault. Incorrectly dimensioned control cables. Interference noise in the control cables.
Poor or detached contacts on the connections of the control cables, or wiring fault Incorrectly dimensioned control cables. Interference noise in the control cables. Voltage board on the outdoor unit defective
Poor or detached contacts on the connections of the control cables, or wiring fault. Incorrectly dimensioned control cables. Interference noise in the control cables.
F9
FA
EA
Eb
EC
High and low pressure switches 63H, 63L
Thermal relay 51CM If the circuits of the identified components report a contact for over 3 mins after applying the supply voltage, fault message "F9" is issued.
Thermal relay 51CM
If the circuits of the thermal relay 51CM report a contact for over 3 mins after applying the supply voltage, fault message "FA" is issued.
Control cables between indoor and outdoor units defective, too many indoor units connected
A test circuit will automatically detect the number of indoor units connected. If the control cables continue not to work for longer than 4 mins after the power supply is applied, fault message "EA" is issued.
Wiring fault on the control cables between the indoor units and outdoor unit (phases reversed, no contact)
A test circuit will automatically set the number of indoor units connected. If the control cables continue not to work for longer than 4 mins after the power supply is applied, fault message "Eb" is issued.
Time limit for start of operation exceeded
The system has still not been properly initialised over four mins after the start of operation. The fault message "EC" is issued.
Remedial measures
Check contacts on the connectors on the control board and repair. Check contacts and cables of the components and repair. Test electrical components. Replace defective components. Replace defective control board.
Check contacts on connector 51CM on the control board and repair. Check contacts and cable on 51CM and repair. Test electrical components. Replace defective components. Replace defective control board.
Check contacts, cables and connections of the control cables on all units and repair.
Check cable section and lengths of the control cables and correct: max. length 50 m (indoor­outdoor) or max. 30 m (indoor­indoor) Check polarity of control cables S1, S2 and S3 and correct.
Switch the supply voltage off and back on once and check if the fault still occurs. Replace the control boards of the affected indoor and outdoor units if the fault does still occur. Check control cables.
Check control cables and rectify the cause of the interference noise.
These remedial measures apply to "EA", "Eb" and "EC".
24
Page 25
Fault code Meaning Cause Remedial measures
Dirt on the heat exchanger in the indoor module. Pump motor in the indoor unit jammed. Malfunction of the pump motor in the indoor module.
U1
High pressure too high (63H was triggered)
The high pressure switch 63H was triggered because the high pressure exceeded 4.14 MPa during continuous condenser operation.
Faulty ball shut-off valve (not fully open). Blocked or cracked refrigerant line. Fan motor on the outdoor unit jammed. Malfunction of the fan motor on the outdoor unit. Air "short-circuit" on the outdoor unit. Dirt on the heat exchanger of the outdoor unit. Reduced airflow volume due to inaccurate temperature measurement on the outdoor air temperature sensor (measurement too low). Defective contact of connector 63H to the control board of the outdoor unit. Faulty connection of 63H. Control board of the outdoor unit defective. Faulty LEV Defective fan drive Too much refrigerant in the system
Check components and rectify cause of the fault. Check that all ball shut-off valves are fully open. Check pipework and rectify fault. Check outdoor unit and replace/ repair defective components. Check the temperature sensor with the help of the system monitor and proceed accordingly in order to rectify the fault. Switch supply voltage off and back on again once. Check if fault codes "F5" or "UH" are displayed. If so, see "Remedial measures" for "F5" or "UH". Check LEV. Replace defective control board of the outdoor unit. Correct refrigerant level
U2
Hot gas temperature too high
At hot gas temperature sensor TH4, over 125°C was detected or over 110°C for a period of 5 minutes. In defrost mode, over 40°C was detected at TH5 and over 110°C at hot gas temperature sensor TH4.
Continued on the next page
Rise in temperature in the condenser due to lack of refrigerant.
Defective temperature sensor TH4, TH5, TH6.
Control board of the outdoor unit defective.
Faulty LEV.
Check inlet overheating.
Check pipework, refrigerant level and additional fill amount.
Switch supply voltage off and back on again once. Check if fault code "U3" is then displayed. If so, see "Remedial measures" for "U3".
Check LEV.
25
Page 26
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Fault code Meaning Cause
Refrigerant level
Incorrect if the hot gas overheating in cooling mode TH4–TH5 / in heating mode TH4–TH6 rises as follows.
U2
All conditions must be fulfilled for a period of 10 mins (at least 6 mins after the condenser starts up)!
The condenser is working in heating mode. The hot gas overheating is 70°C or more. TH6 > TH7 – 5K TH5 < 35°C
The condenser is working (C/H). In cooling mode the hot gas overheating is 80°C or more. In heating mode the hot gas overheating is 90°C or more. In cooling mode the condensation temperature is TH6 < –40°C
Rise in temperature in the condenser due to lack of refrigerant.
Defective temperature sensor TH4, TH5, TH6.
Control board of the outdoor unit defective.
Faulty LEV.
Remedial measures
Check inlet overheating.
Check pipework, refrigerant level and additional fill amount.
Switch supply voltage off and back on again once. Check if fault code "U3" is then displayed. If so, see "Remedial measures" for "U3".
Check LEV.
26
U3
Open circuit/short-circuit on the hot gas temperature sensor TH4 or condenser temperature sensor TH32
If no resistance (0°C = 0 Ω) or infinite resistance (>217°C = Ω) is measured on the hot gas temperature sensor TH4 when the condenser is operational, fault message "U3" is issued (this function is not available in the first 5 to 10 mins after the condenser begins operation, after the conclusion of defrost mode or while defrost mode is operational.)
Poor or detached contacts of the cables and connectors on the control board. Temperature sensor defective. Control board of the outdoor unit defective.
Check connectors and contacts of the temperature sensor on the control board and repair. Check connection cables of the temperature sensor for cable break or similar.
Check the temperature sensor with the help of the system monitor and proceed accordingly in order to rectify the fault.
Replace defective control board of the outdoor unit.
Page 27
Fault code Meaning Cause
Open circuit/short-circuit on the temperature sensors of the outdoor unit (TH3, TH32, TH33, TH6, TH7 and TH8).
If no resistance (0 Ω) or infinite resistance ( Ω) is measured by one of the temperature sensors when the condenser is operational, fault message
U4
Name Description Open(XX),at Short-circuit (0X), at
TH3, TH32, TH33 Cable temperature sensor -40°C and lower 90°C and higher
TH6 Two-phase mixture -40°C and lower 90°C and higher
TH7 Outdoor air -40°C and lower 90°C and higher
TH8 Inverter cooling block -27°C and lower 102°C and higher
"U4" is issued. With the help of the system monitor on the outdoor unit, you can detect which temperature sensor is affected (this function is not available in the first 10 mins after the condenser begins operation, after the conclusion of defrost mode or while defrost mode is operational.)
Poor or detached contacts of the cables and connectors of one or more of the temperature sensors on the control board. Temperature sensor defective. Control board of the outdoor unit defective.
Remedial measures
Check connectors and contacts of the temperature sensors on the control board and repair. Check connection cables of the temperature sensors for cable break or similar.
Check the temperature sensor with the help of the system monitor and proceed accordingly in order to rectify the fault.
Replace defective control board of the outdoor unit
U5
Temperature fault on inverter cooling block
If the temperature at TH8 on the inverter cooling block reaches or exceeds the value specified below, fault message "U5" is issued.
CMF80/90: 77°C
CMT100: 77°C
CMF140/150: 95°C
CMT150: 95°C
Fan motor jammed. Fault on the fan motor. Air inlets and outlets dirty/ blocked. Increase in outside air temperature. Temperature sensor defective. Input circuits (supply voltage) on the voltage board of the outdoor unit defective. Drive circuit of the outdoor unit fan defective.
Check fan motor. Check air inlets and outlets and clean. Check whether other weather­related causes are responsible for the rise in temperature. Upper temperature limit 46°C.
Switch the supply voltage off and back on. Check if fault "U5" is issued again within the next half hour. If "U4" is issued, rather than "U5", you can find the descriptions under "U4". Measure the resistance of the temperature sensor TH8 or use the system monitor to query the temperature at TH8. Replace defective temperature sensor. Replace defective voltage board on the outdoor unit.
27
Page 28
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Fault code Meaning Cause Remedial measures
U6
U7
Power modules in the inverter circuit defective.
If overcurrent is detected in the inverter circuit ("UF" or "UP" is displayed), the inverter circuit is defective and fault message "U6" is issued.
Overheating interrupted by too low hot gas temperature
If the overheating is around -15 K for over 3 mins, the LEV is almost closed (lowest impulse rate) and 10 mins have passed since the condenser was started up, fault message "U7" is issued.
Faulty ball shut-off valve (not fully open). Increase in supply voltage. Poor or detached contacts of the connection cables to the condenser or reversed phases. Condenser defective. Voltage board defective.
Poor or detached contacts of the cables and connectors of the hot gas temperature sensor TH4 on the control board. Hot gas temperature sensor TH4 not properly secured. Poor or detached contacts of the cables and connectors on the LEV drive. Poor or detached contacts of the LEV cables on the control board. LEV defective.
Check and fully open all ball shut-off valves. Check supply voltage (mains). Check condenser wiring and correct (phases U, V, W). Check condenser, replace condenser if defective Replace defective voltage board on the outdoor unit.
Check contacts, cables and connections of the temperature sensor TH4 and repair. Secure temperature sensor TH4 properly. Check contacts, cables and connections of the LEV drive and repair. Check LEV and replace.
28
U8
Speed fault on the fan motor.
The speed of the fan motor is determined to be faulty if: at an outdoor temperature above 20 °C for a duration of 15 s, a maximum of only 100 rpm is measured. for a duration of one minute, less than 50 rpm or over 1500 rpm is measured.
Fan motor defective.
Control board defective.
Check fan motor and replace defective motor.
Check control board and replace defective circuit board
Page 29
Fault code Meaning Cause Remedial measures
Rise in the supply voltage (mains).
U9
Overvoltage or undervoltage in the inverter and fault in the serial communication of the circuit boards.
Drop of the bus voltage below 310 V
Sudden drop of the bus voltage below 200 V (CMF80/90 CMT100) below 350 V (CMF140/150 CMT150)
Rise of bus voltage above 420 V ( CMF80/90 CMT140) above 760 V ( CMF140/150 CMT 150)
Drop in the power consumption of the outdoor unit to just 0.5 A with an operating frequency of 40 H� or condenser current of 5.0 A.
Wiring detached from the condenser. Contactor 52C defective. Connector CN52C detached or unplugged. PFC module on the voltage board of the outdoor unit (CMF80/90CMT100) defective ACT module defective. ACT circuit defective. Connector CNAF detached or unplugged. Converter circuit on outdoor unit (CMF140/150CMT150) defective 52C circuit on the control board (CMF80/90CMT100) defective Connector CN5 on the voltage board detached or unplugged 52C circuit on the voltage board (CMF140/150CMT150) defective Connector CN5 on the voltage board detached or unplugged
Check supply voltage at the mains. Check wiring to the condenser and voltage board and correct. Replace defective 52C. Check fit and wiring of CN52C and correct. Replace control board. Replace ACT module. Replace voltage board. Check fit and wiring of CNAF and correct. Replace converter board. Replace control board. Check fit and wiring of CN5 and correct. Replace voltage board. Check fit and wiring of CN2 and correct.
UA
Ud
Thermal relay 51C was triggered.
If thermal relay 51C is triggered, fault message "UA" is issued.
Overheating protection (overload protection, fan motor fault)
If the line temperature (TH3) exceeds 70°C, fault message "Ud" is issued.
Shut-off valves closed during operation. Fault on the condenser. Variations in the supply voltage (mains). Brief interruption to the supply voltage (mains).
In cooling mode: fan motor defective, air "short-circuit". Temperature sensor TH3 defective. Control board defective.
Shut-off valve fully open. Check condenser and if necessary replace. Check supply voltage (mains).
Check fan motor, replace if defective. Switch supply voltage off and back on to check if "U4" will be displayed when the system starts back up. If "U4" is displayed, see "U4". Check temperature sensor, replace if defective. Check control board, replace if defective.
29
Page 30
REMKO SYSTEM MONITOR
FOR REMKO SUPERTEC INVERTER
Fault code Meaning Cause Remedial measures
UE
UF
High pressure fault, 63H was triggered
The high pressure protective switch detected 4.14 MPa in heating mode for the first time within the first 20 s after condenser startup, and switched the condenser off. Fault message "UE" is issued.
Protective device to protect against overcurrent on the condenser: condenser blocked
If the operating current of the condenser exceeds 1.2 times the permissible value, fault message "UF" is issued. If overcurrent is detected on the DC bus or in the condenser 30 s after condenser startup, fault message "UF" is issued.
Shut-off valves closed during operation. Connector 63H detached or unplugged. Control board defective. Power supply was switched back on, air filters on indoor unit are dirty, overload operation. Control board defective LEV defective
Shut-off valves closed. Rise in the supply voltage (mains). Connector detached or unplugged, cable break, phases reversed. Condenser defective. Voltage board defective Phase fault on the condenser
Shut-off valve fully open. Switch supply voltage off and back on to check if "F5" will be displayed when the system starts back up. If "F5" is displayed, see "F5". Replace defective control board. Check LEV.
Open shut-off valves. Check supply voltage at the mains. Check wiring and phases (U, V, W) on the condenser and voltage board, correct and replace defective components. Check condenser, replace defective condenser. Replace voltage board. Check wiring on the condenser and correct.
30
UH
Fault on the current sensor.
If a current between -1.5 A and +1.5 A is detected on the current sensor while the condenser is running, fault message "UH" is issued. This fault is ignored during test runs.
Poor or detached contacts of the connection cables to the condenser or reversed phases.
Circuit (current sensor) on the voltage board of the outdoor unit defective.
Check condenser wiring and correct (phases U, V, W).
Replace defective voltage board on the outdoor unit.
Page 31
Fault code Meaning Cause
Low pressure fault (63L was triggered).
If one of the two following conditions are met in heating mode for a duration of 3 mins within the first 10 mins after condenser startup, fault message "UL" is issued (this fault is
UL
ignored if the total operating time of the condenser since it was started has reached or exceeded a sum of 30 mins.) TH7 – TH3 4 K TH5 – room temp. 2K Meaning the following: TH3: liquid line temperature in the outdoor unit in °C. TH5: vaporiser/condenser temperature in the indoor unit in °C. TH7: Outdoor air temperature in °C
Shut-off valves closed.
Lack of refrigerant or leakage.
LEV defective.
Remedial measures
Open shut-off valves
Check refrigerant level and additional fill amount. Check pipe system for leaks and rectify.
Check LEV.
Ball shut-off valve closed during operation.
Rise in the supply voltage (mains).
Poor or detached contacts of the connection cables
Overcurrent in the condenser – protective device was triggered.
UP
* Before replacing the condenser, check that the voltage and frequency applied between phases U-V, V-W and W-U is the same.
To do so, disconnect the condenser and start the test run. Measure the voltage. If the same voltage and frequency is applied between the phases, the condenser is defective and must be replaced.
If, 30 seconds after condenser startup, the protective device has been triggered due to DC overcurrent, fault message "UP" is issued.
to the condenser or reversed phases.
Blower or fan defective.
Air "short circuit" on outdoor unit.
Input circuit (voltage) on the control board of the outdoor module defective.
Condenser defective.
Inverter board defective.
Incorrect DIP switch settings on the control board of the outdoor unit.
Check and fully open all ball shut-off valves.
Check supply voltage (mains).
Check condenser wiring and correct (phases U, V, W).
Check blower and/or fan.
Rectify air "short-circuit".
Replace defective circuit boards.
Check condenser and replace if defective.*
Replace defective circuit boards.
Check DIP switch and correct settings.
31
Page 32
REMKO INTERNATIONAL
...and right in your own location too! Benefit from our experience and advice
REMKO GmbH & Co. KG Air conditioning and heating technology
Consultation
Thanks to intensive training, our
consultants are always com-
pletely up-to-date in terms of
technical knowledge. This has
given us the reputation of being
more than just an excellent, reli-
able supplier.
REMKO is a partner
that helps you find solutions to
your problems.
Sales
REMKO offers not just a well
established sales network both
nationally and internationally, but
also has exceptionally highly-
qualified sales specialists.
REMKO field staff are more than
just sales representatives; above
all, they must act as advisers to
our customers in air conditioning
and heating technology.
SFlbCustomer Service
Our units operate precisely and
reliably. However, in the event of
a fault, REMKO customer service
is quickly at the scene. Our com-
prehensive network of experi-
enced dealers always guarantees
quick and
reliable service.
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 e-mail info@remko.de Website www.remko.de
Hotline
Air conditioning and heat­ing technology
+49 5232 606-0
Export
+49 5232 606-130
We reserve the right to make technical changes, and provide no warranty as to the accuracy of this data!
Loading...