REMKO SLN Series, SLN 65, SLN 45, SLN 85 Operating And Installation Instructions

Operating and installation instructions
REMKO SLN series Swimming pool dehumidifiers
SLN 45, SLN 65, SLN 85
Edition GB – N12
Read the instructions prior to performing any task!
Contents
Safety notes
Air dehumidification
Testing the water quality
Unit description
Set-up
Commissioning
Unit function
Wireless remote control
Care and maintenance
Troubleshooting
Fault and information messages
Diagram, cooling cycle
4
5-7
8
9
10-12
13-14
15
16-18
19
20
21
22
Electrical wiring diagram
Intended use
Customer service and guarantee
Environmental protection and recycling
Exploded view of the unit
Spare parts list
RS-485 interface
USB interface
Maintenance protocol
Technical data
27-29
32-33
23
24
24
24
25
26
30
31
These original instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO SLN Series
Safety notes
The units have been subjected to extensive material, functional and quality inspections prior to delivery.
However, dangers can result from the units if they are used improperly or not as intended by untrained personnel.
The following notes must be observed in full:
The units may not be installed or operated in explosive environments
The units must not be installed or operated in atmospheres containing oil, sulphur or salt
The units must not be exposed to direct jets of water
An unobstructed air inlet and air outlet must be guaranteed at all times
The air-inlet grill must always be kept free of dirt and loose objects
The units must not be covered during operation
Never stick foreign objects into the units
All electrical cables on the outside of the units must be protected against damage (e.g. by animals etc.)
The units are only permitted to be set up or installed in the intended position (upright)
Unobstructed and frost-proof condensate drainage must be ensured at all times
The unit connections must always be established according to the applicable installation regulations
CAUTION
The units must be set up and installed in such a way that they are easily accessible for monitoring, repair and maintenance work.
4
Air dehumidification
The correlations occurring when air is dehumidified are based on physical laws. These are depicted here in graphical form in order to provide you with a brief overview of the principles of air dehumidification.
The use of REMKO air dehumidifiers
– Even if windows and doors
are well insulated, water and moisture are still capable of penetrating thick concrete walls.
– The water required for setting
in the production of concrete, mortar and plaster etc. may only be diffused after 1-2 months.
– Even moisture trapped
in the masonry after high­water or a flood is released very slowly.
– The same is also true
of moisture contained in stored materials for example.
The moisture (water vapour) released from parts of a building or materials is absorbed by thesurrounding air. As a result, the moisture content increases, which ultimately gives rise to corrosion, mould, rot, peeling of paint and other unwanted damage.
By way of example, the diagram shows the corrosion rate of metal in different levels of humidity.
Corrosion rate
Rel. humidity %
It is evident that the corrosion rate below 50 % relative humidity (RH) is low, and below 40 % is negligible.
The corrosion rate increases significantly above 60 % RH. This threshold for damage as the result of humidity also applies to other materials, such as powdery substances, packaging, wood and electronic units.
Buildings may be dried in a variety of ways:
1. By heating and air exchange:
The air in the room is heated
in order for moisture to be removed and then this air is fed outside. All of the energy that is involved is lost together with the moist air that is released.
2. By air dehumidification:
The moist air that is present
within an enclosed space is continuously dehumidified according to the condensation principle.
With regard to energy consumption, air dehumidification has one distinct advantage:
Energy expenditure is limited exclusively to the air volumes present. The mechanical heat that is released by the dehumidification process is fed back into the room.
Under normal use, the
air dehumidifier
uses approximately 25 % of the energy that is required for the
“heating and ventilating”
principle.
Relative air humidity
Our ambient air is a gaseous mixture which always contains a certain volume of water in the form of water vapour. This volume of water is specified in g per kg of dry air (absolute moisture content).
1 m3 of air weighs approx. 1.2 kg at 20 °C
Depending on the temperature, each kg of air is only capable of absorbing a certain volume of water vapour. Once this capacity has been reached, the air is referred to as “saturated” and has a relative humidity (RH) of 100 %.
Relative humidity is understood to mean the ratio between the current quantity of water vapour in the air and the maximum possible quantity of water vapour at the same temperature.
The ability of the air to absorb water vapour increases as the temperature rises. I.e. the maximum possible (absolute) water content becomes greater as the temperature rises.
5
Verdampfer Kondensator
°C
30
25
20
15
% r.F.
100
90
80
70
60
50
40
30
20
10
+
+
-
Lufttemperatur
Luftfeuchte
Verlauf
Luftrichtung
Evaporator Condenser
Air temperature
Air humidity
Air direction
% RH
Progression
REMKO SLN Series
Temp. Water vapour content in g/m3 at humidity of
°C
-5 1.3 1.9 2.6 3.3
+10 3.8 5.6 7.5 9.4
+15 5.1 7.7 10.2 12.8
+20 6.9 10.4 13.8 17.3
+25 9.2 13.8 18.4 23.0
+30 12.9 18.2 24.3 30.3
40 % 60 % 80 % 100 %
Drying materials
Building materials and structures are capable of absorbing considerable volumes of water, such as brick 90-190 l/m³, heavy concrete 140-190 l/m³ and limestone 180-270 l/m³. The drying of moist materials such
The air containing water vapour
is constantly circulated through the REMKO air dehumidifier. The air is dehumidified and, slightly heated, leaves the unit in order to re-absorb water vapour
as masonry is effected as follows:
In this way, the moisture
The moisture moves from the inside
contained in the material is reduced gradually
The material is dried!
of the material to its surface
The accumulated condensate is collected in the unit and drained
Evaporation occurs on
off from there. the surface = transfer of water vapour to the ambient air
The condensation of water vapour
Because the capacity for the maximum possible volume of water vapour increases as the air is heated, the volume of water vapour contained remains constant and so relative humidity falls.
In contrast, because the capacity for the maximum possible volume of water vapour decreases as the air is cooled, the volume of water vapour contained remains constant and so relative humidity increases. If the temperature continues to fall, the capacity for the maximum possible volume of water vapour is reduced so much so that it is ultimately equal to the volume of water vapour contained in the air. This temperature is referred to as the dew point. If the air is cooled to below dew point, the volume of water vapour in the air will become greater than the maximum possible volume of water vapour. At this point, the water vapour begins to precipitate. It then condenses to water. Humidity is then removed from the air.
As it flows through or over the evaporator, the air stream is cooled to dew point. The water vapour condenses, and is collected in a condensate trap from where it is drained off.
6
Examples of condensation include steamed-up window panes in winter, or the moisture on the outside of a cold drinks bottle.
As the relative humidity of the air increases, so too does the dew point, making it easier for the temperature to fall below it.
Condensation heat
The Energy transferred to the air from the condenser consists of:
1. The amount of heat derived beforehand in the evaporator.
2. The electrical drive energy.
3. The condensation heat released by liquefying the water vapour.
Energy must be supplied when liquid is converted into a gas. This energy is designated as evaporation heat. It does not cause any increase in temperature, but is required to convert a liquid into a gas.
Conversely,
energy is released when gas is liquefied, this is designated as condensation heat.
The amount of energy from evaporation heat and condensation heat is the same.
For water, this is: 2250 kJ/kg (4.18 kJ = 1kcal)
From this it is evident that the condensation of water vapour causes a large quantity of energy to be released. If the moisture that it is to be condensed is not introduced by evaporation in the room itself, but from outside, e.g. through ventilation, the condensation heat released contributes to the heating of the room.
When dehumidifying, a heat cycle is created, whereby heat is consumed for evaporation and released for condensation. When dehumidifying fed air, a larger contribution of heat is created, which manifests itself as a temperature increase.
Generally speaking, the time required for the drying process is not only dependent on the output of the unit, but is determined to a greater extent by the speed at which the material or building section loses its moisture.
7
REMKO SLN Series
Testing the water quality
Water quality
The correct combination of chemicals in swimming pools in indoor areas is of major importance to the health of the users and for systems in the vicinity of the swimming pool and its plant room. Inadequately treated water leads to poor hygiene, whilst water that has been excessively treated gives off chlorine into the air, which can irritate the eyes and lead to respiratory problems. At the same time, an incorrect combination of chemicals in the water can lead within a very short time to the destruction of all systems ­including the dehumidifier and other systems that have been installed for air treatment. The following tables contain the limit values for swimming pools in indoor areas in accordance with EN/ISO 12944-2, corrosivity category C4. These limit values must be observed, otherwise the guarantee is voided
When adding chemicals
The following guideline values apply to swimming pools when adding chemicals:
Chemical values ppm
Free chlorine content 1,0 - 2,0
Combined chlorine content max. 1/3 of the free chlorine content
pH value 7,2 - 7,6
Total alkalinity 80 - 150
Calcium hardness 250 - 450
Total dissolved solids < 2000
Sulphates < 360
With own production of chlorine
The following guideline values apply to swimming pools with own production of chlorine:
Chemical values ppm
Salt (NaCl) < 30000
Total dissolved solids < 5 500
pH value 7,2 - 7,6
Total alkalinity 80 - 150
Calcium hardness 250 - 450
Sulphates < 360
Langelier saturation index
To make sure the various water quality parameters remain within an acceptable range, the Langelier saturation index should be applied.
8
Unit description
The units have been designed for universal and straightforward air dehumidification. Their compact dimensions allow the units to be transported and set up/installed with ease in the adjacent room.
The units operate in accordance with the condensation principle and are equipped with a hermetically sealed refrigerant system and low-noise and low­maintenance fan(s).
The fully-automated electronic controller, an integrated hygrostat and connection ports for condensate drainage provided by the customer ensure continuous fault-free operation.
The units are reliable and conform to the fundamental health and safety requirements of the appropriate EU stipulations.
The units are used in all locations where dry air is a must and where economic consequential damage (such as that caused by mould) must be prevented.
The units have been designed exclusively for installation in a suitable adjacent room by way of a duct interface.
The units may be used to dehumidify areas such as:
Private swimming pools
Spa areas
Fitness centres
Storage rooms
Archives
Museums
Operating sequence
The units are switched on and off using the integrated hygrostat.
The hygrostat is set to 60 % RH in the factory.
The respective unit function is indicated by a multi-colour LED display on the front of the unit.
The fan extracts the moist room air through the lower duct connector and filter.
Heat is removed from the room air on the cold evaporator. The air is then cooled to below dew point. The water vapour contained in the room air is then deposited as condensate or rime on the evaporator fins.
On the condenser, the cold and dehumidified air is warmed up again and discharged back into the room via the upper duct connectors with a temperature increase of around 5 °K above the room temperature. The processed, dry air therefore continuously mixes with the room air.
Continuous circulation of the room air through the unit gradually reduces the relative humidity (% RH) in the room to the desired humidity level.
Schematic depiction of the workings of the SLN 45-85 air dehumidifier
Warmed and dehumidified air
Moist room air
Adjacent room
REMKO
SLN
Swimming pool
9
REMKO SLN Series
Set-up
For optimum and safe use of the units, the following notes must be followed in full:
Two duct openings must
be created in the wall between the room to be dehumidified and the installation room before the units are installed in the adjacent room. The inside dimensions of these openings can be taken from the sketch.
The openings must be created
in such a way that the air in the room to be dehumidified can be extracted through the lower duct (with filter) in an unrestricted manner and blown out through the upper duct.
The unit must be mounted
upright to ensure that the condensate can drain freely.
Observe the illustrated
minimum gaps between theunit and the ceiling and floor in the installation room to ensure safe operation.
The wall fittings must be adjusted
to the required length before assembling the duct interfaces. The max. wall strength is limited to 290 mm. Ensure that the embossed side is not damaged when adjustments are made.
Wall-mounted bracket for the units
SLN 45
437 437
SLN 65
341 341 341
SLN 85
450 450 450
Fit the air circulation inlet filter,
the grille installation fittings and the ventilation grille together with the wall supports.
Install both duct interfaces into
the duct openings.
Fit the duct piece together
with the filter into the lower duct opening where the air in the room being dehumidified is to be extracted.
From the adjacent room side,
connect the unit connection fittings together with the self­sealing profile to the
All measurements in mm
Series Dimension A Dimension B Clear wall opening
SLN 45 464 998 110 x 610 SLN 65 614 1148 110 x 760 SLN 85 949 1483 110 x 1095
Mounting the units on the wall
20
110
395
110
90
65
10
304
min.
403
68
700
Detailed information on the wall-mounted bracket
min.
730
A
B
444
294
All measurements in mm
Duct interface found in the wall opening.
The unit must never be
mounted in the immediate vicinity of heaters or other
Secure the wall spacers provided
sources of heat. with the unit to the bottom corners of the unit using adhesive.
The room being dehumidified
must be closed to
the neighbouring atmosphere.
Affix the wall-mounted bracket
to the wall in the adjacent room and hang the unit on it.
Avoid having opened windows
and doors etc., and avoid
frequent entry to or exit from
The unit is connected to
the room as much as possible. the duct interfaces that are already mounted on the wall by way of the self-sealing profile lips on the unit connection fittings.
In order to achieve optimum
room air circulation using
the dehumidifier, the supply
and exhaust air openings must
remain clear.
Location of the wall-mounted bracket using the example of the unit SLN 65
Condensate water drain
The condensate water drain is located on the unit's base. The condensate drainage is connected to the discharge nozzle supplied. A solid or flexible ½” discharge connector can be installed on this.
The discharge hose must always
be laid at an incline of at least 2 % so that the water can flow unhindered from the drip tray.
Alternatively, a condensate
pump can be fitted to the unit in order to pump the condensate water to a drainage point located at a higher level.
If drainage is to be carried out
through the wall, the relevant measures such as holes for correct condensate drainage must be taken before installing the unit.
min. 403
Location of the condensate drain
110290 110
395
min. 730 178
Detailed information on the wall-mounted bracket
min. 225 700 min. 225
All measurements in mm
430
All measurements in mm
56
See the diagram at the side for
information on the location of the drainage connection.
Access to the controller
Remove the front plate after opening the lock on the underside. Lift the cover vertically upwards and then pull away from the unit horizontally.
The controller is located behind the top cover of the internal housing parts above the compressor.
The controller is accessed by removing the 2 screws on the front of the internal housing parts.
11
REMKO SLN Series
Mounting the unit exchange adapter
If the SLN unit is replacing aprevious model, then the unit exchange adapter is required. This is affixed using the sealing tape provided as shown in the image. Attach the adapter in such a way that it covers the existing apertures in the wall and creates a seal at the wall where the sheet-metal edges were affixed previously.
Once the adapter has been fitted to the wall correctly, the unit can be hung on the bracket that is fitted to the adapter. The rubber lips together with the unit housing and the adapter create a complete seal.
NOTE
Unit exchange adapter
Make sure that there are no air leaks as these will severely impair the functionality of the unit.
Mounting the units with an adapter
12
Commissioning
Before commissioning the unit or if local requirements dictate, the air-inlet grill and air-outlet grill must be checked for contamination.
The units are operated using an integrated hygrostat that is set to 60 % RH (default value for spas and indoor swimming pools). If the room humidity is below 60 % RH, the unit does not start. If the relative humidity is above 60 %, the unit starts the dehumidification process automatically.
If you would like to make changes to the hygrostat settings, remove the front housing cover and the control board cover located in the upper section in order to access the control board.
NOTE
Interrupting the operation of the unit before the compressor has run for 6 minutes will activate a restart lock lasting approx. 4 minutes.
Control board
The units are equipped with an electronic controller. This features various interfaces and a display. The following section describes these features in detail.
Control board, front
Display and operator panel
The display is a four-digit seven segment display. The first two digits are used to display the respective “code”, e.g. rHXX, for setting the room humidity and the last two digits correspond to the value set.
USB interface
The information on the USB interface can be found further on in this manual.
RS-485 interface
The information on the RS-485 interface can be found further on in this manual.
EXT RH/T
These terminals allow you to connect up an external electronic humidity and temperature probe. The temperature probe must be an NTC probe with 10 kΩ at 25 °C and a B25/85 of 3969 K. The humidity probe must be designed for a voltage supply of 12 V DC and feature an analogue voltage output of 0-10_V with max. 10 mA.
NOTE
If the air humidity is lower that the set value, the unit will not start up, even if the mains voltage is connected.
NOTE
When the unit is switched on or off using the main switch, a signal is issued upon startup and the LED display lights up blue as soon as the unit is ready for operation. Once all conditions have been met, the dehumidifying process begins.
Code Value
In the standard view, no code is shown on the display. It is only the value of the humidity currently measured that is displayed.
The operator panel with the buttons “Up”, “Down” and “OK” can be found on the right­hand side of the front of the control board. These can be used to navigate around the menu structure of the control board and to couple the control board with a wireless remote control.
ALARM
The alarm contacts are two potential-free contacts that are open in an unswitched state. The RUN contact is closed when the compressor is in operation. The FAIL contact is closed when there is a malfunction in the unit.
12VDC
Relays can be controlled via the HEAT contacts in order to switch the external heating on and off. They are active when the °C option in the menu is set to a value.
13
REMKO SLN Series
Menu structure
To define the setpoints using theintegrated operator panel, hold down the “OK” key for 5 seconds so that the display switches from the humidity currently measured to the menu item rHXX. If you would like to exit the menu, do not press any keys on the operator panel for 10 seconds.
Menu items
Code: RH The code “RH” stands for the relative air humidity that the unit should reach. The value can be set between 40 and 99 % RH. The default value is 60.
Code: °C The code “°C” stands for external heating control with the aim of reaching a defined setpoint. The value can be set to between 05 and 34. This value is set to “OF” by default.
Code: EF The code “EF” stands for external heating control with the aim of reaching the specified air humidity more quickly. The set value may differ from the setpoint humidity so that the external heating can either operate permanently or merely provide a support function. The value can be set between 40 and 99 % RH. The default value is set to “OF” in this case.
Code: SI The code “SI” stands for themaintenance interval that the operator or fitter requires. Thisvalue is indicated in weeks and can be set from 01 to 99. Thedefault value is “OF.”
Code: tE The code “tE” stands for testing and the value “St” for self-test. To start the self-test, press “OK” and to cancel it, hold the down key down for 5 seconds.
NOTE
The corresponding terminals for these options are located on the control board of the unit.
Menu structure of the SLN air dehumidifier
1. Level
rHXX
°CXX
External heating
EFXX
External fan
SIXX
Service interval
2. Level
OK
OK OK
OK
OK
Value”
Value”
Value”
Value”
OK
OK
OK
3. Level
"Value confirmed"
Value confirmed"
Value confirmed”
Value confirmed”
14
tESt
Self-test
OK
“Test confirmed”
Unit function
Fan control
When the control board puts the dehumidifier into operation, the fan(s) switch on together with the compressor.
Defrosting
The units feature an intelligent and active defrosting function. If the room temperature is below 20 °C, the evaporator will start to ice up after a short time. If the evaporator probe registers a temperature of less than 5 °C on the evaporator surface, the unit only continues to run in dehumidification mode for a further 30 minutes. Once this time has expired, the fans stop and the solenoid valve for hot-gas defrosting opens. When the evaporator probe registers a temperature higher than 5 ºC again, the solenoid valve closes and the unit resumes dehumidification.
Compressor control
The compressor has a 6 minute restart delay as a safety function. The delay period must elapse before it is possible to restart the compressor. This safety function protects the compressor against an overload caused by overly high pressure in the cooling cycle.
In order to prevent damage to the condenser, the units are equipped with a mechanism that prevents the compressor being immediately switched back on after it is switched off via the mains power supply.
The compressor does not switch back on until after a waiting time of approx. 30 seconds!
Safety circuit
If the temperature exceeds 55 °C on the condenser (e.g. due to a fan failure or an overly high room temperature (higher than 36 °C)), the compressor stops automatically to prevent an overload. As soon as the temperature on the condensor permits dehumidification again, the unit starts up automatically.
15
REMKO SLN Series
Wireless remote control
Wireless remote control
Wireless remote control allows an SLN unit to be operated and adjusted in a simple and convenient manner. The current humidity and temperature can be viewed on the wireless remote control and the setpoint humidity can be adjusted.
The wireless remote control is intended for use with the dehumidifier models SLN 45-65-85.
The wireless remote control has a coverage distance of up to 50 metres from the installation location of the unit.
Overview of the display
Design of the wireless remote control
The wireless remote control is
equipped with a large, clear display and has operating buttons for the different options Up, Down, Left, Right and Enter.
The display values and the air humidity scale have a value range of 0 to 99 % RH.
The display values and the air temperature scale have a value range of 0 °C to 40 °C.
Information display
The information display shows
the setpoint values for the unit. Fault messages together with the fault symbols are also displayed here.
Humidity indicator and scale
External fan
Operating button control options
Dehumidification External heating
Fault symbol Information display
Up
Left (Decrease value)
Remote control lock Battery indicator
Wireless symbol
Service Temperature indicator
and scale
Right (Increase value)
Power supply
The wireless remote control can be powered using 2 AAA batteries with 1.5 V each or can be powered externally using the USB cable provided.
16
Down
Enter (Change menu item)
Coupling
Connecting the antenna
The antenna is located on
the control board inside the unit or can be fitted there. This will be pre-installed if the unit is delivered together with the remote control. Before fitting the antenna, disconnect the unit from the power supply. Then slacken the two fastening screws on the underside of the unit, tilt the front cover of the unit and lift it up. In the upper right area, remove the two screws on the board cover and remove the cover. Pull the control board forwards, screw the antenna into place and bend it forwards. Once the antenna is screwed in place and the board has been returned to the previous position, the unit can now be provided with power in order to couple it with the wireless remote control. Then screw the housing parts back into place.
Location of the control board
Connecting the antenna
Switching on and coupling the remote control
The wireless remote control must
be coupled with the unit before it can be used. To do so, carry out the following steps.
1. Insert the batteries provided into the battery compartment on the rear of the wireless remote control.
2a. The remote control will search for the unit for two minutes. During this time, the remote control display flashes every 2 seconds.
2b. During the search phase, hold down the Up and Down keys on the operator panel of the control board at the same time for 5 seconds.
3. If coupling was successful, the unit sends a serial number to the wireless remote control and the wireless symbol is displayed.
4. The swimming pool dehumidifier confirms the connection by displaying the code “Conn” for a period of 3 seconds.
This procedure can also be carried out using several remote controls so that an air dehumidifier can be controller by several remote controls.
Coupling failure
If the wireless remote control fails to couple with the unit, the fault symbol becomes visible, “Conn” is shown permanently on the display and the wireless symbol flashes.
The wireless remote control needs to be reset before a new coupling attempt can be made. To do so, hold the Left key on the wireless remote control down for 10 seconds.
17
REMKO SLN Series
General
The wireless remote control displays the values for humidity and temperature at all times. The values only disappear when a malfunction arises. Depending on which function is currently active, one or more of the symbols appear in the centre of the display.
User setup menu
Hold down the Enter key for 3 seconds to open the user setup menu.
In this menu it is possible to switch between the wireless remote control symbols using the Up and Down keys provided the corresponding option of “OF” has been set to a value on the control board itself. Please read pages 11 and 12 to set these values.
User setup menu symbols
External heating
Fitter setup menu
Hold down the Right key for 5 seconds to open the fitter setup menu. At this point it is possible to access all four menu items. It is also necessary to set the respective “OF” option on the control board to a specific value to enable access.
Fitter setup menu symbols
External heating
Dehumidification
External fan
Maintenance interval
Fault messages
The fault messages correspond
to the alarm messages which can also be shown on the unit’s control board display. To make the alarm message recognizable, the fault symbol is also displayed on the wireless remote control.
Fault priority
In the event that several faults
occur at the same time, only the fault with the highest priority is displayed.
Fault priority
HP High priority LP SEnS Abt AbrH Low priority
NOTE
Do not simply reset the fault messages without establishing the cause first.
Maintenance message
Unlike the other fault messages,
the maintenance message can be acknowledged or reset via the wireless remote control. This is due to the fact that it is a purely informative message.
Maintenance message
Dehumidification
The Left and Right keys can be used to set these parameter values. The parameter is confirmed as a new setpoint using the Enter key. When this is confirmed, the remote control switches back to the symbol and exits the menu. If you would like to exit the user setup menu, do not press any keys on the remote control for 10 seconds.
18
Examples of fault messages
Sensor fault
Overly high pressure level detected
Generally speaking, the fault messages can only be reset on the display panel of the control board. The unit must be thoroughly inspected and the fault reset following rectification each and every time.
No changes can be made to the setpoints in the setup menus while there is an active fault.
Proceed as follows to set up the new maintenance interval.
1. Hold down the Right key for 5 seconds to open the fitter menu.
2. Use the Up and Down keys to navigate to the maintenance symbol.
3. Use the Right and Left keys to change the 0 value to the required maintenance interval.
4. Confirm the new maintenance interval by pressing the Enter key.
Care and maintenance
NOTE
Regular care and maintenance is fundamental to a long service life and fault-free operation of the unit.
All moving parts have a low­maintenance permanent coat of lubricant. The refrigerant system is designed as a hermetically sealed system and may only be repaired by a specialist.
Observe the regular care and
maintenance intervals
In accordance with
the operating conditions, the units must be checked as and when required, but at least once per year, by a specialist to ensure that they are in a condition that is safe to use
Keep the units free of dust and
other debris
If the unit is contaminated,
it can be cleaned using a vacuum cleaner. The condensor in particular must be vacuumed thoroughly
Cleaning the suction filter
Check the suction filter at regular intervals and clean if necessary. The filter is secured in a bracket behind the intake openings.
CAUTION
Check the intake openings, as well as filters, regularly for contamination.
Light filter contamination can be
remedied with careful blowing
or suction
Heavier contamination may
be remedied by rinsing the filter
in a lukewarm (max. 40 °C)
soap solution Finally, always
rinse the filter carefully with
clear water and allow to dry
Before refitting the filter, ensure
that its fully dry and that no
damage has been sustained
The units may only be operated
with the filter in place
and
outlet
Operating LED
The multi-colour LED display is located at the upper edge in the centre of the unit. They indicate the current operating state of the unit.
Legend of the LED colours
The LED lights up “blue” and stays that way when the unit is connected to the mains power supply.
The LED lights up “green” and stays that way when the compressor is in operation and the unit is in dehumidifying ordefrosting mode.
The LED lights up “yellow” and stays that way when the unitis operating in wireless remotecontrol mode.
The LED lights up “red” when a fault has occurred. Please refer to the Troubleshooting chapter torectify the fault.
If the evaporator’s fins are
heavily soiled, they can be cleaned carefully with soapy water
Never subject to direct jets
of water e.g. pressure washers
etc.
Never use abrasive or solvent-
based cleaners
Use only suitable cleaners, even
for heavy contamination
NOTE
Heavily contaminated filters must be replaced with new parts. Only original replacement parts may be used.
Cleaning the condensate water collection tray
To ensure that the condensate water that accumulates can always drain freely, the collection tray for the condensate and the drain must be cleaned regularly.
19
REMKO SLN Series
Troubleshooting
Malfunction Possible cause Remedial measures
•Theunitdoesnotstart.
•Thedisplaydoesnotlightup.
•Theunitdoesnotstart.
•Displayindicatesincorrecttype.
•Thecompressordoesnotstart. The compressor switched off
No mains voltage. • Checkthepowersupplyorfuses
Air humidity in room too low.
The unit is outwith its usable limits of 10 - 36 °C.
automatically due to an overly high condensor temperature.
Lack of air ventilation.
Overly high ambient temperature.
Contaminated filter/intake device.
or switches on site.
• Checktheintegratedhygrostatand
set it to a low relative humidity, e.g. < 40 % RH.
• Checktheroomconditionsand
alter as required.
Check the following points if the unit does not start after 45 minutes:
• Checkifthefan(s)is/areworking.
• Checkiftheintakelteris
contaminated.
• Checkthattheintakeandoutlet
openings are free of contamination.
• Checkifthecondensorns
are contaminated.
• Checkiftheroomtemperature
is above 36 °C. If the room temperature is above 36°C, the unit must be switched off.
NOTE
If it is not possible to determine the cause of the fault, switch off the unit immediately and disconnect it from the mains power supply to prevent further damage.
NOTE
If all of the functional checks have been carried out without any findings, please contact an authorised service station.
20
CAUTION
Work on the refrigerant system and on the electrical equipment must only be conducted by a specially­authorised specialist!
CAUTION
Prior to maintenance or repair work, the unit must be disconnected from the mains power supply.
Fault messages
Code and
value
LOSS
Abt
AbrH
SEnS Sensor fault, causes the unit to stop
The connection to the remote control has been lost
Ambient temperature is outwith the permissible range
Air humidity is outwith the permissible range
Cause Remedial measures
When the connection is restored, acknowledge by clicking “OK”.
Acknowledgement not possible. Automatic reset as soon as the temperature has returned to the permissible range.
Acknowledgement not possible. Automatic reset as soon as the air humidity has returned to the permissible range.
Press the Up or Down key to see which probe is affected. Exchange the probe if necessary.
COnd - condensor probe EUAP - evaporator probe RH°t - humidity and temperature probe
Acknowledgement possible only by way of unlocking sequence. Initiate the sequence by pressing the “OK” key.
Malfunction must be established and rectified
LP Low pressure level detected
HP High pressure level detected
Unlocking sequence
Once the unlocking sequence has been initiated, the unit displays the information “Loc”. If the Down key
is pressed at this point, the information display switches to “UnLo” which displays the unlocking option. If “UnLo” is confirmed with the “OK” key, the unit is enabled again.
by specialist personnel. Acknowledgement possible only by way of unlocking sequence. Initiate the sequence by pressing the “OK” key.
Malfunction must be established and rectified by specialist personnel. Acknowledgement possible only by way of unlocking sequence. Initiate the sequence by pressing the “OK” key.
Information messages
Code and
value
Log
After inserting a USB memory stick into the USB interface
Occurrence Comment
Once the USB stick has been inserted, the process of copying the log data from the internal memory to the USB memory stick is initiated and declared as finished by the information “Log”.
21
REMKO SLN Series
Cooling cycle
7
1
3
SLN 45 - 85
5
6
2
4
Legend:
1. Compressor
2. Evaporator
3. Condenser
4. Thermal expansion valve
5. Dry filter
6. Solenoid valve
7. Fan
22
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Electrical wiring diagram
SLN 45 - 85
Electronic control board
Remote
Display
Legend:
FAN 1 = fan motor 1 FAN 2 = fan motor 2 FAN 3 = fan motor 3 CAP 1 = capacitor 1 CAP 2 = capacitor 2 CAP 3 = capacitor 3
L N PE
USB
RS485
_
Ext. RH/T
COMP. = compressor VALVE = solenoid valve RUN = potential-free contact FAIL = potential-free contact HEAT 1/2 = 12 V supply voltage
for controlling relays
NOTE
Alarm
12 V DC
Operator panel
Bedienfeld
Fan motors:
SLN 45 = FAN 1 SLN 65 = FAN 1 and FAN 2 SLN 85 = FAN 1, FAN 2 and
FAN 3
CAUTION
A main switch should be installed
NOTE
at a suitable and easily accessible
Prior to maintenance or assembly work, the unit must be disconnected from the mains power supply.
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
point in the mains supply line. We recommend using a mains supply line of 2.5 mm² for the units.
Assembly and maintenance work on the units may only be carried out by authorised and qualified technicians.
23
REMKO SLN Series
Intended use
The units are designed exclusively for dehumidification purposes on the basis of their structural design and equipment.
A failure to observe the manufacturer's specifications, the respective local legal requirements or arbitrary alterations to the units, exempts the manufacturer from liability for resulting damage.
NOTE
Operation other than the types listed in this operating manual is prohibited. With non-observance, any manufacturer liability or guarantee claims are voided.
Customer service and guarantee
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or their representative complete and return the “Certificate of guarantee” to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units are tested several times to verify their correct function. However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
Environmental protec­tion and recycling
Disposal of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in stable transport packaging and, if applicable, on a wooden pallet. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
CAUTION
Copyright The redistribution, even in part, or the use of this documentation for purposes other than intended is strictly prohibited without the written authorisation of
REMKO GmbH & Co. KG
.
NOTE
Setting and maintenance work may only be carried out by authorised and qualified technicians.
Important information concerning recycling
The units are operated with environmentally-friendly and ozone-neutral R407C refrigerant. The mixture of refrigerant and oil within the unit must be disposed of properly in accordance with the statutory or locally-applicable regulations.
Disposal of the old unit
The manufacturing process for the units is subject to continuous quality control.
Only high-grade materials are processed, the majority of which are recyclable.
You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner.
Therefore, only bring the old unit to an authorised recycling business or to an appropriate collection point
.
24
Exploded view of the unit
2
3
4
1
8
22
21
5
6
7
9
10
11
12
13
14
15
20
19
18
17
16
25
REMKO SLN Series
Spare parts list
No. Designation SLN 45 SLN 65 SLN 85
1 Wall-mounted bracket
2 Wall spacer
3 Cable gland
4 Series terminals on DIN rail
5 Control board
6 Holder for control board with operator panel
7 Condenser fan
8 Compressor capacitor
9 Spatter guard
10 Compressor
11 Compressor accessories
12 Solenoid valve
13 Dry filter
14 Copper piping set
15 Condensate tray
16 Housing cover
17 Fan module
18 Fan
19 Evaporator
20 Condenser
21 Temperature valve
22 Compressor insulation.
- Air circulation intake filter (duct)
EDP no. on request
26
When ordering replacement parts, please always state the EDP no. and unit number (see name plate)!
RS-485 interface
The RS-485 interface uses the Modbus RTU protocol as a slave unit. The unit does not have an address. Settings: 115200, N, 8, 1. It accepts queries for any address.
Code functions
0x06 Present single register
0x10 Present multiple register
0x03 Read holding register
Register Byte
2 Comp_state 0 1 0
2
3 Fan_state 0 1 0
4 Sole_state 0 1 0
3
5 ExFan_state 0 1 0
6 Heat1_state 0 1 0
4
7 Heat2_state 0 1 0
8 Alarm1_state 0 1 0
5
9 Alarm2_state 0 1 0
10
6
11
Database
parameters
Evap_temp1
(decimal)
Evap_temp1
(fraction)
Min Max Hr. Description
Compressor status: 0 – Compressor stopped 1 – Compressor running
Fan status: 0 – Fan stopped 1 – Fan running
Solenoid valve: 0 – closed 1 – open
Extractor fan status: 0 – Fan stopped 1 – Fan running
Status HEAT 1: 0 – HEAT 1 off 1 – HEAT 1 on
Status HEAT 2: 0 – HEAT 2 off 1 – HEAT 2 on
Output alarm 1: 0 – Alarm output off 1 – Alarm output on
Output alarm 2: 0 – Alarm output off 1 – Alarm output on
-40 100 0
-40 100 0
Temperature of evaporator 1: Decimal: Can be used as an integer value for temperature. Fraction: Can be converted to a decimal value. To obtain the total value, use the equation for floating-point numbers: “Value = decimal + (fraction/256)”.
12
7
13
Evap_temp2
(decimal)
Evap_temp2
(fraction)
-40 100 0
-40 100 0
Temperature of evaporator 2: Use as described above.
27
REMKO SLN Series
Register Byte
14
8
15
16
9
17
18
10
19
20
11
21
Database
parameters
Cond_temp1
(decimal)
Cond_temp1
(fraction)
Aux_temp
(fraction)
Aux_temp
(fraction)
Amb_temp
(decimal)
Amb_temp
(fraction)
Amb_hum
(high byte)
Amb_hum (low byte)
Min Max Hr. Description
-40 100 0
-40 100 0
-40 100 0
-40 100 0
-40 100 0
-40 100 0
0 100 0
Condenser temperature: Use as described above.
Auxiliary probe temperature: Use as described above.
Ambient air temperature: Use as described above.
Ambient air humidity: High byte is insignificant and always contains zero. Only low byte can be used.
12
13
16
17
18
19
22 RH_set 40 95 40 Humidity setpoint.
23 RH_Fan 40 95 40 Humidity setpoint for extractor fan start.
24
25
30 Fail_start 0 1 0 Status of Fail_start mode.
31 SB_mode 0 1 0 Standby mode status.
32 DEH_mode 0 1 0 Dehumidification status.
33 Ice_mode 0 1 0 Defrosting mode.
34 LP_mode 0 1 0 LP fault mode status.
35 Sens_mode 0 1 0 Sensor fault mode status.
36 HP_mode 0
37 Amb_mode 0 1 0 Ambient fault mode status.
Temp_set
(decimal)
Temp_set
(fraction)
0 36 0
1 0 HP fault mode status.
Temperature setpoint: Used in the same way as Evap_temp1.
28
20
38
39
AmbT_
mode
AmbRH_
mode
0 1 0 Ambient temperature fault mode status.
0 1 0 Ambient humidity fault mode status.
Register Byte
Database
parameters
Min Max Hr. Description
21
22
23
41
42
40
41
42
43
44
45
number (high)
number (low)
Software version
(main version)
Software version
(minor version)
HP alarm temp.
HP alarm temp.
80
Fan_function 0 1 0 Activate fan function in standby mode.
81
82
Time_wait_fan 60 7200 3600
83
SW build
SW build
(decimal)
(fraction)
0
65535 x Software build number.
0
0 255 x Main version number of the software.
0 255 x Minor version number of the software.
HP faults occur when Cond_temp1 is greater than
0 99 60
this value. Used in the same way as Evap_temp1.
Waiting time until fan starts up in standby mode, if activated (seconds).
43
44
45
84
Time_run_fan 15 600 60
85
Fan operating time in standby mode, if activated (seconds).
86 RH_Fen 0 1 0 Activate/deactivate extractor fan function.
87 Service_ena 0 1 0 Activate/deactivate maintenance interval function.
88
Service_int 0 99 0 Maintenance interval value in weeks.
89
29
REMKO SLN Series
USB interface
The USB interface is used for transferring data logs from the unit to a USB stick. The unit data is saved every three hours and stored in the internal memory. Switching the status to fault mode also triggers the storage of data. If the memory is completely full, the oldest logs are overwritten by the newest logs. When a USB stick is inserted into the USB interface, all of the logs that have been recorded are saved in the CSV file “data_log.csv”. The data is the internal memory is not deleted as a result of this process and can therefore be transferred to several USB sticks.
The data log is saved in the form of the following parameters:
Database parameters Size (bits) Output text CSV column
Work_time 32 <dd:mm:hh:ss> Time stamp
Amb_temp 8 <Value> T_amb
Amb_int_temp 8 <Value> T_amb_int
Amb_ext_temp 8 <Value> T_amb_ext
Aux_temp 8 <Value> T_aux
Cond_temp1 8 <Value> T_cond
Evap_temp1 8 <Value> T_evap1
Evap_temp2 8 <Value> T_evap2
Temp_set 8 <Value> T_set
Amb_hum 8 <Value> RH_amb
Amb_int_hum 8 <Value> RH_amb_int
Amb_ext_hum 8 <Value> RH_amb_ext
RH_set 8 <Value> RH_set
RH_Fan 8 <Value> ExtFanSet
Evap_temp_err 1 EVAP Error
Cond_temp_err 1 COND Error
Aux_temp_err 1 AUX Error
Amb_int_err 1 AMB_INT Error
Amb_ext_err 1 AMB_EXT Error
SB_mode 1 SB Mode
Startup_mode 1 STARTUP Mode
DEH_mode 1 DEH Mode
Ice_mode 1 ICE Mode
LP_mode 1 LP Mode
HP_mode 1 HP Mode
Sens_mode 1 SENS Mode
AmbT_mode 1 AMBT Mode
AmbRH_mode 1 AMBRH Mode
Service_ena 1 ENABLED Mode
30
Maintenance protocol
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Condenser cleaned
Evaporator cleaned
Fan function checked
Unit checked for damage
Safety devices checked
All fastening screws checked
Electrical safety check
Test run
Comments: ..........................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
1. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
11. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
17. Date: ............
..............................
Signature
3. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
13. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
5. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
31
REMKO SLN Series
Technical data
Series SLN 45 SLN 65 SLN 85
Daily dehumidification capacity at 30 °C and 80 % RH Litres/day 47 78 104
Daily dehumidification capacity at 30 °C and 60% RH Litres/day 35.5 56.2 78.8
Operational temperature range °C 10 to 36
Usable humidity range
Air volume m
% RH 40 to 100
3
/h 400 680 900
Power supply V/Hz 230/1~/50
Max. power consumption kW 0.9 1.5 1.8
Max. rated current consumption A 3.8 6.6 8
Max. switching voltage from RUN and FAIL contact V 50 50 50
Max. switching current from RUN and FAIL contact A 0.5 0.5 0.5
HEAT contact voltage V 12 12 12
Maximum current limit of a HEAT contact mA 60 60 60
Refrigerant
1)
R407C
Refrigerant quantity kg 0.7 0.9 1.2
Sound pressure level L
pA
1m
Depth / Width / Height mm
dB (A) 43 44 47
294/998/700 294/1148/700 294/1483/700
2)
Weight kg 57 66 77
IP enclosure class X4 X4 X4
EDP no. 616455 616655 616855
1) Contains greenhouse gas according to Kyoto protocol 2) Noise level measurement DIN 45635 - 13 - KL 3 carried out at duct openings
Capacity diagram SLN 45
40
35
30
25
20
Room temperature [°C]
15
B
A
10
5
0
0 0,5 1 1,5 2 2,5
32
C
Dehumidification capacity [l/h]
40% r.F.
A
60% r.F.
B
80% r.F.
C
Capacity diagram SLN 65
40
35
40% r.F.
A
60% r.F.
B
30
25
20
Room temperature [°C]
15
B
A
10
5
0
0 0,5 1 1,5 2 2,5 3 3,5 4
C
Dehumidification capacity [l/h]
80% r.F.
C
Capacity diagram SLN 85
40
35
30
25
Room temperature [°C]
20
15
B
A
10
5
0
0 1 2 3 4 5
C
Dehumidification capacity [l/h]
40% r.F.
A
60% r.F.
B
80% r.F.
C
Notes
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 E-mail info@remko.de Internet www.remko.de
Consulting
Thanks to intensive training,
our consultants are always
completely up-to-date when
it comes to technical expertise.
This has given us the reputation
of being more than just
an excellent, reliable supplier:
REMKO, a partner who helps
to solve problems.
Sales
REMKO offers not just a well
established sales network both
nationally and internationally, but
also has exceptionally highly-
qualified sales specialists.
REMKO employees in the field
are more than just sales
people: above all, they must
be advisers to our customers
in air conditioning and heating
technology.
Customer service
Our units operate precisely and
reliably. However, in the event
of a malfunction REMKO
customer service is quickly
on the scene. Our extensive
network of experienced dealers
guarantees quick and reliable
service.
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!
Loading...