REMKO SLE Series, SLE 40, SLE 80, SLE 60 Assembly And Operating Instructions Manual

Assembly and operating instructions
REMKO SLE series
Pool dehumidifiers
SLE 40, SLE 60, SLE 80
Edition GB - N11
Read the instructions prior to performing any task!
Contents
Dehumidification
Safety information
Unit description
Installation
Commissioning
Care and maintenance
Troubleshooting
Refrigeration circuit
Electrical wiring diagram SLE 40-80
Diagram of unit SLE 40-80
Spare parts list SLE 40-80
Maintenance log
Intended use
4-6
6
7
8
9
10
11
12
13
14
15
16
17
Customer service and warranty
Environmental protection and recycling
Unit dimensions
Technical data
This operating manual is a translation of the German original.
17
17
18
19
These instructions are part of the unit and must always be kept near to the site of installation or on the unit.
Subject to changes; errors and typographical errors excepted!
3
REMKO SLE series
Dehumidification
The interrelated processes occur­ring during dehumidification are based on physical laws. These are illustrated here in simpli­fied form in order to explain the principle of dehumidification.
The use of REMKO dehumidifiers
– No matter how well windows
and doors are insulated, damp and moisture can penetrate even through thick concrete walls.
– The water volumes required for
binding concrete, mortar, plas­ter, etc. are diffused out initially after 1-2 months under certain circumstances.
– Even moisture that has penetrat-
ed masonry following high wa­ter or flooding is only released very slowly.
– This applies similarly to e.g.
moisture contained in stored materials.
The moisture (water vapour) es­caping from buildings or materials is absorbed by the ambient air. This increases their moisture content and ultimately results in corrosion, mould, rot, peeling of paint coat­ings and other unwanted moisture damage.
The diagram opposite shows an example of the rate of corrosion, e.g. for metal at different humidity levels.
corrosion rate
relative humidity
It can be seen that the rate of corrosion is insignificant below 50% relative humidity and can be disregarded below 40% relative humidity.
The rate of corrosion increases noticeably from 60% relative hu­midity. This moisture damage limit applies also to numerous other materials, e.g. powders, packag­ing, wood or electronic units.
Buildings can be dried out in differ­ent ways:
1. By heating and air exchange:
The room air is heated to absorb
moisture in order to then be dis­charged to the atmosphere. The total input energy is lost with the discharged, moist air.
2. By dehumidification:
The moist air in an enclosed
room is continuously dehumidi­fied according to the condensa­tion principle.
In terms of energy consumption, dehumidification has one decisive advantage:
Energy expenditure is restricted solely to the existing room vol­ume. The mechanical heat released through the dehumidification proc­ess is returned to the room.
With correct use, the dehumidifier consumes only about 25% of the energy required for the “heating and ventilation” principle.
Relative humidity
Ambient air is a gas mixture and always contains a certain amount of water in the form of water vapour. This water volume is ex­pressed in g per kg dry air (abso­lute water content).
1m3 air weighs about 1.2 kg at 20°C
Depending on the temperature, each kg of air is only able to ab­sorb a certain amount of water va­pour. When this absorptive capac­ity is reached, reference is made to “saturated” air; this has a relative humidity of 100%.
Relative humidity is therefore un­derstood to be the ratio between the amount of water vapour cur­rently contained in the air and the maximum water vapour volume at the same temperature.
The ability of air to absorb water vapour increases with increas­ing temperature. This means that the maximum (= absolute) water content increases with increasing temperature.
4
Temp. Water vapour content in g/m3 at a humidity of
Verdampfer Kondensator
°C
30
25
20
15
% r.F.
100
90
80
70
60
50
40
30
20
10
+
+
-
Lufttemperatur
Luftfeuchte
Verlauf
Luftrichtung
Verdampfer Kondensator
°C
30
25
20
15
% r.F.
100
90
80
70
60
50
40
30
20
10
+
+
-
Lufttemperatur
Luftfeuchte
Verlauf
Luftrichtung
°C 40% 60% 80% 100%
-5 1.3 1.9 2.6 3.3
+10 3.8 5.6 7.5 9.4
+15 5.1 7.7 10.2 12.8
+20 6.9 10.4 13.8 17.3
+25 9.2 13.8 18.4 23.0
+30 12.9 18.2 24.3 30.3
Drying materials
Building materials or structures can absorb substantial amounts of wa­ter, e.g. bricks 90-190 l/m³, heavy concrete 140-190 l/m³, lime-sand bricks 180-270 l/m³. The drying out of moist materials, e.g. masonry, takes place as fol-
The air enriched with water
vapour continuously circulates through the REMKO dehu­midifier. It is dehumidified and leaves the unit at a slightly higher temperature to absorb water vapour from anew.
lows:
In this way, the moisture con-
The contained moisture moves from the
tained in the material is gradu­ally reduced.
The material dries!
inside of the material to its surface.
Evaporation takes place on the
The produced condensate is col­lected in the unit and discharged.
surface = transition as water va­pour to the ambient air.
Condensation of water vapour
Since the maximum water vapour volume increases when the air is heated, the contained water va­pour volume remains the same however, this results in a reduction of the relative humidity.
In contrast, when the air is cooled, the capacity to absorb the maxi­mum water vapour volume reduc­es, the water vapour volume con­tained in the air remains the same and the relative humidity increases. If the temperature falls further, the capacity to absorb the maximum water vapour volume is reduced until it is equal to the contained water vapour volume. This temperature is called dew­point temperature. When the air is cooled below the dew-point temperature, the contained water vapour volume is larger than the maximum water vapour volume. Water vapour is discharged. This condenses to water. The air is relieved of moisture.
Examples of condensing are misted windows in winter or misting of a cold drinks bottle.
The air flow is cooled on its way through or via the evaporator to below the dew point. The water vapour condenses and is collected in a condensate trap and discharged.
Evaporator Condenser
Air temperature
Air flow direction
Air humidity
Trend
The higher the relative humidity, the higher the dew-point tempera­ture, which is easier to fall below.
5
REMKO SLE series
Heat of condensation
The energy transferred from the condenser to the air is composed of:
1. Heat energy previously removed in the evaporator.
2. Electrical motive energy.
3. Heat of condensation released during condensation of the water vapour.
For the change from a liquid to a gaseous state, energy is necessary. This energy is termed heat of eva­poration. It does not cause any rise of tem­perature, it is only necessary for the change from a liquid to a gaseous state.
Vice versa, energy is released during the liquefaction of gas, which is termed heat of condensation.
The amount of heat of evaporation and condensation is the same. For water, this is:
2250 kJ/kg (4.18 kJ = 1kcal)
This shows that a relatively large amount of energy is released through the condensation of water vapour. If the moisture to be condensed is not introduced through evapo­ration in the room itself, but from outside, e.g. via ventilation, the heat of condensation released in the process contributes towards room heating. During dehumidifi­cation, the heat energy is recircu-
lated, which is consumed during evaporation and released during condensation. During dehumidification of the supplied air, a large amount of heat energy is produced, which is expressed in a rise of temperature.
The time necessary for drying normally does not depend only on the unit capacity, but is rather determined by the rate at which the material or parts of the build­ing release their moisture.
Safety information
The units were subjected to ex­tensive material, functional and quality inspections and tests prior to delivery.
However, the units may constitute a hazard if used by untrained per­sonnel, improperly or not for the intended purpose.
The following information must be observed:
The units must not be installed and operated in hazardous lo­cations.
The units must not be installed and operated in atmospheres containing oil, sulphur or salt.
The units must not be exposed to direct water jets.
The air openings must always be kept free.
The air suction grilles must al­ways be kept free of dirt and loose objects.
The units must not be covered during operation.
Never insert foreign objects into the units.
All electrical cables outside the units must be protected against damage (e.g. animals, etc.).
The units must only be installed or mounted in the intended position (horizontal).
Free and frost protected condensate discharge must always be ensured.
The unit connections must always comply with the respectively applicable installation regulations.
ATTENTION
The units must be installed and mounted so that they are easily accessible for monitoring, repair and maintenance.
6
Unit description
The units are designed for univer­sal and problem-free dehumidifica­tion. They can be installed at numerous locations due to their compact size.
The units operate on the conden­sation principle with hermetically sealed refrigeration system with silent and low maintenance recir­culation fan(s).
The fully automatic electronic control, integrated hygrostat and connections for local condensate discharge ensure trouble-free, con­tinuous operation.
The units are reliable and easy to use and comply with the funda­mental health and safety require­ments of the pertinent EU regula­tions.
The units are used wherever dry rooms are a necessity and dam­age (e.g. due to mould) is to be avoided.
The units are also used for dehumidification of:
Private swimming pools
Wellness spas
Operation
All units are switched on and off by the integrated hygrostat. The respective unit function is shown on the front display.
The recirculation fan sucks in the humid room air via suction open-open­ings below the front panel.
This is transported via a filter, evaporator and condenser. At the cold evaporator, heat is extracted from the room air and cooled to below the dew point. The water vapour contained in the room air deposits as condensate or frost on the evaporator gills.
At the condenser (heat ex­changer), the cooled and dehu­midified air is reheated and blown back into the room via the upper blow out openings with a slight rise of temperature of about 5°C above room temperature. The conditioned drier air conti­nuously mixes with the room air. Due to the constant circulation of the room air through the unit, the relative humidity in the room is gradually reduced to the required humidity (% relative humidity).
The hygrostat is set at the factory to 60% relative humidity.
Depending on the room air tem­perature and relative humidity or only during the defrost phase the condensed water constantly drips into the condensate trap and sub­sequently via the integrated drain connection into the condensate drain to be provided locally.
Safety circuit:
If the temperature at the condens-at the condens­er should exceed 55°C (e.g. due to fan failure or clogged suction filter), the compressor automatical-tomatical­ly stops to avoid being overloaded. The compressor restarts automati-s automati­cally after 45 minutes.
The compressor always starts with a 30 second delay.
Whirlpool areas
Sports studios
Store rooms/archives
Museums
Functional diagram of SLE 40-80 dehumidifier
Heat and dehumidified air
Humid room air
7
318
105
REMKO SLE series
Installation
!
ATTENTION
A installation of the unites are in areas with a higher risk po­tential. In addition to the local regulations especially the VDE regulations in terms of protec­tion areas, local equipotential bonding, equipment, protection and safety classes are observed.
The unit should not be installed
close to radiators or other heat sources.
The room to be dehumidified
must be closed from the ambi­ent atmosphere.
Open windows, doors, etc., as
well as frequent entering and leaving the room should be avoided as far as possible.
Access to control
After removing 2 screws at the top of the unit, lift up the front panel and remove it from the unit horizontally. The control is located in a housing above the compressor. Access to the control takes place by removing the 2 screws on the front of the housing.
For optimal and reliable unit op­eration, the following information must be observed in any event:
The unit must be mounted or
installed in a suitable location appropriate to the structural conditions.
The supplied wall bracket with
suitable fixing material (not included) must be fixed securely to the wall.
The unit must be mounted or
installed horizontally to ensure free condensate drainage.
The unit must be mounted or
installed so that the air is able to be sucked in and blown out unhindered.
For optimal operation of the
unit, the minimum clearances from the unit to the ceiling and floor must be maintained.
For optimal room air circulation
by the dehumidifier, the supply and exhaust air openings must always be kept free of dirt and other obstacles.
Wall mounting of units
Condensate drain
The condensate drain is located at the bottom of the unit. The condensate drain must be connected to the supplied drain connection. A solid or flexible ½“ drain con­nection can be connected.
The drain hose must always be
installed with a minimum gradi­ent of 2% to enable the water to drain unhindered from the drip tray.
Alternatively, a condensate
pump (accessory) can also be mounted on the unit in order to pump the produced condensate to an outlet.
For an outlet through the wall,
specific preparations are neces­sary for correct condensate drainage prior to installation of the unit, e.g. the drilling of holes.
Positioning the condensate drain
8
The position of the outlet con-
nection is shown in the diagram below.
Commissioning
Prior to each commissioning or as required, the air inlet and outlet grilles must be checked for clog­ging.
The units operate via an integrated hygrostat set to 60% relative hu­midity (standard value for swim­ming baths and indoor swimming pools). The unit does not start at room air conditions below 60% relative humidity. If the relative humidity is above 60%, the unit automatically starts the dehumidi­fication process.
The front housing panel can be removed to make any changes to the hygrostat setting. The hygrostat is located next to the evaporator below the com­pressor housing. Turning the control knob clockwise reduces the humidity, turning an­ticlockwise increases the humidity. An external hygrostat (accessory) can be fitted if required. Connection option, see under “Electrical wiring diagram”.
In order to prevent compressor damage, the units are provided with reclosing protection, which prevents immediate reconnection of the compressor after disconnec­tion
The compressor initially switches on again after a delay of about 30 seconds!
LED display
The units are provided with an electronic control. The following functions are controlled, monitored and displayed:
Safety
Monitoring
On/off
The LED display is located on the side of the unit.
NOTE
If the unit is switched on or off via a main switch, all LEDs successively show green and the triangle red.
Symbol legend
The LED shows constant „green“ when the unit is connected to the supply.
The LED shows constant „green“ when the com­pressor is operating and the unit is dehumidifying.
This LED has no function for dehumidification.
+
A constant „green“ lightning symbol indicates that the supply is connected to the unit. Alternating „green“ and „red“ flashing LEDs indicate a unit fault registered via the condenser sensor (overheating).
If the condenser sensor registers an excessive temperature, the compressor is switched off and the unit remains inoperational for 45 minutes. After lapse of this time, the unit is automatically switched on again. After switching on again, the „red“ triangle symbol no longer flashes, the drop symbol continues to flash.
The lightning symbol shows con­stant „green“.
+
A „green“ flashing drop symbol and a constant „green“ lightning symbol indicate that the unit is functioning, but has been switched off by the condenser sensor (over-nsor (over­heating).
+
NOTE
Interruption of unit operation for less than 6 minutes com­pressor operating time will force a restart lockout of about 4 minutes.
NOTE
If the relative humidity is below 60%, the unit will not start, even when the supply is connected.
NOTE
The flashing drop symbol is extinguished when the power is switched off and on again.
9
REMKO SLE series
Care and maintenance
Fan control
When the hygrostat starts the dehumidifier, the fan(s) is/are switched on together with the compressor.
If constant ventilation is required, i.e. independent of dehumidifica­tion, a jumper can be connected between terminals 25 and 26.
The fan or fans then operate in a continuous mode!
Defrosting
At room temperatures below 20°C, the evaporator will start to frost after a short time. When the evaporator sensor registers a temperature below 5°C on the evaporator surface, the unit continues to operate for 30 min­utes in dehumidification mode. After lapse of this time, the com­pressor stops and passive defrost­ing starts in that the fan or fans slowly blow room air over the evaporator and gradually defrost the same in the process. When the evaporator sensor regis­ters a temperature above 5°C, the compressor is switched on again.
Safety circuit
If the temperature at the conden­ser should exceed 55°C (e.g. due to fan failure or excessive room temperature (above 36°C), the compressor automatically stops to avoid being overloaded. The compressor restarts automati­cally after 45 minutes.
The drop symbol in the display flashes!
NOTE
Regular care and maintenance is a basic precondition for a long useful life and trouble­free operation of the unit.
All moving parts are provided with low-maintenance permanent lub­rication. The refrigeration system is a hermetically sealed system and must only be repaired by authori­sed specialist companies.
Observe regular care and main-
tenance intervals.
Depending on the particular
operating conditions, the units should be tested by an expert for reliable operation as neces­sary, but at least once a year.
Keep the unit free of dust and
other deposits.
If the unit should become
fouled, it can be cleaned with a vacuum cleaner, whereby the condenser should be thorough­ly cleaned.
If the evaporator gills are
heavily fouled, they should be cleaned carefully with soapy water.
Do not use a direct water jet
e.g. high pressure cleaner, etc.
Do not use caustic cleaning
agents or those containing solvents.
Only use suitable cleaning
agents to remove heavy foul­ing.
Cleaning the suction filter
The suction filter should be checked at regular intervals and cleaned if necessary. The filter is fixed in a holder be­hind the suction openings.
ATTENTION
Regularly check the suction and blow out openings as well as filters for clogging.
A lightly clogged filter can be
cleaned by carefully blowing out or using suction.
A heavily clogged filter can be
washed in a luke warm (maxi­mum 40°C) soap solution. Sub­sequently rinse thoroughly with clear water and allow to dry!
It must be ensured that the
dust filter is completely dry and undamaged prior to refitting.
The units must only be operated
with the dust filter fitted.
NOTE
Heavily clogged dust filters must be replaced with new ones. Only original spare parts must be used.
Cleaning the condensate water collecting tray
To ensure that the produced con­densate water is able to drain fre­ely, the condensate collecting tray and the outlet must be cleaned at regular intervals.
10
Troubleshooting
Fault Possible cause Remedy
•Theunitdoesnotstart.
•Lightningsymbolindisplaydoes
not light.
•Theunitdoesnotstart.
•Lightningsymbolindisplay
shows constant „green“.
•Thecompressordoesnotstart.
•Thetrianglesymbolinthe
display flashes constant „red“.
No supply voltage. • Indicatesthattheunitisoperating,
but has switched off due to over­heating.
Room humidity too low.
The unit is outside its operating limits of 10 – 36°C.
The compressor was automati­cally switched off due to exces­sive temperature.
Lack of ventilation.
Excessive ambient temperature.
Clogged filter/suction.
• Checktheintegratedorexternal
hygrostat by setting it to a low rela­tive humidity, e.g. < 40%.
If the unit does not switch on
again, the integrated or external hygrostat must be checked for a fault.
• Checktheroomconditionsand
change if necessary.
If the unit does not start after 45 min­utes, the following must be checked:
• Checkthatthefan/fansis/areop­erating.
• Checkwhetherthesuctionlteris
clogged.
• Checkthatthesuctionandblow
out openings are free.
• Checkwhetherthecondensergills
are fouled.
• Checkwhethertheroomtempera­ture is possibly above 36°C. If the room temperature is above 36°C, the unit must be switched off.
•Thelightningsymbolinthe
display shows constant „green“.
•Thedropsymbolinthedisplay
flashes constant „green“.
NOTE
If no result is achieved after carrying out all functional checks, an authorised service station should be contacted.
Indicates that the unit is operat­ing, but has switched off due to overheating.
ATTENTION
All work on the refrigeration system and electrical equip­ment must be referred to an authorised specialist!
• Theindicationcanbecancelledby
disconnecting and reconnecting the supply.
ATTENTION
Prior to carrying out mainte­nance or repairs, the unit must always be disconnected from the supply.
11
REMKO SLE series
Refrigeration circuit
7
3
SLE 40
1
5
6
2
4
Legend:
1. Compressor
2. Evaporator
3. Condenser
4. Thermal expansion valve
5. Dry filter
6. Solenoid valve
7. Fan
SLE 60 and SLE 80
7
8
1
3
12
5
6
2
We reserve the right to make dimensional and design changes in the interest of technical advances.
4
Legend:
1. Compressor
2. Evaporator
3. Condenser
4. Thermal expansion valve
5. Dry filter
6. Solenoid valve
7. Fan
8. Non-return valve
Electrical wiring diagram
R3.1 R3.2
HY-G
230V
50 Hz
M 1
M
1~
M
1~
M 2
Y 1
Test
M
1~M1~
M 4M 3
AMB.
NTC
COND.
NTC
EVAP.
NTC
PRES.
THA
WAT.
SENS
HYG TH.
STAT
FAN
0/1
MAINS FANCOMPA VALVE
HEAT
1 2 1 2
2
1
TEST/ COMM
S
C
R
PE
PE
SOLENOID VALVE
PE
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 1 2 3 4 5 6 7 8
PE N L14 3 2 1
EA
SLE 40 - SLE 80
Electronic control board
Fan motors:
SLE 40 = Motor M2 SLE 60 = Motor M2 and M3 SLE 80 = Motor M2, M3 and M4
Legend:
EA = Electr. connection box HY-E = Room hygrostat
(accessories) HY-G = Hygrostat
Constant ventilation:
If constant air circulation is re­quired, i.e. independent of de­humidification, a jumper can be connected between terminals 25
and 26.
External hygrostat (accessories):
Remove the both jumper at the terminals 1+3 and 2+4 in the con­nection box EA.
M 1 = Compressor M 2 = Fan motor 1 M 3 = Fan motor 2 M 4 = Fan motor 3 Y 1 = Solenoid valve R3.1 = Condenser sensor R3.2 = Evaporator sensor
The fan or fans then operate with­out any control and monitoring in a continuous mode.
Install the external hygrostat at a suitable location in the room to be dehumidified and connect to terminals 1 and 2.
The output voltage on terminals 1 and 2 is 12V.
ATTENTION
Prior to carrying out mainte­nance or repairs, the unit must always be disconnected from the supply.
NOTE
A disconnector switch should be installed in the supply con­nection at a suitable and easily accessible location.
Only authorised special­ists may install and carry out maintenance work on the units!
EA
HY-E
NOTE
% RF
PE N L14 3 2 1
230V
50 Hz
We reserve the right to make dimensional and design changes in the interest of technical advances.
13
REMKO SLE series
Diagram of unit SLE 40 - 80
4
7
6
1
2
8
9
11
5
25
24
16
20
22
18
15
27 28
3
30
35
14
Fig. REMKO SLE 80
We reserve the right to make dimensional and design changes in the interest of technical advances.
12
38
Spare parts list
No. Designation SLE 40 SLE 60 SLE 80
EDP No. EDP No. EDP No.
1 Wall bracket 1109144 1109165 1109177
2 Housing rear 1109145 1109166 1109178
3 Cable gland 1109129 1109129 1109129
4 Condenser 1109146 1109167 1109179
5 Fan complete with 800mm cable 1109147 1109147 1109147
6 Fan complete with 1200mm cable — — 1109168 1109168
7 Fan complete with 1600mm cable — — — — 1109180
8 Evaporator 1109148 1109169 1109181
9 Condensate tray, complete 1109149 1109170 1109182
11 Suction filter 1109150 1109171 1109183
12 Front panel 1109151 1109172 1109184
15 Evaporator sensor (metal) 1109160 1109160 1109111
16 Condenser sensor 1109161 1109161 1109161
18 Thermo valve 1109158 1109173 1109185
20 Hygrostat 1109115 1109115 1109115
22 Dry filter 1109157 1109157 1109157
24 Control board 1109152 1109152 1109152
25 Diode board with cable 1109154 1109154 1109154
27 Terminal, two-pole 1109155 1109155 1109155
28 Capacitor 1109156 1109156 1109156
30 Solenoid valve, complete 1109110 1109110 1109110
35 Non-return valve — — 1109176 1109176
38 Compressor, complete 1109162 1109174 1109186
Spare parts (not illustrated)
Electrical connection box 1109163 1109163 1109163
When ordering spare parts, please always also quote the serial number (see rating plate) in addition to the EDP No.!
15
REMKO SLE series
Maintenance log
Model: .................................. Serial No.: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - externally
Unit cleaned - internally
Condenser cleaned
Evaporator cleaned
Fan function checked
Unit checked for damage
Protective devices checked
All fixing screws checked
Electrical safety check
Test run
Remarks: .....................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
1. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
11. Date: ............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
3. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
13. Date: ............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
5. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
The unit must only be serviced by authorised specialists in compliance with the statutory requirements.
16
17. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
Intended use Environmental
The units are designed and equipped for dehumidification purposes.
The manufacturer is not liable for any damage attributed to failure to observe the manufacturer‘s instructions or applicable statu­tory requirements or unauthorised changes to the unit.
NOTE
Use for any other purpose than that described in these operating instructions is not permitted. Failure to observe this rule will invalidate all liability and warranty.
Customer service and warranty
A precondition for any warranty claims is that the dealer or his cus­tomer has completed and returned the enclosed “Warranty Docu- ment” to REMKO GmbH & Co. KG at the time of sale and com­missioning of the units.
The units have been repeatedly tested for perfect functioning. If malfunctions should occur that cannot be remedied by trouble­shooting, your specialised dealer or contract partner should be con­tacted.
NOTE
Only authorised specialists may carry out adjustments and maintenance.
protection and recycling
Disposal of packaging
Think of the environment when disposing of the packaging mate­rial. Our units are carefully packed for transport and delivered in sturdy cardboard packaging on a wooden pallet, if necessary. The packaging materials are en­vironmentally-friendly and can be recycled. By reusing packaging material, you make a valuable contribution towards waste reduction and the conservation of raw materials.
Only dispose of packaging mate­rial at the facilities provided.
Disposal of old unit
ATTENTION
Copyright Any copying of this document in whole or part or use for pur­poses other than the intended is strictly forbidden without the prior written permission of
REMKO GmbH & Co. KG.
Important information on recycling
The units are operated with en­vironmentally-friendly and ozone neutral refrigerant R407C. In accordance with legal and lo­cally applicable requirements, the mixture of refrigerant and oil con­tained in the unit must be disposed of properly.
Our production is subject to con­stant quality controls.
Only high-quality materials are used, the majority of which are recyclable.
Make your contribution towards environmental protection by disposing of your old unit in an environmentally-friendly manner.
Only dispose of your old unit at an authorised recycling facility or similar.
17
REMKO SLE series
Unit dimensions
B
315
140
130
A-A
Series Dimensions in mm
A B
SLE 40
SLE 60
950 890
1260 1190
675
50
A
35
90
800
A-A
14
18
SLE 80
Maß- und Konstruktionsänderungen, die dem technischen Fortschritt dienen, bleiben uns vorbehalten.
1800 1730
30
22
52
Technical Data
Series SLE 40 SLE 60 SLE 80
Daily dehumidification capacity at 30°C and 80% relative humidity
Daily dehumidification capacity at 30°C and 60% relative humidity
Litre/day 50.4 70.8 100.8
Litre/day 32.2 43.2 64.0
Operating temperature range °C 10 to 36
Humidity operating range
Refrigerant
1)
Max. operating pressure, refrigerant
% rel. humidity
kPa
40 to 100
R407C
1900 / 2800
Refrigerant quantity kg 0.6 0.95 1.6
Max. air capacity m3/h 250 500 750
Sound pressure level LpA 1m
2)
dB (A) 47 49 51
Power supply V/Hz 230/1~/50
Enclosure class IP X4
Max. power consumption kW 0.72 1.05 1.65
Max. rated power consumption A 2.8 4.3 7.2
Depth mm 315 315 315
Width mm 950 1260 1800
Height mm 800 800 800
Weight kg 60 74 101
Serial number 731... 732... 733...
EDP No. 615400 615600 615800
1) Contains greenhouse gas according to Kyoto protocol,
2) Noise measurement DIN 45635 - 13 - Category 3
We reserve the right to make dimensional and design changes in the interest of technical advances.
19
REMKO SLE series
Capacity diagram SLE 40
40
35
30
25
20
Room temperature [°C]
15
A
10
B
C
40% r.F.
A
60% r.F.
B
80% r.F.
C
5
0
0 0,5 1 1,5 2 2,5
Dehumidification capacity [l/h]
Capacity diagram SLE 60
40
35
30
25
40% r.F.
A
60% r.F.
B
80% r.F.
C
Room temperature [°C]
20
15
A
10
5
0
0 0,5 1 1,5 2 2,5 3 3,5
20
B
C
Dehumidification capacity [l/h]
Capacity diagram SLE 80
40
35
30
25
Room temperature [°C]
20
15
A
10
5
0
0 1 2 3 4 5
40% r.F.
A
60% r.F.
B
80% r.F.
C
B
C
Dehumidification capacity [l/h]
21
REMKO SLE series
22
23
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage PO Box 1827 D-32777 Lage Telephone +49 52 32 606-0 Telefax +49 5232 6 06-260 E-mail info@remko.de Website www.remko.de
Consulting
Thanks to intensive training,
our consultants are always
completely up-to-date in terms
of technical knowledge. This has
given us the reputation of being
more than just an excellent,
reliable supplier:
REMKO, a partner
helping you find solutions to
your problems.
Distribution
REMKO offers not just a well
established sales network both
nationally and internationally, but
also has exceptionally highly-
qualified sales specialists.
REMKO field staff are more than
just sales representatives: above
all, they must act as advisers to
our customers in air conditioning
and heating technology.
SFlbCustomer Service
Our equipment operates
precisely and reliably. However,
in the event of a fault, REMKO
customer service is quickly at
the scene. Our comprehensive
network of experienced dealers
always guarantees quick and
reliable service.
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...