These operating instructions should be read carefully
prior to commissioning / operation of the equipment!
20-21
21
22
23
23
24-25
24-25
26
Made by REMKO
These instructions are part of the equipment and must always
be kept in the vicinity of the installation or on the equipment
Subject to modifications; No liability accepted for errors or misprints!
3
REMKO RXD
4
Safety notes
Carefully read this manual before
starting the unit for the first time.
It contains useful tips, information
as well as hazard warnings to
prevent injury or material damage
. Non-observance of this
manual may endanger persons,
the environment as well as the
equipment itself and will void any
claims for liability.
■ Store this manual as well as
the refrigerant datasheet in the
vicinity of the unit.
■ The unit should only be set
up and installed by qualified
personnel.
■ The setup, connection and
operation of the unit and
its components must be in
accordance with the operating
conditions stipulated in this
manual and comply with all
applicable local regulations.
■ Units designed for mobile use
should be safely set up on a
suitable floor and in a vertical
position. Units designed for
stationary use should only be
operated in their permanently
installed state.
■ It is prohibited to make
modifications or changes to
equipment or components
supplied by REMKO as this may
cause malfunctions.
■ Equipment and components
should not be operated in areas
where there is a heightened
damage risk. Observe the
minimum clearances.
■ The electrical supply should
be adapted to fulfil the
requirements of the unit.
■ The operational safety of
equipment and components is
only assured providing they are
used as intended and in a fully
assembled state. Safety devices
should not be modified or
bypassed.
■ Do not operate equipment
or components with obvious
defects or signs of damage.
■ All housing parts and openings,
e.g. air inlets and outlets, must
not be blocked by foreign items,
fluids or gases.
■ The equipment and components
must be kept a safe distance
from inflammable, explosive,
combustible, aggressive and
dirty areas or atmospheres.
■ Persons coming into contact
with equipment parts may suffer
burns or injury.
■ Installation, repair and
maintenance work should only
be carried out by authorised
specialists. Inspection and
cleaning can be performed
by the operator providing the
equipment is not under voltage.
■ Take appropriate hazard
prevention measures when
performing installation, repair or
maintenance work or cleaning
the equipment.
■ The equipment or components
should not be exposed to any
mechanical stresses, extreme
levels of humidity or direct
exposure to sunlight.
Environmental
protection and
recycling
Disposal of packaging
All products are packed for
transport in environmentally
friendly materials. Make a valuable
contribution to reducing waste
and sustaining raw materials. Only
dispose of packaging at approved
collection points.
Disposal of old
equipment
Our production facility is subject
to continuous quality control.
Only high-grade materials are
processed, the majority of which
are recyclable. Help protect the
environment by only disposing
of old equipment in accordance
with local regulations and in an
environmentally safe manner, e.g.
through authorised disposal and
recycling specialists or at collection
points.
Warranty
Prerequisite for any warranty
claims is that the purchaser or his
client has completely filled out the
"warranty registration card" and
commissioning report included
with the unit at the time when
the equipment was purchased
and commissioned and returned
these papers to REMKO GmbH &
Co. KG. The warranty conditions
are detailed in the "General terms
and conditions". The contractual
parties can also agree additional
terms beyond the scope of the
above. In this case, first contact the
contractual partner.
Transport and
5
packaging
The equipment is shipped in sturdy
packaging. Immediately check
the equipment on delivery and
make a note of any damage or
missing parts on the delivery note.
Inform the forwarding agent and
contractual partner.
No warranty can be assumed for
later claims.
Description of the
equipment
The indoor unit on the split-design
combined room air conditioning
units serves to extract heat from
the indoor room being cooled. The
outdoor component then expels
this heat to the outside.
If combined heating/cooling
units are operated as heaters, the
heat absorbed by the outdoor
component can be discharged
by the interior unit into the room
being heated.
The unit is designed for
suspended ceilings with Euroraster
dimensions. The cassette is hidden
behind the suspended ceiling, only
its cover is visible. It is operated via
an infrared remote control.
The indoor unit consists of a fin
vaporiser, vaporiser fan, regulation
system and condensation pan.
The indoor unit can be combined
with REMKO outdoor components
that provide sufficient cooling
output. The outdoor component is
controlled via the regulation of the
indoor unit.
Condensation pumps and wired
remote controls are available as
accessories.
Schematic of refrigerant circuit
Vaporiser fan
Vaporiser
System design
Indoor area
Indoor unit with
Cover
Outdoor area
Condensation pipe
Condensation
pipe
Outdoor component
Connection to suction pipe
Connection to injection pipe
Control cable
Injection pipe
Mains cable
Suction pipe
Stop valve
Liquefier fan
Refrigerant pipes are used to connect the indoor unit to the outdoor
component.
The indoor unit is easy to operate
using an infrared remote control.
This is supplied as standard. The
indoor unit beeps to acknowledge
the correct transmission of data.
If it is not possible to program
the indoor unit using the remote
control, it can also be manually
operated.
Display on indoor unit
Manual operation
The indoor units can be started
manually.
Press the RESET button on the
receiver unit of the cover to
activate automatic mode. In manual
operation, the following settings
apply:
Cooling mode: 24 °C,
Fan speed: AUTO
Heating mode: 26 °C,
Fan speed: AUTO
Pressing any button on the infrared remote control interrupts
manual operation
Infrared remote control
The infrared remote control
sends the programmed settings
at a distance of up to 6 m to the
receiver on the interior unit.
Data will only be received correctly
if the remote control is pointed
at the receiver and no objects are
obstructing the transmission path.
First insert the supplied batteries (2
each, type AAA) into the remote
control. To do so, remove the
cover on the battery compartment
and insert the batteries. Take into
account the correct polarity (see
markings).
Max. distance 6 m
The lit display LEDs indicate the settings.
LED H red = high fan speed
LED M yellow = medium fan speed
LED L green = low fan speed
Display on indoor unit
Unit for receiving signals
from the remote control
CAUTION
Problems are shown in code
(see chapter on trouble-
shooting and customer
service).
LEDHLEDMLEDLRESET button
max. 6 m
Manual operation
NOTE
Immediately replace flat
batteries with a new set,
otherwise there is a risk of
leakage. It is recommended that
the batteries are removed if the
equipment is shut down for
long periods.
Buttons on the remote control
7
Buttons on the remote control
"POWER" button
Press this button to start the
unit.
"TEMP" Button
Press this button to set the
desired temperature in 1 °C
steps within the range 16 °C to
30 °C.
"TIME-SET" Button
Press this button to set the
time.
"MODE" button
Press this button to select the
operating mode. The indoor unit
has 5 modes:
1. Automatic mode
(COOL/HEAT):
In automatic mode, the
temperature is maintained at
the target temperature.
"SWING" Button
This button switches on the
oscillating fins to provide
improved air distribution in the
room. It can also be used to
lock the fins.
"FAN" button
Press this button to set the
required fan speed. 4 levels
are available: Automatic, high,
medium and low fan speed.
"TIME-OFF" Button
This button is used to program
the automatic switch-off
function for the indoor unit.
"TIME-ON" Button
This button is used to program
the automatic switch-on
function for the indoor unit.
"C" Button
Press this button to activate the
time setting.
2. Cooling mode (COOL):
In cooling mode, the warm
room air is cooled to the lower
preset target temperature.
3. Dehumidifying mode (DRY):
In this mode the room is mainly
dehumidified.
4. Circulation mode (FAN)
In circulation mode only the
air is circulated. The room
temperature is not controlled.
5. Heating mode (HEAT):
(only for RXS...H)
In heating mode the cold room
air is heated to the preset higher
temperature.
This mode should not be used
on RXM units (malfunctions may
occur)!
"R" Button
Press this button to reset the
remote control to its factory
default configuration.
"NETWORK" Button
This button has not been
assigned a function.
"SLEEP" Button
Pressing this button will
automatically increase or
decrease the target temperature
by 1 °C within an hour in
cooling and heating mode
respectively.
REMKO RXD
8
Button functions
A symbol is shown on the display to indicate that the settings are being transferred.
POWER Button
TEMP Button
Press the POWER button to activate/deactivate the indoor unit. The
programmed settings and adjustment values before the unit was turned
off will appear in the display.
POWER
The TEMP button is used to set the desired target temperature in 1 °C
steps. This setting is not supported in FAN circulation mode.
TEMPTEMP
TIME Button C
RESET Button R
Use a small pen or similar to press recessed button C, the time will flash
on the display. Press and hold the TIME-SET button to, at first slowly,
and then quickly adjust the clock time. Once it has been set, press the C
button again to save the time. The display will stop flashing.
TIME-SETCC
Setting the clock
Use a small pen or similar to press recessed button R. All the symbols will
appear on the display. After approx. 5 seconds only the time will flash on
the display. After pressing recessed button C, press and hold the TIMESET button to set the time. Once it has been set, press the C button
again to save the time. The display will stop flashing.
R5 sec.C
MODE Button
9
Press the MODE button to change to another mode. A total of 5 modes
are available:
1. AutomaticAutomatic selection of cooling or heating operation
2. CoolingCooling mode, predominantly used during summer
3.
Dehumidification
Dehumidifying mode, used in summer or winter
4. Air circulationCirculation mode, no cooling or heating output
5. HeatingPredominantly used during winter (only for RXS...H)
MODEMODEMODEMODE
Mode AUTO
Mode COOL
Press the MODE button once or repeatedly to switch to automatic mode.
In this mode, the regulation automatically selects COOL or HEAT mode
depending on the temperature. The temperature is then maintained at
the set value. This function should only be used on RXS...H units. Only
cooling mode is activated on RXM units; heating mode is not supported.
The FAN should be set to AUTO.
Set temperature is below the
room temperature
Set temperature is above the
room temperature
MODE
TEMP
COOLING
or
HEATING
Press the MODE button once or repeatedly to switch to cooling mode.
Use this mode to cool the room air to the desired target temperature.
Press the TEMP ▲/▼ buttons to set the desired room temperature
in 1 °C steps. If the room temperature is 1 °C above the desired
temperature and sufficient coolant is available, the indoor unit will start
to cool the room air. f the actual temperature falls approx. 0.5 °C below
the set room temperature, the controller switches the cooling off.
TIP
It is recommended that the
target temperature is set to
max 6 °C below the outdoor
temperature. The automatic
fan speed and swing functions
should also be used.
MODE
COOLING MODE
REMKO RXD
10
Mode DRY
Mode FAN
Press the MODE button once or repeatedly to switch to dehumidifying
mode. Use this mode to dehumidify the room in an unregulated fashion.
After pressing the DRY button, select the desired temperature and fin
position. It is not possible to set the fan speed. The fan is switched off at
certain intervals to lower the temperature at the cooling battery. The low
temperature causes the air temperature at the fins to fall below the dew
point. Excess humidity in the air condenses on the cooling battery and
the room is dehumidified.
MODE
DEHUMIDIFYING MODE
Press the MODE button once
TIP
or repeatedly to switch to
circulation mode. In this mode,
the equipment is used as an
air circulation unit. The room is
neither heated nor cooled.
MODE
This mode is used in winter
to circulate the heat trapped
under the ceiling to the lower
regions of the room.
CIRCULATION MODE
SWING Button
Mode HEAT
NOTE
The SWING button is used to provide continual and automatic vertical
adjustment of the fins. This facilitates improved distribution of the cooled
air inside the room. If the SWING button is pressed during the swing
motion, the fins stop in their current position. Pressing the button again
resumes the swing motion.
SWINGSWING
SWINGSWINGSWINGSWING
Press the MODE button once or repeatedly to switch to heating mode.
Use this mode to heat the room air to the desired target temperature.
This function should only be used on RXS...H units. Only cooling mode is
activated on RXM units; heating mode is not supported.
The fan will only start when the fin temperature reaches 38°C.
Press the TEMP ▲/▼ buttons to set the desired room temperature
in 1 °C steps. If the room temperature falls 1 °C below the set target
temperature, heating mode is activated. f the actual temperature rises
approx. 1 °C above the set room temperature, the controller switches the
heating off.
It is recommended that the
target temperature is set to
max. 28 °C. Maximum fan
speed and the lowest fin
setting should also be used.
MODE
HEATING MODE:
TIME Buttons
11
Switch-on time
Switch-off time
The TIME-ON/-OFF buttons are used to program the switch-on/off time,
the TIME-SET button to set the time.
Press the TIME-ON or TIME-OFF button to activate the timer. The clock
display then disappears. The timer symbol for the switch-on/off time will
flash. Press the TIME-SET button to set the desired switch-on/off time in
10 minute steps.
After programming has been completed, the settings are transmitted to
the indoor unit. For delayed switch-on press the TIME-ON button, for
delayed switch-off press the TIME-OFF button. The timer symbol will
stop flashing and the indoor unit beeps to acknowledge the programmed
parameters.
When the programmed time has been reached, the device is
automatically turned on or off. If the indoor unit is automatically
switched on, then the mode, temperature and fan speed for the last
setting is reactivated.
The switch-on/off time can be prematurely cancelled by pressing the
appropriate TIME button or POWER button
Switch-on time
TIME-ONTIME-SETTIME-ON
SLEEP Button
NETWORK Button
Switch-off time
TIME-OFFTIME-SET
TIME-OFF
After the SLEEP button is pressed, the symbol is shown on the display
and the room temperature is raised or lowered by 0.5 °C in cooling and
heating mode respectively 30 minutes after the function starts up. After
a further 30 minutes the room temperature is raised or lowered by 1 °C
in cooling and heating mode respectively. After a further hour the room
temperature is held at a constant 2°C above or below the original target
temperature in cooling and heating modes respectively. The temperature
is then maintained at a constant level. This function is disabled by pressing
the POWER or SLEEP button. The symbol on the display goes out.
COOLING
SLEEPSLEEP
MODE
HEATING
SLEEPSLEEP
MODE:
The NETWORK button on RXD units has not been assigned a
function.
REMKO RXD
12
Shutdown
Temporary shutdown
1. Allow the indoor unit to run
for 2 to 3 hours in circulation
mode or in cooling mode at the
maximum temperature setting
in order to remove any residual
moisture from the unit.
2. Shut down the unit using the
remote control.
3. Switch off the voltage supply to
the unit.
4. Check the unit for visible
signs of damage and clean as
described in the chapter "Care
and maintenance".
Permanent shutdown
Ensure that equipment and
components are disposed of
accordance with local regulations,
e.g. through authorised disposal
and recycling specialists or at
collection points.
Contact REMKO GmbH & Co. KG
or your contract partner for a list
of specialist companies near you.
Care and maintenance
Regular care and observation
of some basic points will ensure
trouble-free operation and a long
service life.
CAUTION
Prior to performing any work,
ensure the equipment is
isolated from the voltage
supply and secured to prevent
accidental switch-on!
Care
■
Ensure the unit is protected
against dirt, mould and other
deposits.
■
Clean the unit using a damp
cloth. Do not use any caustic,
abrasive or solvent-based
cleaning products. Do not use
a jet of water.
■
Clean the fins on the unit prior
to long shutdown periods.
Maintenance
■
It is recommended that you
take out a maintenance
contract with an annual service
from an appropriate specialist
firm.
TIP
This ensures the operational
reliability of your equipment!
Cleaning the cover of the
indoor unit
1. Disconnect the supply voltage
to the equipment.
2. Open and fold down the air
inlet guard on the cover. The
filter is held in place by the flaps
screwed in at the side of the
guard (Page 13, Fig. 1).
3. Clean the guard using a soft,
damp cloth.
4. Switch the supply voltage back
on.
Type of task
Checks / maintenance / inspection
General
Measure voltage and current
Check fan is functioning correctly
Dirt on vaporiser
Check condensation drain
Test insulation
Check moving parts
Commissioning
Monthly
Six-monthly
••
••
••
••
••
••
••
Yearly
Air filter for indoor unit
13
Clean the air filter at intervals of
no more than 2 weeks. Reduce this
interval if the air is especially dirty.
9. Switch the supply voltage back
on.
10.
Switch the unit back on.
1 Guard on cover
Cleaning the filter
1. Disconnect the supply voltage
to the equipment.
2. Open and fold down the air
inlet guard on the cover. The
filter is held in place by the flaps
screwed in at the side of the
guard (Fig. 1).
3. Tilt the filter to lift it out (Fig. 2).
4. Clean the filter using a normal
vacuum cleaner (Fig. 3). Turn
the dirty side until it faces up.
5. Any dirt can be cleaned off
using lukewarm water and mild
cleaning agents.
To do so, turn the dirty side
downward (Fig. 4).
Cleaning the condensation
pump
The indoor unit includes a built-in
condensation pump, for pumping
the condensation to a drain at
a higher level.
The pump is more or less
maintenance free. The condensation
pipes should be checked for dirt
at regular intervals. Clean them as
required.
If an external pump is also used,
observe the maintenance and care
instructions given in the separate
operating manual.
2 Pull out the filter
3 Clean with a vacuum cleaner
6. When using water, allow the
filter dry out properly in air
before replacing it in the unit.
7. Carefully insert the filter. Make
sure it is seated correctly.
8. Close the cover as described
above but in reverse order.
4
Cleaning with lukewarm water
REMKO RXD
14
Troubleshooting and customer service
The equipment and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the
list below. For installations with an indoor unit and outdoor component, refer to the chapter "Troubleshooting
and customer service" in both manuals. Please inform your dealer if the unit is still not working correctly after all
the functional checks have been performed!
Malfunction
FaultPossible causeChecksRemedial measures
The unit does not start
or switches itself off
The unit does not respond
to the remote control
Power outage, undervoltage,
defective mains fuse / main circuit
breaker switched off
Damaged mains cable
Waiting time after switch-on too short
Temperature outside operating range.
Overvoltages caused by thunder
storms
Fault in external condensation pump
Transmission distance too far /
receiver affected by interference
Defective remote controlIs the unit running in manual mode?Replace the remote control
Receiver or transmitter unit exposed
to excessive solar radiation
Electromagnetic fields are interfering
with transmission
Button in remote control jammed /
two buttons pressed at same time
Batteries in remote control are flat
Filter is unclean / air inlet / outlet
blocked by foreign items
Are all other electrical installations
functioning correctly?
Are all other electrical installations
functioning correctly?
Have approx. 5 minutes
elapsed since the restart?
Are the fans in the indoor unit
and outdoor component working
correctly?
Has there recently been lightning?
Did the pump shut down due to a
fault?
Does the indoor unit beep when
pressing a button?
Does it function correctly in the
shade?
Does it function when switching off
possible sources of interference?
Does the “Send” symbol appear on
the display?
Have new batteries been inserted? Is
the display incomplete?
Have the filters been cleaned?Clean the filters
Check voltage, possible wait until
turned on again.
Repair by a specialist
Schedule longer waiting periods
Take into account the temperature
range for the indoor unit and outdoor
component
Switch off the mains breaker and
switch it back on. Have it checked by
a specialist
Check and if necessary clean the
pump
Reduce the distance to less than 6 m
or change position
Place the receiver&transmitter unit in
the shade
Signal is not transmitted when
interference sources are operational
Release the button / only press one
button
Insert new batteries.
The unit is running
but only provides
reduced cooling / heating
performance
Condensation discharge
on unit
Icing up of
unit
Windows and doors open. Heating/
cooling output increases
Neither cooling nor heating mode has
been set
Fins on outdoor component blocked
by foreign items
Leaking refrigerant circuit
Outdoor component iced up
Drainage pipe on collection container
clogged / damaged
Faulty external condensation pump
or float
Condensation has not drained away
and has collected in the condensation
pipe
Condensation does not drain off
Float is stuck or jammed due to
excessive dirt.
In conjunction with RXM:
Heating/automatic mode set
Have there been any constructional /
application-related changes?
Does the cooling symbol appear on
the display?
Is the fan on the outdoor component
running? Are the fins unobstructed?
Are there signs of frost on the fins of
the indoor unit?
Check outdoor component. Has
the cassette sensor on the outdoor
component been correctly positioned?
Can the condensation drain off
without any obstruction?
Is the collection tray full of water and
the pump not running?
Is there a steady fall on the
condensation pipe? Check there is no
blockage in the pipe.
Are the condensation pipes unblocked
and is there a steady fall? Are the
condensation pump and float switch
functioning correctly?
Are the LEDs on the receiver unit of
the indoor unit flashing?
Check mode settingSet cooling mode
Close windows and doors / install
additional units
Correct the settings for the unit
Check the fan or winter controller,
reduce the air resistance
Repair by specialist
De-ice and fit the sensor at the point
where the most ice forms
Clean the drainage pipe and collection
container
Call out a specialist to replace the
pump
Ensure there is a fall when laying the
condensation pipe and clean the pipe.
The condensation pipe must have
a fall. If necessary, clean the pipe. A
faulty condensation pump and float
switch should be replaced.
Should be cleaned by specialist firm
Error and operational malfunction indicated by flashing code
Observe the manuals for
the indoor unit and outdoor
component when installing the
entire system.
■
Transport the unit in its original
packaging as close as possible
to the installation location to
avoid transport damage.
■
Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report
any damage immediately to
your contracting party and the
shipping company.
■
Lift the unit at the corners
and not by the refrigerant or
condensation connections.
■
The refrigerant pipes (injection
and suction pipe), valves and
connections must be insulated
impervious to vapour diffusion.
If necessary, also insulate the
condensation pipe.
■
Select an installation location
which allows air to freely flow
through the inlet and outlet (see
section "Minimum clearances").
■
Do not install the unit in
the immediate vicinity of
devices with intensive thermal
radiation. Installation near
sources of thermal radiation
reduces the output of the unit.
■
Seal off open refrigerant pipes
with suitable caps or adhesive
strips to avoid infiltration of
moisture and never kink or
compress the refrigerant pipes.
■
Only use the union nuts for the
refrigerant pipes included in
the delivery, and remove them
shortly before connecting the
refrigerant pipes.
■
Establish all electrical
connections in accordance with
the relevant DIN- and VDE
standards.
■
See electrical connection
diagram Always properly
insert electrical cables into the
electrical terminals. Otherwise
a fire could result.
REMKO RXD
16
■
Service openings should be
provided in the suspended
ceiling to allow maintenance
access to the control box.
■
Any ventilation ducts or pipes
and connection fittings, which
are used to connect a second
room or supply fresh air, should
be insulated with diffusion-tight
material.
Installation material
The indoor unit is fastened using
4 threaded rods (provided by the
customer) at the side mounts.
In order to complete the
installation, wall plugs, trapezoidal
sheet metal supports, steel profiles,
fixing clamps for refrigerant and
condensation pipes (as well as
laying ducts) and connection
fittings for condensation pipes are
also required.
Selection of the installation
location
The indoor unit is designed
for horizontal mounting in
suspended ceilings with Euroraster
dimensions. It can also be installed
in other types of suspended
ceilings with different dimensions.
Take into account the installation
height of the equipment.
Installation
Minimum clearances
Observe the minimum clearances to allow access for maintenance and
repair work and facilitate optimum air distribution.
Minimum clearances
300
300
300
300
300
300
300
NOTE
Installation should only be
performed by authorised
specialists.
Unit installation
The unit is mounted face down
on four threaded rods. Take into
account the ceiling grid and any
other installations.
1. Use the dimensions of the
ceiling cassette to mark the
fixing points for the threaded
rods on structural parts
approved to support the static
load above the suspended
ceiling.
2. Fit any connection nozzles
before installing the unit
if connections to a second
room or a fresh air intake are
required.
See section Connections to
a second room or a fresh air
intake.
300
300
300
All values in mm
3. Fit the indoor unit onto the
threaded rods and use the
lower nuts to level the unit
(Fig 5 and 6).
4. Make sure that clearance A,
17
as specified in the table below,
is provided between the
underside of the suspended
unit and the underside of the
fastening surface. Connect
the refrigerant pipes, electrical
cables and condensation pipe
to the indoor unit as described
below (Fig. 7).
5 Hooking in the unit
Structural component
6 Mounting the unit
RXD 260-520
5. Check that the unit is level.
6. The final task is to tighten the
counternuts and attach the
cover.
RXD 680-1200
Connection of refrigerant
pipes
The refrigerant pipes are
connected to the RXD 260-520 on
the angled side of the unit and on
the RXD 680-1200 in the middle
of the longer side.
It may be necessary to fit a
reducer or flared adapter to the
indoor units. These fittings are
included as standard with the
indoor unit. Once installed, the
connections should be made tight
against vapour diffusion.
CAUTION
The units are factory filled with
dry nitrogen to check for leaks.
The pressurised nitrogen is
released when loosening the
union nuts.
280
615
7 Fastening the unit
Structural component
A
B
Dimensions in mm
Distance A35 mm
RXD
260
RXD
350
RXD
520
810
All values in mm
RXD
680
RXD
1200
615
Distance B25 mm
Mounting the unit615 x 280 mm615 x 810 mm
REMKO RXD
18
Connections to adjacent room
and fresh air intake
The indoor unit has been designed
to allow the cooling of a second
room as well as the intake of fresh
air.
CAUTION
It is only permitted to connect
one fresh air intake and one
adjacent room!
Installation instructions
Proceed as follows to make the
connections to a second room and
the fresh air intake:
1. Please note that the vaporiser
fins are located directly behind
the cover being removed. These
should not be damaged under
any circumstances (Fig. 8).
Connections to adjacent room and fresh air intake
Fresh air intake
Connection to
adjacent room
Connection to
adjacent room
8 Remove the cut-out9
Connection to
adjacent room
Fresh air intake
Connection to
adjacent room
Fresh air intake
Carefully remove the insulation
2. Carefully remove the insulation
behind the opening (Fig 9).
3. Break through the appropriate
opening (Fig. 10).
4. Keep the ventilation pipes as
short as possible and lay them
in such as way as to minimise
the amount of bends.
5. The collars, screws, flexible /
folded spiral seam pipes and
insulation materials should be
provided by the customer.
The above items can be
obtained from specialist
suppliers (Fig. 11).
10
Break through the opening
11
Attaching the pipe collar
Connection to adjacent room
19
The indoor unit can also be used
to cool an adjacent room through
a duct system, e.g. hidden behind
a suspended ceiling. The following
conditions must be met:
■
The rated cooling output of the
indoor unit must be sufficient
for both rooms.
■
An opening must be made
between both rooms to allow
the air to circulate.
■
The maximum pipe length of
7 m should not be exceeded.
■
Observe the regional
regulations concerning air
treatment.
■
Fit a collar with a nominal
diameter of 70 mm to the fresh
air intake.
■
The fresh air content should not
exceed 10 % of the nominal
air flow rate for the equipment.
The fresh air supply should
be controlled by an additional
speed-regulated fan.
Connection to adjacent room
■
The air at the outdoor air intake
should be sucked in through
a dust filter at a maximum
rate of 2.5 m/s to prevent the
ingress of rain water.
■
The fan should be connected to
a separately protected electrical
supply (to be provided by the
customer).
■
In order to ensure that the air
is transported to the adjacent
room, close off 1 or 2 of the
four outlets on the cover. Stick
a black single-sided adhesive
fabric strip over the outlet
openings being covered. This
strip must be able to withstand
the effects of a continual air
flow.
Fresh air intake
As already mentioned, the indoor
unit can also be employed to suck
in and regulate the temperature of
fresh (outdoor) air in addition to
room air.
This is the preferred option for
rooms with a high rate of air
consumption.
Fresh air intake
Main room
max. 7 m
Adjacent room
Fresh air
intake
InsideOutside
REMKO RXD
20
Condensation
connection
If the temperature falls below the
dew point, condensation will form
on the cooling fins during cooling
mode.
A collection tray together with
a condensation pump and float
switch are fitted as standard below
the cooling fins. Should the float
switch trip a protective shutdown
due to inadequate removal of
the condensation, the pump will
switch on immediately and run on
for approx. three minutes.
Riser pipe too far awayCondensation pipe too large/small
■
The condensation pipe should
have a fall of min. 2 %.
This is the responsibility of
the customer. If necessary,
fit vapour diffusion tight
insulation.
■
If the level of the condensation
pipe on the unit is above
that of the outlet, route the
pipe vertically upwards (max.
1000 mm from the bottom
edge of the unit) and then with
a fall to the drain.
■
The condensation pipe from
the unit should run freely
into the drainage pipe. If the
condensation runs directly
into a sewer pipe, fit a trap to
prevent any unpleasant odours.
■
When operating the unit at
outdoor temperatures below
0 °C, ensure the condensation
pipe is laid to protect it against
frost.
If necessary, fit supplementary
pipe heating.
■
Once the pipe has been laid,
check the condensation drains
off and permanently seal it.
min. 2% fall
16-20 mm
No fallCannot freely drain away
Electrical connection
A protected mains supply cable
and six-core (RXS) or four-core
(RXM) control cable should
be connected to the outdoor
component and indoor unit
respectively.
CAUTION
All electrical installation
work should be performed
by specialist contractors.
Isolate the voltage supply
when connecting the electrical
terminals.
■
We recommend that customers
install a main/repair switch
in the vicinity of the outdoor
component.
■
The terminal blocks for making
the connections are located at
the rear of the unit. When the
unit is installed, measurements
can be made from the front by
removing the cover.
maximum
1,000 mm
max. 100 mm
■
If an optional condensation
pump is used in conjunction
with the unit, it may be
necessary to install an
additional relay with a higher
contact rating after the switchoff contact on the pump to
switch off the compressor.
Make the following electrical
21
connections:
1. Connect the control cable from
the outdoor component
Make the connection as follows:
1. Open the control box cover by
removing the fixing screws and
lifting off the cover (Fig. 12).
12
Connecting the unit
2 Connection of external
temperature sensor in indoor
unit/outdoor component.
2. Feed the voltage-free cable
through the edge protection
rings on the control box and
clamp the cable in the strain
3. If necessary, connect a fresh air
relief.
fan
3. The connect the cable as shown
4. If necessary, connect an
on the connection diagram.
external condensation pump
4. Connect the electrical
Make all connections inside the
control box. The connection
terminals are at the side of the unit
in the suspended ceiling.
connectors on the cover to
the mating connectors on the
cassette. It is not possible to
incorrectly connect these.
5. Re-assemble the unit.
Electrical connection diagram
Connection of RXS 261-681H
CAUTION
Check all plugged and clamped
terminals to verify they are
seated correctly and making
a permanent contact. Retighten as required.
Connection of RXS 1200H
Outdoor componentIndoor unitMains cable
Phase conductor
Control conductor
Control conductor
Control conductor
O
O
Neutral conductor
3
Compressor contactor
2
Reverse flow valve
1
Fan motor
Earth conductor
O
O
Defrost sensor Outdoor component
should be fitted on the pipe bend in
the lower third of the liquefier.
230 V~,
50 Hz,
L1 / N / PE
Connection of RXM 226-268, RXM 326-335,
RXM 426-435
Outdoor componentIndoor unitMains cable
Phase conductor
Control conductor
O
O
Neutral conductor
1
Compressor contactor
Earth conductor
Fasten the defrost sensor for the
outdoor component in the control
box of the indoor unit!
230 V~,
50 Hz,
L1 / N / PE
Indoor unitOutdoor component Mains cable
L
N
C
Control conductor
V
Control conductor
F
Control conductor
PEPEPE
HP
HP
LP
LP
O
O
Phase conductor
L1
Phase conductor
L2
Phase conductor
L3
N
Neutral conductor
3
Compressor contactor
2
Reverse flow valve
1
Fan motor
Earth conductor
HP
P
HP
LP
P
LP
O
O
L1
L2
L3
N
High pressure sensor
in outdoor component
Low pressure sensor
in outdoor component
Fit the defrost sensor for the
outdoor component on the pipe
bend in the lower third of the
liquefier.
400 V~,
50 Hz,
L1 / L2 / L3 / N / PE
SM1 SM2 SM3 SM4
Jp12
M
T
JP1
M
N
V
L
C
Ec
F
O
PL
O
HP
HP
LP
Jp11
OPT
Jp9 Jp10 Jp7 Jp8
J 1P
Jp3
5Jp
JpF
pCJ
4pJ
REH REL
UX CA E
Jp6
MF
LF
FH
Jp 31
Jp 41
C UP
M
5Jp
SM5 Sm6
Jp15 Jp16
Jp6
SM1 SM2 SM3 SM4
MF
FL
HF
Jp12
M
T
JP1
M
1Jp 3
N
V
L
C
Ec
F
O
PL
O
HP
HP
LP
Jp11
OPT
Jp9 Jp10 Jp7 Jp8
Jp14
1JP
Jp3
Jp5
FJp
JpC
Jp4
REH REL
AUX EC
CPU
REMKO RXD
22
Electrical circuit diagram
RXD 260 - 520
Vaporiser sensor
Wired
remote control
Air circulation sensor
Swing motor 1-4
Sensor
Defrost
Jumper
Jumper
RXD 680 - 1200
remote control
Display
Display
Condensation float switch
Air circulation sensor
Vaporiser sensor
Wired
Fan
motor
Swing motor 1-6
Transformer
Condensation
pump
Defrost sensor
Bridge LP/LP
and HP/HP only
on RXD 680
Transformer
Float
switch
Condensation
Condensation
pump
Legend
L = Phase conductor
N = Neutral conductor
= Earth conductor
F = Fan motor
C = Compressor control
V = Reverse flow valve
Fan motor
1 and 2
LP/LP = Low pressure sensor (if fitted), external
HP/HP = High pressure sensor (if fitted), external
O = Fit the defrost sensor for the outdoor component (only on RXS...H, install in the lower third of the liquefier)
Commissioning
23
NOTE
Commissioning should only be
performed by specially trained
personnel and documented
after the certificate has been
issued.
Observe the manuals
for the indoor unit and
outdoor component when
commissioning the entire
system.
Functional test for cooling
mode.
1. Switch the supply voltage on.
2. Use the remote control to
switch on the unit and select
the cooling mode, maximum
fan speed and lowest target
temperature.
3. Measure and record all
the required values in the
commissioning report and
check the safety functions.
4. Check the control system
for the unit using the
functions described in the
chapter "Operation". Timer,
temperature setting, fan speeds
and switching to ventilation or
dehumidifying mode.
5. Check the correct function
of the float switch and
condensation pump by
pouring distilled water into the
condensation tray.
A bottle with a spout is
recommended for pouring the
water into the condensation
tray.
Functional test for
heating mode.
(only on RXS.H)
1. Switch the supply voltage on.
2. Use the remote control to
switch on the unit and select
the heating mode, maximum
fan speed and highest target
temperature.
3. Measure and record all
the required values in the
commissioning report and
check the safety functions.
4. Check the control system for
the unit using the functions
described in the chapter
"Operation".
Timer, temperature setting, fan
speeds.
Final tasks
■
Re-fit all the dismantled parts.
■
Familiarize the operator with
the system.
NOTE
Check that the stop valves
and valve caps are tight after
carrying out any work on the
refrigerant circuit. If necessary,
use appropriate sealant
products.
Unit dimensions
28
207
298
28
RXD 520RXD 260, RXD 350
580
298
100
100
250
190
1110
195
250
All values in mm
230
100
RXD 260 to 520
280
28
258
580
100
150
185
650
650
615
RXD 680, RXD 1200
1220
690
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
580
810
615
245
REMKO RXD
24
Exploded view RXD 260 to 520
6
4
5
10
7
17
8
11
3
12
13
9
1
2
18
6
14
1516
Spare parts list
the dimensions and constructional design as part of the ongoing
No.Designation RXD 260RXD 350RXD 520
1Air inlet guard110665011066501106650
2Air filter110666411066641106664
3Cover110665311066531106653
4Fin motor110667111066711106671
5Air inlet, module110665411066541106654
6Outlet fins, set of 4110666811066681106668
7Condensation tray110665211066521106652
8Condensation hose110665911066591106659