REMKO ATY 261 DC User Manual

REMKO ATY
ATY 261 DC, ATY 351 DC
Inverter wall - room air conditioner in split - design
Operation · Technology · Spare parts
Edition GB – V08
Contents
Safety notes
Environmental protection and recycling
Warranty
Transport and packaging
Equipment description
Operation
Shutdown
Care and maintenance
Troubleshooting and customer service
Control and resistance
Installation instructions for qualified personnel
Installation
Monitoring for leaks
4
4
4
5
5
6-14
15
15-16
17-18
19
20-23
23-25
25
Condensate drain
Electrical connection
Electrical connection diagram
Electrical circuit diagram
Before commissioning
Add refrigerant
Commissioning
Unit dimensions
Technical data
Exploded view
Spare parts list
Declaration of conformity
Read these operating instructions carefully before commissioning / using the device!
26
26-27
27
28
28
28
29
30
31
32-33
32-33
34
Made by REMKO
Subject to modifications; No liability accepted for errors or misprints!
3
REMKO ATY
Safety notes
Carefully read this manual before putting commissioning the equipment. It provides useful tips and information as well as hazard warnings to prevent injury or material damage . Failure to follow the directions in this manual can result in endangerment to persons, the environment and the equipment itself and will void any claims for liability.
Keep this manual and the refrigerant datasheet near the unit.
The unit may only be set up and
installed by qualified personnel.
The setup, connection and
operation of the unit and its components must be in accordance with the operating conditions stipulated in this manual and comply with all applicable local regulations.
Mobile units must be set up
securely on suitable surfaces and in an upright position. Stationary units must be permanently installed for operation.
Modification of equipment
and components supplied by REMKO is not permitted and can cause malfunctions.
Equipment and components
may not be operated in areas where there is an increased risk of damage. Observe the minimum clearances.
The electrical voltage supply
is to be adapted to the requirements of the equipment.
The operational safety
of equipment and components is only assured if they are used as intended and fully assembled. Safety devices may not be modified or bypassed.
Do not operate equipment
or components with obvious defects or signs of damage.
All housing parts and openings,
e.g. air inlets and outlets, must be free of foreign objects, fluids or gases.
The equipment and components
must be kept an adequate distance from flammable, explosive, combustible, aggressive and dirty areas or atmospheres.
Touching equipment parts can
result in burns or injury.
Installation, repair and
maintenance work may only be carried out by authorised specialists. Visual inspections and cleaning can be performed by the operator as long as the equipment is not under voltage.
Take appropriate hazard
prevention measures when performing installation, repair or maintenance work or cleaning the equipment.
The equipment or components
are not to be exposed to any mechanical stresses, extreme levels of humidity or direct sunlight.
Environmental protection and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components, Help protect the environment by ensuring that the devices or components (for example batteries) are not disposed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recycling specialists or at collection points.
Warranty
In order to make warranty claims, it s essential that the ordering party or their representative complete and return the "certificate of warranty" and "commissioning report" to REMKO GmbH & Co. KG at the time when the equipment was purchased and commissioned. The warranty conditions are detailed in the "General terms and conditions". Only the contractual parties can strike special agreements beyond these conditions. In this case, first contact the contractual partner.
4
Transport and Packaging
The equipment is shipped in sturdy transport packaging. Immediately check the equipment on delivery and make note of any damage or missing parts on the delivery note and inform the forwarding agent and your contractual partner. No warranty can be assumed for later claims.
Equipment description
The ATY 261-351 DC room air
conditioning units have a REMKO
ATY...AT outdoor component as
well as an ATY...IT indoor unit.
When in cooling mode, the outdoor component serves to release the heat extracted by the indoor unit from the room being cooled. In heating operation, the heat absorbed by the outdoor component can be discharged through the indoor unit into the room being heated. In both operating modes, the performance of the compressor precisely adjusts itself to the demand, thereby regulating the nominal temperature with minimal temperature variations.
This "inverter-technology"
results in energy savings over conventional split systems and also reduces noise emissions to a particularly low level. The outdoor component can be installed outdoors or indoors.
The latter requires the fulfilment
of certain conditions. The indoor unit is designed to be mounted high up on indoor walls. Operation takes place using an infrared remote control.
The outdoor component consists
of a refrigerant circuit with compressor, fin condenser, condenser fan, reverse flow valve and throttle element. The outdoor component is controlled via the controller of the indoor unit.
The indoor unit consists of a fin
vaporiser, vaporiser fan, regulation system and condensation pan.
Floor consoles, wall consoles, refrigerant pipes and condensation pumps are available as accessories.
Schematic of outdoor refrigerant circuit
Reverse flow valve
Condenser fan
Condenser Filter dryer Flow regulator
Refrigerant circuit diagram for the indoor unit
Vaporiser
System configuration
Indoor area
Indoor unit
Electr. power supply line Control line
Condensation line
Outdoor area
Outdoor component
M
M
Capillary tube
Vaporiser fan
Injection line
Condensation line
Compressor
Connection valve Suction line
Connection valve Injection line
Connection to suction pipe
Connection to injection line
Suction line
Stop valve
Condenser fan
The connection between the indoor unit and the outdoor component is made by way of the refrigerant lines.
5
REMKO ATY
Operation
The indoor unit is easily operated using the standard infrared remote control. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit using the remote control, it can also be manually operated.
Manual operation
The indoor unit can also be started manually. To do so, press the button on the right side of the unit to activate the automatic mode.
In manual operation, the following settings apply:
Automatic operation: Above 21°C = cooling operation, set temperature 24°C under 21°C = heater operation, set temperature 24°C Fan speed AUTO
Press the button on the infra-red remote control to interrupt manual operation.
Display on indoor unit
The display illuminates according to the settings. In operation, the display lights up, the selected mode and the nominal temperature are shown.
Display on indoor unit
Power
Unit turned on
Ion generator
switched on
Air circulation
mode set
SET
TURBO
C
Timer operation
Display
Display of
coded error
messages, room
and nominal temperature
Fan speed
Stage 1, 2 and 3 and
Auto (blinking)
Infrared remote control
The infrared remote control sends the programmed settings over a distance of up to 6 m to the receiver of the indoor unit. Data will only be received correctly if the remote control is pointed at the receiver and no objects obstruct the transmission path.
First insert the batteries supplied on delivery (2 x type AAA) into the remote control. To do so, pull off the flap of the battery compartment and insert the batteries according to their polarization (see marks).
1 max. distance 6 m
max. 6 m
NOTE
Faults are indicated by codes (see chapter Troubleshooting and customer service).
NOTE
Replace discharged batteries immediately with a new set in order to avoid risk of leakage. It is recommended that the batteries are removed if the equipment is shut down for longer periods.
6
Buttons on the remote control
3. Heating mode In this mode,
the warm air in the room is warmed to the desired temperature.
4
. Air circulation mode In this mode, the air in the room is recirculated.
"MIN."button
This button increases the
minute value for time and timer programming.
Buttons on the remote control
"ON/OFF" Button
Press this button to start the unit.
"  "button
This button is used to set
the desired temperature between 18°C and 30°C.
"MODE"button
Use this button to select the operating mode. The indoor unit has 5 modes:
1. Automatic mode In this mode, the unit works in cooling or in heating mode.
2. Cooling mode In this mode the cold air in the room is cooled to the desired temperature.
5
. Dehumidification mode In this mode the room is mainly dehumidified and the adjusted temperature is maintained.
"FAN" button
Press this button to set the
desired fan speed. 4 speeds are available: Automatic, high, medium and low fan speed.
"(SLEEP)" button
After pressing this button,
the Sleep mode is activated and in cooling operation, the nominal temperature increases automatically by 1 °C within an hour, in heating operation, the nominal temperature is lowered by 1 °C within an hour. After the second hour, the temperature is increased/ lowered by 2°C. After 6 hours, the function is switched off.
"(SWING)"button
This button directly activates
the oscillating function of the fins for better air distribution in the room.
"TIMER ON"button
This button is used to
activate the automatic on and/ or off time of the unit and is programmed with buttons and at intervals of 10 minutes.
"HR"button
This button increases the
hour value for time and timer programming.
"CLOCK"button(recessed)
By pressing this button, the
time setting is activated.
"ION" button
By pressing this button, the ion
generator and turbo mode are activated.
"TIMER OFF" button This button serves to program
the automatic switch-off time for the unit within the next 24 hours.
"RESET" button
(recessed)
This button resets the remote
control to its factory default configuration.
7
REMKO ATY
Button functions
A symbol is shown on the display to indicate that the settings are being transferred.
ON/OFF Button
/Button
By pressing the ON / OFF button, you can activate or deactivate your unit. The programmed settings and adjustment values before the unit was turned off will appear on the display.
ON/OFF ON/OFF
The remote control has its own temperature display. If buttons / are pressed alternately, the display changes to . The button can be used to reduce the desired nominal temperature, the button can be used to increase it. This adjustment is only possible in coolingand heating mode. In automatic mode, the fixed temperature of 24°C is preset. The current setting is shown next to the temperature display.
In dehumidification mode, no temperature adjustment can be made.
MODE Button
Cooling / mode

heating
Use the MODE button to select between the individual operating modes. 5 modes are available:
1. Automatic automatic selection of cooling or heating operation
2. Cooling predominantly summer operating mode
3. Dehumidification Summer or winter operating mode
4. Heating predominantly winter operating mode
5. Air circulation only for circulation of air
Automatic Cooling
MODE
Dehumidifying
MODE MODE MODE MODE
Heating
Air circulation
8
AUTOMATIC MODE
In automatic mode, the controller autonomously selects between heating and cooling operation when the unit is first turned on. A nominal temperature of 24 °C is preset.
Cooling MODE
MODE
AUTOMATIC
In cooling mode, the air in the room is cooled down to the set nominal temperature. The desired room temperature is set with the /buttons in 1 °C increments. If the room temperature is 1 °C above the selected nominal temperature, the indoor unit starts to cool the air in the room. The inverter controller checks the difference between the adjusted nominal temperature and the actual room temperature. If there is a large difference, the cooling output is very high. If the difference is smaller, a lower cooling output is produced. This serves to maintain the air discharge temperature and the room temperature. If the adjusted room temperature is lower than approx. 2 °C, then the control system turns the cooling function off. To protect the compressor, the controller only turns the cooling on again after a waiting period of 3 minutes.
MODE
COOLING OPERATION
Functional diagram
Nominal temperature
Nominal temperature -2°C
Compressor operation AT
Fan operation AT
Fan operation IT
Actual temperature
> 6 Min.
> 6 Min.> 3 Min.
30 sec. 30 sec.
Start cooling mode
Cooling mode
Stop cooling mode
Operation
Stop
9
REMKO ATY
Heating MODE
In the heating mode, you can heat the room in spring or fall. The desired room temperature is set with buttons / in 1 °C increments. If the room temperature is 1 °C below the selected nominal temperature, then the indoor unit starts to warm up the air in the room. If the adjusted room temperature is exceeded by approx. 0.5°C, then the controller turns the heater function off. To protect the compressor, the controller will not switch the heating on again until it has waited for 3 minutes.
MODE MODE
HEATING OPERATION
Functional diagram
Nominal temperature +5
Nominal temperature +2
Compressor operation AT
Fan operation AT
Fan operation IT
Reverse flow valve
Actual temperature
°C
°C
> 6 Min.
> 6 Min.> 3 Min.
30 sec. 30 sec.
30 sec. 30 sec.
Stop heating operation
Heating mode
Start heating mode
Operation
Stop
Air circulation MODE
During the defrosting cycle, the indoor unit vaporiser fan and the outdoor unit condenser fan are switched off. After the cycle is concluded, the fans are switched to their previous settings.
Reverse flow valve
Compressor operation AT
Fan operation AT
Fan operation IT
Defrost period
30 sec.
< 7 Min.
15 sec.
30 sec.
60 sec.
30 sec.
3 Min.
Operation
Stop
In the air circulation mode, the air in the room is only circulated. The room temperature cannot be changed in this mode. The cooling or heating operation is not activated. The fan has four speeds. Neither the ion generator nor turbo mode can be selected in this mode.
MODE
AIR CIRCULATION
10
Dehumidification MODE
In dehumidification mode, the room temperature cannot be set. Due to the low temperature of the refrigerant, the dew point of the air at the condenser is undercut. The excess moisture in the air is condensed on the condenser, the room is dehumidified. The fan has four speeds. Neither the ion generator nor turbo mode can be selected in this mode.
FAN Button
MODE
DEHUMIFICATION MODE
Functional diagram
Nominal temperature
Nominal temperature -2°C
Compressor operation AT
Fan operation AT
Fan operation IT
Actual temperature
Low fan speed
Start Dehumidifying mode
Dehumidifying mode
Stop Dehumidifying mode
30 sec.
Operation
Stop
The fan speed can be adjusted with this button. A selection can be made between low, medium, high and automatic fan speed.
FANFANFAN FAN
CLOCK Button (recessed)
NOTE
The speed change is achieved with a phase control. When switching between individual speeds, virtually no audible difference is noticeable.
The time can be programmed by pressing the CLOCK button. The time blinks in the display and the current time can be set using the HR. and MIN. button. Programming is completed by pressing the CLOCK button, the display will stop blinking.
CLOCK
HR./MIN.
CLOCK
11
REMKO ATY
SWING Button (covered)
SLEEP Button
The oscillating function of the air discharge fins can be adjusted with this butto. This makes it possible to switch directly between a fixed position and the oscillating function. The air distribution in the room is improved using the swing function.
This button activates a programming function, which causes the nominal temperature in cooling mode to increase after one hour by 1°C and after two hours by 2 °C. In heating mode, the nominal temperature is decreased after one hour by 1°C and after 2 hours by 2°C . In this function, the fan is in automatic mode.
SLEEP
TIMER Button
Functional diagram
1st
hour
2nd
Nominal temperature +2
Nominal temperature +1°C
unit operation
Nominal temperature -1
Nominal temperature -2
°C
°C
°C
hour
1st hour 2nd hour 6th hour
6th
hour
Opera
Stop
tion
The turn on and turn off time can be programmed with this button. By pressing the TIMER button several times, the turn on, the turn off and the combined turn on and off timer is activated. The turn on or turn off time blinks. The timer display on the indoor unit illuminates. The desired turn on or turn off time is set by pressing the buttons HR. and MIN. After completed adjustment, the timer symbol will continue to blink for approximately 15 seconds. When the programmed time has been reached, the unit automatically switches on or off. If the unit is automatically switched on, the mode, temperature and fan speed for the last setting are activated. The prior deletion of the on and off time is made by pressing the corresponding timer button. The timer display on the indoor unit goes out.
12
PROGRAMMINGTIMER ON
The controller turns the unit on after programming. During operation, all settings can be seen on the display. Out of operation, only the timer settings are visible.
PROGRAMMING TIMER OFF
PROGRAMMING TIMER ON/OFF
Timer on
HR/MIN
30 sec.
The controller turns the unit off after programming. During operation, all settings can be seen on the display. Out of operation, only the timer settings are visible.
Timer off HR/MIN 30 sec.
The controller turns the unit on or off after programming. In operation, all settings are visible on the display. Out of operation, only the timer settings are visible.
Unit On Unit Off
Example:
The controller turns on at 10:20. The unit is in operation until 05:00.
13
REMKO ATY
INDOOR UNIT DISPLAY
SET
TURBO
C
By pressing the "ION" button several times, the "ION" function, the "Turbo" function, or both can be set at the same time.
Ion function
The unit is equipped with an ion generator to generate negative ions. A high concentration of negative ions is found for example in mountains, near waterfalls and in forests and people perceive this inhaled air as "clean". Only a slight ion concentration is found in interior rooms. In this case, the ion generator can enhance the ions to the oxygen molecules of the surrounding air and can increase the feeling of well-being. In addition, atmospheric particles and dust particles in the air are bound, naturally cleaning the air. Any dust can settle on smooth surfaced due to the ionization and can be removed manually. Weekly cleaning of the housing and the filter should be observed when using the ionization feature. The function is available in all operating modes.
Turbo function
With this button, the air volume flow in cooling and heating operation is increased for 30 minutes. This makes it possible to cool off or warm up a room quicker. The ventilation and dehumidification mode cannot be obtained, the system changes to automatic mode.
After 30 minutes, the controller returns to the last programmed settings.
SET
TURBO
C
14
Shutdown
Care and maintenance
Temporary Shutdown
1. Allow the indoor unit to run for 2 to 3 hours in air circulation mode or in cooling mode at the maximum temperature setting in order to remove any residual moisture from the unit.
2. Shut down the unit using the remote control.
3. Switch off the voltage supply to the unit.
4. Check the unit for visible signs of damage and clean as described in the chapter "Care and maintenance".
Permanent Shutdown
Ensure that equipment and components are disposed of in accordance with local regulations, e.g. using certified firms and recycling specialists or at collection points.
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms near you.
Regular care and maintenance serves to ensure trouble-free operation and long service life of the unit.
CAUTION
Prior to performing any work, ensure the equipment is disconnected from the voltage supply and secured to prevent accidental switch-on!
Care
Ensure the indoor unit and outdoor component are protected against dirt, mould and other deposits.
Clean the equipment using a damp cloth. Do not use any caustic, abrasive or solvent­based cleaning products. Do not use a jet of water.
Before an extended shut down period, clean the fins on the outdoor unit and cover the outdoor unit with plastic to avoid infiltration of dirt into the unit.
Maintenance
We recommend concluding a maintenance contract with annual service from an appropriate specialty company.
NOTE
This ensures the operational reliability of your system!
NOTE
Statutory regulations require an annual leak test for the refrigerant circuit in relation to the refrigerant filling capacity. Inspection and documentation is to be carried out by specialty technicians.
Cleaning the housing of the indoor unit
1. Disconnect the supply voltage to the equipment.
2. Clean the unit with a soft damp cloth.
3.
Switch the supply voltage back on.
CAUTION
Care and maintenance work may only be carried out if the unit is disconnected.
Air filter for indoor unit
Clean the air filter at intervals of no more than 2 weeks. Reduce this interval in case of heavily soiled air.
Cleaning the filter on the indoor unit
The indoor unit is equipped with a filter with antibacterial coating. The filter cleans the air of dust and thereby reduces the distribution of bacteria.
15
REMKO ATY
1. Switch the indoor unit via the remote control to air circulation (the front cover of the air inlet must be open!) (Figure 2).
Type of task
Checks/Maintenance/Inspections
2. Open the lower display cover on the front side of the unit by pressing both latches and carefully fold the cover downward and remove it from the bracket (figure 3).
3. Push the clips on the filter up and pull it out on the clips (figure 4).
4. Clean the filter with a standard vacuum cleaner. Turn the dirty side upward (figure 5).
5. Carefully clean off any dirt in lukewarm water and with mild cleaner. Turn the dirty side downwards (figure 6).
6. If water is used, let the filter dry out air before replacing it in the unit.
General
Measure voltage and current
Check function of compressor
Check fan function
Contamination of evaporator fins
Check refrigerant fill quantity
Check condensation drain
Test insulation
Check moving parts
Sealing test for refrigerant circuit
1) see note S.15
2 Open front cover
Commissioning
Monthly
Six-monthly
Yearly
Cleaning the condensation pump (accessories)
An optional integrated or separate condensation pump may be included with the indoor unit, which pumps out any accumulated condensation into higher positioned drains. Observe the care and maintenance instructions given in the separate operating instruction manual.
1)
7. Carefully insert the filter. Make sure it is seated correctly.
8. Close the display cover as described above but in reverse order.
9. Set the desired operating mode.
4 Pull out the filter
5 Cleaning using a vacuum cleaner 3 Remove the display cover
6
Cleaning with lukewarm water
16
Troubleshooting and customer service
The equipment and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the list below. Please inform your dealer if the unit is still not working correctly after all the functional checks have been performed!
Fault
Fault Possible cause Checks Remedial measures
The unit does not start or switches itself off continually.
The unit does not respond to the remote control
Power failure, low voltage, main fuse defective / main switch turned off.
Power line damaged.
Waiting time after turn on too short.
Operating temperature fallen below / exceeded.
Power surge due to thunderstorm.
Problem of external condensation pump.
Transmission distance too large / receiving problem.
Remote control is defective.
Receiver and transmitter are exposed to too much sun exposure.
Electromagnetic fields disrupt the transmission.
Button of remote control stuck / dual button control.
Are all other electrical installations functioning correctly?
Are all other electrical installations functioning correctly?
Have approx. 5 minutes elapsed since the restart?
Are the fans in the indoor unit and outdoor component working correctly?
Have there been lightning strikes in the area recently?
Did the pump shut down due to a fault?
Does the indoor unit beep when pressing a button?
Is the unit running in manual mode?
Does it function correctly in the shade?
Does it function after removing potential fault sources?
Does the "Send” symbol appear on the display?
Check voltage if necessary wait until turned on again.
Repair by a certified service centre.
Schedule longer waiting periods.
Observe temperature ranges of indoor unit and outdoor unit.
Switch off the mains breaker and switch it back on. Inspection by certified service centre.
Check or clean the pump, if necessary.
Reduce the distance to less than 6 m and change location.
Replace remote control.
Shade the transmitter and receiver.
Signal is not transmitted when interference sources are operational.
Release the button / press only one button.
The unit is running with reduced or without cooling output.
Condensation discharge on unit.
Batteries of remote control are discharged.
Filter is dirty / air inlet / outlet opening is blocked by debris.
Windows and doors open. Heating/cooling loads increased.
No cooling operation is set.
Fins of the outdoor unit are blocked by foreign matter.
Leaks in refrigerant circuit.
Drain pipe of collector reservoir plugged / damaged.
External condensation pump or floater defective.
Non-discharged condensation is in the condensation line.
Condensation cannot be discharged.
Have new batteries been inserted? Is the display incomplete?
Have the filters been cleaned? Clean filters.
Have there been any constructional / application­related changes?
Is the cooling symbol activated in the display?
Is the fan on the outdoor component running outdoor component. Are the evaporator fins clear?
Is frost formation visible on connections of the outdoor unit?
Is unrestricted condensation discharge ensured?
Is the collection tray full of water and the pump not running?
Has the condensation pipe been laid on a slope and is not blocked?
Are the condensation lines unblocked and laid on a slope? Are the condensation pump and float switch functioning correctly?
Insert new batteries.
Close windows and doors / install additional systems.
Correct the settings for the unit .
Check fan or winter regulation, reduce air resistance.
Repair by certified service centre.
Cleaning of drain pipe and collector reservoir.
Have pump replaced by certified service centre.
Route the condensation line downward or clean it.
The condensation line must have a fall. If necessary, clean the pipe. A faulty condensation pump and float switch should be replaced.
17
REMKO ATY
Problem display by blinker code
LED in AT
No.
No.
Display
16
red
yellow
ER01 flashes - - -
ER02 flashes - - -
ER03 flashes - - -
ER04 flashes - - -
ER05 flashes - - -
ER06 flashes - - -
ER07 flashes - - -
ER08 flashes
ER09 flashes
ER10 flashes
ER11 flashes
ER12 flashes
ER13 flashes
ER14 flashes
ER15 flashes
ER16 flashes
ER18 flashes
ER19 flashes
ER20 flashes
O
O
O O
O O
O O
×
×
O ×
× O
× O O
× × ×
× ×
17
No.
Fault description Checks Remedial measures
18
green
Air circulation sensor on indoor unit is defective / triggered Indoor unit power supply defective
Frost protection sensor on indoor unit faulty/tripped
Vaporiser fan motor speed too low / defective
EEPROM indoor unit control board error
Communication error between IT and AT
Refrigerant fill quantity incorrect
AT condenser sensor faulty / tripped
Communication error between IT and AT
Compressor speed too low
Over-current error
PFC error
Inverter-control board communication error
Inverter board safety shut-off
Indoor unit outdoor air sensor defective
Compressor temperature too high
EEPROM Outdoor unit control board error
Compressor start error
Outdoor unit system error
Check resistance (see p. 19) Replace defective sensor
Check power supply Repair power supply
Check resistance (see p. 19) Replace defective sensor
Check fan motor, fan blade Replace motor or blade
Check refrigerant pressure.
Check resistance (see p. 19) Replace defective sensor
Check wiring and connections
Check cable connections, pipe connections, shut-off valves, compressor
Check voltage, cable connections, refrigerant pressure, ambient conditions
Check cable connections, pipe connections, shut-off valves, compressor
Check cable connections, pipe connections, shut-off valves, compressor
Check cable connections, pipe connections, shut-off valves, compressor
Check resistance (see p. 19) Replace defective sensor
Check condenser for dirt, check refrigerant pressure Check fan
Check cable connections, pipe connections, shut-off valves, compressor
HL
OT
OP
OD
OH
× ×
O ×
× × O
× O
× O ×
O × ×
Incorrect setting type for unit Contact specialist firm
Power supply fault
Ambient temperature too high
Liquid temperature too high
Hot gas temperature too high
Inverter board overheat
• = Off O = On × = flashes
18
Check voltage, cable connections, refrigerant pressure, ambient conditions
Switch unit off, switch unit back on when ambient temperature is lower
Check condenser for dirt, check refrigerant pressure Check fan
Check condenser for dirt, check refrigerant pressure Check fan
Controller, safety controller and resistance
Hot gas sensor, IPM AT sensor
Temp.
0 160.73 kΩ
5 125.57 kΩ
10 98.78 kΩ
15 78.23 kΩ
20 62.35 kΩ
25 50.00 kΩ
30 40.33 kΩ
Resistance
AT condenser sensor, AT ambient temperature sensor IT vaporiser sensor, IT circulation sensor
Temp.
0 27.42 kΩ
5 22.15kΩ
10 18.00 kΩ
15 14.72 kΩ
20 12.10 kΩ
25 10.00 kΩ
30 8.31 kΩ
Resistance
AT compressor
Temp.
Resistance
20 0.71 Ω
Measuring
point
U-V V-W U-W
Compressor control by via gas temperature Compressor control via vaporiser temperature
Hot gas tempera-
ture
< 87°C
93°C - 97°C no change to frequency
97°C - 110°C
> 110°C
Normal operating condition
decrease in frequency 1Hz/3sec.
Controller
control via IT
Switch off compressor
IT surface tempera-
ture
> 6°C
< 6°C no change to frequency
< 4°C decrease in frequency 1Hz/3sec.
< 1°C Switch off compressor
Cooling regulation
Normal operating condition
control via IT
Compressor control via ambient temperature
Ambient temperature
> 53°C Frequency 32Hz
47°C - 53°C Frequency 50 Hz
39°C - 47°C Frequency 70Hz.
15°C - 39°C
< 15°C Frequency 32Hz
Cooling mode regulation
Normal operating condition
control via IT
Compressor control via ambient temperature
Ambient temperature
> 23°C Frequency 32Hz
19°C - 23°C Frequency 50 Hz
12°C - 19°C Frequency 70Hz.
< 12°C
<-25°C or >+70°C Switch off compressor
Heating mode regulation
Normal operating condition
control via IT
Compressor control via vaporiser temperature
IT surface tempera-
ture
< 51°C
51°C - 55°C no change to frequency
55°C - 65°C decrease in frequency 1Hz/3sec.
> 65°C Switch off compressor
Heating regulation
Normal operating condition
control via IT
Compressor control via power consumption
Power consumption
> 6.1 A no change to frequency
6.2 - 6.7A decrease in frequency 1Hz/3sec.
6,7-7,5 Switch off compressor
Cooling / heating regulation
19
REMKO ATY
Installation instructions for qualified personnel
Important notes prior to installation
NOTE
The assembly and installation of the units and components may only be carried out by especially trained technicians.
Transport the unit in its original packaging as close as possible to the installation location. You avoid transport damages by doing so.
Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contractual partner and the shipping company.
Lift the unit at the corners and not by the refrigerant or condensation connections.
The refrigerant pipes (injection and suction line), valves and connections must be insulated against vapour diffusion. If necessary, also insulate the condensation pipe.
Select an installation location which allows air to freely flow through the inlet and outlet. (See section "Minimum clearances").
devices with intensive thermal radiation. Installation near sources of thermal radiation reduces the output of the unit.
Only open the shut-off valves of the refrigerant lines after the installation is complete.
Before connecting the injection line, remove the valve core in the indoor unit connection ports.
Seal off open refrigerant lines with suitable caps or adhesive strips to avoid infiltration of moisture and never kink or compress the refrigerant lines.
Avoid unnecessary bends. In doing so, you minimise loss of pressure in the refrigerant lines and ensure clear return flow of the compressor oil.
Take special precautions with regard to the oil return if the exterior component is located above the indoor unit. (See section "Oil return flow measures").
If the basic length of the refrigerant line exceeds 5 metres, add refrigerant. The quantity of additional refrigerant is provided in the chapter "Add refrigerant".
Only use the union nuts for the refrigerant pipes included in the delivery, and remove them only shortly before connecting the refrigerant lines.
Make electrical connections in accordance with the effective DIN and VDE standards.
Always fasten electric cables properly to the electrical terminals. Otherwise a fire could result.
Do not install the unit in the immediate vicinity of
20
Wall openings
Selection of the installation location
Wind
A wall opening of at least
70 mm diameter and 10 mm slope from the inside to the outside must be made for each indoor unit.
We recommend that the inside
of the opening is padded or lined, e.g. using a PVC pipe, to prevent the lines being damaged.
After installation, the wall
opening should be closed off with a suitable sealant. Do not use materials containing cement or lime!
Lines in the wall throughput
Control line
The indoor unit is designed for horizontal wall installation in the upper wall area (at least 1.75 m from the upper edge - floor). However, it can also be used in the upperwall area above doors.
The outdoor component is designed for horizontal installation on a base in outdoor areas. It should be placed on level, flat and firm surface. The unit should also be secured to prevent toppling. The outdoor unit can be set up outside as well as inside a building. For external installation, please observe the following notes to protect the unit from weather conditions.
Rain
If the unit is being installed in windy areas, ensure that the warm outlet air discharges in the main wind direction. If this is not the case it may be necessary to install a windbreak (provided by the customer). Ensure that the windbreak does not adversely affect the air intake to the unit.
Windbreak
Wind
PVC tube
Suction line
Condensation line
Injection line
Installation material
The indoor unit is attached with 4 screws on the building side, through the back wall of the unit.
The outdoor unit is attached with 4 screws via a wall bracket on the wall or a floor bracket on the ground.
NOTE
Install the outdoor unit with appropriate anchors, depending on the type of wall.
The unit should be at least 10 cm off the ground when mounted on the roof or ground. A pedestal is available as an accessory.
Sun
The evaporator fins (condenser) of the outdoor unit are the heat discharge components in cooling operation. Exposure to direct sunlight further increases the temperature of the fins and so reduces the heat released by the finned heat exchanger. The outdoor component should be installed on to the north side of the building whenever possible. If necessary, take measures to provide sufficient shade (responsibility of customer). This could be a small roof. However, the discharging warm air flow may not be affected by the measures.
Snow
The unit should be wall-mounted in areas of heavy snowfall.
Installation should then be at least 20 cm above the expected level of snow to prevent snow from entering the outdoor component. An optional wall bracket is available as an accessory.
Minimum clearance to snow
Snow
20 cm
21
REMKO ATY
Installation inside buildings
Ensure that heat can dissipate adequately when placing the outdoor component in cellars, attics, adjoining rooms or halls (figure 7).
Install an additional fan with a rated flow comparative to that of the outdoor component being installed in the room. This is used in conjunction with ventilation ducts to compensate any pressure losses (figure 7)
NOTE
Ensure a continuous and unobstructed air flow from outside, preferably using sufficiently large air intakes placed opposite each other (figure 7).
7 Installation inside buildings
Warm air
Additional fan
Light well
Warm air
Comply with any regulations and conditions affecting the structure of the building. If necessary, fit acoustic installation.
Outdoor component
Cold Fresh air
Light
well
In heating mode, condensation formation may occur due to cold surfaces.
Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air distribution.
Minimum clearances
1000
300
1000
1000
1000
Air intake
D
A
E
C
Air discharge
B
22
ATY 261 DC AT ATY 351 DC AT
A 100 mm 100 mm
B 700 mm 700 mm
C 400 mm 400 mm
D 100 mm 100 mm
E 300 mm 300 mm
Installation
Oil return measures
If the outdoor unit is installed at a higher level than the indoor unit, we recommend that suitable oil return measures are taken. Usually an oil pump bend is installed for every 2.5 metres of height difference.
Oil return measures
Outdoor component
Oil pump bend
in suction pipe to outdoor component 1 x every 2.5 metres
of rise in the line
max. 5 m
NOTE
Installation may only be performed by authorised specialists.
Unit installation
When attaching the indoor unit, pay attention to the lower, upper and side area air discharge.
1. Use the dimensions of the unit to mark the fixing points on structural parts approved to support the static load.
2. Open the display cover(figure 8) and remove the two screws from underneath the filter (figure 9).
8
Open display cover
9
Remove screws
Radius: 50 mm
Outdoor component
Connection variations of indoor unit
Connection variations
1
2
1 Outlet on the wall, right 2 Outlet through the wall, right 3 Outlet through the wall, left 4 Outlet on the wall, left
View from the rear
3. Remove the front of the unit by lifting the front in the lower area from the body approx. 10 cm and folding it upward (figure 10).
4. Pull the plugs of the front cover from the circuit board (figure 11).
5. Remove the housing's break out opening if necessary.
6. nstall the unit on the wall. Ensure undistorted installation.
7. Connect the refrigerant
4
3
lines, electrical cables and condensation line to the indoor unit as described below.
8. Check that the unit is level.
9. Re-assemble the unit.
10
R
elease unit front
11
Remove the plug
Installation of the indoor unit
The wall bracket for the unit must be attached with suitable screws and anchors.
23
REMKO ATY
Connecting the refrigerant lines
The on-site connection of the refrigerant lines is undertaken inside the unit.
It may be necessary to fit a reducer or flared adapter to the indoor unit. These fittings are included with the indoor unit as an accessory kit. Once installed, the connections should be sealed to prevent vapour diffusion.
CAUTION
The units are factory filled with dry nitrogen to check for leaks. The pressurised nitrogen is released when the union nuts are loosened.
The following instructions describe the installation of the refrigerant circuit and the assembly of the indoor unit and the outdoor component.
1.
Check the "Technical Data"
chart for the required pipe diameters and connect the refrigerant line.
2. To bend the copper tubing, use the appropriate bending tool to prevent kinks in the tubing.
3. Observe the permitted bending radius for the refrigerant pipes during installation. Never bend a pipe twice in the same place. Brittleness and cracking can result.
4. Lay the refrigerant lines from the indoor unit to the outdoor component. Ensure that the fastenings are adequate and if necessary, take appropriate oil return measures!
5. Use the wall or floor brackets to fit the outdoor component against structural parts approved to support the static load (refer to the installation instructions for the brackets).
6. Ensure that structure-borne sound is not transferred to parts of the building. Use vibration dampers to reduce the effects of structure-borne sound!
7. Remove the factory-fitted protective caps and the union nuts from the blocking valve connections and use them for further installation.
8. Before flanging the refrigerant lines, ensure that the union nut is on the pipe.
9. Prepare the refrigerant lines as shown below (figure 12+13, page 23).
10.
Check if the flange has the
correct shape (figure 14, page 23).
11 Before connecting the injection
line, remove the valve core in the indoor unit connection ports.
12.
First connect and hand-tighten the refrigerant connections to ensure they are correctly seated.
13.
Now fully tighten the fittings using 2 suitably sized open­ended spanners. Use one spanner to counter the force when tightening the fitting (figure 15, page 23).
14.
Apply appropriate heat insulation to both installed refrigerant lines, including connector.
15.
Only use insulating hoses suitable and diffusion-safe or the temperature range.
NOTE
Use only tools which are approved for use in an HVAC environment. Pipe cutter, deburrer, bending pliers and flanging tool.
Supplementary information for Installation
When combining the outdoor component with some indoor units, the connection of the refrigerant pipes may differ. In that case, install the provided reducer or expansion fittings to the indoor unit.
If the basic length of the refrigerant line exceeds 5 m, add refrigerant when commissioning the system for the first time. (See chapter "Add refrigerant").
24
Monitoring for leaks
12 Deburring the refrigerant line
Refrigerant line
Deburrer
13 Flanging the refrigerant line
Flanging tool
14 Correct flange shape
Once all the connections have been established, the pressure gauge station is attached as follows to the Schrader valve (if fitted):
red = small valve = injection pressure
blue = large valve = suction pressure
After completed connection, the leakage test is carried out with dry nitrogen.
CAUTION
Before the leakage test, the pipe connections must be checked.
The tightness test involves spraying a leak detection spray onto the connections. If bubbles are visible, the connections have not been properly made. Tighten the connection or prepare a new flange.
The time required to generate the vacuum is dependent on the pipework volume of the indoor unit and the length of the refrigerant lines. The process will always take at least 60 minutes. Once any foreign gases and moisture have been completely extracted from the system, the valves on the pressure gauge station will be closed and the valves on the outdoor component will be opened as described in the chapter on "Commissioning".
15 Tighten fittings
Tighten 1st Spanner
Counter 2nd Spanner
Tightening torque:
12 - 16 Nm
28 - 32 Nm
40 - 44 Nm
64 - 68 Nm
After successful leakage test, the excess pressure in the refrigerant lines is removed and a vacuum pump with the absolute final partial pressure of min. 0.01 mbar is used to remove all the air and empty the lines. Any moisture present in the pipes will also be removed.
NOTE
A vacuum of min. 0.05 mbar must be created!
25
REMKO ATY
Condensate drain
Due to the dew point shortfall on the vaporiser, condensation is created on the indoor unit during the cooling operation and on the outdoor unit during the heating operation.
Below the vaporiser is a collection tray, which must be connected to a drain.
The condensation line is to be installed with a minimum slope of 2 %. (figure 11). If necessary, fit vapour diffusion tight insulation.
Lead the condensation line freely to the run-off line. If the condensation runs directly into a sewer pipe, fit a trap to prevent any unpleasant odours.
When operating the unit at outdoor temperatures below 0°C, ensure the condensation pipe is laid to protect it against frost. If necessary, fit supplementary pipe heating.
After completed installation, check for unobstructed condensation run off and ensure that a permanent seal is provided.
The condensation hose is designed to be installed on the right and the left side (view from front). Remove the plug at the corresponding connection.
Indoor unit condensation connection
50
65
40
45
Condensate drain right or left
Electrical connection
Mains cable must be installed as voltage supply to the indoor unit and a control cable to the outdoor component, with appropriate safeguards.
We recommend installing a main / repair switch on the building near to the indoor unit.
Power is supplied to the indoor unit, the outdoor unit is supplied via a control line from the indoor unit.
The terminal blocks for making the connections are located behind the cover on the outdoor component.
If an optionally available condensation pump is used on the unit, then an additional relay for the shut-off contact of the pump will be needed to increase the switching power to shut off the compressor.
Control cables should be screened if laid in areas exposed to strong magnetic fields.
16
Slope of the condensation line
26
at least 2% fall
Condensation connection - outdoor component
Opening for Condensate drain
Condensation tray for the outdoor unit.
NOTE
A condensation pump cannot be installed within the units.
Electrical protection is provided in accordance with the technical data.
CAUTION
All electrical installation work is to be performed by specialty companies. Disconnect the voltage supply when connecting the electrical terminals.
Connecting the indoor unit Figure 17
Connecting the outdoor component
Proceed as follows to connect the cable:
1. Remove the cover from the unit.
2. Remove the side panel next to the terminals.
Terminal bar / control bar
Mains cable
Before connecting the refrigerant piping, the valve core must be removed from the injection line.
3. Feed the cables through the ferrite core supplied in the delivery (figure 17+18).
4. Feed the cable through the edge protection ring of the fixed connection plate.
5. Connect the cable as shown on the electrical connection diagram.
6. Anchor the cable in the strain relief and re-assemble the unit.
Check all plugged and clamped terminals to verify they are seated correctly and make a permanent contact. Tighten as required.
Figure 18
Connecting the indoor unit
Make the connection as follows:
1. Remove the front of the unit, as described in chapter "Unit installation" .
2. Select the cable cross-section according to the relevant standards.
Electrical connection diagram
ATY 261 DC / ATY 351 DC
Outdoor
component
Exterior conductor
A
B
Neutral conductor
C
Control conductor
D
PE
Earth conductor
the indoor unit
Exterior conductor
L
1N
Earth conductor
PE
1
2
3
4
PE
Mains cable
L1
N
PE
230 V~, 50 Hz, L1 / N / PE
3. Connect the unit to the mains cable and control cable on the outdoor component. (See electrical connection diagram).
4. Re-assemble the unit.
27
U
V
W
U
V
W
REMKO ATY
Electrical circuit diagram
ATY 261 DC AT / ATY 351 DC AT
Check the refrigerant lines and insulation for damage.
L in
W
U
Compressor
W VV U
A = Reverse flow valve B = Condenser fan
IPM
Sensor
IPM inverter power drive
N out P out
A
B
J1
P N
ATY 261 DC IT / ATY 351 DC IT
Swing motors
Lift motors
L N
N L C
J4
N out P out P
N
Vaporiser fan
J2
J1
N-Out
L-Out
Control board
E
COMM AC N In AC L In
Condenser
Ion generator
LDC
Pe
D
S
C
N
B
L
A
Terminal strip
Outdoor
component
Condenser
Test
Air-intake sensor
Condenser sensor
Hot gas sensor
AC N
AC L
4 3 2 1
Terminal strip
the indoor
unit
Check the electrical connection between the indoor unit and the outdoor unit for correct polarity.
Check that all fastenings, mountings etc. are firm and at the correct level.
Add refrigerant
CAUTION
Wear protective clothing when handling refrigerant.
Display
Air circulation sensor
Antifreeze sensor
Before commissioning
After successful leakage test, the vacuum pump must be connected using the pressure gauge station to the valve connections of the outdoor unit (see chapter "Leakage test") to create a vacuum.
Perform the following checks prior to commissioning the unit for the first time and after
Display
Pe
Mains cable
N
230/1Ph/50Hz
L
Button
manual operation
any interventions affecting the refrigerant circuit. Record the results in the commissioning report:
Check all refrigerant lines and valves with leak detection spray or soapy water for leaks and for inadvertent mix up of suction and injection line. Perform this check when the unit is not running.
The equipment contains a basic quantity of refrigerant. Furthermore, for refrigerant line lengths of more than 5 metres per circuit, an additional amount of refrigerant must be added,
Control line
in accordance with the following chart:
ATY 261 DC ATY 351 DC
Basic line length
Additional fill quantity
Up to and incl.
0 g/m
5 m 5 m to max. 15 m
20 g/m
NOTE
Ensure that the refrigerant in use is always replenished in liquid form!
28
Commissioning
NOTE
Commissioning is only to be performed and documented by specially trained personnel.
Once all the components have been connected and tested, the system can be commissioned . A functional check should be performed to verify its correct function and identify any unusual operational behaviour prior to handing it over to the operator.
Function test and test run
Check the following points:
Leak tightness of refrigerant lines.
Compressor and fan running smoothly.
Function test of Cooling operating mode
1. Remove the caps from the valves.
2. Begin the commissioning process by briefly opening the shut-off valves of the external unit until the manometer displays a pressure of approx. 2 bar.
3. Use leak detection spray or suitable devices to check that all the connections are tight.
4. If no leaks are found, open the stop valves by turning them anti-clockwise as far as they will turn using a hexagon spanner. If leaks are found, draw off the refrigerant and rework the defective connection. It is imperative that the vacuum creation and drying steps are repeated!
5. Switch on the mains switch or circuit breaker.
9. Check the correct function of the condensation line by pouring distilled water into the condensation tray. A bottle with a spout is recommended for pouring the water into the condensation tray.
10.
Switch the indoor unit to cooling mode.
NOTE
Due to the turn on delay, the compressor will start up a few minutes later.
11.
Check the correct function and settings of all control and safety devices during the test run.
12.
Check the control system in the indoor unit using the functions described in the operating manual. (Timer, temperature settings and all mode settings).
In cooling mode, cold air output by the indoor unit, and warm air output by the outdoor component.
Functional test of the indoor unit and all program sequences.
Check of the surface temperature of the suction pipe and determination of vaporiser overheating. To measure the temperature, hold the thermometer to the suction pipe and subtract the boiling point temperature reading on the pressure gauge from the measured temperature.
Documentation of the measured temperatures in the commissioning report.
6. Use the remote control to switch on the unit and select the cooling mode, maximum fan speed and lowest nominal temperature.
7. Measure and record all the required values in the commissioning report and check the safety functions.
8. Check the control system for the unit using the functions described in the chapter "Operation". Timer, temperature setting, fan speeds and switching to circulating or dehumidifying mode.
13.
Check the overheating, outdoor, indoor, outlet and vaporisation temperatures and record the measured values in the commissioning report.
14.
Remove the pressure gauge and fit the sealing caps.
NOTE
Then, check the blocking valves for leaks.
Final tasks
Reassemble all disassembled parts.
Familiarise the operator with the system.
29
REMKO ATY
Unit dimensions
ATY 261 DC AT / ATY 351 DC AT
623
265
ATY 261 DC IT / ATY 351 DC IT
148
720
567
245
532
All values in mm
470
567
47
45
396
25
All values in mm
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
30
495
Technical data
Series ATY 261 DC ATY 351 DC
Operational mode Inverter-wall room air conditioner combination for cooling and heating
Nominal cooling output
Nominal heating output
Energy efficiency class, cooling EER
Energy efficiency class, heating COP
Energy efficiency ratio EER
Coefficient of performance COP
Power consumption, annual, (500h) K / H kWh 365 495
Operating range (room volume), approx. 80 110
Refrigerant R 410A
Operating pressure, max. per cooling circuit kPa 3800/1200 3800/1200
Power supply V/Hz 230/1~/50 230/1~/50
Nom. electrical power consumption, cooling
Nom. electrical power consumption, heating
Elec. nominal power consumption cooling
Elec. nominal power consumption heating
Elec. starting current, max. A 20 25
Refrigerant connection - injection line
Coolant connection - suction line
Data specific to indoor unit
Operating range °C/ %r.F +16 to +32 / 80% +16 to +32 / 80%
Adjustment range - Cooling °C +18 to +30 +18 to +30
Adjustment range - Heating °C +16 to +28 +16 to +28
Air flow volume per speed setting m³/h 360/390/420 380/410/440
Protection class IP X0 X0
Sound pressure level per speed setting
Dimensions - height mm 567 567
Width mm 567 567
Depth mm 148 148
Weight kg 12,0 12,0
Corresponding outdoor component
Operating range - cooling °C +15 to +45 +15 to +45
Operating range - heating °C -7 to +24 -7 to +24
Air volume flow, max. K/H m³/h 1340 1890
Protection class IP X4 X4
Sound pressure level, max.
Refrigerant, basic quantity
Refrigerant, additional quantity > 5 m g/m 20 20
Refrigerant line, max. length m 15 15
Refrigerant line, max. height m 5 5
Dimensions - height mm 532 532
Width mm 720 720
Depth mm 245 245
Weight kg 37,0 38,0
Serial number 937... 938... EDP no. 1624261 1624351
1) Air inlet temperature TK 27°C / FK 19°C, outdoor temperature TK 35°C, FK 24°C, max. air flow volume, 5m line length, according to DIN EN14511
2) Air inlet temperature TK 20°C, outdoor temperature TK 7°C / FK 6°C, max. air flow volume, 5m line length, according to DIN EN14511
3) Distance 1 m free field
4) Contains greenhouse gas according to Kyoto protocol
1)
2)
1)
2)
1)
2)
kW 2,69 (1,00-2,93) 3,52 (1,2-3,87)
kW 2,93 (1,00-3,20) 3,87 (1,20-4,10)
A A
A B
3,68 3,56
3,64 3,49
4)
1)
kW 0,75 0,99
2)
kW 0,81 1,11
1)
A 3,48 4,62
2)
A 4,00 5,21
Inches (mm)
Inches (mm)
1/4 (6,35) 1/4 (6,35)
3/8 (9,52) 1/2 (12,7)
R 410A
4)
ATY 261 DC IT ATY 351 DC IT
3)
dB(A) 33/36/40 35/37/41
ATY 261 DC AT ATY 351 DC AT
3)
4)
dB(A) 45 49
kg 410 A / 0.63 410 A / 0.83
31
REMKO ATY
Exploded view ATY 261 DC IT / ATY 351 DC IT
3
17
15
1
5
7
14
6
7
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
13
5
14
8
7
4
11
10
2
12
Spare parts list
No. Designation ATY 261 DC IT ATY 351 DC IT
1 Cover - air inlet 1107400 1107400
2 Cover - display 1107401 1107401
3 Air filter 1107402 1107402
4 Display board 1107470 1107470
5 Lift motor, set 1107404 1107404
6 Swing motor 1107405 1107405
7 Air outlet fins, set 1107406 1107406
8 Condensation tray 1107439 1107439
9 Fin vaporiser 1107409 1107486
10 Fan wheel, vaporiser 1107410 1107410
11 Fan motor, vaporiser 1107471 1107471
12 Control board 1107472 1107473
13 Ion generator 1107415 1107415
14 Housing angle, set (right & left) 1107416 1107416
15 Mounting clip - cover, set 1107417 1107417
16 Antifreeze sensor / air circulation sensor 1107418 1107418
17 IR remote control 1107474 1107474
16
9
When ordering spare parts, please state the computerised part no., unit number and type (see identification plate) !
32
Exploded view ATY 261 DC AT / ATY 351 DC AT
14
1
9
4
15
16
6
13
10
11
12
5
8 7
3
14
14
2
We reserve the right to modify
the dimensions and constructional design as part of the ongoing technical development process.
Spare parts list
No. Designation ATY 261 DC AT ATY 351 DC AT
1 Front panel 1107421 1107421
2 Fan blade, condenser 1107422 1107422
3 Fan motor, condenser 1107449 1107424
4 Ribbed condenser 1107444 1107426
5 Side panel, right 1107475 1107475
6 Compressor, cpl. 1107476 1107477
7 Stop valve, suction line 1107434 1107435
8 Stop valve, injection line 1107436 1107436
9 Side section, left 1107438 1107438
10 Reverse flow valve 1107437 1107437
11 Reverse flow valve coil 1107478 1107478
12 Control board 1107479 1107480
13 IPM inverter power drive 1107481 1107482
14 Hot gas, condenser, air-intake sensor set 1107483 1107483
15 Compressor sensor 1107484 1107484
When ordering spare parts, please state the computerised part no., unit number and type (see identification plate) !
33
REMKO ATY
34
Notes
35
REMKO ACROSS EUROPE
… and also right in your neighbourhood! Make use of our experience and advice
REMKO GmbH & Co. KG
Air conditioning and heating technology
Im Seelenkamp 12 · 32791 Lage
PO Box 1827 · 32777 Lage
Telephone +49 5232 606-0
Telefax +49 52 32 6 06-260
E-mail info@remko.de
Website www.remko.de
Hotline
Air conditioning and heating technology
+49 5232 606-0
Export
+49 5232 606-130
Consultation
Thanks to intensive training,
our consultants are always
completely up-to-date in terms
of technical knowledge. This has
given us the reputation of being
more than just an excellent,
reliable supplier:
REMKO, a partner helping you
find solutions to your problems.
Distribution
REMKO offers not just a well
established sales network both
nationally and internationally,
but also has exceptionally highly
qualified sales specialists.
REMKO field staff are more than
just sales representatives: they
must primarily act as advisers
in air conditioning and heating
technology for our customers.
SFlbCustomer service
Our equipment operates
precisely and reliably. However,
in the event of a fault, REMKO
customer service is quickly at
the scene. Our comprehensive
network of experienced dealers
always guarantees quick and
reliable service.
Subject to technical modifications, no liability assumed!
Loading...