This technical information contains useful and important information
for proper dimensioning of a cascade system with wall-mounted
boilers. It describes the correct use of the complete Remeha cascade
systems with the modulating wall-mounted boilers Quinta Pro
30/45/65/90/115.
Please contact us if you have any questions or for further
information about cascade configurations.
230413 - 124823-01
4
2. General description of cascade systemsCascade systems Quinta Pro
2General description of cascade systems
2.1The optimum number of boilers in a cascade
In many situations it is advantageous to spread the total required heat
output over several boilers. This can be made possible by means of
a "cascade system". In a cascade configuration, heating boilers are
connected hydraulically. If the heat demand increases or decreases,
boilers are switched on or off respectively. If using a Remeha multiple
boiler controller or a quality building management system. It is then
important to determine the ideal number of boilers for the cascade.
The following factors need to be taken into account when deciding on
the number of boilers:
4 Investment:
When boilers are split up, the investment costs (boiler cost
including installation, fittings, pipe work, pumps and control
equipment) can work out lower or higher. However, this depends
to a large extent on the situation.
4 Reliability:
Reliability increases with the number of boilers. Research has
shown that reliability is already optimum for systems with four
boilers in a cascade.
4 Efficiency:
There is no appreciable difference in terms of efficiency between
several small or one or two larger boilers.
4 Maintenance and faults:
There is a greater overall risk of faults in a system with several
boilers. A larger group of engineers can service and maintain
smaller boilers.
4 Configuration:
The lightweight and compact design means that you have more
flexibility when siting the boilers. Very little floor space is required
and there is minimum load on the floor.
4 Adjustment:
When using several boilers and modulating control, the heat
output offered is virtually equal to the heat output requested.
A number of the points mentioned are dependent on the
situation and so consideration as to which solution is the
best will need to be given on a project-by-project basis.
The cascade kits are not supplied with the boilers they must
be ordered separately.
5
230413 - 124823-01
Cascade systems Quinta Pro
2.2Compact cascade configurations
The boilers Quinta Pro 30/45/65/90/115 are particularly suitable for
use in a cascade configuration. Their width of only 50 cm means that
a high heat output level can be installed on a small wall. This big
difference becomes apparent when comparing a Remeha cascade
system with cascade systems using boilers from other manufacturers.
2.3Cascade systems
For installing 2 to 6 boilers, our product range includes systems that
are very comprehensive and easy to install. The hydraulic and gas
system can be put together entirely without welding, using screw
connections, compression connections and flanges. The individual
components of the cascade systems are available for independent
cascade installation.
2. General description of cascade systems
For example, using 6 times a Quinta Pro 115, only approx.
3.8 m (including low loss header) wall width is required for
642 (80/60℃) kW. The boilers therefore allow an
exceptionally compact cascade configuration.
2.4Hydraulic isolation: low loss header
Practical experience has shown that it is beneficial to create hydraulic
isolation between the boiler circuit and the system circuit using a low
loss header. This means that a widely varying volume flow on the
system side hardly influences the volume flow on the boiler side at
all. This also applies in reverse: a widely varying volume flow on the
boiler side hardly influences the volume flow on the system side at
all. Controlling several different groups hydraulically is therefore
significantly easier as they do not, or barely, influence each other.
This creates better overall operating conditions for the system.
2.5Output control
Use the iSense Pro for up to 6 boilers or the iSense in combination
with the Celcia MC4 for a maximum of 4 boilers.
230413 - 124823-01
6
3. Remeha cascade systemsCascade systems Quinta Pro
3Remeha cascade systems
3.1General
In order to make it as simple as possible to create a cascade
configuration, our product range has included complete cascade
systems for years. The compact design of the boilers, combined with
the smart gas and water connection technology of the cascade
system, makes it possible to install a high heat output in a small
area. For example, using six Quinta Pro 115 boilers, only 3.8 m
approx. (including low loss header) wall width is required for 642 kW
(60/80℃). The cascade systems can be divided into 3 main groups:
4 2 to 6 boilers in a linear configuration, wall mounted.
4 2 to 6 boilers in a linear configuration, mounted on a free-standing
frame.
4 3 to 6 boilers in a back-to-back configuration, mounted on a free-
standing frame.
3.2Structure of cascade systems
The return, flow, and gas connections of the individual boilers are
connected using the fittings supplied by means of horizontal
connections to main pipes for return, flow and gas. These pipes are
welded onto a frame that rests on the floor and is fixed to the wall or
to a free-standing frame.
The low loss header supplied has flange connections, which can be
fitted to the left or right of the cascade main pipe as required. The
blind flanges supplied are then fitted on the other side. The gas main
pipe has a flange to which the optional gas filter can also be
connected on the left or right as required. When a gas filter is used,
a pressure loss of 3 mbar over the gas filter must be taken into
account.The minimum gas pressure after the gas filter is 20 mbar for
L gas and 17 mbar for H gas.
A common PVC condensed water discharge pipe (not supplied) can
be installed in the frame. For this purpose, holes have been made in
the frame into which this pipe can be fitted (to the left or right as
required) sloping downwards.
Please contact us for different configurations (specials).
We also provide in-depth advice on the choice of flue gas
discharge material and control engineering, including for
non-standard configurations.
Any combination of boilers is possible. See the table for the
corresponding heat outputs.
7
230413 - 124823-01
Cascade systems Quinta Pro3. Remeha cascade systems
Boiler typeUseful output [kW]
50/30 °C 80/60 °C
Quinta Pro 3031.429.3
Quinta Pro 4543.040.0
Quinta Pro 6565.061.0
Quinta Pro 9089.584.2
Quinta Pro 115114.0107.0
230413 - 124823-01
8
T003254-B
4. Cascade system components
4Cascade system components
4.1General
The cascade systems consist of the following components:
4 Main pipes.
4 Low loss header.
4 Boiler pump.
4 Boiler connection kits.
4 Free-standing frames.
4 Accessories.
4.2Main pipes
Cascade systems Quinta Pro
The main pipes consist of: main flow, return and gas pipe with wall
bracket for all boilers. The cascade systems consist of the following
components. By connecting main pipes, it is possible to extend the
system to a maximum of 6 boilers in a linear configuration or 2 x 3
boilers in a back-to-back configuration. In a linear configuration, the
rear connections must be capped off using the caps supplied. In a
back-to-back configuration with an odd number of boilers, the unused
connections must also be capped off.
Diameter flow and return pipe 65 mm:
4 Main pipes for 2 boilers with gas pipe DN 50
4 Main pipes for 3 boilers with gas pipe DN 50
4 Main pipes for 4 boilers with gas pipe DN 50
Diameter flow and return pipe 100 mm:
4 Main pipes for 2 boilers with gas pipe DN 65
4 Main pipes for 3 boilers with gas pipe DN 65
4 Main pipes for 4 boilers with gas pipe DN 65
9
230413 - 124823-01
T003256-B
Cascade systems Quinta Pro
4.3Low loss header
4.4Boiler pump
4. Cascade system components
The low loss headers have the following connecting flanges:
4 Low loss header for main pipes with diameter = 65 mm up to a
heat output of 460 kW. Boiler-side connection: DN 65 (PN6, DIN
2631; 4 holes). System-side connection: DN 100 (PN6, DIN 2631;
8 holes).
4 Low loss header for main pipes with diameter = 100 mm up to a
heat output of 642 kW Boiler-side connection: DN 100 (PN6, DIN
2631; 4 holes). System-side connection: DN 125 (PN6, DIN 2631;
8 holes).
The low loss header is supplied with a manual air vent as
standard.
4.5Boiler connection kits
The cascade sets are supplied complete with pump for each Quinta
Pro. Designed for a nominal flow rate based on a design condition of
20℃ on the boiler primary side of the header.
The boiler connection kits include the required glands.
The boiler connection kit consists of service shut-off valves in the flow,
return and gas pipes and also include the pipes between boiler and
main pipes. In a back-to-back configuration, the length of the pipes
that go to the rearmost row of boilers has been adjusted to the correct
length. It is assumed that, when an odd number of boilers are
supplied, the larger number of boilers is mounted on the front. The
service shut-off valve in the return includes safety valve, non-return
valve, filling and drain cock and expansion vessel connection. The
return valve has a T piece for additional connections (for example an
expansion vessel or calorifier).
230413 - 124823-01
10
T003258-C
35 x 1.5 mm
35 x 1.5 mm
11/4" bu11/4" bu 3/4" bu
28 x 1.5 mm
1
2
3
T003260-A
T003261-A
315mm
315mm
4. Cascade system components
Cascade systems Quinta Pro
4.5.1.Connection kit with pump
4.6Free-standing frames
Ù
Flow connection:
(1¼" female thread to boiler and 35 x 1,5 mm to main
pipe):
Ú
Return connection:
(1¼" female thread to boiler and 35 x 1,5 mm to main
pipe)
ß
Gas connection:
(¾" female thread to boiler and 28 x 1,5 mm to main pipe)
ç
1
Boiler pump
Ball valve, overflow, non-return valve, expansion vessel
connection (¾" male thread) and filling/drain cock in
return pipe
2
3
Ball valve in flow pipe
Gas cock
The free-standing frames consist of a combination of I and/or L poles
with an intermediate frame. 1 intermediate frame is required per
boiler. The L poles have bolt holes for fixing to the floor. The frame is
equipped with a fitting bracket. L poles are only required if boilers are
mounted at the rear of the frame (for a back-to-back configuration).
Only l poles are used with linear configurations. The top of the frame
can be used as a cableway. The nuts and bolts required are included
with the delivery, along with installation instructions. Fastenings for
fixing to the floor are not included.
4.7Accessories
4 Elbow kit for angled connection of the low loss header in 65 and
100 mm diameters.
4 Connecting flanges for system side of the low loss header.
Depending on the system resistance, it may be necessary
to switch to a larger pipe diameter after the connecting
flanges of the low loss header.
4 Modulating weather compensator iSense Pro.
4 Modulating controller Celcia MC4 (always with a iSense
controller).
4 Frame fixing plate for iSense Pro and Celcia MC4.
4 Insulation for low loss header, low loss header elbow, connection
kits and main pipes.
4 Gas filters DN 50 and DN 65.
11
230413 - 124823-01
Cascade systems Quinta Pro4. Cascade system components
4 Gas filter extension piece (for fitting gas filter next to low loss
header) DN 50 and DN 65 (To be used when gas filter is fitted on
the same side as the low loss header + elbows or low loss header
+ insulation).
4 Adjustable legs.
4.8Installation area and dimensions
Select the desired combination of boilers on the basis of the required
heat output. We recommend a clearance of 1 m (at least 60 cm) in
front of the units. The distance between the boilers is 3 cm. A wall
bracket is supplied for wall-mounted linear configuration. This must
be mounted at a height as specified in the installation manual supplied
with the cascade system. We recommend a clearance of at least 40
cm above the units. This distance also depends on any installation of
flue gas discharge and air supply collector pipes.
230413 - 124823-01
12
5. Installation drawings for cascade systemsCascade systems Quinta Pro
5Installation drawings for cascade
systems
5.1General
The cascade systems can be divided into 3 main groups:
4 2 to 6 boilers in a linear configuration, wall mounted.
4 2 to 6 boilers in a linear configuration, mounted on a free-standing
frame.
4 3 to 6 boilers in a back-to-back configuration, mounted on a free-
standing frame.
The boiler side of the cascade systems is sized to 20∆T.
The low loss header is based on 20 / 11∆T.
13
230413 - 124823-01
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.