The device complies with the standard type described in the EG
declaration of conformity. It was manufactured and commissioned in
accordance with European directives.
The original declaration of conformity is available from the
manufacturer.
In these instructions, various danger levels are employed to draw the
user’s attention to particular information. In so doing, we wish to
safeguard the user’s safety, obviate hazards and guarantee correct
operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical
injury.
WARNING
Risk of a dangerous situation causing slight physical
injury.
1.2Abbreviations
1.3General
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages in the
instructions.
4 Central heating: Central heating
4 PCU: Primary Control Unit - PCB for managing burner operation
4 PWM: Pulse Wide Modulation
4 SCU: Secondary Control Unit - Electronic printed circuit board for
extra connections
1.3.1.Manufacturer’s liability
Our products are manufactured in compliance with the requirements
of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
6
160414 - 123157-05
Quinta Pro 30 - 45 - 65 - 90 - 115
1. Introduction
In the interest of customers, we are continuously endeavouring to
make improvements in product quality. All the specifications stated in
this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following
cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
1.3.2.Installer’s liability
The installer is responsible for the installation and inital start up of the
appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.3.3.User’s liability
To guarantee optimum operation of the appliance, the user must
respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Call on qualified professionals to carry out installation and initial
start up.
4 Get your installer to explain your installation to you.
4 Have the required checks and services done by a qualified
professional.
4 Keep the instruction manuals in good condition close to the
appliance.
This appliance is not intended to be used by persons (including
children) whose physcial, sensory or mental capacity is impaired or
persons with no experience or knowledge, unless they have the
benefit, through the intermediary of a person responsible for their
safety, of supervision or prior instructions regarding use of the
appliance. Care should be taken to ensure that children do not play
with the appliance.
If the mains lead is damaged it must be replaced by the original
manufacturer, the manufacturer’s dealer or another suitably skilled
person to prevent hazardous situations.
160414 - 123157-05
7
1. Introduction
1.4Homologations
Quinta Pro 30 - 45 - 65 - 90 - 115
1.4.1.Certifications
CE identification no
NOx classification
Type of connection
(Flue gas outlet)
PIN 0063CL3333
5 (Standards EN)
B23, B
, B33, C13, C33, C43, C53, C63, C83, C
23P
93
1.4.2.Equipment categories
Gas category
II
2H3P
Gas typeConnection pressure (mbar)
G20 (Gas H)20
G31 (Propane) 37/50
1.4.3.Additional Directives
Apart from the legal provisions and Directives, the additional
Directives described in these instructions must also be observed.
For all provisions and Directives referred to in these instructions, it is
agreed that all addenda or subsequent provisions will apply at the
time of installation.
1.4.4.Factory test
Before leaving the factory, each boiler is set for optimum performance
and tested to check the following items:
4 Electrical safety
4 Adjustment (CO2)
4 Water tightness
4 Gas tightness
4 Parameter settings
8
160414 - 123157-05
Quinta Pro 30 - 45 - 65 - 90 - 1152. Safety instructions and recommendations
2Safety instructions and
recommendations
2.1Safety instructions
DANGER
If you smell gas:
1.Do not use a naked flame, do not smoke, do not
operate electrical contacts or switches ( doorbell,
light, motor, lift, etc..).
2.Shut off the gas supply.
3.Open the windows.
4.Report any leaks immediately.
5.Trace possible leaks and seal them immediately.
6.If the gas leak is before the gas meter, contact the
gas supplier.
2.2Recommendations
DANGER
If you smell flue gases:
1.Switch the appliance off.
2.Open the windows.
3.Report any leaks immediately.
4.Trace possible leaks and seal them immediately.
WARNING
4Installation and maintenance of the boiler must be
carried out by a qualified professional in compliance
with prevailing local and national regulations.
4When working on the boiler, always disconnect the
boiler from the mains and close the main gas inlet
valve.
4After maintenance or repair work, check all
installations to ensure that there are no leaks.
160414 - 123157-05
CAUTION
The boiler must be installed in a frost-free environment.
Keep this document close to the place where the boiler is
installed.
9
2. Safety instructions and recommendationsQuinta Pro 30 - 45 - 65 - 90 - 115
Casing components
Only remove the casing for maintenance and repair operations. Put
the casing back in place after maintenance and repair operations.
Instructions stickers
The instructions and warnings affixed to the appliance must never be
removed or covered and must remain legible during the entire lifespan
of the appliance. Immediately replace damaged or illegible
instructions and warning stickers.
Modifications
Modifications may only be made to the boiler after the written
permission of Remeha to do so.
10
160414 - 123157-05
T002036-B
8
7
4
55
6
2
3
9
11
10
12
13
1
Quinta Pro 30 - 45 - 65 - 90 - 115
3Technical description
3.1General description
High-efficiency wall-hung condensing gas boilers
4 High efficiency heating (Production of domestic hot water can be
ensured by a separate hot water calorifier).
4 Low pollutant emissions.
4 Very suitable for cascade systems with several boilers.
3.2Main parts
3. Technical description
1
2
3
4
5
6
7
8
9
10
11
12
13
3.3Operating principle
Flue gas discharge pipe / Air intake
Casing/air box
Heat exchanger (Central heating)
Outlet for measuring combustion gases
Ignition/ionization electrode
Mixer pipe
Combined venturi and gas valve unit
Air intake silencer
Instrument box
Siphon
Box for the control PCBs
Fan
Water flow pipe
160414 - 123157-05
3.3.1.Circulation pump
The boiler is supplied without a pump. When choosing a pump, take
account of the boiler resistance and system resistance.
If possible, install the pump directly under the boiler on the return
connection.
¼See chapter: "Connection of the heating circuit", page 20.
11
3. Technical description
Quinta Pro 30 - 45 - 65 - 90 - 115
CAUTION
The pump may have a maximum input of 200 W. Use an
auxiliary relay for a pump with a larger input.
3.3.2.System in cascade
The boiler is ideally suited for a cascade system. There are a number
of standard solutions available. For example:
4 Cascade sets (quick assembly) for the installation of 2 to 6 boilers
next to each other or 3 to 6 boilers mounted back to back on a freestanding frame. When the boilers are mounted next to each other,
they can be mounted either on the wall or on a free-standing frame.
4 Low loss headers for a cascade system of 2 or 3 boilers (Quinta
Pro 45 and/or Quinta Pro 65). The flow and return of each boiler
can be directly connected to these.
Please contact us for further information.
3.3.3.Calorifier connection
A calorifier can be connected to the boiler. Our product range includes
various calorifiers.
Please contact us for further information.
The calorifier can be connected to the boiler in two ways:
4 Using a 3-way diverting valve.
4 Using a calorifier pump.
3.3.4.Water flow rate
The boiler’s modulating control system limits the maximum difference
in temperature between the heating flow and return and the maximum
speed at which the flow temperature increases. For this reason the
boiler is, so to speak, insensitive to a flow which is too low.
In all cases, maintain a minimum water flow of 0.4 m3/h.
If DHW regulation is progressively activated with parameter p35,
The engineer must be Gas Safe registered and have the
correct ACS qualifications.
Codes of Practice - refer to the most recent version.
In GB the following Codes of Practice apply:
4 BS 6891: Gas installation.
4 BS 5546: Installation of hot water supplies for domestic purposes.
4 BS EN 12828: Heating systems in buildings.
4 BS EN 14336: Installation & commissioning of water based
heating systems.
4 BS 6798: Installation of gas fired hot water boilers.
4 BS 5440 Part 1: Flues.
4 BS 5440 Part 2: Ventilation.
4 BS 7074: Expansion vessels and ancillary equipment for sealed
water systems.
4 BS 7593: Treatment of water in domestic hot water central heating
systems.
4. Installation
4.2Package list
4.2.1.Standard delivery
The delivery includes:
4 The boiler, fitted with a connection cable
4 Connection cable for pump
4 Mounting rail and mounting accessories for wall mounting
4 Mounting template
4 Installation and Service Manual
These installation and maintenance instructions deal only with the
items included in a standard delivery. For installation and assembly
of any accessories supplied with the boiler, see the relevant
installation/assembly instructions.
160414 - 123157-05
15
T001982-A
4. InstallationQuinta Pro 30 - 45 - 65 - 90 - 115
4.2.2.Accessories
Description
Remeha qSense basic modulating control system
Remeha iSense extended modulating control system
Cascade controller
Outside temperature sensor
Flue kit
Combustion air/flue gas adapter 80/80 (Quinta Pro 30/45)
Combustion air/flue gas adapter 100/100 (Quinta Pro 65/90/115)
Calorifier tank
Kit for connection to the water heater
DHW sensor
Modulating pump
3 -speed pump
Flue gas thermostat
Cascade set (For fitting a Quinta Pro boiler in a Quinta cascade frame)
Cascade set
Duo and Trio low loss headers
Various control PCBs
Protective cover for the connections
Exchanger cleaning tool
Maintenance box
Recom communication kit
Propane conversion kit for Quinta Pro 90
4.3Choice of the location
4.3.1.Type plate
The data plate located on top of the boiler provides important
information on the appliance: serial number, model, gas category, etc.
16
160414 - 123157-05
T002599-B
500
min.1000
500
min.
400
350
min.
250
750
Quinta Pro 30 - 45 - 65 - 90 - 1154. Installation
4.3.2.Location of the boiler
4 Before mounting the boiler, decide on the ideal position for
mounting, bearing the Directives and the dimensions of the
appliance in mind.
4 When choosing the position for mounting the boiler, bear in mind
the authorised position of the combustion gas discharge outlets
and the air intake opening.
4 To ensure adequate accessibility to the appliance and facilitate
maintenance, leave enough space around the boiler.
WARNING
4Fix the appliance to a solid wall capable of bearing
the weight of the appliance when full of water and fully
equipped.
4It is forbidden to store inflammable products and
materials in the boiler room or close to the boiler,
even temporarily.
CAUTION
4The boiler must be installed in a frost-free
environment.
4An earthed electrical connection must be available
close to the boiler.
4A connection to the mains drainage system for the
discharge of condensate must be available close to
the boiler.
4.3.3.Ventilation
The installation must comply with BS 5540 (part 1 + 2), BS 6640 and
IGUP/10.
160414 - 123157-05
17
T002614-C
191
500
750
500
100
50
50
130
191
365
4. InstallationQuinta Pro 30 - 45 - 65 - 90 - 115
4.3.4.Main dimensions
i
h
â
z
Gas /
Gaz
Connection of the combustion gas exhaust pipe;
Ø 80 mm (≤ 45 kW) / Ø 100 mm (≥ 65 kW)
Connection of the air intake pipe;
Ø 125 mm (≤ 45 kW) / Ø 150 mm (≥ 65 kW)
Siphon connection bush
Heating circuit return; 1 ¼" Male thread
Gas connection; ¾" Male thread
18
{
Heating circuit flow; 1 ¼" Male thread
160414 - 123157-05
T001540-B
2
1
5
4
3
Quinta Pro 30 - 45 - 65 - 90 - 1154. Installation
4.4Positioning the boiler
The boiler is delivered with a mounting template.
A suspension clamp situated at the rear of the casing enables the
boiler to be directly suspended on the mounting bracket.
1. Position the mounting template to the wall with adhesive tape.
CAUTION
4Using a spirit level, check that the mounting axis is
perfectly horizontal.
4During mounting, cover up the connection points for
the air supply and the combustion gas exhaust, to
protect the boiler and its connections from dust. Only
remove this protection at the time when these
connections are made.
2. Drill 2 holes with a Ø of 10 mm.
3. Insert the rawplugs with a Ø of 10 mm.
4. Attach the mounting bracket to the wall with the provided bolts with
a Ø of 10 mm.
5. Hang the boiler on the mounting bracket.
160414 - 123157-05
19
T002856-C
4. InstallationQuinta Pro 30 - 45 - 65 - 90 - 115
4.5Hydraulic connections
4.5.1.Flushing the system
The installation must be cleaned and flushed according to BS 7593
(2006).
Installing the boiler in new installations (installations less than
6 months old)
4 Clean the installation with a universal cleaner to eliminate debris
from the system (copper, hemp, flux).
4 Thoroughly flush the installation until the water runs clear and
shows no impurities.
Installing the boiler in existing installations
4 Remove sludge from the installation.
4 Flush the installation.
4 Clean the installation with a universal cleaner to eliminate debris
from the system (copper, hemp, flux).
4 Thoroughly flush the installation until the water runs clear and
shows no impurities.
Suitable chemicals and their use should be discussed with
specialist water treatment companies in respect to
aluminium heat exchangers.
4.5.2.Connection of the heating circuit
1. Remove the anti-dust plug located on the heating outlet
connection { under the boiler.
2. Connect the heating water outlet pipe to the heating flow
connection.
3. Install a filling and drainage valve on the installation for filling and
draining the boiler.
20
160414 - 123157-05
T002857-C
T002858-B
Quinta Pro 30 - 45 - 65 - 90 - 1154. Installation
4. Remove the anti-dust plug located on the heating return
connection z under the boiler.
5. Connect the heating water return pipe to the heating return
connection.
6. Fit the pump in the return pipe (if possible).
For the electrical connection of the pump, see chapter:
¼
"Connecting the pump", page 28
To facilitate maintenance work, we recommend mounting
a shut off valve on the heating flow and return pipes.
CAUTION
4The heating pipe must be mounted in accordance
with prevailing provisions.
4If installing shut off valves, position the filling/
drainage valve, the expansion vessel and the safety
valve between the shut off valves and the boiler.
4When installing open vented systems, the cold feed
and expansion tank heights must comply with the
requirements laid down in the Health and Safety
Executive publication PM5. The Quinta Pro boilers
require a minimum static head of 3 (Quinta Pro
30/45/65/90) or 5 (Quinta Pro 115) m.
4.5.3.Connecting the expansion vessel
Install the expansion vessel on the heating return pipe z.
4.5.4.Connecting the condensate discharge pipe
1.
Fit the condensate drain hose and the syphon of the boiler j:
these are supplied separately.
2. Mount a standard drainage pipe, Ø 32 mm or more, leading to the
mains drainage system.
3. Insert into this the hose of the condensate drain.
4. Mount a trap or a siphon in the discharge pipe.
CAUTION
Do not make a fixed connection owing to maintenance
work on the siphon.
4Do not plug the condensate discharge pipe.
4Set the discharge pipe at a gradient of at least 30 mm
per metre, maximum horizontal length 5 metres.
4Do not drain condensation water into a roof gutter at
any time.
4Connect the condensate discharge pipe in
accordance with prevailing standards.
160414 - 123157-05
21
T002859-C
4. InstallationQuinta Pro 30 - 45 - 65 - 90 - 115
4.6Gas connection
WARNING
4Close the main gas valve before starting work on the
gas pipes.
4Before mounting, check that the gas meter has
sufficient capacity. To do this, you should keep in
mind the consumption of all appliances.
4If the gas meter has a too low capacity, inform the
energy supply company.
1. Remove the anti-dust plug located on the gas connection GAS/GAZ under the boiler.
2. Connect the gas inlet pipe.
3. Mount a gas isolation valve on this pipe, directly under the boiler.
4. Connect the gas pipe to the gas shut off valve.
CAUTION
4Ensure that there is no dust in the gas pipe.
4We recommend installing a gas filter on the gas pipe
to prevent clogging of the gas valve unit.
4Connect the gas pipe in accordance with prevailing
standards and regulations.
4.7Connections for the air and exhaust pipes
The boiler is suitable for the following types of flue gas
connections.
¼See chapter: "Certifications", page 8.
4.7.1.Classification
The table specifies this classification in detail according to [.
Type
B23
B23P
B33Open
C13Room sealed
(1) Including the pressure classification P1
(2) EN483: 0,5 mbar suction by pressure reduction
(3) An under pressure of 4 mbar is possible
(4) See table for minimum sizes of duct or sleeving
ExecutionDescription
Open
(1)
4Without fire-stop approval.
4Exhaust of combustion gases above the roof.
4Air in the installation room.
4Without fire-stop approval.
4Common exhaust of combustion gases above the roof.
4Common exhaust of combustion gases mixed in the air, air in the installation room (special
4Vent in the outside wall.
4The opening for the air-supply inlet is located in the same pressure zone as the vent (For
construction).
example, a common passage through the outside wall).
22
160414 - 123157-05
Quinta Pro 30 - 45 - 65 - 90 - 1154. Installation
TypeExecutionDescription
C33Room sealed
(2)
C43
C53Room sealed
C63Room sealed
C83
C93
(1) Including the pressure classification P1
(2) EN483: 0,5 mbar suction by pressure reduction
(3) An under pressure of 4 mbar is possible
(4) See table for minimum sizes of duct or sleeving
Room sealed/
Cascade
(3)
Room sealed
(4)
Room sealed
4Exhaust of combustion gases above the roof.
4The opening for the air-supply inlet is located in the same pressure zone as the vent (For
example, a concentric passage to the roof).
4Common channelling for the air-supply and exhaust of combustion gases (CLV):
-Concentric.
-Eccentric; Air supply from the shaft.
4This also relates to the overpressure cascades.
4Closed equipment.
4Separate channelling for the air-supply.
4Separate channelling for the combustion gases.
4Terminating on different pressure surfaces.
4The manufacturer delivers this type of equipment without a supply or exhaust system.
4The equipment can be connected on a so-called semi-CLV system (with common
combustion gas exhaust).
4Channel for the air-supply and exhaust fumes in a duct or surrounded by a sleeve:
-Concentric.
-Eccentric; Air supply from the shaft.
-Exhaust of combustion gases above the roof.
-The opening for the air-supply inlet is located in the same pressure zone as the vent.
Type Execution DiameterMinimum size of the duct or jacket
Without air-supplyWith air-supply
∅ Channel Channel∅ Channel Channel
C93Rigid60 mm110 mm110 x 110 mm120 mm110 x 110 mm
80 mm130 mm130 x 130 mm140 mm130 x 130 mm
100 mm160 mm160 x 160 mm170 mm160 x 160 mm
Flexible60 mm110 mm110 x 110 mm120 mm110 x 110 mm
80 mm130 mm130 x 130 mm145 mm130 x 130 mm
100 mm160 mm160 x 160 mm170 mm160 x 160 mm
Concentric60/100 mm120 mm120 x 120 mm120 mm120 x 120 mm
80/125 mm145 mm145 x 145 mm145 mm145 x 145 mm
100/150 mm170 mm170 x 170 mm170 mm170 x 170 mm
4.7.2.Outlets
4.7.3.Lengths of the air/flue gas pipes
4
The boiler is also suitable for longer chimney lengths
with diameters other than those indicated in the
table. Please contact us for further information.
4To define the maximum final length, you must deduct
the pipe length in accordance with the reduction table.
160414 - 123157-05
23
T002998-A
T001882-B
L
4. InstallationQuinta Pro 30 - 45 - 65 - 90 - 115
Open flue (B23, B23P, B33)
n
"If using an open flue version, the air supply opening remains open;
only the combustion gas opening is connected". The boiler then takes
in the combustion air required directly from the premises in which it
is installed.
CAUTION
4The air supply opening must remain open.
4The premises in which the appliance is installed must
be fitted with the necessary air supply openings.
They must not be reduced or closed.
Chimney length for the open flue version
Maximum length (L)
Diameter
30456590115
80 mm 40 m 33 m 10 m 9 m8 m
90 mm 40 m 40 m 18 m 16 m 12 m
100 mm 40 m 40 m 27 m 24 m 19 m
110 mm 40 m 40 m 40 m 40 m 37 m
Quinta Pro
Room sealed flue (C13, C33, C43, C63, C93)
n
If using a room sealed version, both the combustion gas exhaust
opening and the air supply opening must be connected
(concentrically). Refer to the table to determine the maximum pipe
length of the flue gas pipes in room sealed operation.
Chimney length for room sealed operation
Maximum length (L)
Diameter
30456590115
80-125 mm 20 m 16 m---
100-150 mm 20 m 20 m 13 m 13 m 7 m
Quinta Pro
24
160414 - 123157-05
T000780-C
L
Quinta Pro 30 - 45 - 65 - 90 - 115
4. Installation
Connection in areas of different pressure (C53, C83)
n
Combustion air supply and combustion gas discharge are possible in
various pressure zones, semi-CLV systems. With the exception of
coastal areas. The maximum permissible difference in height
between the combustion air supply and the combustion gas discharge
is 36 m.
Chimney length in the various pressure zones
Maximum length (L)
Diameter
30456590115
80 mm 20 m20 m---
90 mm 36 m36 m2 m--
100 mm 36 m36 m8 m4 m-
110 mm 36 m36 m34 m32 m24 m
130 mm 36 m36 m36 m36 m36 m
Reduction table
n
Quinta Pro
Pipe reductions per element used
Diameter
80 -125 mm1 m2 m
100 -150 mm1 m2 m
80 mm1.2 m4.0 m
90 mm1.3 m4.5 m
100 mm1.4 m4.9 m
110 mm1.5 m5.4 m
130 mm1.6 m6.2 m
Elbow 45°Elbow 90°
Pipe reduction Pipe reduction
4.7.4.Additional Directives
4 Please refer to the manufacturer’s instructions for the material in
question when installing the flue gas discharge and air supply
materials. If the flue gas discharge and air supply materials are not
installed according to the instructions (e.g. they are not leakproof,
not clamped in place etc.), this may cause hazardous situations
and/or result in bodily injury. After assembly, check at least all flue
gas and air–carrying parts for tightness.
4 Connection of the combustion gas exhaust directly to the buildings
brick chimneys or flues is forbidden for condensation reasons.
4 Always clean the ducts thoroughly in cases where lining pipes are
used and/or a connection of the air-supply.
4 It must be possible to inspect the flue or chimney.
4 In cases where condensate coming from the stainless steel or
plastic sections of the flue gas pipe can be driven back towards
the aluminium section, this condensate must be removed using a
collecting device before the aluminium section is reached.
160414 - 123157-05
25
T001990-A
80/125 mm
100/150 mm
S
4. InstallationQuinta Pro 30 - 45 - 65 - 90 - 115
4 For long, aluminium, combustion-gas exhaust pipes it is initially
necessary to consider the relatively high quantity of corrosive
products which are brought together with the condensate from the
exhaust pipe. The siphon on the equipment requires regular
cleaning or, preferably, an additional condensate collector can be
installed above the equipment.
4 The combusted gas discharge pipe must be sufficiently inclined
towards the boiler (at least 50 mm per metre) and an adequate
condensate collection tank and discharge system constructed (at
least 1 m before the boiler opening). The elbows fitted must be at
more than 90° to guarantee the provision of an adequate gradient
and tightness on the lip rings.
Please contact us for further information.
4.7.5.Connection of the combustion gas exhaust
pipe
4.8Electrical connections
S
Insertion depth 25 mm
Mounting
Fit together the combustion gas exhaust pipes, without welding.
The pipes must allow no leakage of flue gases and be
4
resistant to corrosion.
4Connect the pipes together without stress between
the sections.
4The horizontal sections need to be constructed with a
gradient of 50 mm per metre: Back to the boiler.
4.8.1.Control unit
The boiler is not line- and neutral sensitive. The boiler is fully prewired. All external connections can be made on the connection
connector (low voltage). The main characteristics of the control unit
are described in the table below.
26
Power supply voltage
Rating of the main fuse F1 (230 VAC) 6.3 AT
Fuse rating F2 (230 VAC)2 AT
Fan230 VAC
230 VAC/50Hz
160414 - 123157-05
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.