Remeha P520-17 Technical Specifications

Boiler Type
P520 – 17
Issue Date :
June 2012
MODEL : P520
No of SECTIONS : 17
Rated Output kW :
928 - 986
Efficiency % : NCV Full load (³)
90
Weight (dry) kgs :
3756
Seasonal Efficiency : % GCV
84.3
Overall Dim WxHxD mm :
1172x1760x2445
Radiated Losses % :*
0.07
BURNER TYPE
Pressure Jet
Fuel Available :
Nat Gas
Oil - Kgs/hr
Dual Fuel
Fuel Consumption :
Check burner details
92.28 ##
Noise levels dB(A) :
Check burner details
Min Op Gas Press mbar :
Check burner details
HYDRAULICS
Water Content ltrs :
769
Min Return Temp °C
50
Resist @ 11°C t mbar :
Connection Size mm (weld) :
Resist @ 20°C t mbar :
7.6
Std Operating Temp °C :
80
Nom Flow Rate @ 11° C ∆t l/s :
21.41
Max Operating Temp °C :
90
Nom Flow Rate @ 20° C ∆t l/s :
11.78
High Limit Set Point °C :
110
Min Flow Rate l/s : #
5.21
Test Press bar:
As per Assembly Manual
FLUE
Diameter mm :
400
Flue Gas Flow kgs/hr Gas : (¹)
1440
Flue Type :
Conventional
Flue Gas Flow kgs/hr Oil : (¹)
1370
Chamber Resist. mbar :
+ 2.6
Flue Gas Temp °C : (¹)(²)
<190
Voltage :
230.1.50
Note: 1ph burners obtain their power supply via the boiler.
Fuse rating amps :
10Amp Circuit Breaker
3ph burners require a 3ph
supply + a 1ph to the boiler.
CONTROL OPERATION
Standard :
On / Off Thermostat
Temperature indication
L/O lamp
High limit Thermostat
Volt free run/lock indication
On/Off switch
High / Low
3 Position Switch Auto/Man/Test
10amp CB
Optional :
Hours Run Meters
Modulating(via burner)
TECHNICAL SPECIFICATION SHEET
Quick reference specification sheet full details can be found in the P520 series Installation/Service guide. General Details Corrosion resistant cast iron sectional boiler, jointed by conical nipples and ceramic rope, designed with three passes for high efficiency and low NOx emission. Large insulated door (hinged left or right) allowing easy access for cleaning. Powder coated enamel steel casing c/w glass fibre insulation. All of the P520 Boiler Range are supplied un-assembled for delivery to site. CE approved. Boiler Efficiency data to 92/42-EEC
Max Op Press bars :
25.10
As per Technical Manual
140
(¹) Boiler at full output average temperature 80/60°c (70°c mean)
Boiler temperature: 80 °C, Ambient temperature: 20 °C
(²)
(³) 70°c average temperature
* Maintenance consumption@ 30
# Based on ∆t of 45°c, ## @ 12 bar pump pressure Ours is a policy of continuous development, we therefore reserve the right to alter specifications without prior
notification. Remeha Commercial accept no liability for any loss or damage rising from any errors or omissions that may be inadvertently contained in this specification sheet.
0
delta t - refer to boiler installation/service manual
Loading...