The information contained in this document is subject to change without notice.
This document contains proprietary information which is protected by copyright. All rights are reserved. No part of this
document may be photocopied, reproduced, or translated to another language without prior written consent of ADIC.
ADIC shall not be liable for errors contained herein or for incidental or consequential damages (including lost profits) in
connection with the furnishing, performance or use of this material whether based on warranty, contract, or other legal
theory.
All trademarks within this document are the property of their respective owners.
All rights reserved. No part of this document may be copied or reproduced in any form or by any means, without prior
written permission of ADIC Europe, ZAC des Basses Auges, 1 rue Alfred de Vigny, 78112 Fourqueux, France.
ADIC Europe assumes no responsibility for any errors that may appear in this document, and retains the right to make
changes to these specifications and descriptions at any time, without notice.
This publication may describe designs for which patents are pending, or have been granted. By publishing this
information, ADIC Europe conveys no license under any patent or any other right.
ADIC Europe makes no representation or warranty with respect to the contents of this document and specifically
disclaims any implied warranties of merchantability or fitness for any particular purpose. Further, ADIC Europe reserves
the right to revise or change this publication without obligation on the part of ADIC Europe to notify any person or
organization of such revision of change.
Every effort has been made to acknowledge trademarks and their owners. Trademarked names are used solely for
identification or exemplary purposes: any omissions are unintentional.
ADIC is a registered trademark and ADIC Europe is a trademark of Advanced Digital Information Corporation.
ADIC USA
Tel.: +1 303-705-3900
Fax: +1-303-792-2465
ATAC: 1-800-827-3822
http://www.adic.com
ADIC Europe
ZAC des Basses Auges
1, rue Alfred de Vigny
78112 Fourqueux, France
Tel.: +33.1.3087.5300
ADIC Germany Beteiligungs GmbH, KG
Eschenstraße 3
D-89558
Böhmenkirch, Germany
Tel:+00.800.9999.3822
Fax: +33.1.3087.5301
Published: Nov 2003 Document Number: 62-2308-03 Rev A
ADIC • 11431 WILLOWS ROAD, NE • REDMOND, WASHINGTON, USA • 1-800-336-1233
•Appendix F: Warranty and EULA - Provides warranty and licensing information for the SNC 4000.
•Appendix G: Acronyms - Describes acronyms used in SNC4000 documentation.
SNC 4000 User’s Guide1
Associated Documents
The following documents are associated with this guide:
•Scalar 24 Installation and Operation Guide (62-2301-01 Rev. A)
•ADIC Management Console 3.2 User’s Guide (6-00064-01 Rev. B)
Explanation of Symbols and Notes
The following symbols and highlighted passages note important information:
SymbolDamage to ...Signal WordDefinitionConsequence
PersonWARNING:Imminent
hazardous electrical
situation
MaterialCAUTION:Potential damaging
situation
NOTE:Indicates important
information that
helps make better
use of the system
Death or serious injury
Possible damage to
the product, data, or
environment
No hazardous or
damaging
consequences
Environmental Notices and Statements
The following are the environmental notices and statements for the SNC 4000.
Product Recycling
This unit contains recyclable materials. These materials should be recycled where processing sites are
available and according to local regulations.
Lithium Battery
WARNING
RISK OF FIRE, EXPLOSION, OR BURNS. DO NOT SHORT
CIRCUIT, CRUSH, HEAT ABOVE 100
DISASSEMBLE THE BATTERY.
N
C, INCINERATE, OR
Laser Safety
This unit may contain a single-mode or multi-mode transceiver, both of which are Class 1 laser products.
The transceiver complies with IEC 825-1 and FDA 21 CFR 1040.10 and 1040.11. The transceiver must be
operated under the recommended operating conditions.
Usage Restrictions
The optical ports of the modules must be terminated with an optical connector or with a dust plug.
2SNC 4000 Introduction
Technical Assistance
If problems cannot be solved with the aid of this document or if training is desired, contact the ADIC
Technical Assistance Center (ATAC).
In the USA:800.827.3822
Outside the USA, toll free:00.800.9999.3822
Internet:www.adic.com
SNC 4000 User’s Guide3
4SNC 4000 Introduction
Description
This chapter describes the SNC (Storage Networking Controller) 4000.
Overview
The Scalar 24 enables customers to use and manage the library in a storage area network, via an integrated
SNC 4000. When configured as a storage networking library, the Scalar 24 delivers the following
functionality:
•The ability to create separate data paths between heterogeneous hosts library and components
(drives and/or media changer) using Scalar Firewall Manager (SFM). SFM allows the zoning of
resources so that hosts are restricted to seeing only storage they need. This endpoint security is
standard in ADIC storage networking libraries and is OS, HBA, and switch/hub independent.
Heterogeneous support also enables multiple hosts with varying OSs and backup applications to
access the same library.
•End-to-end path verification between the library and open system host interfaces that enables
administrators to discover and remedy path failures before the library is needed for backup
applications.
•Drive performance optimization to eliminate protocol bridging latencies and keep drives streaming
by pre-fetching data and overlapping commands via an ADIC patent-pending technique.
•Serverless backup via an integrated Data Mover Module.
One possible configuration of the of the SNC 4000 is illustrated in Figure 1
SNC 4000 User’s Guide5
.
Figure 1Configuration Overview
Configuration Support
The SNC provides one FC interface. The FC interface is configured with a small form factor pluggable
transceiver (SFP). In addition, the SNC has two Ultra2 SCSI interfaces.
Address Mapping
The SNC maps addresses across and between these different interfaces and preserves the persistency of
the address maps across power ups of systems, devices, and the SNC.
Interface Protocol Awareness
The SNC processes SCSI-3 and SCSI-2 protocols for disk, tape, and tape medium changer devices. It can
report the host and devices that are attached to its interfaces. The SNC has the capability to manage the
access security between end points on the FC interface and the SCSI channels.
FC Interface
Interfaces for host and device attachment include one, 1- and 2-Gb/s bi-directional Short Wave connection.
The SFP can interoperate with both 2 Gb/s and 1 Gb/s data links. The SFP is hot-swappable and is the only
component, except for the SNC module itself that is a field replaceable unit (FRU). Refer to Removing and
Replacing the SFP on page 27.
Cables should have a duplex LC connector on the SFP end and a connector appropriate to the HBA in use
on the host end.
The FC interface supports the following Public and Private Loop modes:
•Target
6Description
•Initiator
•Target and Initiator
The FC Interface also supports the following connection options:
•Loop
•Point-to-Point
•Loop Preferred
The FC interface controller is in compliance with the following standards and specifications:
•Fibre Channel Arbitrated Loop (FC-AL-2) working draft, rev 6.4, August 28, 1998
•Fibre Channel Fabric Loop Attachment (FC-FLA) working draft, rev 2.7, August 12, 1997
•Fibre Channel Private Loop SCSI Direct Attach (FC-PLDA) working draft, rev 2.1, September 22,
1997
The Scalar 24's SNC supports SCSI-3 commands over an Ultra2 bus. The SNC is Ultra160 hardware
compatible and will support Ultra160 bus speeds via a planned firmware upgrade. The SNC contains two
Low Voltage Differential/Single-Ended (LVD/SE) Ultra2 SCSI channels with internal termination. The SCSI
channels have automatic speed and width negotiation capability for wide or narrow bus widths and
Standard, Fast, Ultra or Ultra2 speeds. These parameters can be viewed from the ADIC Management
Console.
The SCSI interfaces are compliant with the following SCSI specifications:
The 10/100 Base-T Ethernet port has an RJ-45 connector for out-of-band management. It can be connected
to a network hub, switch, or router using an unshielded twisted-pair Ethernet cable. The Ethernet port
complies with the IEEE 802.3 specification.
Service Port
The service port is an RS-232 connection with a 9-pin D-shell connector. It connects to the host serial port
with a 9-pin to 9-pin straight through cable. It is compatible with serial ports on personal computers.
The service port is used for local service and diagnostics when you use a terminal session to access the
shell interface.
The service port is configured at:
•VT100 or ANSIW terminal emulation
•19,200 Baud
SNC 4000 User’s Guide7
•8 data bits
•No parity
•One stop-bit
•Hardware Flow Control or Xon/Xoff
LED Indicators
The interface panel of the SNC provides LEDs that indicate the status and activity of the SNC and its
interfaces.
Figure 2LEDs
When the SNC is first turned on, some of the LEDs will be on and others will flash while it is booting.
The following list briefly describes how to interpret the LED signals. See also POST Error Codes
143.
FC
•For the FC channel, the LED will be OFF when the channel is not connected. It will be ON when the
channel is connected to a live FC device. It will flash when there is activity on the channel.
S1 and S2
•For each SCSI channel, the LED will be OFF when no devices have been detected on the port. It
will be ON when a target has been found on the channel. The LED will return to the OFF state if the
channel is reset.
PWR
•The PWR (Power) LED will be ON when the SNC has power. It will flash if the on-board power
sensors determine that any of the required supply voltages are out of range.
RDY
•The RDY (Ready) LED indicates status of Ready. Normally the RDY LED flashes when the SNC
has finished booting. If the RDY LED remains ON or OFF for more than a few seconds, it means
there is a problem.
on page
•The RDY LED will flash rapidly, four times per second, when the SNC is running in diagnostic mode.
ERR
•The ERR (Error) LED indicates that an error condition exists. This may indicate such errors as overtemperature conditions, fan stalled or other internally detected error conditions. See POST Error
Codes on page 143.
8Description
Firmware 4.40 Features
This chapter describes the functionality of the Storage Networking Controller (SNC) Firmware 4.40. The
SNC interface between storage and host provides Fibre Channel to SCSI connectivity.
The SNC firmware enables you to map addresses across and between different interfaces, to configure
private maps for security purposes, to condition the data path, and to preserve the persistency of the
address maps when systems, devices, switches, and the SNC are turned on and off. The SNC supports up
to 2048 unique storage devices across multiple interfaces.
Features highlighted with this release are described below.
Multi-path Mapping
Multi-path mapping enables an administrator to map a single Fibre Channel-attached storage device
through all SCSI communication channels on the SNC to provide redundancy. Both manual and automatic
versions of the multi-path feature are available. The automatic version of this feature is used by specialized,
high-availability host software. Both versions require a license.
WWN Change Capability
The world wide name (WWN) change capability enables an administrator to change the WWN on the SNC.
Text is posted during the procedure regarding the requirement to maintain a globally unique name. A
password is required in order to complete the change. The world wide node name or just the world wide port
name can be changed. This feature is being implemented to facilitate SNC replacement.
DHCP
DHCP enables an administrator to configure network parameters such as IP addresses and lease durations
for a device from a common server. When DHCP is enabled, the SNC requests configuration data from the
DHCP server and configures the Ethernet interface based on the results. DHCP can be activated in
environments in which the SNC is attached to a private network and the AMC is not used for direct SNC
control. DNS is used by target devices to determine the IP addresses of named hosts and is active
whenever DHCP is enabled.
Supported Platforms
The SNC is a platform-independent product. You can connect a host to the SNC after you have installed
the appropriate host bus adapter and drivers. You can also connect host systems with different operating
systems to the SNC through the FC.
For a current list of supported platforms, configurations, and host bus adapters, see www.adic.com/
scalar24.
Supported Devices
The SNC supports connections to the Scalar 24 and supports all tape drives available for that unit.
Operating Specifications
This section contains the physical, electrical, and environmental specifications for the product.
SNC 4000 User’s Guide9
The SNC is integrated in the Scalar 24. The interface panel of the unit is visible from the back of the Scalar
24.
The external dimensions are:
•3” high
•7” deep
•6” wide
•weight: 2.19 lbs.
In order to provide a safety margin and permit adequate cooling, the unit is fitted with a 12 VDC tach-output
blower. Should temperatures exceed specifications, an environmental alarm violation is sent and logged,
permitting environmental causes of failure to be determined. This information can be viewed using the ADIC
Management Console.
Operating Environment
The operating environment is as follows:
•Operating Temperature: 5° C to 45° C (50° F to 113° F)
•Storage Temperature: -40° C to 70° C (-40° F to 158° F)
The SNC is powered by the Scalar 24. Maximum power consumption is 58 watts, in active mode. The power
supply status is monitored and is reported by the PWR LED and to the ADIC Management Console.
ADIC Management Console
The ADIC Management Console (AMC) offers remote, centralized management of Scalar storage
networking libraries. Features of the AMC include:
•Management and monitoring of multiple Scalar libraries at the same time
•Customizable graphical view of ADIC libraries
•Policy based event logging and email notification
•Device-level diagnostics, reporting, and configuration
All of these functions are embedded into a point and click interface designed to simplify management. The
AMC receives information from Scalar storage networking libraries using the industry standard SNMP
protocol. Because ADIC uses an industry standard protocol, information can be directed from ADIC libraries
to framework applications. These framework applications can use SNMP Traps to generate reports and
pager alerts as part of an enterprise management program. For more information, see the ADIC
Management Console User’s Guide.
10Description
Getting Started
This section describes how to install and set up the SNC 4000, SCSI devices, and the Host Bus Adapter.
Installation is divided into four sections:
•Unpacking and Inspecting
•Pre-installation
•Installation
•Post-installation
Unpacking and Inspecting
Unpack the SNC from the carton. Check to make sure that the following items are included with your SNC
and that none of them are damaged:
•One SFP
•Product documentation and software CD-ROM
•Two HD68/VHDCI SCSI cables
•One LVD terminator
NOTE: Save the CD-ROM in a safe location for future reference.
Pre-Installation
It is important that the items in the steps below are verified before installation of the SNC begins. This
ensures a successful installation of the product.
Required ToolsRequired SoftwareOther Resources
RS-232 straight through cableADIC Management Console
server/client software
RJ-45 patch cableSNC firmwareSystem with HyperTerminal
SC/LC fibre cablesServer to run ADIC
SNC 4000 User’s Guide11
IP information for the SNC
Management Console
1Install the ADIC Management Console server and client software. For installation instructions, see the
ADIC Management Console User’s Guide. It is recommended that you use this software to verify
connections and during the post-installation process.
2Check that you have the latest firmware for the SNC by going to www.adic.com/downloads/firmware.
3Verify that host OS and service pack are up to date and supported by the library.
4Verify that Host Bus Adapter (HBA) have been installed on SAN attached hosts and configured
properly. HBA BIOS and device drivers should be at the most current level.
5Install the Host Registration Service on hosts that will be connected to the library.
6Ensure that all necessary FC cables are present.
Note
7Label both ends of each SCSI cable with drive ID and SNC connector number.
8If you are using the ADIC Management Console to manage the SNC 4000, configure an Ethernet
environment. You will need to set the following network parameters:
Static IP address____________
Netmask _________
User-defined SNC name __________________
Default Gateway _____________________
CAUTION
Note
The Scalar 24 uses an LC high density connection. In environments where the
library will attach to SC interfaces (GBIC, 1x9, etc.) make sure that SC to LC
cables are available.
Use of incorrect network parameters can cause problems on the
Ethernet network.
The default network name is the unit’s serial number. If you choose a different
name, it becomes the prompt displayed on the service terminal. Choosing a
different name may be useful if you have more than one SNC 4000. To change
the name, use the hostNameSet command. For more information, see
hostNameSet
on page 89.
9Connect the Ethernet port on the SNC to the LAN. Library connectivity and monitoring parameters can
be managed from the ADIC Management Console.
Installation
Follow the instructions below to install the SNC with SCSI attached storage and FC attached hosts.
1Power down your Scalar 24 and disconnect the AC line cord from the AC source outlet.
2From the rear of the Scalar 24, locate the available SNC slot. Loosen the four thumbscrews on the cover
plate and remove the cover plate. Store the cover plate in a convenient place. It is required for proper
operation and cooling of the library if the SNC is ever removed.
12Getting Started
Figure 3Cover Plate Removal
3Slide the SNC into position until it mates with the connector then tighten the thumbscrews.
SNC 4000 User’s Guide13
Figure 4SNC Installation
4Connect one end of the RS-232 cable to the service port on the SNC and the other end to a service
terminal.
5Start a terminal emulation session using HyperTerminal and the following settings:
•VT100 or ANSW terminal emulation
•19,200 Baud
•8 data bits
•No parity
•One stop-bit
•Hardware Flow Control or Xon/Xoff
6Run the Ethernet cable from the network hub to the SNC.
7Connect the SCSI cables to the library. An example of typical cabling for two drives connected to each
of the SCSI channels on the SNC is shown below. Both drives must have the last device on the SCSI
bus terminated, as shown.
14Getting Started
Figure 5SCSI Cabling for Two Drives
8Turn on the Scalar 24.
Within one minute, the RDY LED on the SNC should start flashing once per second and the Done
executing startup script message should be displayed on the service terminal.
9Configure the network information by typing the following at the service terminal:
ethAddrSet "ip_address","subnet_mask"
where “ip_address” and “subnet_mask” are replaced with actual values, for example:
ethAddrSet “172.16.32.12”,“172.16.1.1
Then enter:
gateAddrSet "default_gateway_ip"
where “default_gateway_ip” is replaced with the default gateway IP address.
Then enter:
hostNameSet "name"
where “name” is replaced with the name you would like displayed in the ADIC Management Console.
10 Configure the date and time. You can either set the real time clock manually, or use a timeserver. Refer
to the procedures below to set the date and time.
”
Setting the Time and Date
Follow the procedure below to set the Real Time Clock (RTC). For more information on the commands used
in this procedure, see Commands Listed Alphabetically by Function
1Use the rtcDateSet command to manually set the Real Time Clock. The rtcDateSet command
2Use the dateSetFromRTC command to set the RTC as the source of date display:
SNC4000 > dateSetFromRTC
value = 0 = 0x0
3Use the tzSet command to set the time zone. EST is used in the example for Eastern Standard Time:
SNC4000> tzSet "EST"
TZ Set TIMEZONE = EST:EDT:300:040202:101502
value = 0 = 0x0
SNC 4000 User’s Guide15
4Use the date command to confirm.
SNC4000 > date
SNC4000 > FRI JAN 26 9:30:49 2001
CAUTION
Use 24 hour time when programming the real time clock. The time will
be one hour off while Daylight Savings time is in effect.
Adding a Host System Running Timeserver
Follow the procedure below to configure the date to be automatically set. For more information on the
commands used in this procedure, see Commands Listed Alphabetically by Function
1To enable the timeserver functionality use the setNettime command.
SNC4000 > setNettime 1
Nettime 1 value = 0 = 0x0
2Add a host running timeserver to the SNC using the setTimeHost command.
SNC4000 > setTimeHost "butter"
Time Host butter value = 0 = 0x0
3Set the remote system as the source of date/time display using the rdate command.
SNC4000 > rdate "butter"
Get time from butter using UDP/SNTP
value = 0 = 0x0
4Use the tzSet command to set the timezone. In the following example, EST is used for Eastern
Standard Time.
SNC4000 > tzSet "EST" TZ Set TIMEZONE = EST:EDT:300:040202:101502
value = 0 = 0x0
on page 63.
5To confirm, use the date command.
SNC4000 > date WED JUL 18 14:51:59 2001 value = 0 = 0x0
Synchronizing the Real Time Clock with the Timeserver
Follow this procedure to synchronize the real time clock with the timeserver. For more information on the
commands used in this procedure, see Commands Listed Alphabetically by Function
1Use the setTimeHost command to add a host running timeserver to the SNC.
SNC4000 > setTimeHost “butter”
Time Host butter value = 0 = 0x0
2Synchronize the Real Time Clock with the timeserver using the rtcSetCurrent command.
SNC4000 > rtcSetCurrent
value = 0 = 0x0
on page 63.
Disabling the Timeserver Host
Follow the step below to disable a timeserver host.
1To disable the timeserver functionality, use the setNettime command.
SNC4000 > setNettime 0
Nettime 0 value = 0 = 0x0
The time will revert to the time set on the Real Time Clock.
16Getting Started
Post Installation
Perform the procedures below to verify connections, set up the FC port, SNMP traps, and email alerts. You
will need to use the ADIC Management Console. For more information, see the ADIC Management Console User’s Guide.
1Using the ADIC Management Console, confirm that all attached devices are displayed under each
channel.
2Verify/set configuration for the FC Port. The speed and connectivity settings of the SNC default to auto
detect and in most configurations no additional configuration should be necessary. However, if the
install environment requires custom settings, the following should be confirmed:
Speed
Connection
Options
Loop ID:Soft / Hard and specific ID
Port ModeTarget or Target & Initiator
For more information about configuring FC and the implications of each setting see the ADIC Management
Console User's Guide.
CAUTION
3Configure all SNMP Traps. For more information, see the ADIC Management Console User’s Guide.
4Save your current configuration in case you need to restore it in the future. For more information, see
Configuration Files
5If you are not running the most current level of SNC firmware, update your firmware. For more
information, see Updating Firmware
1Gbps or 2Gbps
Point to Point (Fabric), Loop, or Loop
Preferred
Do not set Port Mode to Initiator for this library. Setting Mode to
Initiator will prevent hosts from seeing library drives and media
changer. Initiator mode makes the SNC appear as a host instead of a
storage device.
.
.
6Configure email alerts. For more information, see the ADIC Management Console User’s Guide.
Configuration Files
It is recommended that you save a copy of your configuration in case you need to restore it at a future date.
The ADIC Management Console is the simplest and most efficient tool for saving/loading configurations.
For more information, see the ADIC Management Console User’s Guide. You can also use the service
terminal as an alternate method to perform these operations. The procedures below explain how to save
and load configuration files using the service terminal.
Saving a Configuration File
Follow the procedure below to save your configuration.
1From the HyperTerminal window type sz “config.cfg” and press Enter.
“config.cfg” is an example of a name. You can specify a different filename but it must be in quotes, it must be eight characters or less, and it must end in .cfg.
SNC 4000 User’s Guide17
2From the HyperTerminal window, select Transfer and Receive File.
3From the Receive File dialog enter the path to the folder where you want to save the file or click the
Browse button and navigate to it.
4For the Receiving protocol select Zmodem and press the Receive button.
5Wait for the Configuration Download Complete status message to be displayed on the service
terminal indicating successful completion.
6If HyperTerminal reports an error, try to receive the file again.
Loading a Configuration File
Follow the steps below to load a saved configuration file.
1From the HyperTerminal window, at the SNC4000> command prompt, type rz and press Enter.
2From the HyperTerminal window select Transfer and Send File.
3From the Send File dialog enter the path and file name where the firmware file is located or click the
Browse button and navigate to it. In the Protocol field, select Zmodem and click the Send button.
4Wait for the Configuration Update Complete status message to be displayed on the service
terminal indicating successful completion.
5Reboot the SNC for the update to take effect.
6If HyperTerminal reports an error, try to send the file again.
Updating Firmware
You can upgrade the firmware on the SNC 4000 using the ADIC Management Console. For more
information, see the ADIC Management Console User’s Guide.
18Getting Started
Scalar Firewall Manager
Scalar Firewall Manager (SFM) is a software feature that collects all host and target information and
manages the end-to-end access control in the SAN. It allows the system administrator to control access
privileges between individual Host Bus Adapters (HBAs) and target devices connected to the SNC’s SCSI
and Fibre Channels. The system administrator uses the ADIC Management Console to administrate SFM.
•SFM technology enables Storage Area Networks with multiple users to share the same connectivity
channels or pipes to access the same or different storage elements or resources. Therefore,
multiple virtual private connections can be created on the same Storage Networking infrastructure.
•SFM is completely host independent and requires no software components on the host (an optional
automatic Host Registration Service that provides periodic host status information is included). It
has no interface dependencies and supports Fibre Channel, SCSI, or any other SAN interface. It is
also independent of the storage elements and requires no change in legacy or new storage devices.
•SFM keeps track of Fibre Channel HBAs by their unique World Wide Name (WWN). Because Fibre
Channel switches also have a WWN, SFM can see FC switches connected to the SNC and control
their access.
•SFM manages access for hosts connected through FC switches and hubs to the SNC. The SNC
supports up to 2048 LUNs across all of its interfaces. It has a virtual limit for how many hosts (HBAs
or Initiators) are connected to each port. The default setting allows 64 initiators per port.
Consequently, with the default setting, an SNC with its two Fibre Channel ports can support up to
128 host connections.
•SFM creates and maintains a database in non-volatile memory to hold persistent information about
each HBA (or Initiator) and its LUN access privileges.
•When you perform a Save Configuration from the ADIC Management Console, it saves both the
persistent device map and the SFM database to a file. This allows all configuration settings to be
loaded onto another SNC in the event that the SNC needs to be replaced.
•When SFM is enabled for the first time, it takes a “snapshot” of the existing configuration. SFM
automatically assigns access between HBAs and the storage elements that they currently have
access to so that an existing configuration will not be affected. Consequently, online hosts attached
to an SNC will continue to retain their current access permissions to storage elements.
•Any HBA (or Initiator) that is added to a SAN connection at a later time will only have access to the
SNC Command and Control LUN. In this case, the system administrator must explicitly set access
privileges to the desired storage element for each host connection
SNC 4000 User’s Guide19
.
Host Registration Service
The Host Registration Service (HRS) is a small service/daemon installed on hosts which access the library.
HRS simplifies security configuration and allows administrators to monitor host connections to the library.
To accomplish this, HRS sends a periodic data pulse through the host’s Fibre channel HBA to the library.
The pulse consists of the host’s WWN, network name, HBA type, and HBA driver level. The SNC records
this information and displays it in the AMC.
This information is used to simplify configuration of the embedded firewall, SFM. Instead of manually
associating an HBA WWN with a specific host, the Scalar Firewall Manager, SFM, is configured using well
known host names. HRS is also used to monitor the status of hosts connected to the library. When the SNC
receives a HRS pulse from a host, the host is displayed in the AMC as online. If the SNC does not receive
two consecutive HRS pulses, the host will be listed as offline.
Note
CAUTION
The SFM database contains separate fields to store the WWN, host name, host type, connection, host
status and a LUN Access field that holds information about LUNs assigned to it.
When the SNC is first booted, SFM initially treats all hosts as “offline” until a host sends an I/O request to
the SNC. SFM detects the I/O and obtains the WWN of the HBA or Initiator. If the WWN is already in the
database (already registered), SFM stores the value “online” in the status field.
If the WWN is not in the database, SFM adds it and stores the value “online” in the status field. SFM sets
the default value for each of the other parameter fields to “unknown”.
At this point, SFM has registered the HBA or Initiator but has minimal information about it. The system
administrator can proceed to complete the registration by using the SNC to manually enter the “unknown”
host information and assign access privileges to LUNs.
The AMC view must be refreshed to see status changes for hosts.
If SFM is not enabled, hosts will not appear in the AMC.
Installing the Host Registration Service
The Host Registration Service software is included on the CD that shipped with the SNC.
1Insert the SNC software CD into the host.
2Browse to the client software directory.
3Open the directory for your Operating System and open the readme. This file lists specific instructions
for installing the package.
4Install the package.
5Reboot the server.
6
(Optional) Configure security for the SNC, channel zoning, and/or the Scalar Firewall Manager. For
definitions and specific instructions, see the ADIC Management Console User’s Guide.
Once installed, the service runs automatically and does not require further system administrator interaction.
From the ADIC Management Console, you can see the Fibre Channel that the host is connected to and you
can tell whether the host is online or offline. For software updates, visit “Service and Support” at
www.adic.com
20Scalar Firewall Manager
.
Note
After SFM is enabled, you may want to add a Host (or Initiator) to the SAN configuration or remove it from
the SAN configuration. This section describes how to add and remove hosts.
You have to refresh the SNC from the ADIC Management Console to see host
status changes.
Adding a Host to the SAN Configuration
You can connect a new host to the SAN at any time. SFM automatically adds the new host to the database
as soon as the host is attached to the SAN. If you want to attach a new host at this time, see Attaching a
New Host to the SAN. Otherwise, if you want to configure SFM before attaching the host, see Adding a Host
Before Attaching it to the SAN.
Attaching a New Host to the SAN
When you attach a new host to the SAN, SFM automatically detects the host and adds it to the SFM
database. When you connect or refresh the SNC from the ADIC Management Console, you can see the
new host in the SFM Access Settings window. If the Host Registration Service is running on the host, SFM
automatically obtains the host parameters. If the Host Registration Service is not running on the host, SFM
only knows the WWN of the HBA. In this case, you can manually enter the other host parameters.
Follow these steps to add a new host to the SAN configuration:
1Connect the host to the SAN.
2If you need to install the Host Registration Service, see Installing the Host Registration Service
20.
3If you need to determine LUN assignments for the devices you want to assign to the new host, see the
ADIC Management Console User’s Guide.
4For further information about entering host parameters, see the ADIC Management Console User’s
Guide.
5Refer to the see the ADIC Management Console User’s Guide to assign access permissions for the new
host.
6Verify that the new host has access to the assigned devices.
7Save your configuration, as explained in Saving a Configuration File
on page 17.
on page
Adding a Host Before Attaching it to the SAN
You can add a host that has not yet been attached to the SAN and configure its access permissions
beforehand. For more information, see the “Add VPS/SFM Hosts” section of the ADIC Management Console User’s Guide.
After the new host has been added you can assign its access permissions.
Removing a Host from the SAN Configuration
You may want to remove a host from the SFM database. SFM will prevent you from removing a host that is
online. For more information, see the “Deleting VPS/SFM Hosts” section of the
User’s Guide.
ADIC Management Console
SNC 4000 User’s Guide21
Combining SFM with Channel Zoning
Although it is possible to combine SFM and Channel Zoning, it is not recommended. SFM cannot assign
access to LUNs on channels rendered inaccessible by Channel Zoning. If you do have a legacy Channel
Zoning configuration, it is recommended that you edit the zones to permit all SAN Connections to have
access to all SCSI channels, or you may end up with inaccessible devices that you had intended to be
accessible.
22Scalar Firewall Manager
Connecting to the Service Port
The service port on the SNC is an RS-232C port, configured at 19200 Baud, with 8 data bits, 1 stop bit, no
parity and either hardware flow control or Xon/Xoff flow control.
To connect the SNC service port, a service terminal will be required. The service terminal can be any
standard personal computer that contains a serial (COM) port. Connection between the SNC and the
service terminal is established using a 9-pin to 9-pin straight through cable.
Note
Some systems, such as Unix workstations, may require a different cable or
adapter to connect to the SNC service port.
Service Port Connections
The figure below shows the service port connections.
Figure 6Service Port Pinout
Connections are listed in the following table.
Table 1DB-9 RS-232 Connector Pin Assignments
Pin
Number
Signal NameAbbreviation
Direction relative to SNC
4000
1Carrier DetectCDIn
2Transmit DataTDOut
3Receive DataRDIn
4Data Terminal ReadyDTROut
5Signal GroundSG-
SNC 4000 User’s Guide23
Table 1DB-9 RS-232 Connector Pin Assignments
6Data Set ReadyDSRIn
7Clear to SendCTSIn
8Request to SendRTSOut
9Ring IndicatorRIIn
Connecting the Service Terminal
Once the service terminal has been attached to the SNC service port, a terminal emulation program will be
required to access the SNC's command line interface. Most operating systems come with HyperTerminal
or some other form of terminal emulation program by default. If a terminal emulation program is not present,
one should be available (or at least recommended) by your operating system provider.
Hardware Required
•RS-232 DB9F straight through cable
•RS-232 DTE terminal or desktop/laptop computer running terminal emulation software
Connecting using HyperTerminal
This section shows the steps to setup use the HyperTerminal program. Other terminal emulation programs
operate in a similar fashion.
1Connect the straight through cable (and the 9- to 25-pin adapter if applicable) from the computer serial
(COM) port to the SNC service port.
2On the service terminal, select the HyperTerminal icon and double-click on it.
3In the New Connection dialog box enter SNC4000 for the name and click OK.
4In the Connect To dialog box, for the Connect using field select the COM port number that you have
chosen and click OK.
In the COM Properties dialog box select the following:
•Bits per second:19200
•Data bits:8
•Parity:None
•Stop bits:1
•Flow Control: Hardware or Xon/Xoff
5Click OK.
Connecting using Telnet
In instances where command line access to the SNC is required and local access is not permissible, it is
possible to Telnet into the SNC. Telnet access should be reserved for remote update of the SNC clock, IP
information, or collection of a supportdump. For all other management tasks, the ADIC Management
Console is the preferred method of updating information.
24Connecting to the Service Port
Loading...
+ 134 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.