Input Voltage (full load230VAC version: 160-276VAC
without using batteries)
Input Frequency45-65Hz
Input Power Factor>0.98 at full load
Input ProtectionBreaker (see notes on next page)
OUTPUT
Output Voltage230VAC nominal
Output Regulation±2% of nominal
Output WaveformSine Wave
Output THD<3% linear load
Crest Factor3:1
Output ProtectionElectronic Overload Protection (ultimately by fuse/breaker)
Efficiency (AC-AC)86% up to 1.5kVA, 90% up to 6kVA
Overload CapacitySee Overload Characteristics
Output Frequency50/60Hz dependant on input
BATTERY
Internal Battery TypeVRLA 5 year design life. For 10 year option add suffix ‘X’ to model number
Recharge<8 hours to 90%, standard battery only
Battery String Voltage48VDC: 1.6kVA, 96VDC: 3.2kVA, 192VDC: 6.0kVA
AutonomySee Tables
TemperatureAutonomy, recharge & battery life based on 25°C ambient
GENERAL
Input ReceptaclesSee rear panel drawings
Output ReceptaclesSee rear panel drawings
Display/AlarmFront panel LED’s, audible alarms. See front panel layout
Interface (Rear Panel)1 x RS232 & 1 x USB (fitted in option slot)
SoftwareSupplied bundled to support Windows 95, 98, ME, 2000, XP & NT
REPO (XTi 6000 only)Remote emergency power off, must be fitted for unit to function. Connector on rear of unit. Remove
ENVIRONMENTAL
Operating Temperature0°C to +40°C
Storage Temperature-15°C to +50°C
Operating Humidity0-95% RH non-condensing
Operating Altitude3000m without derating
Acoustic Noise<45dBA at 1 metre
IngressIP20
XT232RS232 Option Card (XT6000 Models only)
XT SSNMP Network Adaptor Option Card replaces USB port, allowing the UPS to be addressed directly on the LAN
XT V
AS400 Volt Free Contact Option Card replaces USB comms port with a 15 way D-type connector
Providing Utility Fail, Battery Low, Bypass & UPS Alarm Contacts
Option Order Codes
Power (VA)Options
E.G. XT1600V
XT Series, 1600VA
With AS400 Volt Free Contact Card fitted
Options (Examples)
Add suffix ‘S’ to Model Number - Adds internal SNMP to UPS (in place of USB port)
Add suffix ‘V’ to Model Number - Adds AS400 VFC to UPS for Utility Fail, Bypass, Battery Low and UPS Fault (in place of USB port)
Add suffix ‘X’ to Model Number - Replaces 5 year design life batteries with 10 year
(1) Options should be listed in alphabetical order
Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England
The XT S card provides network connectivity and SNMP
management protocol capability to the XT series of UPS.
Supplied with the option card is a CD which contains all
relevant software including the Manual and MIB.
The card can be factory fitted with this option on request
- please contact sales for assistance
www.powersolve.co.uk
XT S Box Contents
XT V Option Card
The XT V card provides true volt free contact indication of the
following key parameters:
Mains Fail
Battery Low
Bypass
UPS Fault
These are 250VAC 2A rated contacts.
REPO (must be fitted to a 6kVA UPS to operate)
The REPO feature shuts down the protected equipment
immediately and does not follow the orderly shutdown
procedure initiated by any power management software.
This occurs when the link between pin 1 and 2 is broken.
XT V Box Contents
Any devices which are operating on battery are also shutdown
immediately. When the REPO switch is closed, the equipment
will not return to battery power until the UPS input is re-cycled.
This can be done by shutting down the UPS and re-starting it.
Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England
1Option SlotOption slot allows user to fit AS400 Dry Contact Card or SNMP Internal Network Adaptor
2Comms. PortStandard Serial RS232 Communications via 9 pin D-type connector
3REPORemote Emergency Power Off (remove link to shutdown)
4Input/Output FusesOverload Protection
5External BatteryAllows user to connect external battery packs
6Maintenance BypassAllows unit to be isolated for maintenance
7Input BreakerInput breaker for 4, 5 & 6kVA Models
8Hardware TerminalsFor Input, Output & Battery (if required)
Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England
The XT is supplied as standard with XProtect software. However, the XT has been designed to work with UPSilon software packages, which allow the user to use the XT where MSXP UPS have previously been used.
UPSilon software must be used with the supplied RS232 cable. It will not function if used with the green UPSilon cable.
UPSilon is also available for Unix operating systems - please consult sales office for details.
XProtect Features:
• Simple installation & configuration
• Read/write function allows for engineer configuration of UPS
• Simple meter display of load battery capacity & temperature
• Complete data & event logging as standard
• Configurable tool bars
All models within the XT range are provided as standard with shutdown &
monitoring software.
This software is supplied on a CD and covers all Windows® based platforms. The software offers all of the functionality of standard shutdown
packages with some additional features for remote monitoring and control.
Monitoring is achieved either locally through the RS232 cable (supplied)
or remotely via a connected network. This can provide the user with information about major input and output parameters along with alarm information as and when it appears.
Control is via the console in the software and allows the user (again locally vis the serial connection or remotely via network connection) to
schedule remote system shutdown (password controlled) and general
UPS housekeeping.
In combination with its very flexible shutdown features, the software also
lets the user know which programs were shutdown at last mains failure,
to ensure that no saved files go unmissed.
Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England
The XT series of On Line UPS provides a high integrity AC power source with zero transfer time on mains fail conditions to battery.
This On Line double conversion topology ensures that the load is protected against noise and transients.