Pilz PSEN 2.1p-34 Data Sheet

Units
PSENmag
PSEN 2.1p-34
2.2
PSEN 2.1p-342.2SEN-D-2-034-2007-03UnitsPSENmagPSEN 2.1p-34PSEN 2.1p-34
Approvals
PSEN 2.1p-34
Unit features
` The actuator PSEN 2,1-10 belongs
to the safety switch
` 2 reed contacts (1 N/C, 1 N/O) ` Assured operating distance: 6 mm ` Assured release distance: 25 mm ` Square design ` Works magnetically ` Switching voltage 24 VDC ` Series connection via PSEN i1 in-
terface
` LED to display switch status
Unit description
The safety switch meets the require­ments of EN 60204-1 and IEC 60204-
1. The safety switch only complies with EN 60947-5-3 in conjunction with the actuator PSEN 2,1-10 and its ap­proved evaluation devices. The safety switch should only be con­nected to the evaluation devices listed under "Connections".
Function description
If the actuator is within the response range, the magnets switch the reed contacts on the safety switch. If the actuator is outside the response range (safety gate open), the reed contacts on the safety switch will switch.
Block diagram
Safety switch
Actuator
Magnet
2.2-146
SEN-D-2-034-2007-03Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Units
PSENmag
PSEN 2.1p-34
Operating distances
Seitenversatz/Lateral offset/
Décalage latéral
active area
aktive Fläche
surface active
Lateral and vertical offset
Assured operating distance Sao in mm
Höhenversatz/Height offset/ Décalage en hauteur
3,02,01,0 4,0 1,0 2,0 3,0 4,0
Seitenversatz/Lateral
offset/Décalage latéral
-
-4,0
5,0
3,04,54,55,5 4,0 2,54,54,55,0 3,5 0,53,54,54,5 2,5
--
Assured release distance Sar: Max. 25 mm with all vertical and lateral offsets
The stated values are valid at a tem­perature of 20 °C.
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
Höhenversatz/Height offset/
Décalage en hauteur
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resist-
R
lmax
ance (see Technical details)
/ km = cable resistance/km
R
l
` When using evaluation devices with
delay-on de-energisation contacts, please note: –Delay time ≤ 30 s: Delay-on de-
energisation contacts satisfy the requirements of category 3 in ac­cordance with EN 954-1 and the requirements of a PDF with sin­gle-fault tolerance (PDF-S).
–Delay time 30 s: Delay-on de-
energisation contacts satisfy the requirements of Category 1 in accordance with EN 954-1 and the requirements of a PDF with designed reliability (PDF-D).
Schaltabstand/Operating distance/
s
ar
s
ao
s
omin
Portee de travail
= 25
= 6
= 0,5
Ein/On/Marche Aus/Off/Arrêt
` In the following commissioning cas-
es, check the function that detects shorts across contacts: – On evaluation devices with DC
supply voltage: Overall cable re­sistance 15 Ohms per channel
– On evaluation devices with AC
supply voltage: Overall cable re­sistance 25 Ohms per channel
– For details of how to perform the
test for shorts across the con­tacts, please refer to the operat­ing manual for the relevant evaluation device.
Connections
NOTICE
The colour marking for the connection lead only applies for the cable that Pilz supplies as an accessory. The safety switch is shown in an unop­erated condition.
2.2
Assignment of the 4-pin M8 male connec­tor
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
2
1
4
3
1
2
3 +
4
SEN-D-2-034-2007-03
2.2-147