Split System Submittal Data
System: KS18NB4UA Indoor: CS-KS18NB4UW Outdoor: CU-KS18NKUA
Ceiling Recessed Heat Pump
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 230/208/1/60
Circuit Ampacity (A) 15
Fuse Size, Max.(A) 15
Compressor DC Twin Rotary (Inverter)
No. Used 1
R.L. Amps - L.R. (A) 8.3 ( 1.2 to 8.3 )-(17.5)
Outdoor Unit
Fan Type Propeller
Dia (in.) - No. Speeds
Type Drive DC Motor
No. Poles (RPM) 8-820
No. Motors (W) 1-50
F.L. Amps (A) 0.5
Coil Type Aluminum Fin and Copper Pipe
Fin Type - Pipe Type Corrugated Plate - Inner Rifled
Rows - F.P.I. 2-21.2
Face Area (sq.ft.) 5.49
Tube Size (in.) 9/32”
Indoor Unit
Fan Type Turbo
Diameter and Depth 12-5/8” x 5-3/4”
No. Speeds Auto and 3 steps
No. Poles (RPM, High) 8-650
No. Motors (W) 1-20
CFM (Hi/Med/Low) 341 / 294 / 253
Operation Sound (Hi/Med/Low)
(dB-A)
F.L. Amps 0.3
Coil Type
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2-18.1
Face Area (sq. ft.) 2.94
Tube Size (in.) 9-32”
Drain tube connection, VP20(in.) (outer dia.1”)
Refrigerant R410A
Lbs. - R410a (outdoor unit) 2.87
16-17/32”-Auto (Hi and multi steps)
44 / 40 / 36
Aluminum Plate Fin & Copper Tube
Approval:
Date:
Construction:
Unit#:
Drawing#:
Refrigerant Control Electronic Expansion Valve
Refrigerant Tubing Connections Flare
Line Length, Max (ft.) 100’
Line Heigth Difference, Max (ft.) 50’
Line Size (in. O.D. Discharge) 1/4”
Line Size (in. O.D. Suction) 1/2”
Pre-charge, tubing length at
shipment
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 11-13/32” x 24-13/16” x 28-1/8”
Indoor Unit (Uncrated) (in.) 11-5/32” x 22-5/8” x 22-5/8”
Outdoor Unit (Crated) (in.) 29-1/8” x 39-27/32” x 14-31/32”
Outdoor Unit (Uncrated) (in.) 26-3/8” x 34-21/32” x 11-7/32”
Weight (lbs.)
(Indoor) Net 35.3
(Indoor) Shipping 41.9
(Outdoor) Net 90.4
(Outdoor) Shipping 99.2
(Indoor) Shipping Volume (cu.ft.) 4.59
(Outdoor) Shipping Volume (cu.ft.) 9.88
25’
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity (BTU/H) 17,500 (4,000-17,500)
Sensible Capacity (BTU/H) 10,600
Latent Capacity (BTU/H) 6,900
SEER 16
Dehumidification (Pints/H) 4.89
Amps (A) 8.3 (1.2-8.3)
Power Inputs (W) 1860 (250-1860)
Outdoor Sound Rating (dB-A) 51
Features
Controls Microprocessor
Remote Controller LCD Wireless Type, Temp. Sensor
Built In
Temperature Control IC Thermistor
Timer 24 Hour, Single Event, ON/OFF
Timer
Night Setback Included
Panel, No.of Louvers, Control (CZ-18BT1U)-4-Automatic/
Sweep/Step
Power Failure Automatic Restart Included
Self-Diagnosis Included
Air Filter Washable, Anti-Mold
Quiet Operation Included
Condensate Drain Pump Included
High Power Included
One Hour Off Timer Included
Options
Refrigerant Line Set Available
Fresh Air Intake Knock-Out (Dia. 3-7/8”)
Air Duct Extension N/A
Hard Wired Remote Control Available / Model Number-CZ-
Non-Removable, Locking
Remote-Control Bracket
Operating Range
Cooling (Max) 95F DB/71F WB 115F DB
Cooling (Min) 67F DB/57F WB 0F DB
Low Ambient Control
Included
Indoor Air Intake Temp
RD515U
RCS4MHVB
Outdoor Air Intake Temp
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144