Omron V500-R521B2, V500-R521C2 User Manual

Page 1
Bar Code Reader
User’s Manual
V500-R521B2/C2
Cat. No. Z253-E1-02 Bar Code Reader V500-R521B2/C2 User’s Manual
Page 2
Introduction
Thank you for purchasing the OMRON V500-R521B2/C2. This manual describes the functions, performance, and application methods of the V500-R521B2/C2.
This manual is intended for personnel with knowledge of electrical systems. Be sure to read and understand this manual thoroughly before using the product, and keep this manual in an easily accessible location for quick reference when required.
Page 3
Introduction
Introduction Section 1 Section 2 Section 3 Section 4 Section 5 Appendix
Introduc- Section 1 Section 2 Section 3 Section 4
Introduction
Section 1
Section 2
Section 3
Section 4
Section 5
READ AND UNDERSTAND THIS DOCUMENT (Be sure to read this.)
Product Overview
Wiring and Installation
Function Explanation
Setting Method
Example of System Configuration
Section 6
Appendix
Bar Code Reader User’s Manual
V500-R521B2 V500-R521C2
Page 4
Introduction
Introduction
READ AND UNDERSTAND THIS DOCUMENT
Please read and understand this document before using the products. Please consult your OMRON representative if you have any questions or comments.
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
SUITABILITY FOR USE
THE PRODUCTS CONTAINED IN THIS DOCUMENT ARE NOT SAFETY RATED. THEY ARE NOT DESIGNED OR RATED FOR ENSURING SAFETY OF PERSONS, AND SHOULD NOT BE RELIED UPON AS A SAFETY COMPONENT OR PROTECTIVE DEVICE FOR SUCH PURPOSES. Please refer to separate catalogs for OMRON's safety rated products.
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer’s application or use of the product.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
V500-R521B2/C2
2
User’s Manual
Page 5
Introduction
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PERFORMANCE DATA
Performance data given in this document is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
Introduction
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This document shall not be copied for sales or promotions without permission.
This document is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this document in any manner, for any other purpose. If copying or transmitting this document to another, please copy or transmit it in its entirety.
V500-R521B2/C2
User’s Manual
3
Page 6
Introduction
Introduction
Meanings of Signal Words
In this manual, precautions are indicated using the following symbols and signal words to ensure safe use of the V500-R521B2/C2. The precautions indicated by these symbols and signal words are important for safety and must be observed.
Indicates a potentially hazardous situation which, if not avoided, will result in
WARNING
minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage.
Meanings of Alert Symbols
Indicates the possibility of laser radiation.
Indicates prohibition when there is a risk of minor injury from electrical shock or other source if the product is disassembled.
Indicates instruction for the user to always connect the ground wire.
V500-R521B2/C2
4
User’s Manual
Page 7
For the Safety Use of Laser Products
Warning display
WARNING
Avoid eye exposure to direct or scattered radiation reflected by a mirror surface. Laser beam emitted from a laser has high power density and may become blind when the beam is directed into eyes.
Do not disassemble this bar code reader. Laser beam may be scattered around when it is disassembled.
This Bar Code Reader uses a laser as the light source. Lasers are classified on IEC standard (IEC 60825-1).
V500-R521B2/R521C2
Wavelength 650 nm
Peak power 1 mW max.
Classification 2
Introduction
Introduction
Labeling on Laser Use
The Bar Code Reader has the following WARNING Label on the bottom.
A different set of regulations, European, IEC 60825 applies when exporting this product to Europe. Replace the warning label with the corresponding English label (supplied with this product.)
When using devices in which a Bar Code Reader is installed in the U.S., the product is subjected to the U.S. FDA (Food and Drug Administration) laser regulations. Replace the warning label with the corresponding English label (supplied with this product.)
Usage
Use laser enclosure device to prevent specular object from reflecting laser beam. When used without an enclosure, be sure to avoid a laser path from eye level.
Although the safety distance (NOHD) is approximately 1 m; it is advisable, however, to terminate the laser on its path if possible. Nonreflective, flatting material is recommendable for termination.
Wear protective glassed to protect against laser light during set up and adjustment.
V500-R521B2/C2
User’s Manual
5
Page 8
Introduction
Introduction
Outline of IEC 60825-1 Standard
The following are the safety measures to be taken by the user for each type of laser equipment.
Classification
Required items
Remote interlock Not required Connect to room or door circuits.
Key control Not required Remove key when not in use.
Beam attenuator Not required When in use prevents inadvertent
Emission indicator device
Warning signs Not required Follow precautions on warning
Beam path Not required Terminate beam at end of useful length.
Specular reflection Not required Prevent unintentional reflections.
Eye protection Not required Required if engineering and
Protective clothing Not required Sometimes
Training Not required Required for all operator and maintenance personnel.
With respect to the requirements of remote interlock connector, key control, beam attenuator, emission indicator
device, and eye protection, Class 3B laser products not exceeding five times the AEL of Class 2 in the wavelength range of 400 nm to 700 nm are to be treated as Class 3A laser products.
Class 1 Class 2 Class 3A Class 3B* Class 4
exposure.
Not required Indicates laser is energized.
signs.
administrative procedures not practicable and MPE exceeded.
Specific
required.
requirements.
Precautions for Safe Use
Observe the following precautions to ensure safe use of the product.
Installation Environment Precautions
Do not use the product in environments with flammable or explosive gases.
Do not install the product close to high-voltage devices and power devices in order to
secure the safety of operation and maintenance.
During installation, make sure that screws are tightened firmly.
Power Supply and Wiring Precautions
Use the product with the power supply voltages specified in this manual.
Use a DC power supply with countermeasures against high-voltage spikes (safe
extra low-voltage circuits on the secondary side).
p.30
Other Precautions
If the product becomes extremely hot, or abnormal odors or smoke occurs, stop using
the product immediately, turn OFF the power, and consult with your OMRON representative.
Dispose of the product as industrial waste.
Do not apply pressure or deform the product when disposing of it.
V500-R521B2/C2
6
User’s Manual
Page 9
Introduction
Precautions for Correct Use
Always observe the following precautions to prevent operation failures, malfunctions, and adverse effects on performance and equipment.
1. Installation of the bar code reader
The bar code should be mounted in a place:
where is not subject to direct sunlight (indoor use),
without any corrosive gas, dust, metallic powder or salt content,
where operation temperature does not exceed the specified range,
where temperature change is not rapid, without dew condensation (within the
specified value),
where humidity change is not rapid, without dew condensation (within the specified value),
where vibration or shock does not reach to the bar code reader directly (within the
specified value),
and without any droplet of water, oil or chemical agent.
Introduction
2. Power supply
Apply voltage to be +5 VDC ±10 % at the connector of the bar code reader side.
Used cable should be 0.3 mm
or resistance is too huge, voltage may be decreased due to fluctuation of consumption current of the bar code reader.
Be careful so that noise or switching surge of relay is not applied on +5 V power
voltage supplied to the bar code reader.
To suppress influence such as noise, use direct current of insulation transformer, not
auto transformer.
Auto transformer
Commercial power source
Insulation transformer
Commercial power source
2
or equivalent, within 5 m. When the wiring is too long
V500-R521
series
V500-R521
series
When high frequency wave such as ultrasonic welding machine is used, insulate it
using auxiliary insulation plate to avoid malfunction due to induction current.
S82K-00705 (made by OMRON Corporation) is recommended for the driving power
supply of the bar code reader.
V500-R521B2/C2
User’s Manual
7
Page 10
Introduction
Introduction
3. Wiring
Extension length of the RS-232C line (SD, RD, SG) should be up to 15 m.
For trigger and power line, use a cable with 0.3 mm
2
or more and extension length
should be up to 5 m.
Wiring should avoid approaching to a high-power heavy electric current wire.
Check the polarity of terminals and be careful of faulty wiring.
Avoid reverse connection of power supply or connection to alternating current.
Turn off the power switch before connecting or disconnecting a connector.
Use a wrist strap etc. to avoid electrostatic charge when you touch terminals and
signal lines, to avoid damage due to static electricity.
4. Installation
When using the bar code reader, fix it to the associated mounting bracket.
When inductive noise is generated at the mounting bracket, attach an associated
insulation board. Use the associated screw to mount the insulation board.
Incline the bar code reader about 15 ° to read the target bar code.
Do not apply stress on the cable when mounting and using.
Distance and angle allowed to read differs according the bar code. Check if the used
bar code can be read actually, before mounting.
5. Timing input with photo-electronic sensor
When taking timing with the photo-electronic sensor, mount the bar code reader so that the footlight beam of the photo-electronic sensor does not spot directly on the reading window of the bar code reader or on the bar code.
Bar code
Photo-electronic sensor
Footlight beam of the photo-electronic sensor spots on the reading window of the bar code reader.
Footlight beam of the photo­electronic sensor spots on the bar code.
6. Influence of reflective objects
When there is any reflective object such as metal or mirror surface on the bar code beam-scanning surface, reading character may be deteriorate. Cover the reflective object with something or change the bar code position to avoid influence.
V500-R521B2/C2
8
User’s Manual
Page 11
Introduction
7. Mutual interference
When mounting the bar code readers side-by-side, laser beams may interfere reading each other. The bar code readers should be placed far enough not to affect reading.
Bar code
Introduction
8. Bar code label
The height of the bar code should be more than the luster scan width (max. 10 mm)
and use a label considering attaching error.
When reading bar code, margin is necessary on the both sides of the bar code. Set
the label so that margin parts do not hide. A space of one character or more and 2.5 mm or more is necessary of both right and left side of the label. (Rough standard: 12 or 13 times or more of the narrow bar width)
Bar code
Margin
Width
Label (Paper which a bar code is printed on)
Narrow bar (Slim lines)
Margin
Height
9. To improve reading reliability
When the digit is determined, designate the digit to use the bar code.
Use the modulus check (addition of check digit).
Bar codes other than the reading object should be set to reading prohibition.
p.61
10. Maintenance and check
Check for any dust or dirt on the reading window regularly. When it is dirty, wipe with
a dry, soft and clean cloth. Do not use solutions such as thinner.
Handle with care, not to apply strong shock such as dropping.
V500-R521B2/C2
User’s Manual
9
Page 12
Introduction
Introduction
How to Use This Manual
How to Use This Manual
In this manual, each part of the bar code is described as follows.
Bar code
Label (Paper which a bar code is printed on)
Narrow bar (Slim lines)
Margin
Margin
Height
Width
For a page format
Section 4
System Settings
Creating Setting Files Using the 2DCR Configear
Creates the data setting file for loading set data to the Handheld 2D Code Reader. Make the settings for the communications conditions, functions, and display conversion.
Se lect Setting Reader - Create Data... from the menu.
The following window for creating the setting data file will be displayed.
Section 4
System Settings
Section 4 Creating Setting Files Using the 2DCR Configear
Section title
Outline
Move to the setting screen.
Screen display
Open
Opens the previously created data setting file for editing. The [Receive (R Reader and edit it.
Save
Saves the created data setting file.
)] function can be used to open the data file downloaded from the Code
To save data to the Memory Card, create a folder with the name SETTINGS, and save. If the data is saved to a folder other than “SETTINGS”, it cannot be uploaded.
Communication Settings
The settings shown in the following table are set in the Communica tion Settings Tab Page in the Create Setting Data Window.
Setting item Settings
Baud Rate
Parity
Data Length
Stop Bit
Header/Footer Prefix
The default settings are indicated with an asterisk.
*
, 19,200, or 38,400
9,600
*
None
, odd, or even
8 bits
77 bits or
*
or 2 bits
1sbit None*, 02 <STX>, or 1B <ESC>
Suffix
ETX, 0A LF,
FCS
ON or
OFF
0D CR
*
*
*
, or 0D0A CR+LF
V500-R521B2/C2
User’s Manual
65
V500-R521B2/C2
User’s Manual
Procedure and additional explanations
Information useful during the operation and reference pages are provided here with special marks to indicate the kind of information being provided.
Section 4 Uploading from the Memory Card
Index label
Provides the section number and subject matter. Can be used to immediately open the desired page.
Describes the settings.
69
V500-R521B2/C2
10
User’s Manual
*This page does not actually exist in this manual.
Page 13
Visual Aids
Introduction
Introduction
Indicates points that are important in using product functions or in application procedures.
Indicates page numbers providing related information.
Indicates helpful information when a problem occurs and explanations of technical terms.
Visual Aids
V500-R521B2/C2
User’s Manual
11
Page 14
Introduction Contents
Introduction
Contents
Introduction
Meanings of Signal Words 4
Meanings of Alert Symbols 4
For the Safety Use of Laser Products 5
Precautions for Safe Use 6
Precautions for Correct Use 7
How to Use This Manual 10
Visual Aids 11
Section 1 Product Overview 15
Features 16
Product Composition 18
Part Names 19
Rating/Performance 20
Usage Flow Chart 24
Section 2 Wiring and Installation 27
Wiring 28
Installation 32
Section 3 Function Explanation 35
Explanation of Reading System 36
Operation Flow Chart 38
Communication Data Format 46
Test Reading Function 49
V500-R521B2/C2
12
User’s Manual
Page 15
Introduction
Section 4 Setting Method 51
How to Use Menu Sheet/Command 52
Menu Sheet/Command List 56
Section 5 Example of System Configuration 87
Example of Connection with a PC 88
Example of Connection with Programmable Controller (CS1) 89
Example of Multi-drop Connection 92
How to Use Command Link Unit V700-L12 96
Introduction Contents
Section 6 Appendix 113
External Dimension 114
Troubleshooting 120
ASCII Code Table 121
Explanation of Terms 122
Corresponding Bar Code List 127
Revision History 132
V500-R521B2/C2
User’s Manual
13
Page 16
Section 1 Product Overview
This section explains about features and rating/performance of this bar code reader.
Features 16
Product Composition 18
Part Names 19
Rating/Performance 20
Usage Flow Chart 24
Section 1 Product Overview
V500-R521B2/C2
User’s Manual
15
Page 17
Section 1 Product Overview
Features
Section 1 Features
A bar code reader is a device to read a bar code attached on a product and transfer the information to upper equipment. Various types of information can be managed efficiently by using it combining with PC and programmable controllers.
Problems on site Bar code solution!
Work data are recorded on papers. > Reading and writing mistakes and
distribution of workers exist.
> Formats are difficult to learn because various
kinds are produced in small numbers.
Cost should be as cheap as possible as the product price is low.
Register product numbers and setting on PC and programmable controllers beforehand and import a product number only by reading a bar code. Input mistake or distribution of workers are eliminated.
Cost is very low by only attaching a printed bar code label.
Ultra-compact design
Optimum for the assembly to each device
Easy installation
Easy to read by pressing the TEST button and know the reading rate with LED illumination and buzzer sound in real time. As reading position is easy to check at site before connecting with upper equipment, installation work and maintenance work hour can be greatly reduced.
p.49
Simple function setting
You can either set the function by reading a menu sheet or by inputting a command on the upper equipment. You can select the setting method according to the condition.
p.52
V500-R521B2/C2
16
User’s Manual
Page 18
Section 1
Product Overview
Perfect reading performance
High speed reading with 500 scan/sec. realized high reliability and wide reading distance of 60 mm to 270 mm (in case of narrow bar width 1.0 mm).
p.21
Easy multi-drop
Connect communication link unit V700-L12 to collect read data from plural bar code readers (max. 31) for one set of upper equipment.
p.92
Communication link unit V700-L12
Communication
Upper equipment
converter K3SC
Bar code reader V500-R521
Section 1 Features
Max. 31 sets
V500-R521B2/C2
User’s Manual
17
Page 19
Section 1 Product Overview
Product Composition
Section 1 Product Composition
The bar code reader is used by connecting with upper equipment such as PC and programmable controllers. The upper equipment receives information which the bar code reader reads and refers with the registered information and records. There are two types in V500-R521 differing in connector shape as follows. Select according to connecting upper equipment.
V500-R521B2 (Cable output type)
Tip of the cable is loose end.
Bar code reader V500-R521B2
PC (PC/AT compatible)
p.88
Programmable controller
p.89
Power supply (5 VDC) Recommended: S8VS-01505
V500-R521C2 (Connecter output type)
Tip of the cable is a connector. Use an appropriate connecting cable according to the upper equipment.
PC (PC/AT compatible)
Bar code reader V500-R521C2
Cable for connecting with PC/AT compatible V509-W011D
p.88
Power supply (5 VDC) Recommended: S8VS-01505
Programmable controller
V500-R521B2/C2
18
User’s Manual
Programmable controller made by OMRON Connecting cable V509-W011
p.89
Page 20
Part Names
Section 1
Product Overview
Front side
Back side
Section 1 Part Names
Main cable (2 m)
Laser alarm label (bottom side)
Reading window Laser beam radiates from here
READ OK LED Illuminates when read correctly.
TEST button Press it once to read once.
Test Reading Function p.49
READ NG LED Illuminates when not read correctly.
V500-R521B2/C2
User’s Manual
19
Page 21
Section 1 Product Overview
Rating/Performance
Section 1 Rating/Performance
Applicable bar code
Reading performance (*1)
Interface Communication specification RS-232C
Function set method
Reading trigger External trigger (Transistor input)
Reading result output
Power supply specification
Environment Ambient temperature At operation: 0 to + 45 °C; At storage: -10 to + 60 °C
Enclosure rating IP54 (IEC60529 Standard)
Mass 80 g (Excluding cables and connectors)
Input/output connector
Code length 2 m
General specification
Types of bar code EAN/UPC (A, E), CODE39, NW-7, ITF
Number of reading digits 32 digits MAX (Changes according to bar width and reading size)
Resolution 0.15 mm (at PCS 0.9)
Contrast (PCS) 0.45 or more (white reflectance 70 % or more)
Reading distance 60 to 270 mm (At narrow bar: 1.0 mm)
Reading angle Within 40 ° (Including margins at left and right sides)
Skew angle ±50 ° (However, exclude from 10 ° upper side to 5 ° lower side)
Pitch angle ±25 ° (Left and right 25 °)
Light source Red semiconductor laser (Wave length: 650 nm)
Light output 1.0 mW or less (Correspond to JIS class 2)
Scan type Luster scan
Number of scan 500 scan/sec.
Number of reading coincidence 2 to 6 times (Verification: 1 to 5 times)
Reading check Buzzer sound, indication LED
OK/NG output (Only V500-R521B2) NPN open collector output 24 VDC, 30 mA
Menu sheet reading method or host command method
Trigger by command (RS-232C)
Trigger a test reading by pressing the TEST button on the product
RS-232C output Reading data output
OK/NG signal (Only V500-R521B2)
Indication LED OK LED illuminates when reading succeeded
Buzzer Notifies a successful reading with a buzzer sound (Muting available)
Power voltage 5 VDC ±10 % (*2)
Consumption current 220 mA typ. (330 mA MAX)
Inrush current 2.5 A MAX
Ambient humidity At operation and storage: 30 to 85 % RH (Without due condensation)
Vibration resistance 12 to 100 Hz 19.6 m/s
Ambient light resistance 3000 lx or less (Fluorescent lamp. Excluding inverter florescent lamp.)
V500-R521B2: Cable output
V500-R521C2: DIN 8 pin connector
STF (2 of 5 bar), CODE93, CODE128 (including EAN128)
OK signal is turned on when reading succeeded NG signal is turned on when reading failed
NG LED illuminates when reading failed
2
(2G) X, Y, Z, 3H each
*1 Unless otherwise specified, use a bar code of EAN 1x, MRD 63 % or more (PCS = 0.9 or more).
Specified at a condition of pitch angle α = 0 °, skew angle β = 0 °, tilt angle γ = 0 °, curvature R = ∞
*2 Power voltage is specified at the input/output connecter end of the bar code reader side.
V500-R521B2/C2
20
User’s Manual
Page 22
Number of reading range performance
Explained with examples of following conditions:
• Contrast: MRD 63 % (PCS = 0.9)
• Bar code: CODE39
• Installation condition: Pitch angle α = 0 °, skew angle β = 15 ° Tilt angle γ = 0 °, curvature R =
Section 1
Product Overview
Section 1 Rating/Performance
Reading distance
Narrow bar width
(Unit: mm)
Narrow bar width
A 0.15 mm (*2) 90 to 110 mm (*2)
B 0.2 mm 80 to 150 mm
C 0.25 mm 60 to 170 mm
D 0.5 mm 60 to 230 mm
E 1.0 mm 60 to 270 mm
*1 Distance from the end of the case. *2 Value at a reading angle 30 ° .
Reading distance
(*1)
V500-R521B2/C2
User’s Manual
21
Page 23
Section 1 Product Overview
Reading angle performance
Section 1 Rating/Performance
Pitch angle
In the following conditions, readable up to α = 25 ° on either side.
• Bar code: Resolution = 0.25 mm, CODE39 (9 digits), MRD 63 % (PCS = 0.9)
• Reading distance: 100 mm from the case end
• Installation condition: Skew angle β = 15 °, tilt angle γ = 0 °, curvature R =
Skew angle
In the following conditions, readable up to β = ± 50 °. However, range from β = -10 to +5 ° is an area difficult to read due to regular reflection.
• Bar code: Resolution = 0.25 mm, CODE39 (9 digits), MRD 63 % (PCS = 0.9)
• Reading distance: 100 mm from the case end
• Installation condition: Pitch angle α = 0 °, tilt angle γ = 0 °, curvature R =
V500-R521B2/C2
22
User’s Manual
Page 24
Product Overview
Tilt angle
Generally, a tilt angle is not specified, because it differs according to the bar code height. Scan all the bar code with the laser.
Section 1
Section 1 Rating/Performance
Curvature
In case of the following conditions, the bar code of 8-digit EAN, curvature range 15 mm or more and 13-digit EAN, curvature range 20 mm or more can be read.
• Bar code: Resolution = 0.26 mm, EAN, MRD 63 % (PCS = 0.9)
• Reading distance: 100 mm from the case end
• Installation condition: Pitch angle α = 0 °, skew angle β = 15 °, tilt angle γ = 0 °
V500-R521B2/C2
User’s Manual
23
Page 25
Section 1 Product Overview
Usage Flow Chart
Section 1 Usage Flow Chart
Examination of the bar code beforehand, installation, and introduction flow chart is as shown below.
Examination
beforehand
Check the type, width, height and numbers of digit of bar codes.
p.20 Rating/Performance p.127 Corresponding Bar Code List
Wiring.
Connection
p.28 Wiring
Connect peripheral equipment.
p.87 Example of System Configuration
Turn on the power switch.
Check that the bar code in subject can be read.
p.49 Test Reading Function
Preparation
Investigate the reading timing and moving speed.
p.38 Operation Flow Chart
Set the reading condition corresponding to the purpose.
p.56 Menu Sheet/Command List
V500-R521B2/C2
24
User’s Manual
Page 26
Install.
Section 1
Product Overview
Section 1 Usage Flow Chart
Execution of reading
of using
p.32 Installation
Installation -
Test in the actual usage environment.
p.49 Test Reading Function
Execute reading.
Applied way
Read only the registered bar code.
p.83 Setting related to sorting read
In case of trouble:
A bar code cannot be read correctly.
p.120 Troubleshooting
I can't understand the operation flow.
p.38 Operation Flow Chart
I don't know the communication specification.
p.46 Communication Data Format
V500-R521B2/C2
User’s Manual
25
Page 27
Section 2 Wiring and Installation
This section explains about the wiring method and installation method of the bar code reader.
Wiring 28
Installation 32
Section 2 Wiring and Installation
V500-R521B2/C2
User’s Manual
27
Page 28
Section 2 Wiring and Installation
Wiring
Section 2 Wiring
• Extension length of the RS-232C line (SD, RD, and SG) should be up to 15 m.
• For trigger and power line, use a cable with 0.3 mm
• Wiring should avoid approaching to a high-power heavy electric current wire.
• Check the polarity of terminals and be careful of faulty wiring.
• Avoid reverse connection of power supply or connection to alternating current.
• Do not use exceeding rating voltage.
• Turn off the power switch before connecting or disconnecting a connector.
• Use a wrist strap etc. to avoid electrostatic charge when you touch terminals and signal lines, to avoid damage due to static electricity.
2
or more and extension length should be up to 5 m.
Wiring diagram
V500-R521B2 (Cable output type)
Wiring color
Brown TRIG External trigger signal
Yellow OK READ OK signal
Orange NG READ NG signal
Blue CS Transmission allowed
Gray RS Transmission request
White RD Received data
Green SD Transmission data
Red VCC Power supply
Black S.GND 0 V (Signal ground)
Shield (FG) F.GND FG (Frame ground)
Signal
name
Function
Connection with upper equipment p.88, p.89
Signal direction
Bar code reader Upper equipment
External
External
V500-R521B2/C2
28
User’s Manual
Page 29
Logic of external trigger signal can be selected.
Section 2
Wiring and Installation
Positive logic (HIGH active)
Negative logic (LOW active)
You can select the output logic of READ OK and READ NG signal.
System Description
Trigger signal synchronous system
One-shot system READ OK/NG signal is turned on during the preset time (one-shot time). One-shot
Maintains ON condition until the next trigger is input. You can select positive logic/ negative logic.
time can be set from 10 to 100 ms (in 10 ms interval). You can select positive logic/ negative logic.
Trigger ON
Trigger ON
Setting method p.57
Setting method p.75
Section 2 Wiring
V500-R521B2/C2
User’s Manual
29
Page 30
Section 2 Wiring
Section 2 Wiring and Installation
V500-R521C2 (Connector output type)
(Pin alignment)
Connector part (DIN: 8P plug) Made by Hosiden Corporation TCP1394-715267 (TypeA)
Pin No.
1 SD Transmission data
2 RD Received data
3 RS Transmission request
4 CS Transmission allowed
5 TRIG External trigger signal
6 NC Not connected
7S.GND 0 V
8 VCC Power supply
Signal name
Function
Bar code reader Upper equipment
Signal direction
External
Connection with upper equipment p.88, p.89
When you make a connection cable, use the following connectors. Recommended parts for the connector
Usage Manufacturer Model
For cable relay Hosiden Corporation TCS8587-0170477
For panel installation 2 Hosiden Corporation TCS1080-0120177
External
Logic of external trigger signal can be selected.
Positive logic (HIGH active)
Negative logic (LOW active)
You can select the output logic of READ OK and READ NG signal.
Power supply
Recommended parts for the power supply
Manufacturer Model
OMRON Corporation S8VS-01505
V500-R521B2/C2
30
User’s Manual
Trigger ON
Trigger ON
Setting method p.57
Page 31
Section 2
Wiring and Installation
Input/output circuit
Input circuit for the external trigger signal (Common to V500-
R521B2/V500-R521C2)
Vcc
Internal
circuit
Maximum
value
External trigger signal
Item
Terminal voltage Von when a
transistor is turned on
Terminal voltage Voff when a
transistor is turned off
Vcc
TRIG
Von/off
SG
Minimum
value
0 V 1.3 V
2.5 V Vcc
Output circuit of the READ OK/NG signal (Only V500-R521B2)
OK/NG
Internal
SG
circuit
Section 2 Wiring
Item Specification
Output system NPN open collector
Rated load 24 VDC 30 mA
Leak current at OFF 0.5 mA or less
Residual voltage at ON 1.0 V or less
Cable specification
• Shape: Straight cable
• Diameter: φ3.8 ± 0.5 mm
• Length: 2000 ± 50 mm
• Number of core: 9
V500-R521B2/C2
User’s Manual
31
Page 32
Section 2 Installation
Section 2 Wiring and Installation
Installation
To avoid regular reflection of laser, incline approx. 15 ° against the bar code subject to read when installing the bar code reader. Use this mounting bracket as the mounting surface of an associated mounting bracket is inclined 15 °. (Tightening torque 0.54 N/m)
V500-R521
V500-R521
1. Attach the mounting bracket on the bar code reader.
2. Install.
When you attach this line of the bracket horizontally, the bar code reader inclines 15 °.
• When inductive noise is generated at the mounting bracket, attach an associated insulation board. Use the associated screw to install the insulation board.
• Do not apply stress on the cable when installing or using.
• Distance and angle allowed to read differs according the bar code. Check if the used bar code can be read actually, before installing.
When you attach this line of the bracket vertically, the bar code reader inclines 15 °.
Vertical
Horizontal
V500-R521B2/C2
32
User’s Manual
Page 33
External dimension
Mounting bracket (accessory)
Material: SUS304
Section 2
Wiring and Installation
(Unit: mm)
Small screw, +Flat head 2-M3X 6
Light axis
Mounting bracket
Dimension of mounting hole
Section 2 Installation
Insulation board (accessory)
Material: Fabric bake
2-M5 holes
When the associated mounting bracket and insulation board are not used, install it by referring to the outline dimension figure.
p.114
Bar code label
Laser beam
(Unit: mm)
V500-R521B2/C2
User’s Manual
33
Page 34
Section 3 Function Explanation
This section explains about representative functions of the bar code reader.
Explanation of Reading System 36
Operation Flow Chart 38
Communication Data Format 46
Test Reading Function 49
Section 3 Function Explanation
V500-R521B2/C2
User’s Manual
35
Page 35
Section 3 Explanation of Reading System
Section 3 Function Explanation
Explanation of Reading System
There are following reading systems for this bar code reader.
Setting method p.67
Reading system Trigger reading Full-time reading
Trigger Input method
Reading operation (*2)
External trigger signal
RS-232C command
TEST button (Back side)
Single reading
Plural reading
Continuous reading
Reading starts by applying reading trigger from outside. This system is mainly used when operation.
When the external trigger signal is turned on, laser radiates and starts reading. The "Trigger controlled system" reads during the trigger is ON, and the "Effective duration designation system" reads only the effective duration (*1) which is set beforehand after the trigger is ON.
The upper equipment sends the communication command and the laser beam radiates to start reading. After receiving the command, it reads only for the effective duration (*1) which is set beforehand.
Press the TEST button once to read once. Handy to use to check if the reading condition setting is appropriate.
When the reading succeeds, the data is output and ends reading automatically.
Reads bar codes continuously during the trigger is ON or effective duration (*1). When the first reading is completed, data is once output and while reading the same bar codes continuously, no output is made. Outputs newly only when the data differ from the adjacent bar code.
Reads bar codes continuously during the trigger is ON or effective duration (*1). Outputs data continuously even for the same bar code.
During the power is turned on, laser is radiated all the time, to be able to read any time. This system is mainly used at installation and system testing.
– (Ignored even when input.)
– (Ignored even when input.)
– (Ignored even when pressed.)
Reads continuously and outputs the data continuously.
The bar code reading continues in series. While reading the same bar code, output is not newly made. Outputs newly only when the data differ from the adjacent bar code.
Reads continuously and outputs the data continuously.
*1 Effective duration of reading
When the trigger input method is external trigger signal effective duration designation system or RS-232C command, effective duration setting is required beforehand. Effective duration is set by combining "effective duration" from 0 to 10 sec. and "minor setting" from 0 to 750 ms.
E.g. 1: When you want to set the effective duration to 2.5 sec., set the effective duration to 2 sec. and the
minor setting to 500 ms.
E.g. 2: When you want to set the effective duration to 0.7 sec., set the effective duration to 0 sec. and the
minor setting to 700 ms.
E.g. 3: When you want to set the effective duration to 10.0 sec., set the effective duration to 10 sec. and the
minor setting to 0 ms.
Effective duration setting method p.70
V500-R521B2/C2
36
User’s Manual
Page 36
Function Explanation
*2 Reading operation
Presence of the READ OK/NG signal output differs according to the reading operation setting. (READ OK/NG signal output is only for V500-R521B1)
In case of single reading and plural reading:
When reading succeeded: OK signal is output. When reading failed: NG signal is output.
In case of continuous reading:
OK or NG signal after reading is not output.
READ OK/NG signal output p.28
Section 3
Section 3 Explanation of Reading System
V500-R521B2/C2
User’s Manual
37
Page 37
Section 3 Function Explanation
Operation Flow Chart
Basic operation flow chart
This clause explains steps of "Power on > Reading > Data output" in case of trigger reading.
In case of single reading
Power on
Section 3 Operation Flow Chart
Wait for the
reading trigger
Laser radiation
Repeat
Reading process execution
Is reading
succeeded?
Laser beam goes out
READ OK LED illuminates
Is reading trigger end?
Laser beam goes out
READ NG LED illuminates
(*1)
Has reading
effective duration
passed?
(*2)
Repeat
Process when reading succeeded
*1 When the trigger by a command is used, ignore this clause. *2 In case of trigger controlled system (reads while the trigger is ON), consider that the reading effective duration
is set to 0.
V500-R521B2/C2
38
User’s Manual
Reading data output
Process when reading failed
Repeat
Process when reading failed
Page 38
In case of plural reading
Power on
Wait for the
eading trigger
Section 3
Function Explanation
Laser radiation
Reading process execution
Is reading
succeeded?
Is the data
differ from the previous
reading?
READ OK LED illuminates
Reading data output
Process when reading succeeded
Repeat
Repeat
Is reading trigger end?
(*1)
Has reading effective
duration passed?
(*2)
Laser beam goes out
Is reading
succeeded even just
once?
Section 3 Operation Flow Chart
*1 When the trigger by a command is used, ignore this clause. *2 In case of trigger controlled system (reads while the trigger is ON), consider that the reading effective duration
is set to 0.
Repeat
READ NG LED illuminates
Process when reading failed
Process when reading failed
V500-R521B2/C2
User’s Manual
39
Page 39
Section 3 Function Explanation
In case of continuous reading
Power on
Wait for the
reading trigger
Laser radiation
Repeat
Section 3 Operation Flow Chart
Reading process execution
Is reading
succeeded?
Is reading trigger
end? (*1)
READ OK LED illuminates
Reading data output
Process when reading succeeded
Has reading
effective duration
passed?
(*2)
Laser beam goes out
*1 When the trigger by a command is used, ignore this clause. *2 In case of trigger controlled system (reads while the trigger is ON), consider that the reading effective duration
is set to 0.
V500-R521B2/C2
40
User’s Manual
Repeat
Repeat
Is reading
succeeded even
just once?
READ NG LED illuminates
Process when reading failed
Process when reading failed
Page 40
Function Explanation
Communication protocol
There are following two types of system to transmit the data read by the bar code reader to the upper equipment.
Nonprocedural system (no protocol system)
The bar code reader transmits the data to the upper equipment and ends.
Bar code reader V500-R521
Data
Upper equipment
End
Section 3
Section 3 Operation Flow Chart
ACK/NAK system
This bar code reader waits for the upper equipment response after transmitting the data. When ACK (06H) 1 byte is received from the upper equipment, buzzer sounds indicating the normal finishing and ends data transmission.
Bar code reader V500-R521
Data
Upper equipment
When NAK (15H) 1 byte is received from the upper equipment data is transmitted again. When the time-up time comes which is set beforehand, the time-up buzzer sounds and the data transmission ends.
Bar code reader V500-R521
End
Data
Upper equipment
Data
Data
V500-R521B2/C2
User’s Manual
41
Page 41
Section 3 Function Explanation
Communication timing chart
This section explains the indication timing of the buzzer and LED indication.
In case when reading OK (single reading)
Trigger
input (*1)
Laser
radiation
Section 3 Operation Flow Chart
Reading
operation
Buzzer,
LED
Communi-
cation
*1 You can change the setting for the trigger input logic.
p.53
Time Description
T0 Trigger ON time. (When effective duration is designated, consider it as effective duration.)
T1 Chattering prevention time. (5 ms)
T2 Buzzer and indication LED illumination time. (Initial value: 200 ms, changing allowed)
T3 Trigger signal minimum OFF time. Be sure to set 30 ms or more.
T4 Communication time. Differs according to communication condition.
Reading
• In case of continuous reading and plural reading, laser is always radiating during trigger input is ON (or during reading effective duration). Concept of T0 to T4 other than this is the same as the case of single reading.
• A rough guide of reading time As this bar code reader is approx. 500 decode/sec., decode process time for once is 2 ms. In case of plural time conformance, "2 ms x (conformance time + 1)". However, it differs according to the reading bar code condition (dirt or thin spot, etc.)
• Concept of communication time
Communication time (ms) =
(Data length) + (1: In case when parity exists) + (Number of stop bit)
V500-R521B2/C2
42
User’s Manual
(Communication speed)
(Number of digit of transmission data +
x
Number of header characters + Number of footer characters) x 10
3
Page 42
In case when reading NG (single reading)
Trigger
input (*1)
Laser
radiation
Section 3
Function Explanation
Reading
operation
Buzzer,
LED
Communi-
cation
*1 You can change the setting for the trigger input logic.
Reading
p.57
Time Description
T0 Trigger ON time. (When effective duration is designated, consider it as effective duration.)
T1 Chattering prevention time (5 ms)
T2 Buzzer and indication LED illumination time. (Initial value: 200 ms, changing allowed)
T3 Trigger signal minimum OFF time. Be sure to set 30 ms or more.
T4 Communication time. Differs according to communication condition.
Section 3 Operation Flow Chart
• In case of continuous reading and plural reading, laser is always radiating during trigger input is ON (or during reading effective duration). Concept of T0 to T4 other than this is the same as the case of single reading.
• Concept of communication time
Communication time (ms) =
(Data length) + (1: In case when parity exists) +
(Number of stop bit)
(Communication speed)
(Number of digit of transmission data +
x
Number of header characters + Number of footer characters) x 10
V500-R521B2/C2
User’s Manual
3
43
Page 43
Section 3 Function Explanation
Concept of moving direction/line speed
When reading a moving bar code, fully investigate from the following viewpoint.
Confirmation of the timing chart
Duration from the reading trigger and outputting the data of actual reading differs according to condition.
Operation Flow Chart p.38
Confirmation of trigger input timing
Section 3 Operation Flow Chart
trigger signal is important. Input the external trigger signal allowing enough timing considering the moving speed (moving distance) of the bar code.
When constructing the system to read the moving bar code, input timing of the external
When the timing is too slow...
The bar code is already
passed and cannot read.
Photoelectronic sensor
Checking the tack timing
In case when bar codes come continuously, calculate how close the bar codes may come, considering above two points.
V500-R521B2/C2
44
User’s Manual
Page 44
Section 3
Function Explanation
Moving direction of a bar code
Stability of reading differs according to the moving direction against the scanning direction. As the appropriate direction differs according to the size of a label, investigate when installing.
Scanning direction
Section 3 Operation Flow Chart
Bar code moving direction Scanning range
Whole height of a bar code is scanned. In case of tall size label, this direction is stable.
A part of the height of a bar code is scanned. In case of short size label, this direction is stable.
V500-R521B2/C2
User’s Manual
45
Page 45
Section 3 Function Explanation
Communication Data Format
This section explains about communication data format of the bar code reader and the upper equipment.
Section 3 Communication Data Format
Upper equipment
Reading data output
Input command
Reading trigger input by RS-232C command
Reading trigger command format is as shown below.
or
. Set command input
Reading condition set command can be transmitted from the upper equipment. Format is as follows.
Bar code reader V500-R521
Command
(In case of one character, m1 only)
For details of command, refer to Section 4.
p.56
V500-R521B2/C2
46
User’s Manual
Page 46
Section 3
Function Explanation
Data output format when reading succeeded
When bar code reading is succeeded, following data is transmitted to the upper equipment.
Header
Number
Output item Description Initial setting
Header
Number of
digit
Footer
Letter strings to add at the head of transmitted data. Max 4 arbitrary characters can be set.
Number of digit of the read data is output in two-digit ASCII code. Whether or not to output the number of digit is selectable.
Letter strings to add at the end of transmitted data. Max 4 arbitrary characters can be set.
Data of read bar code
Footer
No header
No number of digit output
CR (0DH)
Setting methods of whether to output header, number of digit and footer p.79
Process when reading failed
Output format differs according to what is set to "reading failed process".
Selection of output format when reading failed Remarks
No process Nothing is transmitted
BR [CR] is transferred
[STX]?[ETX], [STX]>[ETX] is transferred ?: When it is judged as no bar code
?[CR], >[CR] are transferred
[CAN] [CR] are transferred
[STX] [CAN] [ETX] are transferred
>: In cases other than above
Section 3 Communication Data Format
Setting method p.68
V500-R521B2/C2
User’s Manual
47
Page 47
Section 3 Communication Data Format
Section 3 Function Explanation
Data transfer contents of each reading code type
Reading code Description
UPC-A You can select whether or not to transfer the head character "0" for
transfer digit number adjustment and check digit C/D. ("0" is the additional character combining with C/D to adjust the number of digit to be in accordance with EAN-13.) 0 S X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 C/D S: Number system character (Automatically decided according to the combination of each character of X1 to X10.)
UPC-E You can select whether or not to transfer the head character "0" for
transfer digit number adjustment and check digit C/D. ("0" is the additional character combining with C/D to adjust the number of digit to be in accordance with EAN-13.) 0 S X1 X2 X3 X4 X5 X6 C/D S: Number system character (Automatically decided according to the combination of each character of X1 to X10.)
EAN Reading data (8-digit or 13-digit) is transferred as it is.
ITF, STF (2 of 5 bar) Transfers in the order from the next character of the start code to the
character before the stop code. (Start code and stop code are not transferred.)
NW-7, CODE39 You can select whether or not to transfer the start code and stop code.
When the start code and stop code is permitted to transfer, you can select whether the transferred start/stop code of NW-7 is in lower-case "a/b/c/d" or in upper-case "A/B/C/D". Transfer start/stop code of CODE39 is "*".
EAN128 Add a control character "C1" (ASCII code 5D, 43, 31) which indicates
EAN 128, at the head of the transfer data. Also, FNC1 character, as a separating character, is replaced to GS (ASCII code 1DH) character and transferred.
Setting method p.63
V500-R521B2/C2
48
User’s Manual
Page 48
Function Explanation
Test Reading Function
You can check how stably the subject bar code can be read. Read a bar code at resting state for one sec. and calculate the reading rate.
To enter reading measurement mode using a command
1. Install the bar code at a reading position.
Section 3
2. Enter command "7U".
Mode enters to reading rate measurement mode. Reading rate of every one sec. is measured.
3. To finish the reading rate measurement mode, enter reset command "Z1" or re-start the
bar code reader.
Return to the normal measurement mode.
Do not execute write command "Z2" to nonvolatile memory. A sample setting condition is overwritten and stored, which erases the already set reading condition.
To enter reading measurement mode using a TEST button on the
back side
1. Install the bar code at a reading position.
2. Keep pressing the TEST button until the buzzer (tones repeating "Sol" and "Do")
sounds.
Section 3 Test Reading Function
3. Press the TEST button once.
Press the TEST button within 10 sec. after the buzzer sounds. After 10 sec. or more have passed, it returns to the original state.
Mode entered to reading rate measurement mode. (Reading rate of every one sec. is measured according to the reading condition of factory default.)
4. To finish the reading rate measurement mode, enter reset command "Z1" or re-start the
bar code reader.
Return to the normal measurement mode.
V500-R521B2/C2
User’s Manual
49
Page 49
Section 3 Function Explanation
Output format
Reading rate of every one sec. is output to the upper equipment, while in reading rate measurement mode.
Number of decoded time in one sec.
Of those, correct reading data (*) detected rate = Reading rate Correct reading data (*)
Data, which detected most during measurement mode, is “correct reading data”.
Section 3 Test Reading Function
Communication data format
A rough guide of reading rate
The LED illumination patter on the back side changes according to the result of reading rate.
Reading rate READ NG LED READ OK LED Description
76~100 %
51~75 %
26~50 %
0~25 %
Reading is possible without problem.
When the bar code is at still state when read, reading is possible without problem. However, when the target bar code is moving, reading may be failed according to speed.
There is a possibility to fail even reading at still state. Check if the installation location and angle of the bar code reader is appropriate once more.
Reading is not stable. Check if there is no dirt or lack on the bar code. Check if the installation location and angle of the bar code reader is appropriate once more.
LED indication
: Lights out : Blink : Illuminate
V500-R521B2/C2
50
User’s Manual
Page 50
Section 4 Setting Method
This section explains about setting methods using a menu sheet and entering command from the upper equipment.
How to Use Menu Sheet/Command 52
Menu Sheet/Command List 56
Section 4 Setting Method
V500-R521B2/C2
User’s Manual
51
Page 51
Section 4 Setting Method
How to Use Menu Sheet/Command
There are following two setting methods for the bar code reader. Select either method according to the condition.
Read the menu sheet. This method reads the menu sheet of the function you want to set.
Input a command from the upper equipment.
Read the menu sheet
Section 4 How to Use Menu Sheet/Command
The menu sheet is a special bar code used to set this bar code function. Setting can be changed by reading this menu sheet.
Setting method Description
It is convenient for the initial setting and when testing.
This method inputs a command from the upper equipment. It is convenient when changing setup according to the type of the bar code.
1. Read "Z7" of the menu sheet that means setting start/end.
Buzzer sounds continuously. The bar code reader entered setting mode.
2. Read "UA" on the menu sheet that means to return to factory default setting.
3. Read the item on the menu sheet you want to change setting.
Menu Sheet/Command List p.56
4. To finish setting, read "Z7" on the menu sheet for setting start/end, again.
Buzzer sound stops and returns to normal mode.
V500-R521B2/C2
52
User’s Manual
Page 52
Section 4
Setting Method
How to create menu sheet
The used menu sheet is a code system of CODE39. However, the code is special, using start code and stop code for a space mark. (Normally "*") You can create a menu sheet using bar code creation software available in the market, as shown below.
E.g.: When creating a menu sheet "A3"
Create "* A3 *" and cut the parts of "*" with scissors to create the menu sheet "A3".
Cutting off section
Cutting off section
Section 4 How to Use Menu Sheet/Command
V500-R521B2/C2
User’s Manual
53
Page 53
Section 4 Setting Method
Input command from the upper equipment
1. Transmit the command character strings of the function you want to set.
Section 4 How to Use Menu Sheet/Command
Upper equipment
Transmit command character strings.
Command
(In case of one character, m1 only)
Menu Sheet/Command List p.56
During the bar code reader is processing command, it notifies externally that it is in processing mode turning off the RS signal line. When the RS signal line is not connected, interval between inputting commands should be taken sufficiently.
Bar code reader V500-R521
2. Transmits "Z2", in order to write the set data on the nonvolatile memory in the bar code
reader.
Be sure to write when a condition is set by inputting command from the upper equipment. When you turn off the power without writing the setting in the memory, the set content may be deleted.
V500-R521B2/C2
54
User’s Manual
Page 54
Section 4
Setting Method
Transmission method of the command by designating values and characters is explained as follows.
E.g. 1: Set "AB [CR]" on header. (When designating codes directly)
Transmit a header setting command.
Transmit a character "A".
Transmit a character "B".
Transmit CR code.
E.g. 2: Set "AB [CR]" on header. (When designating hexadecimal number directly)
Transmit a header setting command.
Transmit 41 "A" in hexadecimal number.
Transmit 42 "B" in hexadecimal number.
Transmit CR code.
"00H" (zero) cannot be designated as header or footer. It is regarded as end character. Characters until just before 00H are valid.
E.g. 3: Reading number of digit is set to "8-digit" and "12-digit".
Section 4 How to Use Menu Sheet/Command
Transmit the number of digit command "A".
Transmit "8-digit". (Input in decimal number. Numbers are fix to 2-digit.)
Transmit the number of digit command "B".
Transmit "12-digit". (Input in decimal number. Numbers are fix to 2-digit.)
V500-R521B2/C2
User’s Manual
55
Page 55
Section 4 Setting Method
Menu Sheet/Command List
Groups are classified as follows. Please refer to the corresponding pages.
Setting start/end according to menu sheets p.57
Write setting contents on the nonvolatile memory p.57
Reset p.57
Setting related to external trigger signal p.57
Return to factory default setting p.58
Collective setting p.59
Setting of reading permission and prohibition p.61
Detail setting for reading code p.63
Setting for reading conformance p.66
Section 4 Menu Sheet/Command List
Setting for reading system p.67
Setting for failed reading p.68
Setting for number of reading digit p.69
Setting for reading effective duration p.70
Setting related to LED p.72
Settings related to duration of buzzer sound and volume p.73
Setting related to READ OK/NG signal output (Only when V500­R521B2 is used)
Setting related to communication condition p.77
Setting related to communication protocol p.78
Setting for header, footer and number of reading digit p.79
Setting related to test reading p.79
Direct code designation p.80
Setting related to sorting read p.83
Setting item Reference
p.75
V500-R521B2/C2
56
User’s Manual
Page 56
Section 4
Setting Method
Setting start/end according to menu sheets
When setting using menu sheets, read this menu sheet with the bar code to start and end the setting.
Menu sheet Command
Setting start/end according to menu sheets None
Write setting contents on the nonvolatile memory
Be sure to write when a condition is set by inputting command from the upper equipment. When you turn off the power without writing the setting in the memory, the set content may be deleted.
Menu sheet Command
Write the contents set with a command in the nonvolatile memory.
(No menu sheet)
Z2
Section 4 Menu Sheet/Command List
Reset
Return to the setting, which is already written in the nonvolatile memory.
Menu sheet Command
Reset Z1
Setting related to external trigger signal
Select positive logic/negative logic of the external trigger signal.
Menu sheet Command
External trigger signal Positive logic (H active) 8A
External trigger signal Negative logic (L active)
8B
(Factory default setting)
V500-R521B2/C2
User’s Manual
57
Page 57
Section 4 Setting Method
Section 4 Menu Sheet/Command List
Return to factory default setting
Menu sheet Command
Factory default setting UA
Initial setting
Item Setting content
Types of code, which is possible to read EAN/UPC, CODE39, NW-7, STF, ITF J1+R4+B2+B3
Number of reading digits No designated number of digits H0 Detail condition CODE39 detail setting Invalid C/D of CODE39 C0
Transfer C/D of CODE39 C2 Transfer ST/SP of CODE39 D1
NW-7 detail setting Invalid C/D of NW-7 F7
Transfer C/D of NW-7 F5 Transfer ST/SP of NW-7 (abcd/abcd) F4
ITF/STF detail setting Invalid C/D of ITF/STF G0
Transfer C/D of ITF/STF G2
Reading condition
Communication condition
LED illumination LED illumination time after decoding is 200 ms. T5 Buzzer sound Buzzer sound duration after decoding is 200 ms. W5 Buzzer sound volume Max. T0 Buzzer frequency 3 kHz, 2 kHz W2 External trigger signal Negative logic (L active) 8B READ OK/NG signal output Output 8Q READ OK/NG signal output system Trigger synchronous system, positive logic
Reading system Trigger reading S8 Reading operation Single reading S0 Reading valid time Trigger + 2 sec. Y2 Number of reading
coincidence Communication speed 9600 bps K6 Data length 8-bit L1 Parity None L2 Stop bit length 1-bit L5 Header None 1Y Footer CR 1Z+1C Transfer number of
digits RS/CS control None P0 CS waiting time Infinity I0 Communication
protocol Process when reading
is NG
Twice (Verification: once) X1
Not transferred 2Z
No protocol system P5
No process (Nothing is transferred) 5E
(H active)
Corresponding
command
+R7+R8
8C
V500-R521B2/C2
58
User’s Manual
Page 58
Section 4
Setting Method
Collective setting
Collective setting of conditions appropriate for connection of programmable controller (UB) and for connection of multi-drop using link unit (UC) is allowed.
Menu sheet Command
Setting of programmable controller connection UB
Hatching parts are the changed point from the factory default setting. Collective setting
Item Setting content
Types of code, which is possible to read EAN/UPC, CODE39, NW-7, STF, ITF J1+R4+B2+B3
Number of reading digits No designated number of digits H0 Detail condition CODE39 detail setting Invalid C/D of CODE39 C0
Transfer C/D of CODE39 C2 Transfer ST/SP of CODE39 D1
NW-7 detail setting Invalid C/D of NW-7 F7
Transfer C/D of NW-7 F5 Transfer ST/SP of NW-7 (abcd/abcd) F4
ITF/STF detail setting Invalid C/D of ITF/STF G0
Transfer C/D of ITF/STF G2
Reading condition
Communication condition
LED illumination LED illumination time after decoding is 200 ms. T5 Buzzer sound Buzzer sound duration after decoding is 200 ms. W5 Buzzer sound volume Max. T0 Buzzer frequency 3 kHz, 2 kHz W2 External trigger signal Negative logic (L active) 8B READ OK/NG signal output Output 8Q READ OK/NG signal output system Trigger synchronous system, positive logic
Reading system Trigger reading S8 Reading operation Single reading S0 Reading valid time Trigger + 2 sec. Y2 Number of reading
coincidence Communication speed 9600 bps K6 Data length Parity Stop bit length Header None 1Y Footer CR 1Z+1C Transfer number of digits RS/CS control None P0 CS waiting time Infinity I0 Communication
protocol Process when reading is NG
Twice (Verification: once) X1
7-bit L0 Even number L6 2-bit L6
Not transferred 2Z
No protocol system P5
Transfer ? (CR), > (CR) 5H
(H active)
Corresponding
command
+R7+R8
8C
Section 4 Menu Sheet/Command List
V500-R521B2/C2
User’s Manual
59
Page 59
Section 4 Setting Method
Section 4 Menu Sheet/Command List
Menu sheet Command
Setting for connecting link unit (V700-L12) UC
Hatching parts are the changed point from the factory default setting. Collective setting
Item Setting content
Types of code, which is possible to read EAN/UPC, CODE39, NW-7, STF, ITF J1+R4+B2+B3
Number of reading digits No designated number of digits H0 Detail condition CODE39 detail setting Invalid C/Dof CODE39 C0
Transfer C/D of CODE39 C2 Transfer ST/SP of CODE39 D1
NW-7 detail setting Invalid C/D of NW-7 F7
Transfer C/D of NW-7 F5 Transfer ST/SP of NW-7 (abcd/abcd) F4
ITF/STF detail setting Invalid C/D of ITF/STF G0
Transfer C/D of ITF/STF G2
Reading condition
Communication condition
LED illumination LED illumination time after decoding is 200 ms. T5 Buzzer sound Buzzer sound duration after decoding is 200 ms. W5 Buzzer sound volume Max. T0 Buzzer frequency 3 kHz, 2 kHz W2 External trigger signal Negative logic (L active) 8B READ OK/NG signal output Output 8Q READ OK/NG signal output system Trigger synchronous system, positive logic
Reading system Trigger reading S8 Reading operation Single reading S0 Reading valid time Trigger + 2 sec. Y2 Number of reading
coincidence Communication speed 9600 bps K6 Data length 8-bit L1 Parity Stop bit length 1-bit L5 Header None 1Y Footer CR 1Z+1C Transfer number of
digits RS/CS control None P0 CS waiting time Infinity I0 Communication
protocol Process when reading
is NG
Twice (Verification: once) X1
Even number L3
Not transferred 2Z
No protocol system P5
Transfer ? (CR), > (CR) 5H
(H active)
Corresponding
command
+R7+R8
8C
V500-R521B2/C2
60
User’s Manual
Page 60
Section 4
Setting Method
Setting of reading permission and prohibition
Select bar code types of which subject to read. Prohibit bar codes, which is not subject to read, from reading in order to increase reading reliability.
Menu sheet
Reading permission only for UPC-A/E
(Factory default setting)
Reading permission only for EAN13/8 J4 Reading permission for EAN13/8
Reading permission only for CODE39 A2 Reading permission for CODE39
Command
J1 Reading permission for UPC-A/E R1
(Factory default setting)
Menu sheet
Command
R4
B2
Section 4 Menu Sheet/Command List
(Factory default setting)
Reading permission only for NW-7 A3 Reading permission for NW-7
(Factory default setting)
Reading permission only for ITF J8 Reading permission for ITF
(Factory default setting)
Reading permission only for STF J7 Reading permission for STF
(Factory default setting)
Reading permission only for CODE93 A5 Reading permission for CODE93 B5
B3
R8
R7
V500-R521B2/C2
User’s Manual
61
Page 61
Section 4 Setting Method
Section 4 Menu Sheet/Command List
Menu sheet
Reading permission only for CODE128 A6 Reading permission for CODE128 B6
Reading prohibition for EAN/UPC 4A
Reading prohibition for CODE39 4H
Reading prohibition for NW-7 4I
Reading prohibition for STF 4K
Command
Menu sheet
Command
Reading prohibition for ITF 4L
Reading prohibition for CODE93
(Factory default setting)
Reading prohibition for CODE128
(Factory default setting)
Reading prohibition for all types 4Z
4M
4N
V500-R521B2/C2
62
User’s Manual
Page 62
Section 4
Setting Method
Detail setting for reading code
Conditions of detail reading code such as whether check digit (C/D) is used or start code/stop code (ST/SP) is transmitted are set.
UPC-A
Menu sheet
Output UPC-A in 13-digit
(Factory default setting)
Output UPC-A in 12-digit (without 0 in the beginning)
Command
E2 Output UPC-A in 12-digit (without C/D) E4
E3 Output UPC-A in 11-digit (without 0 in
the beginning or C/D)
Menu sheet
Command
E5
Section 4 Menu Sheet/Command List
UPC-E
Menu sheet
Output UPC-E in 8-digit E6 Output UPC-E in 7-digit (without C/D)
Output UPC-E in 7-digit (without 0 in the beginning)
Command
(Factory default setting)
E7 Output UPC-E in 6-digit (without 0 in
the beginning or C/D)
Menu sheet
CODE39
Menu sheet
Invalid C/D of CODE39
Command
C0 Not transfer ST/SP of CODE39 D0
Menu sheet
Command
E8
E9
Command
(Factory default setting)
Valid C/D of CODE39 C1 Transfer ST/SP of CODE39
(Factory default setting)
D1
V500-R521B2/C2
User’s Manual
63
Page 63
Section 4 Setting Method
Section 4 Menu Sheet/Command List
Menu sheet
Transfer C/D of CODE39
(Factory default setting)
Not transfer C/D of CODE39 C3 CODE39 1-digit reading prohibition
Command
C2 CODE39 1-digit reading permission 7C
(Factory default setting)
Menu sheet
NW-7
Menu sheet
Invalid C/D of NW-7
(Factory default setting)
Valid C/D of NW-7 (modulus 16) F9 Transfer ST/SP of NW-7 (abcd/abcd)
Command
F7 Transfer ST/SP of NW-7 (ABCD/
ABCD)
Menu sheet
Command
7D
Command
F3
F4
(Factory default setting)
Transfer C/D of NW-7
(Factory default setting)
Not transfer C/D of NW-7 F6 NW-7 1-digit reading prohibition
Not transfer ST/SP of NW-7 F0
F5 NW-7 1-digit reading permission 7K
(Factory default setting)
7L
V500-R521B2/C2
64
User’s Manual
Page 64
Section 4
Setting Method
ITF/STF
Menu sheet
Invalid C/D of ITF/STF
(Factory default setting)
Valid C/D of ITF/STF G1 ITF/STF 2-digit reading permission 7M
Command
G0 Not transfer C/D of ITF/STF G3
Menu sheet
Command
Transfer C/D of ITF/STF
(Factory default setting)
G2 ITF/STF 2-digit reading prohibition
(Factory default setting)
7N
CODE128
After executing CODE128 reading permission command (B6), execute commands as shown below.
Menu sheet
All reading permission including EAN128
(Factory default setting)
EAN128 (Reading specification) p.126
Command
G5 Reading permission only for EAN128 in
CODE128
Menu sheet
Command
G6
Section 4 Menu Sheet/Command List
V500-R521B2/C2
User’s Manual
65
Page 65
Section 4 Setting Method
Setting for reading conformance
When decoded results coincide for the set number of conformance, the read results are output to RS-232C interface. Verification system is AND verification (Continuous conformance system). (Change prohibition)
Section 4 Menu Sheet/Command List
Menu sheet
Reading conformance twice (Verification: once)
(Factory default setting)
Reading conformance 3 times (Verification: 2 times)
Reading conformance 4 times (Verification: 3 times)
Command
X1 Reading conformance 5 times
(Verification: 4 times)
X2 Reading conformance 6 times
(Verification: 5 times)
X3
Menu sheet
Command
7R
7S
V500-R521B2/C2
66
User’s Manual
Page 66
Setting for reading system
Set the reading system.
Explanation of Reading System p.36
Reading system
Menu sheet
Full-time reading S7 Trigger reading
Command
(Factory default setting)
Menu sheet
Section 4
Setting Method
Command
S8
Reading operation
Menu sheet
Single reading
(Factory default setting)
Plural reading S1
Command
S0 Continuous reading S2
Menu sheet
Command
Section 4 Menu Sheet/Command List
V500-R521B2/C2
User’s Manual
67
Page 67
Section 4 Setting Method
Setting for failed reading
Process for failed reading is set.
Section 4 Menu Sheet/Command List
Menu sheet
When reading failed: no process
(Factory default setting)
When reading failed: Transfer BR [CR] 5F When reading failed: Transfer [CAN]
When reading failed: Transfer [STX]?[ETX], [STX]>[ETX] (*)
* When it is judged as no bar code:?
In cases other than above: >
Command
5E When reading failed: Transfer ? [CR],
>[CR] (*)
[CR]
5G When reading failed: Transfer [STX]
[CAN] [ETX]
Menu sheet
Command
5H
5I
5J
V500-R521B2/C2
68
User’s Manual
Page 68
Section 4
Setting Method
Setting for number of reading digit
When the number of digit is fixed, designate the number of digit to improve reliability. For number of digit, two types (A and B) can be set. In case of the bar code including C/D, count the C/D as one digit.
Menu sheet
Number of digit is not designated.
(Factory default setting)
Designation of number of digit A (Bar code reading system) *1
Designation of number of digit B (Bar code reading system) *1
*1 After reading this menu sheet, read the bar code of the number of digit you want to register twice,
continuously. When the number of digit is one type, set A and B to the same setting.
*2 After transmitting this command, transmit the character string of the bar code you want to register,
continuously.
Command
None Designation of number of digit A *2
None Designation of number of digit B *2
None
Menu sheet
(No menu sheet)
(No menu sheet)
Command
7V
7W
p.54
Section 4 Menu Sheet/Command List
V500-R521B2/C2
User’s Manual
69
Page 69
Section 4 Setting Method
Section 4 Menu Sheet/Command List
Setting for reading effective duration
After inputting a trigger, set the time for the continuous reading. Effective duration is set by combining "effective duration" from 0 to 10 sec. and "minor setting" from 0 to 750 ms. This is set only in case when the reading system, which is required to set the effective duration, is selected.
Explanation of Reading System p.36
Menu sheet
Coupled with trigger (trigger + 0 sec.) Y0 Trigger +0 ms (minor setting)
Trigger + 1 sec. Y1 Trigger + 5.0 ms (minor setting) YB
Command
Menu sheet
(Factory default setting)
Command
YA
Trigger + 2 sec.
(Factory default setting)
Trigger + 3 sec. Y3 Trigger + 150 ms (minor setting) YD
Trigger + 4 sec. Y4 Trigger + 200 ms (minor setting) YE
Trigger + 6 sec. Y5 Trigger + 250 ms (minor setting) YF
Trigger + 8 sec. Y6 Trigger + 300 ms (minor setting) YG
Y2 Trigger + 100 ms (minor setting) YC
V500-R521B2/C2
70
User’s Manual
Page 70
Section 4
Setting Method
Menu sheet
Trigger + 10 sec. Y7 Trigger + 350 ms (minor setting) YH
Trigger + 400 ms (minor setting) YI Trigger + 600 ms (minor setting) YM
Trigger + 450 ms (minor setting) YJ Trigger + 650 ms (minor setting) YN
Trigger + 500 ms (minor setting) YK Trigger + 700 ms (minor setting) YO
Command
Menu sheet
Command
Section 4 Menu Sheet/Command List
Trigger + 550 ms (minor setting) YL Trigger + 750 ms (minor setting) YP
V500-R521B2/C2
User’s Manual
71
Page 71
Section 4 Setting Method
Setting related to LED
When reading succeeded, READ OK LED illuminates and when reading failed, READ NG LED illuminates. Duration of illumination is allowed to set.
Section 4 Menu Sheet/Command List
Menu sheet
LED does not illuminate after decode. T4 The LED illuminates for 400 ms after
The LED illuminates for 100 ms after decoding.
The LED illuminates for 200 ms after decoding.
(Factory default setting)
Command
decoding.
T8 The LED illuminates for 800 ms after
decoding.
T5
Menu sheet
Command
T6
T7
V500-R521B2/C2
72
User’s Manual
Page 72
Section 4
Setting Method
Settings related to duration of buzzer sound and volume
When reading succeeded, buzzer sounds. Sound volume, frequency and duration of the buzzer are allowed to set. (When sorting read function is used, buzzer sounds when reading result is disagree with the registered data.) Buzzer sound volume Duration of buzzer
Menu sheet
Buzzer sound volume; max.
(Factory default setting)
Buzzer sound volume; middle or above T1 Buzzer sound duration after decoding;
Command
T0 Buzzer sound duration after decoding;
10 ms
50 ms
Menu sheet
Command
W8
W7
Section 4 Menu Sheet/Command List
Buzzer sound volume; middle or below T2 Buzzer sound duration after decoding;
100 ms
Buzzer sound volume; min. T3 Buzzer sound duration after decoding;
200 ms
(Factory default setting)
No buzzer sound after decoding W0 Buzzer sound duration after decoding;
400 ms
W4
W5
W6
V500-R521B2/C2
User’s Manual
73
Page 73
Section 4 Setting Method
Buzzer frequency
Buzzer sound frequency after decoding; 3 kHz
Menu sheet
Command
W1 Buzzer sound frequency after
decoding; 2 kHz, 3 kHz
Menu sheet
Command
W3
Section 4 Menu Sheet/Command List
Buzzer sound frequency after decoding; 3 kHz, 2 kHz
(Factory default setting)
W2
V500-R521B2/C2
74
User’s Manual
Page 74
Section 4
Setting Method
Setting related to READ OK/NG signal output (Only when V500-R521B2 is used)
When you want to output reading succeeded/failed to READ OK/NG signal, set the conditions of output system and duration, then execute "signal output (8Q)".
Output system p.28
Menu sheet
Signal output
(Factory default setting)
No signal output 8R Signal output one-shot duration; 40 ms 8J
Command
8Q Signal output one-shot duration; 30 ms 8I
Menu sheet
Command
Section 4 Menu Sheet/Command List
Signal output trigger signal synchronous system (positive logic)
(Factory default setting)
Signal output trigger signal synchronous system (negative logic)
Signal output one-shot system (positive logic)
Signal output one-shot system (negative logic)
8C Signal output one-shot duration; 50 ms 8K
8D Signal output one-shot duration; 60 ms 8L
8E Signal output one-shot duration; 70 ms 8M
8F Signal output one-shot duration; 80 ms 8N
Signal output one-shot duration; 10 ms 8G Signal output one-shot duration; 90 ms 8O
V500-R521B2/C2
User’s Manual
75
Page 75
Section 4 Setting Method
Section 4 Menu Sheet/Command List
Menu sheet
Signal output one-shot duration 20 ms 8H Signal output one-shot duration; 100 ms 8P
Command
Menu sheet
Command
V500-R521B2/C2
76
User’s Manual
Page 76
Setting related to communication condition
Section 4
Setting Method
Menu sheet
Communication speed; 300 bps K1 Data length; 7-bit L0
Communication speed; 600 bps K2 Data length; 8-bit
Communication speed; 1200 bps K3 No parity
Communication speed; 2400 bps K4 Parity even number L3
Command
Menu sheet
(Factory default setting)
(Factory default setting)
Command
L1
L2
Section 4 Menu Sheet/Command List
Communication speed; 4800 bps K5 Parity uneven number L4
Communication speed; 9600 bps
(Factory default setting)
Communication speed; 19200 bps K7 Stop bit; 2-bit L6
Communication speed; 38400 bps K8 Without RS/CS control
K6 Stop bit; 1-bit
(Factory default setting)
(Factory default setting)
With RS/CS control (BUSY/READY) P1
L5
P0
V500-R521B2/C2
User’s Manual
77
Page 77
Section 4 Setting Method
Setting related to communication protocol
Section 4 Menu Sheet/Command List
Menu sheet
Communication protocol: ACK/NAK system
Communication protocol: No protocol system
(Factory default setting)
ACK/NAK response waiting time: Infinite
(Factory default setting)
ACK/NAK response waiting time: 100 ms I5 CS waiting time: 400 ms I3
Command
P3 CS waiting time: Infinite
(Factory default setting)
P5 CS waiting time: 100 ms I1
I4 CS waiting time: 200 ms I2
Menu sheet
Command
I0
ACK/NAK response waiting time: 500 ms I6
ACK/NAK response waiting time: 1000 ms
I7
V500-R521B2/C2
78
User’s Manual
Page 78
Section 4
Setting Method
Setting for header, footer and number of reading digit
Format when outputting the reading result is set.
Data output format when reading succeeded p.47
Menu sheet
Collective setting of header (Applied to all codes)
Collective setting of footer (Applied to all codes)
Command
1Y Number of reading digit is not
transferred (Applied to all codes)
(Factory default setting)
1Z Number of reading digit is transferred
(Applied to all codes)
Setting related to test reading
Test reading function p.49
Menu sheet
Mode enters to reading rate measurement mode.
Command
7U
Menu sheet
Command
2Z
3Z
Section 4 Menu Sheet/Command List
(No menu sheet)
V500-R521B2/C2
User’s Manual
79
Page 79
Section 4 Setting Method
Direct code designation
Use to set character strings and values directly such as designation of header and footer or number of reading digit.
Menu sheet
"A" is set. 0A "I" is set. 0I
"B" is set. 0B "J" is set. 0J
Command
Menu sheet
Command
Section 4 Menu Sheet/Command List
"C" is set. 0C "K" is set. 0K
"D" is set. 0D "L" is set. 0L
"E" is set. 0E "M" is set. 0M
"F" is set. 0F "N" is set. 0N
"G" is set. 0G "O" is set. 0O
"H" is set. 0H "P" is set. 0P
V500-R521B2/C2
80
User’s Manual
Page 80
Section 4
Setting Method
Menu sheet
"Q" is set. 0Q "Z" is set. 0Z
"R" is set. 0R "0" is set. Q0
'"S" is set. 0S "1" is set. Q1
"T" is set. 0T "2" is set. Q2
Command
Menu sheet
Command
Section 4 Menu Sheet/Command List
"U" is set. 0U "3" is set. Q3
"V" is set. 0V "5" is set. Q5
"W" is set. 0W "6" is set. Q6
"Y" is set. 0Y "7" is set. Q7
V500-R521B2/C2
User’s Manual
81
Page 81
Section 4 Setting Method
Section 4 Menu Sheet/Command List
Menu sheet
"8" is set. Q8 ETX (03H) is set. 1B
"9" is set. Q9 CR (ODH) is set. 1C
STX (02H) is set 1A LF (0AH) is set. 1D
Command
Menu sheet
Command
V500-R521B2/C2
82
User’s Manual
Page 82
Section 4
Setting Method
Setting related to sorting read
Bar code data to read are registered in this bar code reader beforehand and only the registered bar codes are read using this function. When the read bar code does not coincide with the registered data, buzzer sounds. Up to 5 types of bar codes can be registered.
Menu sheet
Register one character each using command. (*1) Register with regular expression. (*1)
Command
7Y
Sorting read operation starts. UE
*1 Execute the command "UE" to start sorting read operation.
When you enter the command "UE", reading system and communication specification are set as follows. When sorting read function is used, do not change the setting basically. To change a part of communication condition, etc, change it after you input command "UE" and sorting read operation starts.
Item Setting content
Types of code, which is possible to read Reading permission for all types
Number of reading digits No designated number of digits
Reading system Reading trigger Valid (Not full-time reading but trigger is used)
Reading operation Single reading
Reading valid time Trigger + 2 sec.
Communication condition
Number of reading coincidence
Communication speed 9600 bps
Data length 8-bit
Parity None
Stop bit length 1-bit
Header None
Footer CR
Transfer number of digits Not transferred
RS/CS control None
CS waiting time Infinity
Communication protocol No protocol system
Process when reading is NG No process (Nothing is transferred)
Twice (Verification: once)
Section 4 Menu Sheet/Command List
V500-R521B2/C2
User’s Manual
83
Page 83
Section 4 Setting Method
Section 4 Menu Sheet/Command List
How to register one character each using command
Register the bar code one character each using the command "7Y". After registration, execute the command "UE" to start sorting read operation.
E.g.: When registering two bar codes, "a123a" and "* ABC *".
Transmit following characters in sequence.
Transmitted character strings Description
[ESC] 7 Y [CR] Label registration command
# 6 1 CR Designation of character string "a (61H)"
[ESC] Q 1 CR Designation of character string "1 (direct code)"
[ESC] Q 2 CR Designation of character string "2 (direct code)"
[ESC] Q 3 CR Designation of character string "3 (direct code)"
# 6 1 CR Designation of character string "a (61H)"
# 0 0 CR Separation
# 2 A CR Designation of character string "* (2AH)"
[ESC] 0 A CR Designation of character string" A (direct code)"
[ESC] 0 B CR Designation of character string "B (direct code)"
[ESC] 0 C CR Designation of character string "C (direct code)"
# 2 A CR Designation of character string "* (2AH)"
# 0 0 CR Separation
# 0 0 CR End of command
How to register data using regular expression
Width of registration data may extend by using regular expression. To use regular expression, use a setting command or "7Y" of the menu sheet. Max. 5 data can be registered. Number of byte of definition character is up to 200. Usable regular expression
Regular expression Description
? Arbitrary one character
! From 0 to arbitrary characters
(any number of characters)
[A|B|C|D•••] One character designated
(One character in the designated character)
[A-D] One character designated
(Character range described within a hyphen)
[A-D|0-5|X|8|Z] Mixed designation
A One character designation
[A] One character designation
[^A] One character negation designation
(One character that is not A)
[^A|B] One character negation designation
(One character that is not A nor B)
[^A-D] One character negation designation
(One character that is not A to D)
V500-R521B2/C2
84
User’s Manual
Page 84
Section 4
Setting Method
Application example
Registration data Description Reading data Determination Operation
[A|F]?QR A or F + one arbitrary character + QRABQR Coincide Reading
succeeded
F9QR Coincide Reading
succeeded
F9QF Inconsistency Reading failed
C9QR Inconsistency Reading failed
V?[^X-Z]! V + one arbitrary character + one
character other than X, Y, Z + arbitrary
E.g.: [A|F] ? When registering "Q R" and "V ?[^X - Z ] !" bar code, transmit following character strings in
sequence.
Transmitted character strings Description
ESC 7 Y CR Label registration command
# 5 B CR Designation of character string "(5BH)"
ESC 0 A CR Designation of character string "A (direct code)"
# 7 C CR Designation of character string "| (7CH)"
ESC 0 F CR Designation of character string "F (direct code)"
# 5 D CR Designation of character string "] (5DH)"
# 3 F CR Designation of character string "? (3FH)"
ESC 0 Q CR Designation of character string "Q (direct code)"
ESC 0 R CR Designation of character string "R (direct code)"
# 0 0 CR Separation
ESC 0 V CR Designation of character string "V (direct code)"
# 3 F CR Designation of character string "? (3FH)"
# 5 B CR Designation of character string "(5BH)"
# 5 E CR Designation of character string "^ (5EH)"
ESC 0 X CR Designation of character string "X (direct code)"
# 2 D CR Designation of character string "- (2DH)"
ESC 0 Z CR Designation of character string "Z (direct code)"
# 5 D CR Designation of character string "] (5DH)"
# 2 1 CR Designation of character string "[ ! (21H)"
# 0 0 CR Character string separation
# 0 0 CR End of command
VA3ABC Coincide Reading
succeeded
VA3 Coincide Reading
succeeded
VAZ123 Inconsistency Reading failed
Section 4 Menu Sheet/Command List
V500-R521B2/C2
User’s Manual
85
Page 85
Section 5 Example of System Configuration
This section explains about connection method with upper equipment.
Example of Connection with a PC 88
Example of Connection with Programmable Controller (CS1)
Example of Multi-drop Connection 92
How to Use Command Link Unit V700-L12 96
89
Section 5 Example of System Configuration
V500-R521B2/C2
User’s Manual
87
Page 86
Section 5 Example of System Configuration
Example of Connection with a PC
Example of connection with PC/AT compatible PC is explained.
Bar code reader
V500-R521C2
PC/AT compatible PC
Special cable V509-W011D
Power supply for bar code
S8VS-01505
AC 100 V
Section 5 Example of Connection with a PC
Wire (When V500-R521B2 is used)
Bar code reader side
Wiring
color
Brown TRIG
Yellow O K
Orange NG
Blue CS
Gray RS
White RD
Green SD
Red VCC
Black S.GND
Shield F.GND
Signal
name
Shield
Example of BASIC program
100 CLS 110 CLOSE #1 120 OPEN "COM:N81NN" AS #1 130 BCDATA$="" 140 AA$=INPUT$(1,#1) 150 IF AA$=CHR$(&H03) GOTO 170 160 BCDATA$=BCDATA$+AA$:GOTO 140 170 PRINT "READ DATA=" ; BCDATA$ 180 GOTO 130
Upper equipment side (Example of PC/AT compatible PC)
5VDC (Supplied from outside) 0V
Signal
name
-1 RD 2 SD 3 ER 4 SG 5 DR 6 CS 7 RS 8
-9
Shield Cover
Pin No.
V500-R521B2/C2
88
User’s Manual
Page 87
Section 5
Example of System Configuration
Example of Connection with Programmable Controller (CS1)
Connection with programmable controller CS1 (Made by OMRON) is explained.
Input unit C200H-ID212
Trigger Switch
Special cable CS1W-CN224
Programming console C200H-PRO27
Bar code reader
V500-R521C2
Power supply unit C200HW-PA204S
Special cable V509-W011
CPU unit CS1H-CPU64-V1
100 VAC
Power supply for bar code S8VS-01505
Connect the connection cable of this bar code reader to RS-232C port of the CPU unit.
Wire (When V500-R521B2 is used)
Bar code reader side
Wiring
color Brown TRIG Yellow OK
Orange NG
Blue CS
Gray RS
White RD
Green SD
Red VCC
Black S.GND
Shield F.GND
Signal
name
Shield
5VDC (Supplied from outside)
0V
CS1 RS-232C port
Signal
name
FG 1 SD 2 RD 3 RS 4 CS 5
-6
-7
-8
SG 9
Section 5 Example of Connection with Programmable Controller (CS1)
Pin No.
V500-R521B2/C2
User’s Manual
89
Page 88
Section 5 Example of System Configuration
Setting at bar code side
Set as follows, using UB command (collective setting for programmable controller connection).
p.59
Setting item Setting content Command
Communication speed 9600 bps (Same as initial setting)
Data length 7-bit L0
Parity Even number L3
Stop bit 2-bit L6
Header None (Same as initial setting)
Footer CR (Same as initial setting)
Reading valid time Trigger + 2 sec. Y2
Process when reading failed ?[CR] or > [CR] is transferred 5H
Section 5 Example of Connection with Programmable Controller (CS1)
Setting of CS1 side
For detail setting method, refer to the operation manual of your programmable controller.
Setting item Setting content
Dip switch of CPU unit OFF
PC system setting 160[8300]
161[0000]
164[000D]
165[0100]
DM setting Set [1B5A] to DM00100.
(Memorize "Z" of ASCII code)
V500-R521B2/C2
90
User’s Manual
Page 89
Section 5
Example of System Configuration
Example of program
When the trigger switch is turned on, the bar code reader starts reading operation and stores the read data to DM (data memory) of CS1. The content is displayed on the programming console. When the bar code cannot read within the duration which is set beforehand (2 sec. in this example), "?" or ">" is transmitted. To check the read data with the programming console, press "Clear > FUN > Monitor" in this order.
00000
00002
00006
00000
00101
A3920
A3920
DIFU (13) 00101
TXD (236)
DM00100
#0000 #0002
BSET (71)
#0000 DM00200 DM00220
RXD(235) DM00200
#0000
A393
MSG (46)
&0
DM0200
When the contact point 00000 is turned on, reading start command (Z) is transmitted to the bar code reader.
Section 5 Example of Connection with Programmable Controller (CS1)
When data is received from the bar code reader, the data is stored starting from the address DM00200 and displays the content on the programming console.
For the program command, refer to the operation manual of your programming console. (Items related to communication method by RS-232C nonprocedural system.)
V500-R521B2/C2
User’s Manual
91
Page 90
Section 5 Example of Multi-drop Connection
Section 5 Example of System Configuration
Example of Multi-drop Connection
When communication link unit V700-L12 (sold separately) is used, you can connect max. 31 sets of the bar code reader to one upper equipment. This is called multi-drop connection. Connection configuration differs according to the interface (RS-485 or RS-232C) of the upper equipment side. Example of connecting communication link unit (hereinafter referred to as "link unit") and the upper equipment using RS-485 is described in this section.
You can supply 5 V power to the bar code reader from V700-L12.
Upper equipment
PC/AT compatible PC
Communication converter K3SC
RS-232C
Communication link unit V700-L12
Special cable V509-W019
Bar code reader V500-R521C2
RS-485
Machine
No. 01
Power supply 24 VDC S8VS-03024
RS-485
External trigger Input terminal
Machine
No. 02
RS-485
Machine
No. 03
V500-R521B2/C2
92
User’s Manual
Page 91
Section 5
Example of System Configuration
Setting at bar code reader side
Set as follows, using UC command (collective setting for link unit connection).
p.60
Setting item Setting content Command
Communication speed 9600 bps (Same as initial setting)
Data length 8-bit (Same as initial setting)
Parity Even number L3
Stop bit 1-bit (Same as initial setting)
Header None (Same as initial setting)
Footer CR (Same as initial setting)
RS/CS control None P0
Process when reading is NG ? [CR] or > [CR] is transmitted 5H
Other setting Same as factory default
setting.
-
Setting at link unit V700-L12 side
Setting item Setting content Setting
Machine No. Set the machine No. differing in each link unit Set DIP-SW 1 to 5.
Communication speed
Transmission procedure
Connection check None DIP-SW9 is OFF
RS-485 termination resistance
* In case of connection example shown here, termination resistors of the machine No. 3 and the upper
equipment (interface converter) are turned ON.
Specification and wiring of the link unit p.93
9600 bps DIP-SW 6, 7 are OFF
Normal procedure (polling procedure) DIP-SW8 is OFF
2 sets on both sides of transmission path are turned ON (*)
In case when turned ON, DIP­SW10 is ON
Section 5 Example of Multi-drop Connection
V500-R521B2/C2
User’s Manual
93
Page 92
Section 5 Example of System Configuration
Operation flow chart
Each bar code reader reads bar codes when the trigger is input. Read data is transmitted to the unit and stored in a buffer inside the link unit. When the data export command (polling command) is transmitted from the upper equipment, the link unit transmits the stored read data to the upper equipment.
PC/AT compatible PC
Communication converter
Section 5 Example of Multi-drop Connection
Link unit
Bar code reader
Reading trigger
Bar code reader
Link unit
Polling
Data export of Machine
No. 1
Polling
Data export of Machine
No. 2
Machine
No. 01
Execution of
reading
Stores data
Link unit
Returns data
Machine
No. 02
Execution of
reading
Stores data Stores data
Link unit
Machine
No. 03
Execution of
reading
Polling
Data export of Machine
No. 3
Data export
End
V500-R521B2/C2
94
User’s Manual
Returns data
Link unit
Returns data
Page 93
Example of System Configuration
Communication format
Communication format used in this connection example is explained. For details, refer to the following page.
p.105
Reading trigger given from the upper unit
Section 5
(Machine No.)
$01 ESC Z $0D
(Check code)
E.g.: When a trigger is given to the bar code reader machine No. 2
$01 ESC Z $0D
02
(Check code)
Polling command given from the upper equipment
(Machine No.)
$01 DLE P $0D
E.g.: When exporting data of machine No. 2
$01 DLE P $0D
02
(Check code)
(Check code)
Reading data transmitted from the bar code reader
(Machine No.)
$01
E.g.: When the reading data of the machine No. 2 is "ABCDE"
$01 $0D
02ABCDE
E.g.: When the read data is not accumulated
Reading data
(Check code)
(Check code)
Section 5 Example of Multi-drop Connection
$0D
(Machine No.)
$01 7 4 $0D
Code indicating that there is no data
When the bar code reader setting is changed from the upper
equipment
(Machine No.)
$01 ESC (m1) $0D
Command character string
(Check code)
(Check code)
(m2)
V500-R521B2/C2
User’s Manual
95
Page 94
Section 5 Example of System Configuration
How to Use Command Link Unit V700-L12
V700-L12 is a communication link unit for communication relay of RS-232C output equipment such as bar code readers and RFID system. (Hereinafter refer to as "link unit".) It is used to connect plural sets of RS-232C output equipment to one port of the upper equipment.
Information only required for connection of the bar code reader and the link unit is described here. When used, be sure to read the operation manual of the link unit V700-L12.
Part names
Multi-connection port (RS-485) p.102
Operation indication lamp
Port for upper level connection (RS-232C)
p.100
ID connection port
p.104
Section 5 How to Use Command Link Unit V700-L12
Set DIP-SW (inside the cover) p.99
24 V power supply terminal (inside the cover)
p.98
Operation indication lamp Operation condition of the link unit is indicated with four LED.
LED Description RUN Illuminate during normal operation of the link unit. COMM Illuminate during data communication with the upper equipment. ID Illuminate during data communication with the bar code reader. ERR
Illuminate in the event of a failure during data communication with upper equipment or a bar code reader.
GR (frame ground) terminal is in the multi-connection port. D type grounding (former type 3 grounding) should be performed.
V500-R521B2/C2
96
User’s Manual
Page 95
Section 5
Example of System Configuration
General specification
Item Specification
Number of connected antenna set
Power voltage 24 VDC + 10 % -15 %
Power consumption 10 W or less
Insulation resistance 50 mM ohm or more (at 500 VDC mega), between power terminal bulk
Withstand voltage 100 VAC (50/60 Hz, 1 min), apply to power terminals and ground
Resistance to vibration 10 to 150 Hz, double amplitude 0.20 mm, vibration with acceleration of
Impact resistance Apply shock with acceleration of 150 m/s2, 3 times for each X, Y, Z
Ambient temperature At operation: 0 to +45 °C
Ambient humidity At operation and storage: 35 to 85 % RH (without due condensation)
Enclosure rating IP20 (IEC60529 Standard)
Ground D type grounding (former type 3 grounding)
Mass Approx. 185 g
1
blocs and ground terminals
terminals, and leak current must be 5 mA or less
15 m/s2, at each X, Y, Z direction 8 min. each, 10 sweeps applied, without abnormal
direction, total 18 times, without abnormality.
At storage: -15 to +50 °C (without freeze or dew condensation)
Section 5 How to Use Command Link Unit V700-L12
Communication function
Item Specification
Machine No. 01 to 31
Communication speed with the upper equipment
Data transmission procedure to the upper equipment
RS-485 termination resistance OFF (invalid)
48000/9600/19200/38400 bps
Normal procedure (polling procedure)
• When inputting data from the upper equipment, it outputs to the ID port immediately and transmits received reply to the upper equipment.
• When inputting data from the ID port, it waits for the inquire command and transmits data.
• In case of 1: N connection, this procedure is recommended.
Through procedure (immediate transmission system)
• When inputting data from the upper equipment, it outputs to the ID port immediately. It does not transmit the received reply to the upper equipment.
• When inputting data from the ID port, it transmits to the upper equipment immediately.
ON (valid)
DIP-SW is used for setting each function.
V500-R521B2/C2
User’s Manual
97
Page 96
Section 5 Example of System Configuration
Power supply
Open the cover of the upper side of the body. There is a power terminal.
Section 5 How to Use Command Link Unit V700-L12
24VDC
The terminal mounting screw size is M3. Use a crimping terminal which fits to M3 screw.
Shape Size
Fork type
6.0 mm or less
Round type
.0 mm or less
Connect 24 V power supply device. Recommended device
Manufacturer Model
OMRON Corporation S8VS-03024
Confirmation should be fully made if there is no mistake after wiring. Faulty wiring may be the cause of failure.
V500-R521B2/C2
98
User’s Manual
Page 97
Section 5
Example of System Configuration
Function setting
Set each function using the DIP-SW of the bar code reader.
RS-485 termination
Machine No.
Transmission procedure
Communication speed
Setting of machine No.
Machine
No.
01 OFF OFF OFF OFF OFF 17 OFFOFFOFFOFF ON 02 ON OFF OFF OFF OFF 18 ON OFF OFF OFF ON 03 OFF ON OFF OFF OFF 19 OFF ON OFF OFF ON 04 ON ON OFF OFF OFF 20 ON ON OFF OFF ON 05 OFF OFF ON OFF OFF 21 OFF OFF ON OFF ON 06 ON OFF ON OFF OFF 22 ON OFF ON OFF ON 07 OFF ON ON OFF OFF 23 OFF ON ON OFF ON 08 ON ON ON OFF OFF 24 ON ON ON OFF ON 09 OFF OFF OFF ON OFF 25 OFF OFF OFF ON ON 10 ON OFF OFF ON OFF 26 ON OFF OFF ON ON 11 OFF ON OFF ON OFF 27 OFF ON OFF ON ON 12 ON ON OFF ON OFF 28 ON ON OFF ON ON 13 OFF OFF ON ON OFF 29 OFF OFF ON ON ON 14 ON OFF ON ON OFF 30 ON OFF ON ON ON 15 OFFONONONOFF 31 OFFONONONON
16 ON ON ON ON OFF
1 2 3 4 5 1 2 3 4 5
DIP-SW
Machine
No.
Setting not
allowed
ON ON ON ON ON
resistance
(Not used when the bar code reader is connected.)
DIP-SW
Section 5 How to Use Command Link Unit V700-L12
Other setting
Setting item Initial setting Description
Communication speed
Transmission procedure
RS-485 termination resistance
9600 bps Communication speed between the link unit and the upper
equipment is set.
• 4800 bps: DIP-SW6 is set to ON, DIP-SW7 is set to OFF
• 9600 bps: DIP-SW6 is set to OFF, DIP-SW7 is set to OFF
• 19200 bps: DIP-SW6 is set to OFF, DIP-SW7 is set to ON
• 38400 bps: DIP-SW6 is set to ON, DIP-SW7 is set to ON
Normal procedure
OFF (invalid) Set whether to make RS-485 termination resistance valid. Turn
Set data transmission system to upper equipment.
• Normal procedure (polling procedure): OFF
• Through procedure (immediate transmission system): ON
on the link unit on both sides of transmission path. (When only one set is connected, turn it ON.)
V500-R521B2/C2
User’s Manual
99
Page 98
Section 5 Example of System Configuration
Upper connection port specification
A port to connect with the upper equipment using RS-232C. A dust cover is attached before shipping. Remove it when used.
Item Specification
Connector specification D-sub 9 pin Connector plug Lock screw: #4-40UNC
Cable length Max. 15 m
Communication system In compliance with RS-232C
Synchronous system Asynchronous system
Communication control system One-to-N procedure dedicated to OMRON
Communication speed 4800/9600/19200/38400 bps (Set with DIP-SW)
Character format (fixed) Start bit Data bit Parity bit Stop bit Total
1 8 None 1 10
Check code (Error detection system) FCS (Frame Check Sequence)/Vertical parity system
Pin arrangement
Connector cap is not conducting with GR (frame ground).
Section 5 How to Use Command Link Unit V700-L12
5 4
3 2
1
Pin No. Signal name Function Signal direction
1 - Not connected ­2 RD Received data Input 3 SD Transmission data Output 4 - Not connected ­5 SG Ground for signal ­6 - Not connected -
7RS
8 CS Transmission allowed Input 9 - Not connected -
Transmission request (Normally ON when operating)
Output
9 8
7 6
RS signal control from the upper equipment In case of 1: N connection with RS-232C interface of the upper equipment, the RS signal of the upper equipment should be input to the CS signal of the link unit. Turn OFF the RS signal within 15ms after data transmission is finished. This control should be performed for normal operation.
Turn ON only in case when data is transmitted from upper equipment. Upper side RS
Upper side SD
V500-R521B2/C2
100
User’s Manual
Within 15 ms
Page 99
Example of System Configuration
Wiring
Example of wiring when connecting with PC/AT compatible PC is explained. Cable length should be 15 m or less. Recommended parts
Model Manufacturer
Cable CO-MA-VV-SB 5PX28AWG Hitachi Cable, Ltd.
Connector Socket XM2D-0901 OMRON Corporation
Hood XM2S-0913 OMRON Corporation
Wiring method 1
PC/AT compatible PC
D-SUB 9 pin
Signal
name
RD 2 SD 3
SG 5
RS 7 CS 8
Pin No.
1
4
6
9
Link unit
D-SUB 9 pin
Pin No.
1 2RD 3SD 4 5SG 6 7RS 8CS 9
Section 5
Signal
name
Section 5 How to Use Command Link Unit V700-L12
*1
Wiring method 2
PC/AT compatible PC
D-SUB 9 pin
Signal
name
RD 2 SD 3
SG 5
RS 7 CS 8
*1 Ground the shield wire on either PC/AT compatible PC side or link unit side. *2 When CS function is used on PC side, a return line is required.
Pin No.
1
4
6
9
Pin No.
*2
*1
Link unit
D-SUB 9 pin
Signal
name 1 2RD 3SD 4 5SG 6 7RS 8CS 9
V500-R521B2/C2
User’s Manual
101
Page 100
Section 5 Example of System Configuration
Multi-connection port specification
When plural bar code readers are connected to one RS-232C port of the upper equipment, connect to a multi-connection port of other link unit. When the upper equipment has the RS-485 port, connect this port to act as upper connection port. However, when the multi-connection port is used as the upper connection port, the upper connection port (RS-232C) of the link unit cannot be used. GR (frame ground) terminal is also on this port.
Item Specification
Connector specification 5 pin special connector (accessory for the link unit)
Cable length Total length: Max. 1 km
Communication system In compliance with RS-485
Synchronous system Asynchronous system
Communication control system One-to-N procedure dedicated to OMRON
Communication speed 4800/9600/19200/38400 bps (Set with DIP-SW)
Character format (fixed) Start bit Data bit Parity bit Stop bit Total
1 8 None 1 10
Section 5 How to Use Command Link Unit V700-L12
Error detection system FCS (Frame Check Sequence)
Pin arrangement
5 4 3 2
1
Pin No. Signal name Function
5 - Short circuit with terminal 2 inside the circuit 4 + Short circuit with terminal 1 inside the circuit 3 GR Frame ground 2 - Short circuit with terminal 5 inside the circuit 1 + Short circuit with terminal 4 inside the circuit
When connecting with RS-485 interface of the upper equipment The upper equipment should be in data reception condition within 15 ms after data transmission. This control should be performed for normal operation.
GR (frame ground) terminal is in the multi-connection port. D type grounding (former type 3 grounding) should be performed.
V500-R521B2/C2
102
User’s Manual
0
Loading...