Omron GRT1 - 11-2007, SMARTSLICE - 11-2007, SmartSlice GRT1 Operation Manual

Slice I/O Units
Cat. No. W455-E1-06
SmartSlice GRT1 Series
OPERATION MANUAL
Operation Manual
Revised November 2007
iv
v
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or dam­age to property.
!DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury. Additionally, there may be severe property damage.
!WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury. Additionally, there may be severe property damage.
!Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Program­ming Device displays to mean Programmable Controller.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 2005
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, o
r
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission o
f
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con­stantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
vi
vii
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
1 Intended Audience. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvi
2 General Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvi
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvi
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvii
5 Application Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .xviii
6 EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xx
SECTION 1
Available Units and Features. . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Slice I/O Terminal Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 Available Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SECTION 2
Shared Specifications and Functions . . . . . . . . . . . . . . . . . . 11
2-1 Specifications Shared by the Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2-2 Unit Numbers and I/O Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-3 Functions Shared by all Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
SECTION 3
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3-2 Power Supply Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3-3 Connecting Turnback Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
SECTION 4
Digital I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4-2 Status Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4-3 I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4-4 Functions of Digital I/O Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
4-5 Maintenance Information Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4-6 Digital I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
SECTION 5
Analog I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
5-1 Overview of Analog I/O Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
5-2 Status Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
5-3 Maintenance Information Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
5-4 Analog Input Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
5-5 Analog Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
viii
TABLE OF CONTENTS
SECTION 6
Temperature Input Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
6-1 Overview of the Temperature Input Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
6-2 Status Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
6-3 Maintenance Information Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
6-4 Temperature Input Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
SECTION 7
Counter Units and Positioning Unit . . . . . . . . . . . . . . . . . . . 225
7-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
7-2 Status Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
7-3 Maintenance Information Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
7-4 GRT1-CT1(-1) Counter Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
7-5 GRT1-CP1-L Positioning Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
SECTION 8
Other Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
8-1 GRT1-TBR Right Turnback Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
8-2 GRT1-TBL Left Turnback Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
8-3 GRT1-PD2 and GRT1-PD2G I/O Power Feed Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
8-4 GRT1-PD8(-1) I/O Power Feed Units and GRT1-PC8(-1) I/O Power Connection Units . . . 277
8-5 GRT1-END End Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .279
SECTION 9
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
9-1 Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
9-2 LED Indicators and Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
9-3 Reading the Error History with a Programming Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
9-4 Other Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
9-5 Troubleshooting by Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Appendices
A Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
B Standard Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
C Power Consumption and Weight Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
D I/O Current Consumption Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
E Precautions When Connecting Two-wire DC Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
ix
About this Manual:
This manual describes the installation and operation of the Slice I/O Units and includes the sections described below. Please read this manual carefully and be sure you understand the information pro­vided before attempting to install or operate Slice I/O Units. Be sure to read the precautions pro-
vided in the following section.
The following manuals also cover information related to DeviceNet applications in which Slice I/O Ter­minals are used. Use the DeviceNet Operation Manual together with other required manuals.
Precautions provides general precautions for planning, installing, and operating the Slice I/O Units and related devices.
Section 1 describes the features of GRT1-series Slice I/O Units and lists the available Units.
Section 2 describes the specifications and functions that are shared by all of the Slice I/O Units.
Section 3 explains how to install and wire the Slice I/O Units.
Section 4 provides the specifications and shows the components, terminal arrangements, wiring dia-
grams, and dimensions for the Digital Slice I/O Units.
Section 5 provides the information required to operate Analog Input Units and Analog Output Units, including functions, status areas, windows, specifications, wiring, data allocation, and settings.
Section 6 provides the information required to operate the Temperature Input Unit, including functions, status areas, windows, specifications, wiring, data allocation, and settings.
Manual Contents Cat. No.
SmartSlice GRT1 Series Slice I/O Units Operation Manual (this manual)
Describes the models, specifications, functions, operating proce­dures, and applications of GRT1-series Slice I/O Units.
W455
DeviceNet Communications Unit for Slice I/O Terminals Operation Manual
Describes the specifications, functions, operating procedures, and applications of the DeviceNet Communications Unit, which allows Slice I/O Units to be set, controlled, and monitored through DeviceNet.
W454
DeviceNet Operation Manual
Describes the configuration and construction of a DeviceNet network, including installation procedures and specifications for cables, con­nectors, and other connection devices, as well as information on functions, operating procedures, and applications.
Read this manual carefully and be sure you understand the informa­tion provided before attempting to use DeviceNet.
W267
CS/CJ Series DeviceNet Units Operation Manual
Describes the specifications, functions, operating procedures, and applications of CS-series and CJ-series DeviceNet Units. (A CS/CJ­series DeviceNet Unit can operate as both a DeviceNet Master and DeviceNet slave at the same time.)
W380
DeviceNet Configurator Ver. 2.@ Operation Manual
Describes the operating procedures of the DeviceNet Configurator. The DeviceNet Configurator can be used to configure, set, and main­tain a DeviceNet system through an easy-to-use graphical interface. Refer to this manual when necessary.
W382
SmartSlice PROFIBUS Communications Unit Operation Manual
Describes the specifications, functions, operating procedures, and applications of the GRT1-PRT PROFIBUS Communications Unit, which allows Slice I/O Units to be set, controlled, and monitored through PROFIBUS.
W04E
PROFIBUS Master Units Operation Manual
Describes the specifications, functions, operating procedures, and applications of CS-series and CJ-series PROFIBUS Master Units.
W409
CX-Profibus Ver. 1.0 Operation Manual
Describes the operating procedures of CX-Profibus. The CX-Profibus can be used to configure, set, and maintain a PROFIBUS system through an easy-to-use graphical interface.
Refer to this manual when necessary.
W05E
x
Section 7 provides information required to operate Counter Units and Positioning Units, including functions, status areas, windows, specifications, wiring, I/O data assignments, and settings.
Section 8 provides the basic specifications and shows the components, wiring diagrams, and dimen­sions for the other Units used in Slice I/O Terminals.
Section 9 describes error processing and troubleshooting procedures needed to keep the Slice I/O Units operating properly.
The Appendices provide information on using explicit messages; tables of standard models, power consumptions, current consumptions, and weights; and precautions for using two-wire DC sensors.
!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
xi
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON­INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
xii
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
xiii
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
xiv
xv
PRECAUTIONS
This section provides general precautions for installing and using the GRT1-series Slice I/O Units and related devices.
The information contained in this section is important for the safe and reliable application of the Slice I/O Units. You must read this section and understand the information contained before attempting to set up or operate a Slice I/O Terminal.
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvi
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvi
3 Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvi
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvii
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xviii
6 EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xx
xvi
Intended Audience 1
1 Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of purchasing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of installing and connecting FA systems.
• Personnel in charge of managing FA systems and facilities.
2 General Precautions
The user must operate the product according to the specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amuse­ment machines, safety equipment, and other systems, machines, and equip­ment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with redundant safety mechanisms.
This manual provides information for installing and operating OMRON DeviceNet products. Be sure to read this manual before operation and keep this manual close at hand for reference during operation.
!WARNING It is extremely important that a PLC and all PLC Units be used for the speci-
fied purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PLC system to the above mentioned applica­tions.
3 Safety Precautions
!WARNING Never attempt to disassemble any Units or touch the terminal block while
power is being supplied. Doing so may result in serious electrical shock.
!WARNING Do not apply voltages or currents outside the specified ranges to a Slice I/O
Unit. Doing so may cause a malfunction or fire.
!WARNING Always turn OFF the I/O power supply to the I/O Unit before performing online
replacement or connecting/disconnecting wiring, including fixing a loose wire. In addition, if external power is supplied to the terminal block for a Unit such as a Relay Output Unit or AC Input Unit, turn OFF that power supply before replacing the Unit. Not turning OFF these power supplies may result in false output signals, false input signals, or electrical shock.
xvii
Operating Environment Precautions 4
!WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, to ensure safety in the system if an abnormality occurs due to malfunction of the PLC or another external factor affecting the PLC operation. Not doing so may result in serious accidents.
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
• The PLC will stop operation when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must be pro­vided to ensure safety in the system.
• The PLC outputs may remain ON or OFF due to deposits on or burning of the output relays, or destruction of the output transistors. As a counter­measure for such problems, external safety measures must be provided to ensure safety in the system.
• When the 24-VDC output (service power supply to the PLC) is overloaded or short-circuited, the voltage may drop and result in the outputs being turned OFF. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
• Slice I/O Terminals will continue operating even if one or more I/O Units is removed from or falls out of the Slice I/O Terminal, i.e., the other I/O Units will continue control operations, including outputs. As a countermeasure for such a possibility, external safety measures must be provided to ensure safety in the system.
!WARNING The CPU Unit refreshes I/O even when the program is stopped (i.e., even in
PROGRAM mode). Confirm safety thoroughly in advance before changing the status of any part of memory allocated to Output Units, Special I/O Units, or CPU Bus Units. Any changes to the data allocated to any Unit may result in unexpected operation of the loads connected to the Unit. Any of the following operations may result in changes to memory status.
• Transferring I/O memory data to the CPU Unit from a Programming Device
• Changing present values in memory from a Programming Device
• Force-setting/-resetting bits from a Programming Device
• Transferring I/O memory files from a Memory Card or EM file memory to the CPU Unit
• Transferring I/O memory from a host computer or from another PLC on a network
4 Operating Environment Precautions
Install the system properly according to the directions in this manual. Do not operate the control system in the following places.
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified in the specifications.
• Locations subject to condensation as the result of severe changes in tem­perature.
• Locations subject to corrosive or flammable gases.
xviii
Application Precautions 5
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to water, oil, or chemicals (Digital I/O Units)
• Locations subject to acid or chemicals.
• Locations subject to shock or vibration.
Take appropriate and sufficient countermeasures when installing systems in the following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
!Caution The operating environment of the PLC System can have a large effect on the
longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PLC System. Be sure that the operating environment is within the specified condi­tions at installation and remains within the specified conditions during the life of the system.
5 Application Precautions
Observe the following precautions when using the Slice I/O Units.
• Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
• Provide external interlock circuits, limit circuits, and other safety circuits in addition to any provided within the PLC to ensure safety.
• Use the power supplies specified in the operation manuals.
• If the system is installed at a site with poor power supply conditions, take appropriate measures to ensure that the power supply remains within the rated voltage and frequency specifications.
• Provide circuit breakers and other safety measures to provide protection against shorts in external wiring.
• Always ground the system to 100
or less when installing the system to
protect against electrical shock.
• Mount the PLC securely on DIN Track or with screws.
• Always turn OFF the power supply when mounting a Slice I/O Unit.
• Always turn OFF the communications power supply and the power sup­plies to the PLC and Slaves before attempting any of the following.
• Mounting or removing a Unit such as an I/O Unit, CPU Unit, Memory Cassette, or Master Unit.
• Mounting or removing Remote I/O Terminal circuit sections.
• Assembling any devices or racks.
• Setting rotary switches.
• Connecting or wiring cables.
• Connecting or disconnecting connectors.
• Do not attempt to disassemble, repair, or modify any Units.
• Be sure that all the terminal screws are tightened to the torque specified in the relevant manuals. Loose screws may cause fire, malfunction, or damage the Unit.
xix
Application Precautions 5
• Be sure that all the mounting screws and cable connector screws are tightened to the torque specified in the relevant manuals.
• Be sure that all the communications connector screws are tightened securely. (The communications connector screw torque is 0.5 to 0.6 N·m.)
• Use the correct wiring components when wiring.
• Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals.
• Double-check all wiring before turning ON the power supply.
• When wiring or performing other tasks, do not allow metal objects such as wire strands to enter the Unit.
• Always follow the electrical specifications for terminal polarity, communi­cations path wiring, power supply wiring, and I/O jumpers. Incorrect wiring can cause failures.
• Always wire the Unit as shown in the manual.
• Be sure to press terminals until they are fully seated.
• Mount Units only after checking terminal blocks completely.
• Before mounting a wired terminal block to the main block, be sure that the terminal block-main block combination is correct.
• Be sure that the communications cable connectors and other items with locking devices are properly locked into place.
• Do not drop the Unit or subject the Unit to excessive vibration or shock. Doing so may cause malfunction or damage to the Unit.
• Use the special packing box when transporting the Unit. Ensure that the product is handled carefully so that no excessive vibration or impact is applied to the product during transportation.
• Check the user program for proper execution before actually running it with the system.
• Do not bend or pull the cables excessively.
• When connecting communications cables, always turn OFF the PLC power supply, all Slave power supplies, and all communications power supplies.
• Observe the following precautions when wiring the communications cables.
• Wire the communications cables separately from the power lines or high-tension lines.
• Do not bend the communications cables excessively.
• Do not pull on the communications cables excessively.
• Do not place objects on top of the communications cables.
• Route communications cables inside ducts.
• Always enable the scan list before operation.
• Before clearing the scan list of a Unit that has user-allocated remote I/O, always confirm that no errors occur after the I/O Area setting is changed to fixed allocation.
• When adding a new node to the network, check that the new node’s baud rate is the same as the baud rate set on the other nodes.
• Do not extend connection distances beyond the ranges given in the spec­ifications.
• Be sure that the Slice I/O Units are lined up correctly when mounting them.
xx
EC Directives 6
• Correctly connect the Slice I/O Units to each other. The I/O power supply will become disconnected if the base blocks on the Slice I/O Units are not connected correctly. While outputs are being transmitted from the Communications Unit, the output indicators on the Slice Output Unit will be lit, but the outputs will actually be OFF.
6 EC Directives
DeviceNet products conform to EMS and low-voltage level directives as fol­lows:
EMC Directive
OMRON devices that comply with EC Directives also conform to the related EMC standards, so that they can more easily be built in to other devices or the overall machine. The actual products have been checked for conformity to EMC standards. Whether they conform to the standards in the system used by the customer, however, must be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Direc­tives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.
Low Voltage Directive
Devices that operate at voltages from 50 to 1,000 VAC or 75 to 1,500 VDC must satisfy the appropriate safety requirements. The applicable standard is EN 61131-2.
Complying with EC Directives
1,2,3... 1. The Slice I/O Units are designed for installation inside control panels. All
Slice I/O Units must be installed within control panels.
2. Use reinforced insulation or double insulation for the DC power supplies used for the communications power supply, internal circuit power supply, and the I/O power supplies. Ensure that stable outputs can be provided even if a 10-ms interruption occurs at the input.
3. The Slice I/O Units conform to the EN 61131-2 (Immunity Zone A), EN 61000-6-2, and EN 61000-6-4 standards. AC power connections to Slice I/O Units must use a protection network if the severity levels for Zone A are exceeded. The radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devic­es connected to the control panel, wiring, and other conditions. You must therefore confirm that the overall machine or equipment complies with EC Directives.
The following examples shows how to reduce noise.
1,2,3... 1. Noise from the communications cable can be reduced by installing ferrite
cores on the communications cable within 10 cm of the DeviceNet Unit and DeviceNet Communications Unit.
xxi
EC Directives 6
2. Wire the control panel with as thick and short cables as possible and ground to 100
min.
3. Keep DeviceNet communications cables as short as possible and ground to 100
min.
Ferrite Core (Data Line Filter): 0443-164151 (manufactured by Nisshin Electric)
Impedance specifications 25 MHz: 156 100 MHz: 250
30 mm
13 mm
29 mm
33 mm
xxii
EC Directives 6
1
SECTION 1
Available Units and Features
This section describes the features of GRT1-series Slice I/O Units and lists the available Units.
1-1 Slice I/O Terminal Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-1 Features of the GRT1-series Slice I/O Units . . . . . . . . . . . . . . . . . . 2
1-2 Available Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-2-1 Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-2-2 Digital I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-2-3 Analog I/O Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-2-4 Counter Units and Positioning Unit . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-2-5 System Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-2-6 Connecting Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1-2-7 Functions Supported by Slice I/O Units. . . . . . . . . . . . . . . . . . . . . . 9
1-2-8 Slice I/O Unit Installation and Power Supply Methods . . . . . . . . . . 10
2
Slice I/O Terminal Introduction Section 1-1
1-1 Slice I/O Terminal Introduction
A Slice I/O Terminal is a building-block style remote I/O terminal made up of a Communications Unit and a number of Slice I/O Units, which each provide a small number of I/O points. The Slice I/O Units communicate with the host by remote I/O communications (cyclic communications) through the Communica­tions Unit. Remote I/O communications (cyclic communications) can be started just by setting the Communications Unit’s node address and turning ON the power supply.
Since the Slice I/O Units expand the system in small I/O increments, a flexible system can be assembled to exactly match various customer applications, with less labor and space.
1-1-1 Features of the GRT1-series Slice I/O Units
The GRT1-series Slice I/O Units have the following features.
Features Shared by all Units
Small I/O Increments The GRT1-series Slice I/O Units have just a few I/O points (2 to 4 points) per
Unit, so the application can be flexibly constructed to match the space and capacity requirements.
Building-block Style Termina ls
Slice I/O Terminals are building-block style Units that can be expanded by attaching additional Slice I/O Units to the side of the Terminal. Up to 64 Slice I/ O Units can be connected to one Communications Unit.
Time-saving Screwless Termina l Blocks
Slice I/O Units are equipped with screwless clamp terminal blocks, which can be wired just by inserting the wire into the terminals. Wires can be removed just by pressing the release button and pulling out the wire.
Example: DeviceNet
PLC
Serial connection (For setting, monitoring, and operating)
Slave
GRT1-DRT DeviceNet Communications Unit
Slice I/O Units
Up to 64 Slice I/O Units can be connected to one DeviceNet Communications Unit. (Up to 1,024 inputs and outputs can be connected.)
Slice I/O Terminals
DeviceNet Unit
3
Slice I/O Terminal Introduction Section 1-1
Parameter Backup and Restore
Before replacing a Slice I/O Unit for maintenance, the parameter data set in the I/O Unit can be backed up in the connected Communications Unit. The backed up parameter data is compared with the replacement I/O Unit’s data and the backed up data is restored to the replacement I/O Unit.
Online Replacement of I/O Units
The Slice I/O Units are made up of 3 blocks (the base block, main block, and terminal block) that can be separated from each other. This means you can leave the base block connected to the Slice I/O Terminal with power supplied to the Slice I/O Terminal and replace the main block or terminal block.
Note Turn OFF the I/O power supply before replacing Slice I/O Unit
blocks. Also turn OFF any external power supplied to the terminals.
Automatic Baud Rate Recognition
It isn’t necessary to set the baud rate on the GRT1-series Slice I/O Units.
Automatic Allocation of Unit Numbers
Unit numbers are allocated automatically to the connected Slice I/O Units from left to right and stored within the Communications Unit. It is not neces­sary for the user to set these numbers.
Remote I/O Communications
GRT1-series Slice I/O Units communicate with the host Master by remote I/O communications through the Communications Unit. The Slice I/O Units’ data is collected in the Communications Unit and exchanged with the Master in a batch.
Unit Conduction Time (Power ON Time) Monitor
This function records the total time that the Slice I/O Unit's internal circuit power has been ON. A warning level can be set in the Unit and a warning flag will be turned ON when the set warning time is exceeded. The Power ON Time can be read with an explicit message command or from the Configura­tor.
Unit Comments A user-set name can be assigned to each Unit and recorded in the Unit.
Connected Device Comments
User-set names can be assigned to each I/O device (sensor, valve, etc.) con­nected to a Unit and recorded in the Unit.
Communications Error History Monitor
The communications error log within the Unit can collect the four most recent communications errors (communications error cause code and communica­tions power supply voltage when error occurred). The information can be read with an explicit message command or from the Configurator.
Last Maintenance Date The date on which maintenance was performed can be written in the Unit.
The date can be written from the Configurator.
Digital I/O Unit Features
I/O Power Supply Monitor This function detects whether the I/O power is being supplied and turns ON a
warning flag in the Unit if the I/O power supply is OFF. The flags can be read with an explicit message command or from the Configurator.
Input Filter The input filter function reads the input value several times during the set
interval and removes irregular data caused by noise and switch chattering. This function can also be used to create ON/OFF delays.
Sensor Power ON Delay When the I/O power has gone OFF, the sensor power ON delay function
blocks inputs for the first 100 ms after the I/O power is turned back ON. This function prevents incorrect inputs caused by inrush current at startup after the I/O power is turned ON.
4
Slice I/O Terminal Introduction Section 1-1
Contact Operation Counter
This function can count the number of times each input or output contact changes from OFF to ON (maximum resolution: 50 Hz). A warning set value can be set in the Unit to monitor the number of contact operations, and turn ON a warning flag in the Status Area when the set value is reached. The Con­figurator or explicit messages can be used to read the information.
Note The Contact Operation Counter and Total ON Time Monitor cannot be used at
the same time for a single contact.
Total ON Time Monitor This function can record the total ON time of devices connected to the Unit,
such as sensors and relays. The total time is stored in the Unit and can be read by the Configurator or explicit messages. A warning set value can be set in the Unit to monitor the total ON time, and turn ON a warning flag in the Sta­tus Area when the set value is reached.
Note The Total ON Time Monitor and Contact Operation Counter cannot be used at
the same time for a single contact.
Operation Time Monitor This function can measure and monitor an Input Unit’s operating time. The
time required for a bit to go ON or OFF can be measured at high speed within the Unit, so that ladder programming is not required to measure the operating time. The trigger edge (ON
OFF or OFFON), input number, and output
number can be selected freely, providing flexibility when testing. A warning set value can be set in the Unit to monitor the operating time, and turn ON a warning flag in the Status Area when the set value is reached.
Analog I/O Unit Features
Setting the Number of AD Conversion Points
The conversion cycle when both analog input points are used is 2.42 ms max. The AD conversion cycle can be shortened by reducing the number of points used (i.e., the number of AD conversion points).
Moving Average Analog Input Terminals can calculate the average of the past eight analog
input values to produce a stable input value even when the input value is unsteady.
Scaling Scaling allows values to be converted according to the industry unit required
by the user. It reduces the number of operations requiring ladder program­ming in the Master CPU Unit. Scaling also supports an offset function for com­pensating for errors in scaled values.
Peak/Bottom Hold The maximum (peak) and minimum (bottom) values input to Analog Input Ter-
minals can be held. These values can then be compared with alarm set val­ues, and flags turned ON accordingly to indicate the status (comparator function).
Top/Valley Hold (Input Units Only)
The top and valley values for values input to Analog Input Terminals can be held. The timing of tops and valleys can be monitored with the Top/Valley Detection Timing Flags. The top and valley values can be compared with alarm set values, and flags turned ON accordingly to indicate the status (com­parator function).
Rate of Change The rate of change for values input to Analog Input Terminals can be obtained
for each sampling cycle.
Comparator Values input to Analog Input Terminals or values after math processing can be
compared to the alarm set values (HH, H, L, and LL), and the result indicated with the Analog Status Flags. If the result is outside the set range, the Normal Flag (pass signal) is turned ON.
Off-wire Detection With Analog Input Terminals, disconnections can be detected in wiring for
analog (voltage or current) inputs that are enabled as AD conversion points.
5
Slice I/O Terminal Introduction Section 1-1
The status can be checked at the Master using the Off-wire Detection Flag. This function is valid only for the input ranges 4 to 20 mA and 1 to 5 V.
User Adjustment Input or output values can be adjusted to compensate for errors in the input or
output voltage or current resulting from the characteristics or connection methods of the I/O device. Compensation is performed by applying linear con­version based on the points corresponding to 0% and 100%.
Cumulative Counter A cumulated value that approximates the integral of analog input or output val-
ues over time can be calculated and read.
Communications Error Output (Output Units Only)
The values output by Output Units when errors occur can be set for each out­put.
Temperature Input Unit Features
Moving Average Temperature Input Units can calculate the average of the past eight input val-
ues to produce a stable input value even when the input value is unsteady.
Scaling Scaling allows values to be converted according to the industry unit required
by the user. It reduces the number of operations requiring ladder program­ming in the Master CPU Unit. Scaling also supports an offset function for com­pensating for errors in scaled values.
Peak/Bottom Hold The maximum (peak) and minimum (bottom) values input to Temperature
Input Units can be held. These values can then be compared with alarm set values, and flags turned ON accordingly to indicate the status (comparator function).
Top/Valley Hold The top and valley values for values input to Temperature Input Units can be
held. The timing of tops and valleys can be monitored with the Top/Valley Detection Timing Flags. The top and valley values can be compared with alarm set values, and flags turned ON accordingly to indicate the status (com­parator function).
Rate of Change The rate of change for values input to Temperature Input Units can be
obtained for each sampling cycle.
Comparator Values input to Temperature Input Units or values after math processing can
be compared to the alarm set values (HH, H, L, and LL), and the result indi­cated with the Temperature Status Flags. If the result is outside the set range, the Normal Flag (pass signal) is turned ON.
Off-wire Detection With Temperature Input Units, disconnections can be detected individually for
each sensor input. The status can be checked at the Master using the Off­wire Detection Flags.
Input Error Detection Disable
Detection of input errors, including off-wire detection, can be disabled for channels that are not used.
User Adjustment Input or output values can be adjusted to compensate for errors in the input or
output voltage or current resulting from the characteristics or connection methods of the I/O device. Compensation is performed by applying linear con­version based on the points corresponding to 0% and 100%.
Cumulative Counter A cumulated value that gives the integral of analog input values over time can
be calculated and read.
Top or Valley Count The numbers of times that the top or valley value is reached can be counted,
e.g., in an application in which the temperature input value varies in a fixed cycle of temperature change. The host will be notified with a flag when the number of cycles exceeds the set value.
6
Slice I/O Terminal Introduction Section 1-1
Temperature Zone Counter
The temperature zone counter can be used to measure how long the temper­ature input value is within a user-set temperature range in 1-second incre­ments. The host will be notified with a flag when the measured value exceeds the set value.
Data Comparison between Channels
The temperature differences between input channels 0 and 1 can be calcu­lated and compared to a set value. The host will be notified with a flag when the temperature difference exceeds a set value.
Counter Unit and Positioning Unit Features
Counter Each Unit provides one high-speed counter with a 32-bit resolution. Counting
is performed in linear fashion, and encoder signals up to 60 kHz can be input with Counter Units and up to 100 kHz can be input with Positioning Units. The Counter Units support 24-V inputs and the Positioning Unit supports either 24-V or line-driver inputs (settable).
Counter Input Modes The counter can be set to any of the following input modes:
• Phase differential
×1
• Phase differential ×2
• Phase differential
×4
• Pulse/direction
•Up/down
Speed Measurement The output pulse frequency is measured and can be read from the I/O area at
any time.
Digital Inputs The Counter Unit supports an input that can be set to operate either as a digi-
tal input or an encoder Z-signal input. The Positioning Unit provides both a digital input and an encoder Z-signal input.
The digital input can be set to reset the counter, preset the counter, or capture the present counter value. Any of these actions can be set to be performed on the rising or falling edge of the digital signal.
The Z-signal input of the Positioning Unit can be set to reset the counter in various ways.
Digital Outputs Each Counter Unit provides one digital output and the Positioning Unit pro-
vides two digital outputs. A digital output can be used as a general-purpose output, or it can be controlled using a settable counter value comparison range.
Comparison Range A comparison range can be enabled for the counter value to control a digital
output. The output will be turned ON or OFF depending on the relationship between the counter value and the range that is set. Each Counter Unit pro­vides one comparison range.
7
Available Units Section 1-2
1-2 Available Units
The following tables list the available GRT1-series Units, categorized by type.
1-2-1 Communications Units
1-2-2 Digital I/O Units
1-2-3 Analog I/O Units
Type I/O points Model number Description
DeviceNet Communications Unit
--- GRT1-DRT Interface Unit that con­nects the DeviceNet Unit with the Slice I/O Units
PROFIBUS Communica­tions Unit
--- GRT1-PRT Interface Unit that con­nects the PROFIBUS Unit with the Slice I/O Units.
Type I/O points Model number Description
DC Input/Transistor Output Units
4 inputs (NPN) GRT1-ID4 4 DC inputs 4 inputs (PNP) GRT1-ID4-1 4 outputs (NPN) GRT1-OD4 4 transistor outputs 4 outputs (PNP) GRT1-OD4-1 4 outputs (PNP) GRT1-OD4G-1 4 outputs (PNP) GRT1-OD4G-3 4 transistor outputs (2 A) 8 inputs (NPN) GRT1-ID8 8 DC inputs 8 inputs (PNP) GRT1-ID8-1 8 outputs (NPN) GRT1-OD8 8 transistor outputs 8 outputs (PNP) GRT1-OD8-1 8 outputs (PNP) GRT1-OD8G-1
AC Input Units 4 inputs GRT1-IA4-1 100 to 120 VAC
4 inputs GRT1-IA4-2 200 to 240 VAC
Relay Output Unit 2 outputs GRT1-ROS2 Relay outputs
Type I/O points Model number Description
Analog I/O Units 2 inputs GRT1-AD2 2 analog inputs
2 outputs GRT1-DA2V 2 analog voltage outputs 2 outputs GRT1-DA2C 2 analog current outputs
Temperature Input Units
2 inputs GRT1-TS2P Resistance thermometer
input Type: PT100 (200 to 850°C) PT100 (200 to 200°C)
2 inputs GRT1-TS2PK Resistance thermometer
input Type: PT1000 (200 to 850°C) PT1000 (200 to 200°C)
2 inputs GRT1-TS2T Thermocouple input
(R, S, K1, K2, J1, J2, T, E, B, N, L1, L2, U, W, or PL2; switchable)
8
Available Units Section 1-2
1-2-4 Counter Units and Positioning Unit
1-2-5 System Units
Type I/O Model number Description
Counter Units
• A and B counter inputs
• One input settable to Z counter input or digital input
• 1 digital output (NPN)
GRT1-CT1 1 counter
Max. frequency: 60 kHz (depend­ing on counter input mode)
• A and B counter inputs
• One input settable to Z counter input or digital input
• 1 digital output (PNP)
GRT1-CT1-1
Positioning Unit
• A, B, and Z counter inputs
• 1 digital input
• 2 digital outputs (PNP)
GRT1-CP1-L 1 counter
Max. frequency: 100 kHz (depend­ing on interface and counter input mode)
Type I/O points Model number Description
Right Turnback Unit --- GRT1-TBR Mounts to the right side of
the last Unit to add a new block.
Left Turnback Unit --- GRT1-TBL Mounts to the left side of
the new block. Power is supplied from the Left Tur nb a ck Un i t.
I/O Power Feed Units --- GRT1-PD2 Feeds I/O power within the
Slice I/O Terminal. 2 voltage terminals and
2 ground terminals
--- GRT1-PD2G Feeds I/O power within the Slice I/O Terminal.
2 voltage terminals and 2 ground terminals Overcurrent protection
--- GRT1-PD8 Feeds I/O power within the Slice I/O Terminal.
8 voltage terminals and 4 ground terminals
--- GRT1-PD8-1 Feeds I/O power within the Slice I/O Terminal.
4 voltage terminals and 8 ground terminals
I/O Power Connection Units
--- GRT1-PC8 Provides extra voltage and ground terminals.
8 voltage terminals and 4 ground terminals
--- GRT1-PC8-1 Provides extra voltage and ground terminals.
4 voltage terminals and 8 ground terminals
End Unit --- GRT1-END An End Unit must be
mounted to the end of the Slice I/O Terminal.
9
Available Units Section 1-2
1-2-6 Connecting Cable
1-2-7 Functions Supported by Slice I/O Units
Type I/O points Model number Description
Turnback Cable for Slice I/O Units (1 m)
--- GCN2-100 This is a special turnback cable. Up to 2 Turnback Cables (2 m total) can be connected for one Communications Unit.
Function GRT1-series Slice I/O Units
Digital I/O Units Analog I/O Units Tempera-
ture Input
Units
Counter
Units and
Position-
ing Unit
DC Input
Units
AC Input
Units
Output
Units
Relay
Output
Units
Input Units
Output
Units
Backup/Restore Supported Online Replacement Supported Automatic Baud Rate
Recognition
Supported
Unit Conduction Time (Power ON Time) Monitor
Supported
Unit Comments Supported Connected Device Com-
ments
Supported
Last Maintenance Date Supported Communications Error
History Monitor
Supported
Detachable Terminal Block
Supported
Total ON Time Monitor Supported --- Supported Contact Operation
Counter
Supported --- Supported
Operation Time Monitor Supported --­I/O Power Supply Monitor Supported --- Supported --- Supported Input Filter Supported --­Sensor Power ON Delay Supported --­Scaling --- Supported --­User Adjustment --- Supported --­Cumulative Counter --- Supported --­Moving Average --- Supported --- Supported --­Setting the Number of AD
Conversion Points
--- Supported --- --- ---
Input Error Detection Dis­able
--- --- --- Supported ---
Peak/Bottom Hold --- Supported --- Supported --­Top/Valley Hold --- Supported --- Supported --­Rate of Change --- Supported --- Supported --­Comparator --- Supported --- Supported --­Communications Error
Output
--- Supported --- Supported --- Supported
Temperature Zone Counter
--- --- --- Supported ---
Data Comparison between Channels
--- --- --- Supported ---
Loading...
+ 335 hidden pages