All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers
to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
IBM and IBM PC/AT are registered trademarks of International Business Machines Corporation.
MS-DOS is a registered trademark of Microsoft Corporation.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1991
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any
form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change
without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no
responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
This manual describes the installation and operation of the NT600M Programmable Terminals (PTs) and
includes the sections described below. Further information is provided in manuals on the Host Interface
Units and Support Tool. Refer to the list in
Please read this manual completely and be sure you understand the information provide before attempting to install and operate a Programmable Terminal.
Section 1 Introduction
.
Section 1
of system configurations for programming and operation.
Section 2
switch settings and installation.
Section 3
Section 4
Included is automatic transfer of data from the host computer via character string and numeral tables.
Section 5
the numeral table.
Section 6
Section 7
Section 8
Appendices of OMRON products used with PTs, PT specifications, and a memory check table are
provided at the back of the manual.
introduces the PTs, describes the terminology used in this manual, and provides examples
provides procedures and specifications required to set up a PT system, including hardware
provides steps required for initial PT operation.
describes functions used to create screens and control display attributes on the PT.
describes functions used to input data on-screen and transfer it to the host computer via
describes basic data transfer and maintenance functions.
describes transferring screens online to and from the host computer.
provides troubleshooting and basic maintenance methods, including battery replacement.
!
WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each
section in its entirety and be sure you understand the information provided in the section
and related sections before attempting any of the procedures or operations given.
This section provides general precautions for using the Programmable Terminal.
The information contained in this section is important for the safe and reliable application of the Programmable Terminal. You must read this section and understand the information contained befor e attempting to set up or operate a
Programmable Terminal.
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2General Precautions
The user must operate the product according to the performance specifications
described in the operation manuals.
Before using the product under conditions which are not described in the manual
or applying the product to nuclear control systems, railroad systems, aviation
systems, vehicles, combustion systems, medical equipment, amusement
machines, safety equipment, and other systems, machines, and equipment that
may have a serious influence on lives and property if used improperly, consult
your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide the
systems, machines, and equipment with double safety mechanisms.
This manual provides information for using the Programmable Terminal. Be sure
to read this manual before attempting to use the software and keep this manual
close at hand for reference during operation.
3
WARNING It is extremely important that Programmable Terminals and related devices be
!
used for the specified purpose and under the specified conditions, especially in
applications that can directly or indirectly affect human life. You must consult
with your OMRON representative before applying Programmable Terminals to
the abovementioned applications.
WARNING Do not use input functions such as PT touch switches for applications where
!
danger to human life or serious damage is possible, or for emergency switch
applications.
3Safety Precautions
Read these safety precautions carefully and make sure you understand them
before using the Programmable Terminal so that you can use it safely and correctly.
Safety Conventions and
their Meanings
DANGERIndicates information that, if not heeded, is likely to result in loss of life or serious
!
This operation manual uses the following conventions and symbols to indicate
cautions, warnings, and dangers in order to ensure safe use of the PT. The cautions, warnings, and dangers shown here contain important information related
to safety. The instructions in these cautions, warnings, and dangers must be
observed.
The conventions used and their meanings are presented below.
injury.
WARNING Indicates information that, if not heeded, could possibly result in loss of life or
!
serious injury.
CautionIndicates information that, if not heeded, could result in relatively serious or mi-
!
nor injury, damage to the product, or faulty operation.
• The ROM may be destroyed if it is mounted while power is being supplied to
the PT.
• Screen memory must be initialized before using a new PT. If the PT is used as
shipped from the factory without initialization, messages indicating errors in
the host will not be displayed.
• After the transfer has been completed, be sure to return to RUN Mode by
pressing the Buzzer Key, Up Key, and Down Key simultaneously. If the power
is turned off or if a reset is executed without having first returned to RUN Mode,
the data that has been transmitted will be corrupted. If that occurs, a message
will be displayed on the screen to indicate that the data has been corrupted.
• If a load (e.g., a buzzer or alarm light) is connected to a 10/02 Terminal or a
32/16 Terminal, it will actually operate. This can be potentially dangerous, so
exercise caution.
• The lithium battery can explode if placed into a fire, or it can explode, burn, or
leak if the + and – terminals are short-circuited or if the battery is recharged or
dismantled. Handle the battery with care.
1) PTs can monitor, in real time, system and equipment operating conditions,
production quantities, and so on. The PT display can show, for example,
whether the production line is operating normally, and what percentage of the
production target has been met. Bar graphs can be continually updated as
data is received from the host. On-screen characters can be displayed as
plain, reverse video, blinking, or reverse blinking. In addition, lamps, bar
graphs, and figures can all be created. Screen data can be registered at the
PT in advance, and can be displayed simply by transmitting the appropriate
screen number from the host.
Lamp DisplayBar Graph Display
Operating conditions
RunAir
RunNormalOil
Emergency
stop
Normal
Error
Rotation (rpm)
0
Oil pressure (kg/cm
0
5.010
Graphics Display
Conveyance System
L1-0
36001800
2
)
M10
L1-2
L2-0
2) PTs can inform on-site personnel of current conditions that need to be addressed. Depending on the nature of the situation, built-in or external buzzers
can be sounded to alert personnel to problems that have developed. Depending on factors such as distance from the host, the number of devices
connected, and the response time, any of a variety of communications methods may be selected.
Abnormality
occurs!
Device
Normal
operation
Device
EMERGENCY STOP
Air pressure is abnormal.
Please check
PC
PT
(Flashing display)
3) PTs can input data for controlling certain operations and communicating
information to the host. Setting switches and a ten-key pad allows a PT to be
used as a control panel. In the example shown below, touch switches used
for inputs to the host are displayed. When this screen is displayed, the onsite operator can control a device by means of touch switches.
Crane Operation
Run
Left
Stop
PC
PT
Up
Down
Right
(Touch switches
created by Support
Tool.)
Aside from touch switches, the PT can provide inputs by means of numeric
settings and externally connected switches. The illustration below shows a
numeric setting screen that can be used for inputting numeric data.
Tank A
06540650
Tank C
00000550
Tank E
08000990
Tank B
Tank D
Tank F
123
456
789
HO
0
ME
ChangeSet
MENU
C
The screens used for these operations can be created in advance by using
the “Support Tool” software on a personal computer. The screen data that is
created using the Support Tool can be printed out, saved to a diskette, or
transferred to the PT. An FA Computer, a Programmable Controller, or a
compatible device can be used as the host.
The NT600-series PTs provide a choice of three models depending on the
input specifications of your system. You can also choose either of two types
of display devices. Any of six methods can be selected for communicating
with the host, which may be an FA Computer, a Programmable Controller, or
a compatible device.
The PTs have a drip-proof front panel structure when the dust cover is
mounted to protect the display area and the key input area.
Either of two types of display can be selected: an STN liquid crystal display
with a backlight, or a yellow-orange EL (electro-luminescent) display.
Screens at the PT can be changed, messages can be received, and numbers can be displayed from the host. The PT, in turn, can transmit key inputs
and numbers back to the host.
A maximum of 1000 screens can be registered. As many as 64 rectangular
or circular lamps can be created for a single screen, up to a total of 256 and
direct connection can be used without restrictions. Character strings, numerals, bar graphs and simple graphics can also be created and registered.
Depending on the input specifications of the control system, any of three
NT600M types may be selected: the touch panel (DT) type, the non-touchpanel type (DN), and the function key type (DF). DT-type PTs enable the user
to create and use as many as 64 touch switches per screen, up to a total of
256 and direct connection can be used without restrictions. DN-type PTs allow the connection of 12-key Function Key Units, up to a maximum of 32 input points and 16 output points. DF-type PTs enable various inputs by means
of 12 function keys.
Standalone Capability
Screens can be changed on-site, using touch switches, function keys, or external inputs. The screen-changing capability can be allocated to touch
switches or function keys at the time that the screens are created in advance
by the Support Tool.
Online Transfer
Screen data can be written by means of commands from the host when an
RS-232C or RS-422A Host Interface Unit is mounted.
Direct Connection
The direct connection function can be used to directly correlate host data
areas with PT operations. Ordinarily, instructions to the PT and inputs from
the PT are executed in response to commands from the host. Such commands are not required for direct connection, however, and thus the size of
the host program can be greatly reduced. The direct connection can only be
used by DT-type PTs, with the restrictions on Host I/F Units, System ROM,
and Support Tool versions shown in the following table.
PTSystem ROMHost Interface UnitSupport Tool
NT600M-DT12
NT600M-DT211
NT600M-SMR31-ENT600M-LK201 Host Link Interface Unit
NT600M-SMR32-ENT600M-LB122-V1 C200H Host Interface Unit
NT20M-ZASAT-EV4
ersion 4.0 or later
NT-ZA3AT-EV2
When direct connection is used, the PT data is as follows:
Lamps255 per screen (with no limit on number registered)
Touch switches128 per screen (with no limit on number registered)
Character string data
memory
50 places per screen (with a maximum of 512
registered)
Names of items in this manual related to the NT-series Programmable Terminals and SYSMAC C-series Programmable Controllers are defined in the
following tables.
AbbreviationsThe following abbreviations are used in the text.
AbbreviationTermMeaning
PTProgrammable TerminalRefers to an OMRON NT-series Programmable Terminal.
PCProgrammable
Controller
I/FinterfaceA communications device that connects the Programmable Terminal with
I/Oinput/outputRefers to PT and PC inputs and outputs.
Refers to an OMRON SYSMAC C-series or CV-series Programmable
Controller, or programmable controllers manufactured by other companies.
peripheral devices.
SYSMAC Terminology
TerminologyExplanation
SYSMACA generic name for OMRON’s Programmable Controllers.
Host Link SystemA system employing SYSMAC C-series Host Link Units used to create a communications bus
between PCs, between PCs and PTs, etc.
SYSMAC BUSA remote I/O network created between SYSMAC C-series PCs and input/output devices.
C200HAn OMRON SYSMAC C-series Programmable Controller.
Reference ManualsThe NT20M/NT2000M Series and NT600M Series are covered in the seven
manuals described below.
Name of ManualContentsManual No.
NT20M/NT2000M Operation
Manual
NT600M Operation ManualThis manual provides specifications, functions, and operating
NT-series Host Interface Unit
Operation Manual
NT20M/NT600M Support Tool
Operation Manual
NT-series Host Interface Unit
Direct Connection Operation
Manual
NT-series RS-232C/RS-422A
Interface Unit Operation Manual
NT-series Support Tool Operation
Manual
This manual provides specifications, functions, and operating
instructions for the NT20M and NT2000M Programmable Terminals.
instructions for NT600M Programmable Terminals.
This manual covers the commands, controls, and communications
specifications for operating the NT20M and the NT600M. Refer to
this manual when programming host computer communications.
This manual covers methods for creating screens, including screen
data preparation, switches, lights, and alarms.
(for NT20M-ZASAT-EV4)
This manual covers the Direct Connection feature which has been
added to the Host Interface Unit.
This manual covers the commands, controls, and communications
specifications for operating the NT20M and the NT600M with the
RS-232C/RS-422 Interface Unit. Refer to this manual when
programming host computer communications.
This manual covers methods for creating screens, including screen
data preparation, switches, lights, and alarms. (NT-ZA3AT-EV2)
Purchased separately.
boards can be SRAM
commercially
available EPROM or
EEPROM.
y
1-4-2Screen Data Memory Boards
A Screen Data Memory Board is required for registering screen, character
string, and numeric data. The Screen Data Memory Board is not built into the
PT and must be purchases separately.
Screen memory capacity varies according to which Screen Data Memory
Board is installed. The screen memory capacity, in turn, determines the number of screens that can be registered. Use the table below as a guide to select the amount of memory suitable for your needs.
Screen memory capacityNumber of registered screens
32K bytesMostly messages: 40 screens
Mostly graphics: 15 screens
64K bytesMostly messages: 120 screens
Mostly graphics: 40 screens
128K bytesMostly messages: 250 screens
Mostly graphics: 100 screens
256K bytesMostly messages: 600 screens
Mostly graphics: 200 screens
Note The table above is strictly a guide. If the messages or other display data per
screen increase, the number of screens that can be registered will decrease.
Likewise, if the messages decrease, the number of screens that can be registered will increase.
1-4-3System ROM
Purchase the System ROM according to the NT600M and Host Interface Unit
models that are used.
NT600M
Host I/F Unit
NT600M-LK201 (RS-232C) (see note 1)
NT600M-LK202 (RS-422A)
NT600M-LK201 (Host Link) (see note 1)
NT600M-RT201 (SYSMAC BUS)
NT600M-LB122-V1 (C200H) (see note 1)NT600M-SMR02-EV1--NT600M-LK201 (see note 1) (Host Link)---NT600M-SMR31-E (Direct connection
NT600M-LB122-V1 (C200H) (see note 2)---NT600M-SMR32-E (Direct connection
NT600M-SMR01-EV1---
NT600M-DT122/211
NT600M-DN122/211
NT600M-DF122
can be used when version 4 of the
Support Tool is used.)
can be used when version 4 of the
Support Tool is used.)
2. For the NT600M-LB122-V1, set the pin 4 of the Interface Unit’s DIP switch
SW2 ON or OFF to determine whether to allow direct connection or not.
Without direct connection: Turn ON pin 4 of SW2
With direct connection: Turn OFF pin 4 of SW2.
1-4-4Host Interface Units
The Host Interface Unit provides the interface for communications between
the PT and the host (either a Programmable Controller or an FA computer).
The Host Interface Unit models that can be used with the NT600M PT are
shown in the table below. Select the Host Interface Unit to match the communications specifications of the system.
NT600M-jjjjj
Model number
Communications specifications
LK: Serial communications
RT: Remote communications
LB: C200H Host Interface
NT600M-series, basic model
NameModel numberRemarks
RS-232C Interface UnitNT600M-LK201
RS-422A Interface UnitNT600M-LK202
SYSMAC BUS Interface UnitNT600M-RT121Can be connected as a Slave Unit in a SYSMAC Wired Remote
Host Link Interface UnitNT600M-LK201Can communicate one-to-one with a SYSMAC Host Link Unit.
C200H Host Interface UnitNT600M-LB122-V1Can be connected to a SYSMAC C200H, C20H, C40H, or C60H
Connect for general-purpose communications with an FA
p
computer or personal computer. For communications w
SYSMAC PC, connect to an ASCII Unit.
I/O System.
PC to provide the functions of an Expansion I/O Rack.
Function-key input for NT600M non-touch panel (DN) type models is made
possible by attaching an NT600M-FK210 12-key Function Key Unit.
NT600M-DN211 PT
(Without touch panel)
NT600M-FK210
12-key Function Key Unit
1-5Support Tools
NT600M screen data, memory table data, and system data are all created by
the Support Tool. In order to fully utilize the functions of the NT600M PTs,
use the NT-ZA3AT-EV2 Support Tool or a version of NT20M-ZASAT-EV4 or
higher.
NT20M-ZASAT-EVj
Version
Overseas specifications (English)
Compatible platform
AT: IBM PC/AT compatible
Floppy disk size
3:3.5 inch
5:5.25 inch
S:3.5 and 5 inch
Support software
NT model
NT:NT Series (common)
NT20M:NT20M Series
Contrast Between Functions when New and Old Versions of Peripheral Devices are Used
(1) I/O Functions
Function
Lamps (bit designation)
Display attributes: Lit or
flashing
Touch switches: Reverse
video display during input
(yes or no)
Standalone functionFXFXAll modelsX: Cannot be used.
Direct connectionSee note 3.SMR 31-E/32-EDT-type only
Display width
enlargement (2
to 255 dots)
+/– display
% value
enlargement
display
NT20M-ZASAT
Support Tool
-EV4
onwards
FXFXAll models
FXFXAll models
FXFXAll modelsX: Equivalent display
-EV1-EV1-E
NT600M-SMRjjj
System ROM
PT ModelsRemarks
X: Horizontal only.
X: Select either 8 or 16
dots.
X: + direction only.
X: Equivalent display
only.
X: Rectangular only.
X: Mark input not
possible.
DT-type onlyX: Rectangular frame
only.
Only when the screen
(See note 1.)
attribute “10-key” is set to
“User.”
only.
Notes 3. Some restrictions may apply, depending on the PT model.
4. In order to use the direct connection function, a Support Tool version of
“-EV4” or higher must be used.
1-6System Configuration
In order to operate the NT600M, connect a personal computer or a Programmable Controller, to serve as a host, to the Host Interface Unit (sold separately) at the back of the NT600M. For details on connecting the Host Interface Unit, and on host programs, refer to the
Manual
The following interfaces can be used for communications: RS-232C,
RS-422A, Wired Remote I/O System (SYSMAC BUS), Host Link System
(SYSMAC WAY), or C200H Host Interface. A Screen Data Memory Board,
NT600M-MP/MRjjj, is also required and must be purchased separately.
Host Link InterfaceUsing the NT600M-LK201 Host Interface Unit, the Programmable Terminal
can be connected one-to-one to a Host Link Unit mounted to a Programmable Controller.
Mini H-type, C200H, C500, C1000H, C2000H PC
Host Link Unit
RS-232C
15 m max.
NT600M with
NT600M-LK201
SYSMAC BUS InterfaceUsing NT600M-RT121 Host Interface Units, up to 8 Programmable Terminals
can be connected to a PC through a Wired Remote I/O Master Unit.
8 Terminals max.
C200H, C500, C1000H, or
C2000H PC
NT600M with
NT600M-RT121
Remote I/O
Master Unit
200 m max. (2 wire cable)
C200H Host InterfaceWith an NT600M-LB122-V1 (for direct connection) Interface Unit, the inter-
face is set up simply by connecting one-to-one with C200H-CN221 Connection Cable to a C200H CPU Rack or Expansion I/O Rack. It is also possible
to connect a PT to a C20H, C28H, C40H, or C60H CPU Unit or I/O Units. Be
sure to use a noise filter when connecting CjjH. Refer to the
Units Operation Manual
for details.
Host Interface
12
Be sure to use a noise filter (TDK’s ZGB2202-O1U or equivalent) when connecting to the Mini H-type PC.
1, 2, 3...
1.The noise filter must be inserted into the power line of the Mini H-type
PC.
2.The distance between the noise filter and the Mini H-type PC must be as
short as possible.
3.Keep the noise filter away from high-tension lines.
4.The case of the noise filter must be grounded to the FG terminal of the
In a C200H PC System, you can ordinarily connect two Expansion I/O Racks to
the CPU Rack. The C200H Host Interface Unit itself, however, functions as an
Expansion I/O Rack, and therefore when using a C200H Host Interface Unit, you
can only connect one other Expansion I/O Rack. (If the CPU Rack is either
C200H-CPU02 or C200H-CPU22, it is not possible to connect both an Expansion Rack and a PT.)
CPU Rack
C20H/28H/40H/60H
CPU Unit
C200H Expansion I/O
Connection Cable
Expansion I/O Rack
NT600M PT + NT600M-LB122-V1
1-7Nomenclature and Functions
1-7-1Front Panel
The illustrations below show the front panels of PTs with and without touch
panels (i.e., DT-type and DN-type PTs) and PTs with function keys (i.e., DFtype PTs). A 12-key Function Key Unit can be attached to a DN-type PT to
give it the same outer appearance and functions of a DF-type PT.
CjjH I/O Unit
NT600M PT +
NT600M-LB122-V1
NT600M-DT/DNjjj: Programmable Terminals With and Without a Touch Panel
POWER Indicator (green)
Lit while power is on.
RUN Indicator (green)
Lit during operation
BAT LOW Indicator (red)
Lights if the lithium
battery voltage level
drops.
Display
Touch Switches (touch panel type only)
Used as an input device corresponding to
the display screen.
There are switches to set under the switch cover on the back of the Terminal
and also on the Host Interface Unit. For Host Interface Unit switch settings,
refer to the
Host Interface Unit Operation Manual
2-1-1System DIP Switch Settings (SW1)
The 8-position DIP switch for system settings is located under the DIP switch
cover on the back of the Terminal. Be sure that power is off when changing
switch settings.
SW1
ON
12345678
Communications specification
(only for when NT600M-LK201 is mounted)
ON:Host Link
OFF:RS-232C
Not used.
Mode change enable/disable
ON:Enable
OFF:Disable
Not used.
(The settings at the time of shipping
are as shown on the left.)
.
Bit designation for lamps/touch switches
ON:0 to 63
OFF:0 to 111
Reserved for system use. (Always keep ON.)
HOST RUN input enable/disable
ON:Disable
OFF:Enable
Automatic reset after communications error
“Automatic reset” means that, when an error occurs, no error message
will be displayed and the next command will be executed when received.
“No Automatic reset” means that, when an error occurs, an error message will be displayed and operation will stop. If an RS-232C or RS-422A
Interface Unit is mounted, the host will be notified that an error occurred
and there will be no automatic reset regardless of whether this pin is set
to ON or OFF.
If this pin is turned OFF, then the host RUN input will be enabled and PT
operation can be controlled by external sequences. If this pin is set to
ON, the PT will operate but when the host RUN input turns OFF, Host
Error will be displayed and operation will stop.
pin is set to OFF, messages will not display properly.
This pin designates the bits for lamp and touch switch display control for
when Host Link Interface Units or C200H Host Interface Units are used.
“Mode change” refers to changing between the System Menu and Transmit Mode, Maintenance Mode, or RUN Mode. When an RS-232C or
RS-422A Host Interface Unit is used, mode changes can be prohibited
by means of a command from the host.
The NT600M-LK201 can be used as either a Host Link Interface Unit or
an RS-232C Interface Unit. Operation will not be possible if the setting of
this switch does not match the communications system. If another type
of Host Interface Unit is mounted, this setting will be ignored.
2-1-2Mounting System ROM
Turn off the power supply to the PT and mount the System ROM into the PT
as described below.
1, 2, 3...
1.Open the System ROM cover on the back of the PT.
2.When the System ROM cover is opened, the IC socket will be exposed.
Turn the tightening screw (located to the left of the IC socket) to align
the slot with the O (open).
Label
Tightening
screw
3.Mount the ROM to the socket in the direction indicated on the label and
turn the tightening screw clockwise to the C (close) secure the ROM.
Socket
0
CautionThe ROM may be destroyed it mounted while power is being supplied to the PT.
!
0
Insufficiently tightened
Turn off the power supply before mounting the System ROM.
Notes 1. The PT may not operate properly if the IC socket is not completely se-
cured. Be sure to install the System ROM securely.
2. OMRON reserves all copyrights to the programs on the System ROM.
Copying these programs is forbidden.
2-1-3Screen Data Memory Board Settings and Installation
There are two types of Screen Data Memory Board: SRAM type and IC socket type. The NT600M-MP251 Screen Data Memory Board does not come
with a memory chip installed, and the memory chip must be purchased separately.
The memory type and capacity must be set for the NT600M-MP251.
Switches SW M1 and SW M2 are used to set the type and capacity of the
screen data memory chip installed in the top socket of the Screen Data
2.Place the Screen Data Memory Board on the main rail, push the spacer
in the direction of the arrow until it makes a clicking sound, and line the
board up with the connector.
Rail
Spacer
Connector
Lined up with connector
3.Holding the Memory Board’s installation fitting as shown in diagram A,
insert the black latch on the bottom into the hole in the main unit and
press the black knob down until it clicks into place.
When the knob is
pulled up, it looks
like Illustration A
on the left.
Installation fitting
Black knob
Black latch
AB
Installation fitting
Spacer
Screen Data Memory Board
When removing the Screen Data Memory Board, first turn off the power to
the PT and then remove the installation fitting by pulling up on the black
knob. Then pull the Memory Board’s spacer in the opposite direction of that
shown above and take out the Memory Board.
2-2Installation Environment
The NT600M has strong environmental resistance and high reliability, but you
can maximize system reliability and make the most of its functions by observing the following considerations during installation.
2-2-1Installation Site
Avoid installing the NT600M where any of the following conditions exist.
• Ambient temperatures exceeding a range of 5°C to 40°C for liquid crystal
• When installing the Terminal near devices with strong electrical or magnetic
fields (such as solenoids), allow a distance of at least 40 mm, more if necessary.
Solenoid
40 mm min.
Solenoid
NT600M
40 mm min.
2-3Dimensions
All dimensions are in millimeters.
2-3-1Terminals with Function Keys (DF-type)
The dimensions illustrated below are for PTs with function keys (i.e., DF-type
PTs). PTs without a touch panel (i.e., a DN-type PT) will have the same outer
appearance and dimensions as a DF-type PT.
2-3-2PTs With (DT-type) and Without (DN-type) Touch Panels
313
198
325
2-4Installing the NT600M PT in a Panel
The NT600M is designed to be inserted in a panel. Install as follows:
1, 2, 3...
1.Cut a hole in the panel in accordance with the recommended dimensions shown below. The panel should be between 1.6 and 4.8 mm thick.
All dimensions are in millimeters.
2.Insert the PT into the hole from the front of the panel.
3.Use the accessory metal fittings and tool to fasten the PT to the panel
surface. Do not use a screwdriver. A screwdriver may damage the fittings or the PT.
After setting the PT in the panel, secure it as shown below.
(1)
Fitting
(1) First pass the plastic part of the fit-
ting through slot (a).
Plastic
(2)
(2) Next, put the hook of the fitting into
slot (b) and pull so that the leg
NT600M
(a)
(b)
catches in the PT case.
Accessory tool
(3) Turn the screw with the tool that
NT600M
comes with the PT, and secure
the PT to the panel. There are six
places to be secured. When you
are finished, rotate the tool in the
inverse direction and remove it
from the screw.
24
4.To remove the PT from the panel, use a flat-blade screwdriver.
The terminal block shown in the following illustration is located on the PT’s
rear panel.
HOST
RUN
INPUT
50/60 Hz
ALARM
OUTPUT
Terminal screws: M4
LGGR100 to 240 VAC
Use crimp-style terminals for wiring. If twisted wires are connected directly,
there is a possibility of poor contact or short-circuiting. Use crimp-style terminals with holes to match M3.5 screws.
Fork-type
7 mm max.
Round-type
8 mm max.
Recommended Crimp-style Terminals
MakerFork-typeRound-typeConforming wire (twisted)
Japan Solderless Terminal MFG2-YS3A2-3.51.04 to 2.63 mm
Fuji Terminals2-YAS3.5V2-S3.5
Nichifu Terminals2Y-3.52-3.5
2-5-2AC INPUT Terminals
These terminals are the power supply input terminals to run the NT600M.
MCCB
100 to 240 VAC
50/60 Hz
Power Supply Wiring
Insulated
transformer
• Provide a 100 to 240 VAC power.
• Use a power supply within the allowable voltage range.
The NT600M has built-in anti-noise features which are sufficient for handling general noise from power lines, but ground noise can be greatly reduced by supplying power through a 1:1 insulated transformer. The secondary side of the insulated transformer should be an isolated neutral system.
• Power Capacity
Use a rated power supply (100 to 240 VAC; 50/60 Hz) of at least 50 VA.
2
• If power lines are long, then use wires of at least 2 mm
to avoid a drop in
voltage.
• Use twisted-pair cables.
2-5-3LG and GR Terminals
HOST
RUN
INPUT
100 to 240 VAC
50/60 Hz
ALARM
OUTPUT
LGGR
Terminal screws are M4.
• GR is the ground terminal. In order to avoid electric shock, use separate
2
ground wire (at least 2 mm
) and a class-3 ground (ground resistance
100 W or less).
• LG is the noise filter neutral terminal. If malfunction results from excessive
noise, or to prevent electrical shock, short-circuit LG and GR and use a
class-3 dedicated ground.
• The ground line should be 20 m or less.
• Sharing a ground line with other machinery or grounding to the girders of a
building may be harmful.
2-5-4HOST RUN INPUT Terminals
Use the HOST RUN INPUT when you want to monitor the RUN status of the
host.
Enable:Turn OFF SW1, pin 2.
Disable:Turn ON SW1, pin 2.
Rated input voltage24 VDC
Input impedance5.6 kW
Input current4.1 mA typical (at 24 VDC)
ON voltage14.4 V min.
OFF voltage5.0 V max.
+10%
/
–15%
If host RUN input goes OFF when this terminal is enabled, a host error is displayed regardless of other conditions and processing is halted. This status is
maintained until the host RUN is restored. When errors are displayed on the
PT screen, it allows for rapid recognition of problems at the host.
2-5-5ALM OUTPUT Terminals
DC Load
100 to 240 VAC input
External device
Load
ALM output
Item
Output typeRelay output
Rated load0.5 A at 100 VAC or 1 A at 24 VDC
Maximum load current1 A
Minimum switching capacity10 mA at 5 VDC
2-6RS-232C Interface Connector
The RS-232C interface connector is used during communications between
the NT600M and Support Tool. It is located under the RS-232C interface connector cover on the back of the NT600M.
This section provides an introduction to the operations necessary to use a PT for the first time and to the menus and keys
used to control PT operation.
When first starting up the system, do not connect the Host Interface Unit to
the host. When power is turned on to the PT, either a “Connecting to host”
message or the initial screen set by the Support Tool will be displayed. The
“Connecting to host” message will be displayed if a Host Link Interface Unit,
a SYSMAC BUS Interface Unit, or a C200H Host Interface Unit is mounted.
The initial screen will be displayed if an RS-232C or RS-422A Interface Unit
is mounted.
If there is no screen data registered for the PT, or if there is an error in the
screen data that is registered, then the System Menu will be displayed
instead, with an error message at the bottom. In that case, it will be necessary to initialize the memory and transmit the correct data.
3-2Initialization
Initialize the memory in the PT using the procedure described below. This
procedure can also be used later to completely delete data from the PT. Data
will be initialized regardless of the setting for the resume function. Always be
careful not to initialize and delete essential data.
3-2-1Initializing Memory
Perform the initialization if the screen memory is either SRAM or EEPROM.
Check to be sure that the screen memory is installed.
Memory initialization can be used to initialize screen memory, memory tables,
and history data. Initializing screen memory completely deletes the contents
of the screen memory, including the contents of numeral tables and text
string memory tables. Initializing memory tables overwrites numeral tables
and text string memory tables with the initial values set by the Support Tool.
Initializing the display history deletes all of the display history data.
To initialize the screen memory, for example, first access the System Menu
by simultaneously pressing the Buzzer Key, Up Key, and Down Key. Then
proceed as shown as shown in the following chart.
System Menu
Select “MAINTENANCE MODE.”
Select “Init. Memory.”
Select “Init. Screen.”
Initialize Screen Memory?
Yes
No
Refer to Section 6.
If you select yes, then memory will be initialized and all data used for displays
will be erased. After initialization, operation will begin in RUN Mode.
If you select no, then operation will begin in RUN Mode without initialization.
When entering RUN Mode after initialization, nothing will be displayed on the
screen and the Terminal will wait for a command from the host.
To initialize other data memory, return to the Maintenance Mode and follow
the same procedure.
CautionScreen memory must be initialized before using a new PT. If the PT is used as
!
shipped from the factory without initialization, messages indicating errors in the
host will not be displayed properly.
The System Menu is called up by using the the system keys during operation. The System Menu can always be displayed regardless of the PT mode.
If there is no key input for 10 seconds after the System Menu has been
called up, the System Menu will be exited and RUN Mode will return.
SYSTEM MENU
Quit
Transmit Mode
Maintenance Mode
Expansion Mode
Using System Keys
OperationContent
Press the Buzzer Key, Up Key,
and Down Key simultaneously.
Press the Up Key.Moves the bar cursor upward.
Press the Down Key.Moves the bar cursor downward.
Press the Enter Key.Selects the menu at the position of the bar cursor.
Pressing the Up Key and Down Key while the Buzzer Key is being held down changes
PT modes and menus in the following ways:
RUN Mode → System Menu
System Menu → RUN Mode
Maintenance Mode → previous screen or RUN Mode
Transmit Mode → RUN Mode
V1.x
Version no.
QuitLeave the system menu and return to operation by either of the following
methods.
1, 2, 3...
1.Select “Quit.”
OR
2.Press the Buzzer Key, Up Key, and Down Key simultaneously.
In addition, if there are no key inputs within 10 s of calling up the system
menu, the system will automatically return to normal operation.
Selecting ItemsTo select an item, move the bar cursor to that item and press the Enter Key.
Selected itemFunction
QuitQuits and return to normal operation.
Transmit ModeShifts to Transmit Mode.
Select when transferring data between the NT600M and Support Tool. For details, refer to
Transferring Data to and from the Support Tool
Maintenance ModeShifts to Maintenance Mode.
Used to check the setting status of the NT600M and conduct self-testing.
Expansion ModeNot used. Reserved for future function expansion.
Transferring Data to and from the Support ToolSection 3-3
Error MessagesWhen there is an error in screen data registered in the NT600M, the System
Menu will appear before entering RUN Mode, and the error message will be
displayed on the bottom line.
System Menu
Quit
Transmit Mode
Maintenance Mode
Expansion Mode
Screen Data CorruptedExample of error message
V1.x
Version no.
There are three types of error messages, as shown below. If an error message is displayed, first initialize the screen data memory before re-transmitting the data. Operation will not begin again until the error has been corrected.
Error messageError Content and Correction
Screen Data CorruptedThis is displayed when registered screen data is corrupted. Initialize the screen data and
then re-register it. Operation will not begin again until the data is restored.
Mark Data CorruptedThis is displayed when registered mark data is corrupted. Initialize the screen data and
transfer the screen data files. The mark data is included in the screen data files. Re-register
the mark data. Operation will not begin again until the data is restored.
Memory Not FormattedThis is displayed when the screen data area is not formatted. Initialize the screen data
memory. All registered screen data, mark data, and system data will be deleted by the
initialization, so they will have to be transferred again from the Support Tool. In addition, if
an IC socket-type Screen Data Memory Board is being used, recheck the socket’s memory
and its settings.
3-3Transferring Data to and from the Support Tool
Data can be transferred back and forth between the NT600M and the Support Tool. Transfer the screen data created by the Support Tool before operating the NT600M.
ProcedureUse the following procedure to transfer data.
1.Connect the NT600M and personal computer running the Support Tool.
2.Select Transmit Mode from the System Menu.
System Menu
Refer to
Select “Transmit Mode.”
3-1 Powering Up
.
3.At the NT600M, it is only necessary to place the NT600M in Transmit
Mode. The direction of transmission and the contents of the data to be
transmitted are set at the Support Tool. (For instructions on operating
the Support Tool, refer to the
NT-series Support Tool Operation Manual
.
35
Page 46
Transferring Data to and from the Support ToolSection 3-3
4.When the data transfer begins, the direction of transmission, the type of
data being transmitted, and the memory capacity are displayed on the
screen.
Abort:
Transmit Mode
KB
PT ––> Tool
Tool ––> PT
Screen Data
System Memory
Memory Tables
Mark Data
History Data
Number of bytes transferred (in kilobytes).
Press these three System Keys simulta-
neously to stop the transfer in progress.
Shows direction
of data transfer.
Shows type of data.
5.When the data transfer has been completed, those items will no longer
be displayed.
Transmit Mode
36
Abort:
6.In the event of a disconnected cable or other disruption while the transfer is in progress, the NT600M screen will go blank and a message telling you that transfer was not possible will be displayed at the Support
Tool. If the transfer is completed successfully, then at the end of the
transfer the NT600M screen will go blank and a message telling you that
the transfer has been completed will be displayed at the Support Tool.
7.To return from Transmit Mode to RUN Mode, press the Buzzer Key, Up
Key, and Down Key simultaneously.
CautionAfter the transfer has been completed, be sure to return to RUN Mode by press-
!
ing the Buzzer Key, Up Key, and Down Key simultaneously. If the power is turned
off or if a reset is executed without having first returned to RUN Mode, the data
that has been transmitted will be corrupted. If that occurs, a message will be displayed on the screen to indicate that the data has been corrupted.
The following data can be transferred between the NT600M and the Support
Tool.
DataSupport Tool to NT600MNT600M to Support Tool
Screen dataAll screens or one screenAll screens or one screen
Character string tableYESYES
Numeral tableYESYES
Mark dataYESYES
Display history data (in
order of frequency or in
order of occurrence)
System Memory (Initial
screen after power-up)
NoneYES
YESYES
Note When using the EEPROM as a screen data memory, screens cannot be
transferred screen by screen from the Support Tool to the PT. The screen
data must be transferred in file units after initializing the memory.
3-4Trial Operation
After screen data has been transferred, or after a screen data memory chip
has been installed (when EPROM is used), the following procedure can be
used to carry out a trial operation.
1, 2, 3...
1.Connect the Host Interface Unit to the host. (Refer to the
Operation Manual
.)
Host Interface
2.If the screen data memory is okay, then the PT will automatically go into
RUN Mode when it is powered up, and the RUN indicator on the front
panel will light.
3.Check the host-to-PT communications by transmitting a screen-change
command from the host, and checking whether the screen is changed.
4.Check the PT-to-host communications by transmitting to the host by
means of function keys, touch switches, and external inputs, and seeing
that they are all transmitting properly.
5.If communications with the host cannot be executed properly, refer to
This section describes the functions used to create screens and control display attributes on the PT. Functions used to input data on-screen are described in Section 5 Input Functions. Data transfer and maintenance functions are described in
Section 6 System Menu. Transferring screens online to and from the host computer is described in Section 7 Online
Transfer.
The type, size, and attributes of characters that can be displayed on the
NT600M screen are shown on the next page. Character type, size, and attributes are set at the time of creation on the Support Tool. When an
RS-232C or RS-422A Host Interface Unit is used, coordinates, characters,
etc, can be designated with commands from the host in Terminal Mode.
4-1-1Types of Characters
Character fonts
Numeric display
Character scaleNo sizing (equal), double-width, double-height, 4x, 9x, 16x, or 64x character sizes
Display attributesStandard display, inverse, blinking, and, inverse blinking
Note When zero suppress is in effect, zeros on the left of the number are not dis-
Half-size characters (8 x 8 dots)Alphanumeric characters, symbols.
Normal characters (8 X 16 dots)Alphanumeric characters, symbols.
Marks (16 X 16 dots)Pictographs defined by the user (up to 64 possible)
Character codes: FF20 to FF5F
Number of digits displayed1 to 8
Number of decimal digits0 to 7
Zero suppress (see note)Select “yes” or “no.”
+/– signSelect “yes” or “no.”
played. For example, “00028050” would be displayed as “28050”.
4-1-2Designating Display Positions
The display positions can be designated in increments of display dots. When
characters overlap, characters written last overwrite those written earlier.
(Terminal Mode)
4-1-3Character Scale
You can designate no sizing (equal), double-width, double-height, 4x, 9x,
16x, or 64x character sizes. When enlarging by 4x or more, you can make
the characters easier to read with the smoothing process (a process that removes the notches from characters when they are enlarged).
Besides the standard display (black characters on a white background), you
can designate individual characters as inverse, blinking, or inverse/blinking.
BlinkingInverse blinking__
Note You cannot designate the blinking cycle.
64x characters
4x
characters
9x characters
4x characters
Wide characters
Double-height characters
Normal
characters
16x
characters
4-2Display Graphics
Polylines (broken continuous lines) and circles can be created on the Support Tool for display on the PT. When using RS-232C or RS-422A communications, coordinates can also be designated through commands from the
host in terminal mode.
64x characters
16x characters
16x characters
64x
characters
9x
characters
16x
characters
16x
characters
4x characters
4x
characters
Wide characters
Display positions for graphics can be designated at dot increments and can
overlap characters on the display. When they overlap, graphics are displayed
on top of characters.
Either continuous lines (called polylines) or circles can be designated. Line
widths are 1 dot for either.
The displayed screen can be changed to another screen by designating the
screen number from the host (a Programmable Controller or personal computer). The designated screen must have already been created at the Support Tool and downloaded to the NT600M or it must have been placed in
ROM, with the Screen Data Memory Board installed.
4-3-1Procedure for Changing Screens
Standalone Function
1, 2, 3...
Screen 1Screen 2
1.By designating a screen number (0 to 1,000) from the host, you can
switch to the designated screen.
Note Screen no. 0 is blank (with no display).
2.When an ordinary screen is displayed, the screens cannot be changed
by means of the Up and Down Keys on the front panel of the NT600M.
3.The screen-changing procedures vary for each interface. For details,
refer to the
When Support Tool versions NT-ZA3AT-EV2 or NT20M-ZASAT-EV4 and later
are used, screen changes can be made on-site. In order to be able to make
on-site screen changes, when creating screen data use the expansion function to assign screen numbers to touch switches, function keys, or external
inputs.
Host Interface Unit Operation Manual
.
Screen 2Screen 1
4-4Continuous Screens
Screens can be linked to display consecutively, without breaks. A maximum
of eight screens can be made consecutive, and treated as one screen.
• By pressing the Up Key and Down Key, you can scroll screens up or down.
• Page number displays are designated on the Support Tool at the time of
For example, here a touch switch is assigned
the screen-change function.
Page 52
Overlapping ScreensSection 4-5
ExampleIf screen 9 is designated from the host, the content of screen 20 is displayed
first. If you press the Down Key, you scroll down to the next screens.
Parent screen for consecutive screens
Screen no. 9
20→21→23
Register the screen numbers of the child screens
that you want to make consecutive. (You can set
screen numbers in any order you want.)
Screen contents
Screen
20
21
22
23
A
B
C
D
Screen no. 9: Screens displayed
20
21
23
A
B
D
Note 1. Parent screens (screen no. 09 in this case) cannot have screen data.
They can be treated only as parent screens.
2. Scrolling is done in screen units.
3. Screens with numeric settings cannot be designated as child screens.
4-5Overlapping Screens
The contents of multiple screens can be laid one on top of another and registered as one screen, when the screens are created on the Support Tool. Just
as with ordinary screens, if the number of a screen registered as an overlapping screen is designated from the host, then the overlapping screens corresponding to that number are displayed.
• A maximum of eight screens may be overlapped.
• Screens with touch switches, lamps, graphs, character strings, and numeric
displays can be overlapped. If screens with numeric settings are to be overlapped with screens that have touch switches or lamps, then use touch
switch/lamp numbers 0 to 243 (or 0 to 230 when the ten-key is registered to
“user”). In addition, do not overlap touch switches/lamps with numeric keys.
• An overlapping screen cannot be set as a child screen of a continuous
A numeral table is stored in the NT600M, and you can display numeric values from the table at designated positions on a screen. In addition, the values in the table can be transferred from the host so that they are renewed
each time a new value is transferred. The display positions are set in advance with the Support Tool.
Example
Screen Registered
Production
Line 1
Weld
Paint
Assem
Final
Contents registered to screens by Support Tool:
Numeral table numbers
Display positions (50/screen max.)
Number of digits displayed (whole numbers, fractions)
Character fonts
Sizes of characters displayed
This function displays variable character strings on the screen. A character
string memory table is stored in the NT600M. By changing, from the host, the
memory table values corresponding to the display position, you can update
the characters displayed. The designation of the display positions is set in
advance at the Support Tool.
Example
Screen Registered
Production
Line 1
Weld
Paint
Assem
Final
Contents registered to screens by Support Tool:
Character string memory table numbers
Display positions
Number of characters displayed
Font displayed
Sizes of characters displayed
Character String Table
(Maximum of 256 entries)
Number
# 0Van
# 1Car A
# 2Car B
# 3High-roof
# 4Sports car
# 5Convertible
# 6
# 7
to
#255
# 0
# 1
# 2
# 3
Line 2
# 4
# 5
# 6
# 7
Contents
Weld
Paint
Assem
Final
Screen Displayed
Production
Line 1
Van
Car A
Car B
High-roof
Line 2
Sports car
Convertible
These contents are transmitted from the host.
When the PC is used as the host, for example, these values will be transferred via the Host
Interface Unit and updated on screen when the contents of the DM Area are changed at the
PC.
If the numeric values that you want to make into a bar graph have been input
into the numeral table in advance, then that graph can be displayed simply
by designating the screen on which the graph is registered. Just as with numeric displays, the graph display is also updated when the contents of the
numeral table are updated. Bar graphs can be displayed either horizontally or
vertically. They can also be displayed in the negative direction.
Example
Graph Display
Production Targets
Line 1
Line 2
Line 3
Contents registered to screens by Support Tool:
Display positions (50 bars max.)
Graph width (2 to 255 dots)
100% value
% display (yes/no)
% display position
Numeral table numbers for referencing
Display direction
Graph frame (yes/no) (see note)
Sign display
% display fonts
% enlargement sizes
+/– sign (yes/no)
Numeral Table
(Maximum of 256 entries)
Number
# 01020
# 1832
# 2711
to
#255
# 0
# 1
# 2
Contents
Production Targets
Order
With sign
Reverse
Line 1
Line 2
Line 3
Production Targets
10%
Note: When “with frame” is set for a graph, the width
of the graph is reduced by two dots, so in that case
the graph must have an original width of at least
three dots.
On the Support Tool you can set lamp areas in the display screen, and the
lamps will light (or blink) by means of a designation from the host. Lamps are
registered in advance at the Support Tool.
Display position:Can be set as desired, but must match the switch
frames when combining lamps with the switch function.
Shape:Rectangle or circle
47
Page 57
Special ControlsSection 4-11
Size:Can be freely set with a rectangle or a circle.
Number:128 maximum per screen
Display attributes:Lit, blinking
Guide characters:Select “yes” or “no.”
Lamps set from the host can be turned on and off by either of two methods:
number designation or bit designation (when there is no direct connection).
For details, refer to the
Host Interface Unit Operation Manual
.
Example 1: Usage with
Switch Frames
Example 2: EmphasisThe display of the number defective can be emphasized setting it to light.
If using a lamp together with a switch, then set the lamp within the switch
frames, of which there are 12 horizontal and 6 vertical.
Goal
Complete
Defective
1234
600
2
4-10Graphics Display
Unbroken straight lines (polylines) and circles can be created by the Support
Tool and displayed at the PT. When an RS-232C or RS-422A Interface Unit is
used, the graphics can be displayed by using the terminal function and transmitting commands from the host.
Designating Display
Positions
Graphics display positions can be designated in dot units. In cases where
graphics and characters overlap, the graphics will be overwritten (Terminal
Mode). Polylines and circles are both drawn with a width of one dot.
4-11Special Controls
The status of the NT600M to be controlled from the host during operation.
4-11-1Backlight ON/OFF
In order to prolong the life of the backlight, the backlight can be turned off by
a backlight-off command from the host when it is not needed during operation.
Note If there is any key input or transmission while the backlight is off, the back-
light will turn on again.
4-11-2Alarm Output On/Off
The output of the ALM OUTPUT terminal, which is located in the terminal
block on the rear panel of the NT600M, can be turned ON and OFF from the
host. The ALM OUTPUT terminal is turned ON and OFF when a screen registered for an alarm is displayed, and also when there is an NT600M error.
ALARM
OUTPUT
4-11-3Buzzer On/Off
The built-in buzzer can be turned on and off from the host. There are two
types of buzzers, continuous and intermittent. The buzzer also sounds when
a screen registered with the buzzer is displayed. The buzzer stops when the
Buzzer Key is pressed.
Continuous
buzzer
Intermittent
buzzer
4-11-4Initialize Display History
History data in the NT600M can be cleared (initialized) by the host. Until this
operation is executed, history data continues to be registered.
4-11-5HOST RUN INPUT
The HOST RUN INPUT detects when the host in not in RUN, and displays
the host error screen. Pin 2 of SW1 is used to enable and disable this input.
When the HOST RUN INPUT is enabled, the host error screen is displayed if
it turns OFF.
Pin 2 of SW1 ON:HOST RUN INPUT disabled.
Pin 2 of SW1 OFF:HOST RUN INPUT enabled.
The display background can be set to either normal or inverse. The normal
background is white, and the inverse background is black.
Normal displayInverse display
Normal display
4-12Terminal Function
This function allows you the option of displaying, by transmission on command, the codes (coordinates, type, etc.) of characters and figures you want
to display from the host, in addition to screens registered in advance. This
function is possible only when the Host Interface Unit is the NT600M-LK201
for the RS-232C or the NT600M-LK202 for the RS-422A. For details, refer to
the terminal commands listed in the
tion Manual
Display positionOptional
Character sizeNormal, half-size, double-height, double-width, 4x, 9x, 16x,
Display attributesNormal, inverse, blinking, inverse blinking
Character designation ASCII
GraphicsPolyline, circle
Inverse display
RS-232C/RS-422A Interface Unit Opera-
.
ItemContent
or 64x
Note 1. If a displayed character string exceeds the line, that string is displayed
2. In addition, strings that do not fit at the bottom of the screen over-write
4-13Display Speed
NT600M display speed varies according to the amount of elements displayed
on the screen. As a standard, the following diagrams shows the time required
for changing displays on screens that include characters.
System ROM:NT600M-SMR02-EV1
Host Interface Unit:NT600M-LB122-V1
Screen data:Character display (1 to 40 characters)
Measurement time:Time (in ms) from when the PT receives the
beginning from the left side of the next line.
from the left side of the same screen.
command until the display is executed.
Page 60
Display SpeedSection 4-13
Time it Takes to Display the Same Normal Characters
This section describes the functions used to input data on-screen. Functions used to create screens and control display
attributes on the PT are described in Section 4 Display Functions. Data transfer and maintenance functions are described
in Section 6 System Menu. Transferring screens online to and from the host computer is described in Section 7 Online
DT-type PTs can transmit to the host the input status of touch switches set on
screens. A maximum of 64 switches can be set per screen. DN-type PTs can
transmit to the host the inputs of 12-key Function Key Units. DF-type PTs can
transmit to the host the input status of the function keys located at the bottom
of the display. (The standard number of function keys is 12.)
5-1-1Transmitting to the Host
There are two ways to transmit the input status of switches to the host.
These two methods, which are determined by a “screen attributes” setting at
the Support Tool, are described briefly below. For more detail, refer to the
Host Interface Unit Operation Manual
tributes, refer to the
NT-series Support Tool Operation Manual
Switch-number MethodIn order to use the switch-number method, “bit input” screen attribute must
be set to “disabled.” Using this method, when a switch is pressed the number
corresponding to that switch is transmitted to the host as a numeric value in
three digits of BCD. When two switches are pressed, the first one is given
priority in transmission. When using an NT600M-LK201 or NT600M-RT121
Host Interface Unit, send the data to the host by means of the strobe signal
in the PT status information which is output when switches are pressed.
. For instructions on setting screen at-
.
Bit-switch MethodIn order to use the switch-number method, “bit input” screen attribute must
be set to “enabled.” When this method is used, the status of each switch is
transmitted to the host as a bit status. This is the method used when substituting for ordinary operating switches. You can use it for ordinary bit input
switches from a Programmable Controller.
Note With this method, it is possible to push a number of switches simultaneously.
The following considerations must be taken into account, however, when
configuring the switches.
Example 1: Switches Created at Points C and D, Which are Vertical and Horizontal Points of
Intersection for Points A and B
A
C
B
D
Minimum touch switch frame
If switches A, B, and C are turned ON
simultaneously in this switch configuration, switch D
will also turn ON.
If switches A, B, and D are turned ON simultaneously, switch C will also turn ON.
The NT600M-DF122 is the PT with function keys. DN-type PTs (NT600MDN-221) can also be provided with function keys by connecting a 12-key
Function Key Unit (NT600M-FK210).
Function keys
Example of Function Key Input Screen
Time Setting
PV
SV
1234567890CLR+/–
The function keys all have the same size screen display frames. You can display customized function names on the screen to identify them. Up to two
function keys can be pressed simultaneously.
Numeric values input while the numeric setting screen is being displayed are
written to the designated numeral table and transmitted to the host.
The standard numeric setting screen is as shown below. This screen is reserved for system use by the Support Tool. Standard screen key arrangements and functions are fixed. In order to change the key arrangement or
add keys (such as a decimal point) for numeric input, set the “numeric setting” item under “screen attributes” to “user.” (When it is set to “system,” the
Page 66
Inputting Numeric SettingsSection 5-2
standard screen will be displayed.) For instructions on registering numeric
setting screens, refer to the
NT-series Support Tool Operation Manual
.
Standard Screen (Screen Attribute: System)
1234567890
Creating Numeric Setting
Screens
When creating a numeric setting screen with the Support Tool, take note of
the following points.
CLR +/–
1) A numeric setting screen cannot be set as the child screen of a continuous
screen.
2) Ordinary touch switches can be set in numeric input screens, but touch
switch numbers 244 through 255 cannot be used.
User-set Screen Example
(Screen Attribute: User)
Tank ATank B
06500654
Tank CTank D
05500000
Tank ETank F
09900800
HOMEMENU
123
456
789
0
CHANGE
↑
↓
←
.
CLR
→
SET
Inputting Numeric Values
(PTs With Touch Panels)
Inputting Numeric Values
(PTs Without Touch Panels)
3) When “10-key” is set to “user” in the screen attributes, touch switch numbers 231 through 255 cannot be used for purposes other than numeric input.
4) The numeric setting function cannot be used when the screen attribute “bit
input” is enabled for PTs with no touch panel.
1) Inputting Numeric Values with the Standard Screen:
• The numeral shifts from the rightmost digit to the left each time a screen
key is pressed.
• If a decimal point is set, the shift is from the rightmost digit in the decimal
area to the integer side.
2) Inputting Numeric Values with a User-set Screen:
• The numeral shifts from the rightmost digit to the left each time a screen
key is pressed.
• If a decimal point is set, the integer portion is received first, and with each
numeric key input there is a shift from the rightmost digit to the left.
• When the decimal point key is pressed, the decimal portion will then be received. From that point on, with each numeric key input there is a shift from
the rightmost digit in the decimal portion to the left.
Use the 12-key Function Key Unit).
1) Inputting Numeric Values with the Standard Screen:
Use the corresponding function keys. Numeric input is the same as for PTs
with touch panels.
2) Inputting Numeric Values with a User-set Screen:
Use the corresponding function keys. Numeric input is the same as for PTs
with touch panels.
Numeric values input with the input keys are stored in the numeral table justified to the right, as shown above. When the CLR Key is pressed for the first
time, the initial display is cleared. If zero suppress were enabled, the number
displayed would be “0.000” instead of “0000.000.” When the “2” is then input,
it is registered at the rightmost integer position, as described on the preceding table. The “2” is then shifted to the left as the “7” is input. After the decimal point is input, numerals are then registered at the rightmost decimal position. (To return to integer input status, press the CLR Key again.) Finally,
pressing the Enter Key causes the numeral table data to be transmitted to
the host.
Pressing the direction keys (i.e., the arrow keys) moves the cursor to other
numeric setting columns. Pressing the Home Key moves the cursor to the
upper left of the screen.
When multiple numeric setting areas are created for a numeric setting
screen, cursor movement will be different depending on whether system keys
or touch switches are used.
Numeric setting 4
Numeric setting n: “n” represents the order
in which numeric setting areas are created
by the Support Tool.
58
Numeric setting 2
Numeric setting 5
Present cursor position
1) When System Keys are Used:
When system keys are used, the cursor moves from area to area in the order
in which the areas were created by the Support Tool. Thus, in the screen example shown above, the cursor would start at numeric setting 2 and move in
order to numeric settings 3, 4, 5, and back to 1.
When touch switches are used, the cursor moves from area to area according to the layout of the screen. Thus, in the screen example shown above,
the Down Key would move the cursor from numeric setting 2 to numeric setting 5. After that, the Down Key cannot move the cursor any further.
Pressing the Up Key would then move the cursor back to numeric setting 2,
and then continue to move it upward in order to numeric settings 1 and 3.
The Right Key would then have to be used to move the cursor to numeric
setting 4.
5-3Standalone Function
When a screen for which the standalone function has been set by the Support
Tool is displayed, the screen can be changed by means of touch switches and
function keys.
Example
Registered Screen
Production Target
Screen 5
Model no. NT600M-DT122
Number
produced
Items Registered to Screen by Support Tool
• Standalone function setting
• Touch switch or function key number
• Screen number to be displayed when touch
switches or function keys are input
Example
Standalone function is set.
Touch switch number:No. 1
Screen to be displayed: No. 5
2,500
Touch switch
no. 1 display
area
Screen No. 5
Production Conditions
Production target:5,000
Number produced: 2,500
Number defective: 2
When touch switch no. 1 is input,
screen no. 5 is displayed.
This section describes data transfer and maintenance functions. Functions used to create screens and control display attributes on the PT are described in Section 4 Display Functions. Functions used to input data on-screen are described in
Section 5 Input Functions. Transferring screens online to and from the host computer is described in Section 7 Online
Transfer.
The System Menu is used to set NT600M system parameters in advance
and perform maintenance. With the System Menu you can, in addition to determining the NT600M’s status, check switch settings and perform simple I/O
checks.
(1) If there is no key input within 10 seconds while the System
Menu is being displayed, the system will automatically return to
RUN Mode. To toggle between RUN Mode and the System
SYSTEM MENU
Menu, press the Up, Down, and Buzzer keys simultaneously.
(2) The RUN indicator will be OFF while the System Menu is being
displayed.
Quit
Quit
Occur.Freq.
QuitTouch Switch
Transmit Mode
Display History
Function Key
*3*4*5
Maintenance
Mode
(Maintenance Mode)
I/O Check
Quit
Quit
Expansion
Mode
PT Settings
Init. ScreenInit. TableInit. History
Key Press SoundBacklight OffResume
LCD DisplayComm. Check
Init. Memory
*1*2
LEDBuzzer
Memory SW
Display
Tool I/FHost I/F
*1: For PTs with EL displays, this becomes the residual image elimination function.
*2: This does not apply to PTs with EL displays.
*3: This in turn has two submenus: “Function Key Check” and “Lamp Check.”
*4: For PTs with EL displays, this becomes “EL Display.”
*5: This applies only to PTs with EL displays.
The NT600M saves into memory and can display the history of screens displayed during operation, as long as the history attribute has been set for
them by the Support Tool. The history can be displayed either in order of occurrence or in order of frequency. This function can be used to help identify
the causes of malfunctions or to enable the operator to know which functions
are often being used.
Setting History Data(1) When creating screens with the Support Tool, use screen attribute desig-
nations to register history attributes and messages (within 24 characters) for
the screens you want to save in the history.
(2) Whenever the screen number registered for history attributes is designated by the host, the occurrence and message are saved in memory. The
capacity of the history is 1,023 screens in chronological order or 255 occurrences per screen in frequency order. The only things that can be recorded
are screen numbers and messages. History record data is backed up by a
battery, so, as long as the battery is installed, the contents will be retained
even when the power is turned off.
(3) Before beginning to record, initialize the history data by transmitting an
Initialize History command from the host, or by selecting Init. Hist. from the
Maintenance Mode. If the history data capacity is exceeded, newly occurring history data will not be saved.
Reading History DataEnter Maintenance Mode from the System Menu.
MAINTENANCE MENU
Quit
Display Hist.
I/O Check
PT Settings
Init. Memory
Memory SW
Move the bar cursor to History Record by pressing the Up and Down Keys.
Then press the Enter Key.
History Record
Occurrence
Frequency
Select whether the history is to be displayed in order of occurrence or in order of frequency. First move the bar cursor to your selection by means of the
Up and Down Keys, and then press the Enter Key.
Order of OccurrenceRecord data is displayed in order of occurrence.
Message
Coolant Mal.
Motor Mal.
Comp. Mal.
Press Mal.
Number of times occurred.
Screen number
Page 73
System Menu and Transmit ModeSection 6-2
• Up to 48 items of registered data can be displayed on a screen.
• If not all of the record data shows on the screen, then use the Down Key to
scroll down.
• To return to the System Menu, press the Buzzer Key, Up Key, and Down
key simultaneously.
Order of FrequencyRecord data is displayed in order of frequency.
No.
200
Times
Of
( 2)
1
( 1)
5
( 1)
Message
Comp. Mal.
Coolant Mal.
Motor Mal.
Number of times occurred.
Screen number
When different messages occur with the same frequency, they are displayed
in order beginning with the lowest screen number.
When there is no display data, the following message will be displayed (for
both order of occurrence and order of frequency).
History Record Not Found
Initializing History DataTo delete history data, first select Maintenance Mode from the System Menu.
The Maintenance Mode Menu will be displayed. Then select “Init. Memory,”
followed by “Init. History.” A message will then be displayed asking for confirmation that you want to initialize the history.
6-2-6I/O Checks
Select whether or not the history is to be initialized. If you select Yes, then
initialization will be executed. All recorded history will be deleted. If you select
No, then operation will commence without initialization.
In the Maintenance Mode Menu, use the Up and Down Keys to move the bar
cursor to I/O Check. When you then press the Enter Key, one of the following
menu will be displayed, depending on the input switch specifications. With
the I/O Check Menu displayed, move the bar cursor to the item you want to
check, and then press the Enter Key.
The operation of the function keys can be checked. Press a function key. If
the number of that key is displayed in reverse video on the screen, then it is
operating properly.
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
Touch Switch Check (DT-type PTs)
The operation of the touch switches can be checked. Press each switch displayed on the screen. If the switch that has been pressed (for approximately
0.5 s) is displayed in reverse video on the screen, then it is operating properly. Switch numbers are not transmitted to the host during the check operation.
If “Key Press Sound” (under the Memory SW Menu in Maintenance Mode) is
set to “ON,” then the buzzer will sound simultaneously with the inverse video
display.
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
12-key Funcion Key Unit inputs and outputs can be checked if the Programmable Terminal is a DN type. Select “Exp. I/O Unit,” and then select either
“Function Key Input Check” or “Lamp Output Check.”
When the external input terminals are turned on one-by-one, the corresponding function keys are displayed in reverse video and can be checked. When
67
Page 76
System Menu and Transmit ModeSection 6-2
a 12-key Function Key Unit is connected, F1 through F12 correspond to IN0
through IN11.
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
Lamp Output Check
!
When “Lamp Output” is selected, “L1” is displayed in reverse video and output 1 turns ON. Use the Up Key and the Down Key to check all of the lamp
outputs. (The Up Key moves the reverse video location from left to right, and
the Down Key moves it from right to left.)
When a 10/02 Terminal or a 32/16 Terminal is connected, the corresponding
output turns on simultaneously with the lamp number that is displayed in reverse video.
When “Communications Check” is selected, the Communications Check
Menu is displayed. Use the Up and Down Keys to move the bar cursor to the
item you want to check, and then press the Enter Key.
COMM. CHECK MENU
Tool I/F
Host I/F
Page 77
System Menu and Transmit ModeSection 6-2
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
Tool Interface CheckData transmitted from the Support Tool is displayed in hexadecimal. If any
numeral is displayed, then the interface is operating properly. If no numerals
are displayed, then there is a Support Tool operation error, communications
cable error, or communications hardware error.
Host Interface Units with RS-232C Specifications (NT600M-LK201)
RS-232C I/F Input Check
1B 51 30 33
LCD/EL Display Check
The display check can be carried out for both the LCD display and EL display.
The lines of the display are reversed one at a time, starting from the top of
the screen. When the reversal is finished, then they are cleared one at a
time. When all of them have been cleared, the I/O Check Menu is returned
to. You can interrupt the check and return to the I/O Check Menu by pressing
the Buzzer Key, Up Key, and Down Key simultaneously while the check is in
progress.
Buzzer Check
LED Check
By selecting “Buzzer” from the I/O Check Menu, the PT buzzer can be
checked. The buzzer should produce a continuous sound. To stop the buzzer, press the Buzzer Key. While the buzzer is sounding, it will not be possible
to change screens or stop the buzzer by pressing the Buzzer Key, Up Key,
and Down Key simultaneously.
When PTs with EL displays (i.e., NT600M-DT/DN211 PTs) are used, a lighting check can be carried out for the front panel RUN and BAT LOW indicators. When“LED” is selected, the RUN and BAT LOW indicators should begin
to blink if they are operating properly. If the battery voltage is low, the BAT
LOW indicator will remain steadily lit.
6-2-7PT Settings Check
The status of the NT600M and Host Interface Unit can be checked, as well
as the settings of switches. First select “PT Settings” from the Maintenance
Menu. There are two screens. One displays the contents of PT settings, and
the other displays the contents of Host Interface Unit settings. Use the Up
Key and the Down Key to change back and forth between the screens.
PT SettingsWhen “PT Settings” is selected, the status of internal NT600M settings is dis-
• When an Expansion I/O Unit is connected to a DN-type PT, the 12-key
Function Key Unit type is displayed.
Standard:12-key Function Key Unit
Not Connected; No Expansion I/O Unit is connected.
• If a 12-key Function Key Unit becomes disconnected during operation, a
continuous buzzer will sound and a “No Expansion I/O Unit” error message
will be displayed.
Host Interface Unit Settings The DIP switch settings on the Host Interface Unit can be displayed by press-
ing the Down Key while PT settings are being displayed. The following display example is for the NT600M-LK201 Host Link Interface Unit. For examples of other Host Interface Units, see the
Manual
.
Host Link I/F Settings
Beginning wordDM0000
Number tables32
String tables8
Baud Rate9600 bps
Host Interface Unit Operation
Page
j
To return to the PT Settings display, press the Up Key.
6-2-8Initialization
You must initialize the internal memory when using the SRAM or EEPROM
for the first time. Initialization can also be used to clear all of the data already
registered in the NT600M. Screen data can be initialized regardless of the
setting for the resume function.
Initializing Screen MemoryIn order to initialize screen memory, for example, first select “Init. Memory”
from the Maintenance Menu. The Memory Initialization Menu will then be displayed, offering several choices of memory to initialize.
Screen dataScreen data and all kinds of set values
Memory table dataNumeral tables, string tables (Initialization restores
values set by Support Tool.)
Display history dataRetains the number of times a screen for which “history
attributes have been set is displayed by means of
commands from the host. (Only when battery is
installed.)
When “Init. Screen is selected, the following screen will be displayed for confirmation.
Initialize Screen Memory?
Yes
No
If you select Yes, then initialization will be executed and all screen data will
be deleted. After processing has been completed, RUN Mode will be restored.
If you select No, then RUN Mode will be restored without initialization.
If you also wish to initialize any other data, display the System Menu again
and start the process from the beginning.
Initializing Display HistoryThe display history can be saved either in terms of order of occurrence or
order of frequency. Once the capacity is full, history records beyond that point
will not be saved, so it is necessary to periodically initialize the history.
To initialize the history, first select “Init. History” from the Memory Initialization
Menu. The following message will then be displayed for confirmation.
Initialize History?
Yes
No
If you select Yes, then initialization will be executed and history data will be
deleted and RUN Mode will be restored. If you select No, then RUN Mode
will be restored without initialization.
It is also possible to initialize the display history by means of a command
from the host. For details, refer to the
6-3Memory Switch Settings
Memory switch settings set the NT600M display and key input sounds.
Select “Memory SW” from the Maintenance Mode Menu.
MAINTENANCE MODE MENU
Quit
Display History
I/O Check
PT Settings
Initialize Memory
Memory SW
Select one
Liquid Crystal Display TypeMove the cursor to the item that is to be set and press the Enter Key. Each time
that it is pressed, the set value will change.
After the settings have been made, press the Buzzer, Up, and Down keys to return to RUN Mode. If the power to the NT600M is turned off at this point, the settings will not be registered.
MEMORY SW MENU
Quit
Key Input SoundON
Backlight Off10 min
DisplayNormal
Resume FunctionON
Display (LCD type)NormalThe screen display is normal.
Reverse videoThe screen is displayed with dark and light reversed.
Residual image elimination
function (EL type)
Resume functionONThe contents of memory tables written by the host during operation are
10 minIf no key input (see note 1) or command (see note 2) is received for 10
minutes while a screen is being displayed, the screen turns off.
1 hrIf no key input (see note 1) or command (see note 2) is received for
one hour while a screen is being displayed, the screen turns off.
NoneThe screen stays on constantly. The residual image elimination
function does not operate, so turn off the screen periodically by means
of the host program.
retained even if the NT600M power turns off or a reset is executed.
OFFIf power to the NT600M is turned off or a reset is executed, the
contents of the memory table are overwritten by the contents of data
created by the Support Tool.
Note1. Key Inputs
System keys, touch switches, function keys
2. Commands
Screen-change command
Setting screen overlap command (serial type communications only)
On-line transfer completed command (Restart with change to RUN Mode)
Backlight-on command
indicates a default setting.
3.
Operating Conditions for
the Backlight Off and
Residual Image Elimination
Functions
When either “backlight off” or “residual image elimination” is set to either “10 minutes” or “one hour,” the internal timer starts counting as soon as the key input or
command is received. When the time is up, the backlight or EL screen turns off.
The relevant key inputs and commands are as follows:
When any one of the above key inputs or commands is received, the backlight
will be turned back on and the internal timer will start counting again. If a key input or command is then received before the time is up, the timer will be reset and
the count will start over.
Resume FunctionThe resume function retains character string and numeral table data when pow-
er is interrupted or when the reset switch is pressed.
1, 2, 3...
1. When the Resume Function is Set to Off
The contents of character string and numeral tables are cleared when the
power to the PT is turned off or when the reset switch is pressed. After the
power is turned back on, or after the reset, character string and numeral
table data is read from the screen memory and operation begins again. If
new character string or numeral table data is transferred from the Support
Tool, that new data overwrites the data in the memory tables.
2. When the Resume Function is Set to On
If the power to the PT is turned off, or if the reset switch is pressed, the character string or numeral table data prior to the power interruption or reset is
retained. If new character string or numeral table data is transferred from the
Support Tool, the contents of the screen memory are refreshed but the
memory table data does not change. In order to return the contents of the
memory tables to the initial values that were created by the Support Tool,
execute “initialize memory table.”
This section describes transferring screens online to and from the host computer. This function can only be used with
RS-232C and RS-422A Host Interface Units. For details on Host Interface Unit commands, refer to information on online transfers in the Host Interface Unit Operation Manual. Functions used to create screens and control display attributes
on the PT are described in Section 4 Display Functions of this manual. Functions used to input data on-screen are described in Section 5 Input Functions. Data transfer and maintenance functions are described in Section 6 System Menu.
• Screen data can be transferred along with screen numbers. Set the desired
screen number. If you set a screen number which is identical with one already registered in the NT600M, then the screen data for that number will
be overwritten.
• In addition to screen data, it is possible to transfer memory tables and
marks.
• A data transfer can be aborted by pressing the Buzzer Key, Up Key and
Down Key simultaneously. If that is done in the middle of a transmission,
that portion of the data which has already been transferred will be stored,
but all data beyond that point will be destroyed.
• If a transfer of mark data is interrupted, the data may be corrupted. If that
occurs, a message will be displayed to that effect when the System Menu is
next opened.
Screen during online transfer processing
Transmitting
KB
Abort: BUZZER + UP+ DOWN
(Blinks during transmission.)
PT ––> Host
Host ––> PT
Screen Data
System Memory
Memory Tables
Mark Data
History Data
Number of bytes transferred (in kilobytes).
Shows direction
of data transfer.
Shows type of data.
7-2PT to Host
PT to HostScreen data can be transferred along with screen numbers. All screens can be
transferred together, or any particular screen can be transferred individually. In
addition to screen data, memory tables, marks, and display histories can also be
transferred. Screen data is not lost even if the transmission is interrupted by a
system key input.
Relationship Between
On-line Transfer and the
Resume Function
Display After Data is Received Directly
9 9 9 9
XYZ
New Data Transferred from the Host
2 7 5 2
UVW
Just as when transferring data from the Support Tool, on-line transfer writes data
directly from the host to the screen memory. The display contents, therefore, are
affected by the resume function.
The hardware status of the NT600M can be checked with the Maintenance
Menu. Symptoms and corrective measures for errors that cannot be checked
are shown in the table below.
RS-232C Cable for Connecting Devices (CV500-CN228)
+150
2 ,000
–0
NoteThe personal computer end of the CV500-CN228 Connecting Cable is a 25-pin D-sub male con-
nector. To connect to an IBM PC/AT or compatibles, a 9-pin or 25-pin D-sub female adapter is
required.
Dustproof Cover
NT600M-KBA01 (for NT600M-DT/DNjjj)
NT600M-KBA02 (for NT600M-DF122 and NT600M-DN211 + NT600M-FK210)
Under severe conditions, this can be used to protect the display area and the controls from oil and dust.
NT600M-KBA11 (for NT600M-DT/DN/DF122)
NT600M-KBA12 (for NT600M-DT/DN211)
The protective sheet protects the display screen from dirt and scratches, and eliminates reflection and glare.
(The back side of the sheet has a sticky surface. Peel the paper off of the back and attach the sheet.)
Protective film
Protective sheet
Display screen
Back-side paper
NT600M
Dimensions
NT600M-KBA11NT600M-KBA12
151.8
28.5+0.3
0
–0.5
32.7+0.3
0
244.8
–0.5
151.8
0
–0.5
0
244.8
–0.5
NT600M-DF122 Key Sheets (Five Sheets)
Use these sheets for NT600M-DF122 and NT600M-FK210 function keys. By simply peeling them off of the
paper, you can easily write on them and attach them. You can also rub off anything written with oil-base ink. If
they get dirty, you can easily remove and replace them.
Power supply voltage100 to 240 VAC
Allowable power supply volt-
age range
Power consumption40 VA max.
Insulating resistanceBetween AC terminal block and GR:20 MW min. (at 500 VDC)
Dielectric strengthBetween AC terminal block and GR:2,300 VAC at 50/60 Hz for 1 min
Noise resistance1000 VAC
Vibration resistanceNT600M-DT/DF-122:
Shock resistanceDestruction: 30G (294 m/s2) 3 times each in X, Y, and Z directions
Ambient operating temperature
Ambient operating humidity35% to 85% (with no condensation)
Operating environmentNo corrosive gas
Storage temperatureNT600M-DT/DF-122: –20°C to 60°C
Enclosure ratingsFront control panelIP52 (Drip-proof when dust cover is installed.)
WeightApprox. 3 kg
DimensionsNT600M-DT122/DT211/DN211: 325 x 198 x 105 (WxHxD)
85 to 264 VAC, 50/60 Hz
Leakage current: 0.8 mA max.
Pulse width:100 ns to 1 ms
Pulse rise time: 1 ns
10 Hz to 22 Hz with 1.5-mm double amplitude in X,Y, and Z directions
22 Hz to 500 Hz (1.5 G; 14.7 m/s
NT600M-DT/DN211:
10 Hz to 50 Hz with 0.5-mm single amplitude (acceleration: 2.0 G; 19.6 m/s
Z directions for 1 hr each
Malfunction: 20G (196 m/s
NT600M-DT/DF-122: 5°C to 40°C
NT600M-DT/DN21 1: 0°C to 50°C
NT600M-DT/DN21 1: –20°C to 70°C
Rear caseIP20
Terminal sectionIP00
NT600M-DF122: 325 x 238 x 105 (WxHxD)
(These dimensions do not include the cable.)
No. of dots:640 x 400
Effective display area: 206 mm x 130 mm
Angle of vision:Up 20°; down 35°; right/left ±30°
Life expectancy:50,000 hrs min.
Backlight
Cold-cathode tube
Life expectancy:10,000 hrs min. (20,000 hrs average)
Automatic turn-off:Can be set to not turn off, or to turn off in 10 min or 1 hr
EL display (9 inches equivalent)
No. of dots:640 x 400
Effective display area: 192 mm x 120 mm
Display color:Yellow-orange
Life expectancy (with a 30% decrease in brightness): Approx. 30,000 hrs
Automatic turn-off:Can be set to none, 10 min or 1 hr
POWER indicator (Green LED):Lit when power is being supplied.
RUN indicator (Green LED):Lit during operation.
BAT LOW indicator (Red LED):Lit when battery level drops.
Appendix BSpecifications
Control Panel Specifications
ItemSpecifications
System keysFour keys: buzzer-stop, up-scroll, down-scroll, execute (enter)
Functions: System Menu selection, buzzer off, bar cursor movement, up/down scroll for
continuous screens, execution of numeric settings
Touch panel (DT type)Number of switches:128 per screen max.
Input switch type:Pressure-sensitive
Operating force:100 g min.
Life expectancy:1,000,000 operations min.
12-key Function Key Unit
(DN type)
NT600M-FK210
Function Keys (DF type)
No. of keys:12 (fixed)
Input switch typePressure-sensitive
Key sheets are replaceable.
Display Capacity
ItemSpecifications
Display charactersHalf-size character (8 x 8 dots):Alphanumeric and symbols
Normal character (8 x 16 dots):Alphanumeric and symbols
Mark (16 x 16 dots):User defined, 64 max.
Character sizeHalf-size characters: Approx. 2.5 x 2.5 mm
Normal characters: Approx. 2.5 x 5.0 mm
Marks:Approx. 5.0 x 5.0 mm
Enlargement functionHorizontal, vertical, 4 times, 9 times, 16 times, 64 times
Display attributesInverse, blinking, inverse blinking
GraphicsPolyline, circle
Alarm outputRelay output on rear terminal block; NO contact.
Rating: 1 A at 24 VDC or 0.5 A at 100 VAC, with resistance load
Output condition: NO Contact (Closes when a command is received from the host or
when there is a screen displayed with an alarm-ON specification.)
Host RUN inputPhotocoupler input on rear terminal block.
Rating 24 VDC
When this input goes OFF, the display “host error” regardless of other conditions.
BuzzersTwo types: Continuous sound and intermittent sound.
ON:The buzzer will sound when a key input is made, when a buzzer-ON com-
OFF:The buzzer is turned OFF when the Buzzer Key is pressed, when a buzzer-
Loudness: 80 dB min. and 87 dB on average (measured at a distance of 10 cm)
Maintenance functionsSelf-test for memory, switches, etc.
Status setting confirmation for communications and other conditions.
Simple communications confirmation.
Battery backupData backed up by battery when screen memory is SRAM.
Data backup time:5 years (at 25°C)
If there is a voltage drop, the BA T LOW indicator on the front panel will light and the Battery Low Flag to the host will turn ON.
The battery can be replaced from the rear of the Terminal during operation.
Key input sound settingIf Key Input Sound is set to ON in the Memory Switch Menu, a beep will sound for 0.2 s
when a system key, function key, or touch switch is pressed.
+10%
/
–15%
mand is received from the host, or when a screen with a buzzer-ON specification is called.
OFF command is received from the host, or when a screen without a buzzer-ON specification is displayed.
Numeric setting---418
Function key------18
Overlapping screen---1818
Continuous screen---1818
File units13,48020,146Minimum amount re-
With history:34
Other:4
1 character1414Fixed information
1 character added+1+11 byte added when all
One1010
One added+4+4
---1216Variable information
No guide characters1630
1 guide character+12+12
1 character added+1+11 byte added when re-
Circle: no guide characters
Rectangle: no guide
characters
1 guide character+12+12
1 character added+1+11 byte added when re-
1630---
1634
With direct
connection
(Unit: byte)
62
Remarks
quired for lower limit.
Number of screens re-
quired.
6Required first time
only.
sums are odd numbers.
---
---
sult is odd number.
sult is odd number.
---
Basic screen information added regardless
of number of child
screens.
NoteIf the edge of a screen goes beyond 64K bytes, the data will move to the next page
(when 128 bytes or 256 bytes). 32K bytes = 32,768; 64K bytes = 65,536; 128K bytes = 131,072;
256K bytes = 262,144
I/O headers:62 bytes (even for only one) + number x 20 bytes
Pin 2 of SW2 must be ON to enable English language messages to use the following codes.
Example: Hex code is represented by 30, decimal code by 48, and character by 0.
30
48
0
Code 20 and 32 in the table represents a space, as indicated by “SP.”