Connection to a PLC by the Host Link (RS-232C Type) Section 2-4
C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other
than the CPU11), or SRM1: Built-in RS-232C port connection
C200HX/HG/HE(-Z)E: Serial Communications Board port A
CQM1H: Serial Communications Board port 1
C200HX/HG/HE(Z)E: Serial Communications Board port B
CPM1: Peripheral port connection through a CPM1-CIF01 RS-232C Adapter
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on
CS1-series PLCs. The CPM2C’s communication port handles both RS-232C
and peripheral port connections, which are divided internally. Therefore, when
using the CPM2C, it is necessary to select RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as
shown in the following table. Refer to the CPM2C Operation Manual for more
details.
Word Writing Value Settings
DM6645 0001 Host Link mode, no CTS control
Communication conditions set by the contents of DM
DM6646 0303 Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
0304 Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
DM6648 0000 Unit # 00
Word Writing Value Settings
DM6555 0001 Host Link mode, no CTS control
Communication conditions set by the contents of DM
DM6556 0303 Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
0304 Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
DM6558 0000 Unit # 00
Word Writing Value Settings
DM6550 0001 Host Link mode, no CTS control
Communication conditions set by the contents of DM
DM6551 0303 Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
0304 Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
DM6553 0000 Unit # 00
Word Writing Value Settings
DM6650 0001 Host Link mode
Communication conditions set by the contents of DM
DM6651 0303 Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
0304 Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
DM6653 0000 Unit # 00